KNX Database
Schrack Technik GmbH KXSK0CRC-- Switching Actuator KXSK0CRC--

Switching Actuator KXSK0CRC-- KXSK0CRC--

Schrack Technik GmbH · Order number KXSK0CRC-- · Ausgabe › Binary output, 12-fold › REG-Devices › KXSK0CRC--

Switching Actuator KXSK0CRC--

Download .knxprod 07 B0 A12 Switching Actuator 12-fold 9A0303 0.3 · 1.6 MB

Product

ManufacturerSchrack Technik GmbH
Product nameSwitching Actuator KXSK0CRC--
Order numberKXSK0CRC--
HardwareHardwareEntry.0.9A03
MediumTwisted Pair
Bus current (mA)20
Rail mountedYes
RegistrationRegistered · 2020-07-28
Languagesen-US, de-DE
Catalog entryM-014F_H-hp.5F00315-2-O0001_HP-9A03-03-982D-O0001_CI-KXSK0CRC.2D.2D-1
Fingerprint982D
SHA-256d9617affeec2e836e1e4ffc4673b4f78049320487bc604249327dea82473e2fc
First seen2026-11-25
Markets58 markets

Application program: 07 B0 A12 Switching Actuator 12-fold 9A0303 0.3

Application number$9A03
Version0.3
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters5166
Group objects4394
Group objects (4394)
NoNameFunctionSizeDPTFlags
1Status device functionok / defect1 Bit1.5 alarmCRT
2Send status valuesrequest1 Bit1.17 triggerCW
3A SwitchingOn / Off1 Bit1.1 switchCW
4A Control ValueValue1 Byte5.10 counter pulses (0..255)CW
4A Control ValueValue2 Bytes9.1 temperature (°C)CW
4A Control ValueValue1 Byte5.1 percentage (0..100%)CW
4A Control ValueValue2 Bytes9.4 lux (Lux)CW
4A Control ValueValue2 Bytes9.21 current (mA)CW
4A Control ValueValue2 Bytes9.24 power (kW)CW
4A Control ValueValue4 Bytes14.56 power (W)CW
5A Status switchingOn / Off1 Bit1.1 switchCRT
6A Logic operation 1On / Off1 Bit1.1 switchCW
7A Logic operation 2On / Off1 Bit1.1 switchCW
8A Central SwitchingOn / Off1 Bit1.1 switchCW
9A 8-bit scenerecall / store 1 Byte18.1 scene controlCW
10A Night modeOn / Off1 Bit1.3 enableCW
11A Night mode timerON time (seconds)2 Bytes7.5 time (s)CRW
12A Day mode timerON time 1 (seconds)2 Bytes7.5 time (s)CRW
13A Forced controlOn / Off2 Bit2.1 switch controlCW
14A Pre-warning expiration of timer periodOn / Off1 Bit1.1 switchCRT
15A Lock TimerOn / Off1 Bit1.3 enableCW
16A Override 1, Permanent OFFOn / Off1 Bit1.3 enableCW
16A Override 1, Manual ONOn / Off1 Bit1.3 enableCW
16A Override 1, LockOn / Off1 Bit1.3 enableCW
16A Override 1, Central ControlOn / Off1 Bit1.3 enableCW
16A Override 1, User-defined ControlOn / Off1 Bit1.3 enableCW
17A Override 1, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
17A Override 1, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
17A Override 1, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
17A Override 1, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
17A Override 1, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
17A Override 1, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
17A Override 1, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
17A Override 1, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
17A Override 1, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
17A Override 1, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
17A Override 1, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
17A Override 1, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
17A Override 1, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
17A Override 1, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
17A Override 1, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
17A Override 1, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
17A Override 1, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
17A Override 1, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
17A Override 1, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
17A Override 1, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
17A Override 1, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
17A Override 1, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
17A Override 1, Lock, ControlValue2 Bytes9.21 current (mA)CW
17A Override 1, Central Control, ControlValue2 Bytes9.21 current (mA)CW
17A Override 1, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
17A Override 1, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
17A Override 1, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
17A Override 1, Lock, ControlValue2 Bytes9.24 power (kW)CW
17A Override 1, Central Control, ControlValue2 Bytes9.24 power (kW)CW
17A Override 1, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
17A Override 1, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
17A Override 1, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
17A Override 1, Lock, ControlValue4 Bytes14.56 power (W)CW
17A Override 1, Central Control, ControlValue4 Bytes14.56 power (W)CW
17A Override 1, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
18A Override 1, Forced ControlOn / Off2 Bit2.1 switch controlCW
19A Override 1, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
19A Override 1, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
19A Override 1, Lock, StatusOn / Off1 Bit1.2 booleanCRT
19A Override 1, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
19A Override 1, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
19A Override 1, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
20A Override 2, Permanent OFFOn / Off1 Bit1.3 enableCW
20A Override 2, Manual ONOn / Off1 Bit1.3 enableCW
20A Override 2, LockOn / Off1 Bit1.3 enableCW
20A Override 2, Central ControlOn / Off1 Bit1.3 enableCW
20A Override 2, User-defined ControlOn / Off1 Bit1.3 enableCW
21A Override 2, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
21A Override 2, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
21A Override 2, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
21A Override 2, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
21A Override 2, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
21A Override 2, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
21A Override 2, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
21A Override 2, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
21A Override 2, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
21A Override 2, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
21A Override 2, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
21A Override 2, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
21A Override 2, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
21A Override 2, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
21A Override 2, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
21A Override 2, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
21A Override 2, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
21A Override 2, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
21A Override 2, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
21A Override 2, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
21A Override 2, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
21A Override 2, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
21A Override 2, Lock, ControlValue2 Bytes9.21 current (mA)CW
21A Override 2, Central Control, ControlValue2 Bytes9.21 current (mA)CW
21A Override 2, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
21A Override 2, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
21A Override 2, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
21A Override 2, Lock, ControlValue2 Bytes9.24 power (kW)CW
21A Override 2, Central Control, ControlValue2 Bytes9.24 power (kW)CW
21A Override 2, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
21A Override 2, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
21A Override 2, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
21A Override 2, Lock, ControlValue4 Bytes14.56 power (W)CW
21A Override 2, Central Control, ControlValue4 Bytes14.56 power (W)CW
21A Override 2, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
22A Override 2, Forced ControlOn / Off2 Bit2.1 switch controlCW
23A Override 2, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
23A Override 2, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
23A Override 2, Lock, StatusOn / Off1 Bit1.2 booleanCRT
23A Override 2, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
23A Override 2, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
23A Override 2, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
24A Override 3, Permanent OFFOn / Off1 Bit1.3 enableCW
24A Override 3, Manual ONOn / Off1 Bit1.3 enableCW
24A Override 3, LockOn / Off1 Bit1.3 enableCW
24A Override 3, Central ControlOn / Off1 Bit1.3 enableCW
24A Override 3, User-defined ControlOn / Off1 Bit1.3 enableCW
25A Override 3, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
25A Override 3, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
25A Override 3, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
25A Override 3, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
25A Override 3, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
25A Override 3, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
25A Override 3, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
25A Override 3, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
25A Override 3, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
25A Override 3, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
25A Override 3, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
25A Override 3, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
25A Override 3, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
25A Override 3, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
25A Override 3, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
25A Override 3, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
25A Override 3, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
25A Override 3, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
25A Override 3, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
25A Override 3, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
25A Override 3, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
25A Override 3, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
25A Override 3, Lock, ControlValue2 Bytes9.21 current (mA)CW
25A Override 3, Central Control, ControlValue2 Bytes9.21 current (mA)CW
25A Override 3, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
25A Override 3, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
25A Override 3, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
25A Override 3, Lock, ControlValue2 Bytes9.24 power (kW)CW
25A Override 3, Central Control, ControlValue2 Bytes9.24 power (kW)CW
25A Override 3, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
25A Override 3, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
25A Override 3, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
25A Override 3, Lock, ControlValue4 Bytes14.56 power (W)CW
25A Override 3, Central Control, ControlValue4 Bytes14.56 power (W)CW
25A Override 3, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
26A Override 3, Forced ControlOn / Off2 Bit2.1 switch controlCW
27A Override 3, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
27A Override 3, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
27A Override 3, Lock, StatusOn / Off1 Bit1.2 booleanCRT
27A Override 3, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
27A Override 3, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
27A Override 3, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
28A Override 4, Permanent OFFOn / Off1 Bit1.3 enableCW
28A Override 4, Manual ONOn / Off1 Bit1.3 enableCW
28A Override 4, LockOn / Off1 Bit1.3 enableCW
28A Override 4, Central ControlOn / Off1 Bit1.3 enableCW
28A Override 4, User-defined ControlOn / Off1 Bit1.3 enableCW
29A Override 4, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
29A Override 4, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
29A Override 4, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
29A Override 4, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
29A Override 4, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
29A Override 4, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
29A Override 4, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
29A Override 4, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
29A Override 4, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
29A Override 4, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
29A Override 4, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
29A Override 4, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
29A Override 4, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
29A Override 4, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
29A Override 4, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
29A Override 4, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
29A Override 4, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
29A Override 4, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
29A Override 4, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
29A Override 4, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
29A Override 4, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
29A Override 4, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
29A Override 4, Lock, ControlValue2 Bytes9.21 current (mA)CW
29A Override 4, Central Control, ControlValue2 Bytes9.21 current (mA)CW
29A Override 4, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
29A Override 4, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
29A Override 4, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
29A Override 4, Lock, ControlValue2 Bytes9.24 power (kW)CW
29A Override 4, Central Control, ControlValue2 Bytes9.24 power (kW)CW
29A Override 4, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
29A Override 4, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
29A Override 4, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
29A Override 4, Lock, ControlValue4 Bytes14.56 power (W)CW
29A Override 4, Central Control, ControlValue4 Bytes14.56 power (W)CW
29A Override 4, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
30A Override 4, Forced ControlOn / Off2 Bit2.1 switch controlCW
31A Override 4, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
31A Override 4, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
31A Override 4, Lock, StatusOn / Off1 Bit1.2 booleanCRT
31A Override 4, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
31A Override 4, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
31A Override 4, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
32A Override 5, Permanent OFFOn / Off1 Bit1.3 enableCW
32A Override 5, Manual ONOn / Off1 Bit1.3 enableCW
32A Override 5, LockOn / Off1 Bit1.3 enableCW
32A Override 5, Central ControlOn / Off1 Bit1.3 enableCW
32A Override 5, User-defined ControlOn / Off1 Bit1.3 enableCW
33A Override 5, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
33A Override 5, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
33A Override 5, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
33A Override 5, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
33A Override 5, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
33A Override 5, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
33A Override 5, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
33A Override 5, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
33A Override 5, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
33A Override 5, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
33A Override 5, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
33A Override 5, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
33A Override 5, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
33A Override 5, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
33A Override 5, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
33A Override 5, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
33A Override 5, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
33A Override 5, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
33A Override 5, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
33A Override 5, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
33A Override 5, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
33A Override 5, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
33A Override 5, Lock, ControlValue2 Bytes9.21 current (mA)CW
33A Override 5, Central Control, ControlValue2 Bytes9.21 current (mA)CW
33A Override 5, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
33A Override 5, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
33A Override 5, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
33A Override 5, Lock, ControlValue2 Bytes9.24 power (kW)CW
33A Override 5, Central Control, ControlValue2 Bytes9.24 power (kW)CW
33A Override 5, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
33A Override 5, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
33A Override 5, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
33A Override 5, Lock, ControlValue4 Bytes14.56 power (W)CW
33A Override 5, Central Control, ControlValue4 Bytes14.56 power (W)CW
33A Override 5, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
34A Override 5, Forced ControlOn / Off2 Bit2.1 switch controlCW
35A Override 5, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
35A Override 5, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
35A Override 5, Lock, StatusOn / Off1 Bit1.2 booleanCRT
35A Override 5, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
35A Override 5, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
35A Override 5, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
36A Override 6, Permanent OFFOn / Off1 Bit1.3 enableCW
36A Override 6, Manual ONOn / Off1 Bit1.3 enableCW
36A Override 6, LockOn / Off1 Bit1.3 enableCW
36A Override 6, Central ControlOn / Off1 Bit1.3 enableCW
36A Override 6, User-defined ControlOn / Off1 Bit1.3 enableCW
37A Override 6, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
37A Override 6, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
37A Override 6, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
37A Override 6, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
37A Override 6, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
37A Override 6, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
37A Override 6, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
37A Override 6, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
37A Override 6, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
37A Override 6, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
37A Override 6, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
37A Override 6, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
37A Override 6, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
37A Override 6, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
37A Override 6, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
37A Override 6, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
37A Override 6, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
37A Override 6, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
37A Override 6, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
37A Override 6, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
37A Override 6, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
37A Override 6, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
37A Override 6, Lock, ControlValue2 Bytes9.21 current (mA)CW
37A Override 6, Central Control, ControlValue2 Bytes9.21 current (mA)CW
37A Override 6, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
37A Override 6, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
37A Override 6, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
37A Override 6, Lock, ControlValue2 Bytes9.24 power (kW)CW
37A Override 6, Central Control, ControlValue2 Bytes9.24 power (kW)CW
37A Override 6, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
37A Override 6, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
37A Override 6, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
37A Override 6, Lock, ControlValue4 Bytes14.56 power (W)CW
37A Override 6, Central Control, ControlValue4 Bytes14.56 power (W)CW
37A Override 6, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
38A Override 6, Forced ControlOn / Off2 Bit2.1 switch controlCW
39A Override 6, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
39A Override 6, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
39A Override 6, Lock, StatusOn / Off1 Bit1.2 booleanCRT
39A Override 6, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
39A Override 6, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
39A Override 6, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
40A Override 7, Permanent OFFOn / Off1 Bit1.3 enableCW
40A Override 7, Manual ONOn / Off1 Bit1.3 enableCW
40A Override 7, LockOn / Off1 Bit1.3 enableCW
40A Override 7, Central ControlOn / Off1 Bit1.3 enableCW
40A Override 7, User-defined ControlOn / Off1 Bit1.3 enableCW
41A Override 7, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
41A Override 7, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
41A Override 7, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
41A Override 7, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
41A Override 7, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
41A Override 7, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
41A Override 7, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
41A Override 7, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
41A Override 7, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
41A Override 7, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
41A Override 7, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
41A Override 7, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
41A Override 7, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
41A Override 7, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
41A Override 7, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
41A Override 7, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
41A Override 7, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
41A Override 7, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
41A Override 7, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
41A Override 7, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
41A Override 7, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
41A Override 7, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
41A Override 7, Lock, ControlValue2 Bytes9.21 current (mA)CW
41A Override 7, Central Control, ControlValue2 Bytes9.21 current (mA)CW
41A Override 7, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
41A Override 7, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
41A Override 7, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
41A Override 7, Lock, ControlValue2 Bytes9.24 power (kW)CW
41A Override 7, Central Control, ControlValue2 Bytes9.24 power (kW)CW
41A Override 7, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
41A Override 7, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
41A Override 7, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
41A Override 7, Lock, ControlValue4 Bytes14.56 power (W)CW
41A Override 7, Central Control, ControlValue4 Bytes14.56 power (W)CW
41A Override 7, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
42A Override 7, Forced ControlOn / Off2 Bit2.1 switch controlCW
43A Override 7, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
43A Override 7, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
43A Override 7, Lock, StatusOn / Off1 Bit1.2 booleanCRT
43A Override 7, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
43A Override 7, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
43A Override 7, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
44A Overrides status1 = Active1 Bit1.2 booleanCRT
45A Number of switching cyclesValue (in cycles)4 Bytes12.1 counter pulses (unsigned)CRT
46A Number for switching cyclesSet Value (in cycles)4 Bytes12.1 counter pulses (unsigned)CW
47A Threshold for switching cyclesSet / Request Value (in cycles)4 Bytes12.1 counter pulses (unsigned)CRW
48A Exceedance of threshold for switching cyclesOn / Off1 Bit1.2 booleanCRT
49A Operating hoursValue (in hours)4 Bytes12.1 counter pulses (unsigned)CRT
50A Operating hoursValue (in seconds)4 Bytes13.100 time lag (s)CRT
51A Operating hoursSet Value4 Bytes12.1 counter pulses (unsigned)CW
52A Threshold for operating hoursSet / Request Value4 Bytes12.1 counter pulses (unsigned)CRW
53A Exceedance of threshold for operating hoursOn / Off1 Bit1.2 booleanCRT
54A Load Check-measured valueCurrent (mA)2 Bytes7.12 current (mA)CRT
55A Load Check-measured valueCurrent (A)4 Bytes14.19 electric current (A)CRT
56A Load Check-Normal value storeOn1 Bit1.3 enableCW
57A Load Check-Normal value recallCurrent (mA)2 Bytes7.12 current (mA)CRT
58A Load Check-Normal value recallCurrent (A)4 Bytes14.19 electric current (A)CRT
59A Load Check-Exceedance of load check limit valueOn / Off1 Bit1.2 booleanCRT
60A Load Check-Shortfall of load check limit valueOn / Off1 Bit1.2 booleanCRT
61A Load Check-Contact FailureOn / Off1 Bit1.2 booleanCRT
62B SwitchingOn / Off1 Bit1.1 switchCW
63B Control ValueValue1 Byte5.10 counter pulses (0..255)CW
63B Control ValueValue2 Bytes9.1 temperature (°C)CW
63B Control ValueValue1 Byte5.1 percentage (0..100%)CW
63B Control ValueValue2 Bytes9.4 lux (Lux)CW
63B Control ValueValue2 Bytes9.21 current (mA)CW
63B Control ValueValue2 Bytes9.24 power (kW)CW
63B Control ValueValue4 Bytes14.56 power (W)CW
64B Status switchingOn / Off1 Bit1.1 switchCRT
65B Logic operation 1On / Off1 Bit1.1 switchCW
66B Logic operation 2On / Off1 Bit1.1 switchCW
67B Central SwitchingOn / Off1 Bit1.1 switchCW
68B 8-bit scenerecall / store 1 Byte18.1 scene controlCW
69B Night modeOn / Off1 Bit1.3 enableCW
70B Night mode timerON time (seconds)2 Bytes7.5 time (s)CRW
71B Day mode timerON time 1 (seconds)2 Bytes7.5 time (s)CRW
72B Forced controlOn / Off2 Bit2.1 switch controlCW
73B Pre-warning expiration of timer periodOn / Off1 Bit1.1 switchCRT
74B Lock TimerOn / Off1 Bit1.3 enableCW
75B Override 1, Permanent OFFOn / Off1 Bit1.3 enableCW
75B Override 1, Manual ONOn / Off1 Bit1.3 enableCW
75B Override 1, LockOn / Off1 Bit1.3 enableCW
75B Override 1, Central ControlOn / Off1 Bit1.3 enableCW
75B Override 1, User-defined ControlOn / Off1 Bit1.3 enableCW
76B Override 1, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
76B Override 1, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
76B Override 1, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
76B Override 1, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
76B Override 1, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
76B Override 1, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
76B Override 1, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
76B Override 1, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
76B Override 1, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
76B Override 1, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
76B Override 1, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
76B Override 1, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
76B Override 1, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
76B Override 1, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
76B Override 1, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
76B Override 1, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
76B Override 1, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
76B Override 1, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
76B Override 1, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
76B Override 1, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
76B Override 1, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
76B Override 1, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
76B Override 1, Lock, ControlValue2 Bytes9.21 current (mA)CW
76B Override 1, Central Control, ControlValue2 Bytes9.21 current (mA)CW
76B Override 1, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
76B Override 1, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
76B Override 1, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
76B Override 1, Lock, ControlValue2 Bytes9.24 power (kW)CW
76B Override 1, Central Control, ControlValue2 Bytes9.24 power (kW)CW
76B Override 1, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
76B Override 1, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
76B Override 1, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
76B Override 1, Lock, ControlValue4 Bytes14.56 power (W)CW
76B Override 1, Central Control, ControlValue4 Bytes14.56 power (W)CW
76B Override 1, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
77B Override 1, Forced ControlOn / Off2 Bit2.1 switch controlCW
78B Override 1, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
78B Override 1, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
78B Override 1, Lock, StatusOn / Off1 Bit1.2 booleanCRT
78B Override 1, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
78B Override 1, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
78B Override 1, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
79B Override 2, Permanent OFFOn / Off1 Bit1.3 enableCW
79B Override 2, Manual ONOn / Off1 Bit1.3 enableCW
79B Override 2, LockOn / Off1 Bit1.3 enableCW
79B Override 2, Central ControlOn / Off1 Bit1.3 enableCW
79B Override 2, User-defined ControlOn / Off1 Bit1.3 enableCW
80B Override 2, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
80B Override 2, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
80B Override 2, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
80B Override 2, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
80B Override 2, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
80B Override 2, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
80B Override 2, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
80B Override 2, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
80B Override 2, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
80B Override 2, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
80B Override 2, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
80B Override 2, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
80B Override 2, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
80B Override 2, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
80B Override 2, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
80B Override 2, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
80B Override 2, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
80B Override 2, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
80B Override 2, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
80B Override 2, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
80B Override 2, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
80B Override 2, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
80B Override 2, Lock, ControlValue2 Bytes9.21 current (mA)CW
80B Override 2, Central Control, ControlValue2 Bytes9.21 current (mA)CW
80B Override 2, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
80B Override 2, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
80B Override 2, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
80B Override 2, Lock, ControlValue2 Bytes9.24 power (kW)CW
80B Override 2, Central Control, ControlValue2 Bytes9.24 power (kW)CW
80B Override 2, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
80B Override 2, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
80B Override 2, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
80B Override 2, Lock, ControlValue4 Bytes14.56 power (W)CW
80B Override 2, Central Control, ControlValue4 Bytes14.56 power (W)CW
80B Override 2, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
81B Override 2, Forced ControlOn / Off2 Bit2.1 switch controlCW
82B Override 2, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
82B Override 2, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
82B Override 2, Lock, StatusOn / Off1 Bit1.2 booleanCRT
82B Override 2, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
82B Override 2, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
82B Override 2, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
83B Override 3, Permanent OFFOn / Off1 Bit1.3 enableCW
83B Override 3, Manual ONOn / Off1 Bit1.3 enableCW
83B Override 3, LockOn / Off1 Bit1.3 enableCW
83B Override 3, Central ControlOn / Off1 Bit1.3 enableCW
83B Override 3, User-defined ControlOn / Off1 Bit1.3 enableCW
84B Override 3, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
84B Override 3, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
84B Override 3, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
84B Override 3, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
84B Override 3, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
84B Override 3, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
84B Override 3, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
84B Override 3, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
84B Override 3, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
84B Override 3, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
84B Override 3, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
84B Override 3, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
84B Override 3, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
84B Override 3, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
84B Override 3, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
84B Override 3, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
84B Override 3, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
84B Override 3, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
84B Override 3, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
84B Override 3, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
84B Override 3, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
84B Override 3, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
84B Override 3, Lock, ControlValue2 Bytes9.21 current (mA)CW
84B Override 3, Central Control, ControlValue2 Bytes9.21 current (mA)CW
84B Override 3, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
84B Override 3, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
84B Override 3, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
84B Override 3, Lock, ControlValue2 Bytes9.24 power (kW)CW
84B Override 3, Central Control, ControlValue2 Bytes9.24 power (kW)CW
84B Override 3, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
84B Override 3, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
84B Override 3, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
84B Override 3, Lock, ControlValue4 Bytes14.56 power (W)CW
84B Override 3, Central Control, ControlValue4 Bytes14.56 power (W)CW
84B Override 3, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
85B Override 3, Forced ControlOn / Off2 Bit2.1 switch controlCW
86B Override 3, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
86B Override 3, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
86B Override 3, Lock, StatusOn / Off1 Bit1.2 booleanCRT
86B Override 3, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
86B Override 3, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
86B Override 3, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
87B Override 4, Permanent OFFOn / Off1 Bit1.3 enableCW
87B Override 4, Manual ONOn / Off1 Bit1.3 enableCW
87B Override 4, LockOn / Off1 Bit1.3 enableCW
87B Override 4, Central ControlOn / Off1 Bit1.3 enableCW
87B Override 4, User-defined ControlOn / Off1 Bit1.3 enableCW
88B Override 4, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
88B Override 4, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
88B Override 4, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
88B Override 4, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
88B Override 4, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
88B Override 4, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
88B Override 4, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
88B Override 4, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
88B Override 4, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
88B Override 4, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
88B Override 4, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
88B Override 4, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
88B Override 4, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
88B Override 4, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
88B Override 4, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
88B Override 4, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
88B Override 4, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
88B Override 4, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
88B Override 4, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
88B Override 4, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
88B Override 4, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
88B Override 4, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
88B Override 4, Lock, ControlValue2 Bytes9.21 current (mA)CW
88B Override 4, Central Control, ControlValue2 Bytes9.21 current (mA)CW
88B Override 4, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
88B Override 4, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
88B Override 4, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
88B Override 4, Lock, ControlValue2 Bytes9.24 power (kW)CW
88B Override 4, Central Control, ControlValue2 Bytes9.24 power (kW)CW
88B Override 4, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
88B Override 4, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
88B Override 4, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
88B Override 4, Lock, ControlValue4 Bytes14.56 power (W)CW
88B Override 4, Central Control, ControlValue4 Bytes14.56 power (W)CW
88B Override 4, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
89B Override 4, Forced ControlOn / Off2 Bit2.1 switch controlCW
90B Override 4, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
90B Override 4, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
90B Override 4, Lock, StatusOn / Off1 Bit1.2 booleanCRT
90B Override 4, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
90B Override 4, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
90B Override 4, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
91B Override 5, Permanent OFFOn / Off1 Bit1.3 enableCW
91B Override 5, Manual ONOn / Off1 Bit1.3 enableCW
91B Override 5, LockOn / Off1 Bit1.3 enableCW
91B Override 5, Central ControlOn / Off1 Bit1.3 enableCW
91B Override 5, User-defined ControlOn / Off1 Bit1.3 enableCW
92B Override 5, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
92B Override 5, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
92B Override 5, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
92B Override 5, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
92B Override 5, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
92B Override 5, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
92B Override 5, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
92B Override 5, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
92B Override 5, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
92B Override 5, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
92B Override 5, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
92B Override 5, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
92B Override 5, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
92B Override 5, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
92B Override 5, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
92B Override 5, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
92B Override 5, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
92B Override 5, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
92B Override 5, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
92B Override 5, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
92B Override 5, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
92B Override 5, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
92B Override 5, Lock, ControlValue2 Bytes9.21 current (mA)CW
92B Override 5, Central Control, ControlValue2 Bytes9.21 current (mA)CW
92B Override 5, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
92B Override 5, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
92B Override 5, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
92B Override 5, Lock, ControlValue2 Bytes9.24 power (kW)CW
92B Override 5, Central Control, ControlValue2 Bytes9.24 power (kW)CW
92B Override 5, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
92B Override 5, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
92B Override 5, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
92B Override 5, Lock, ControlValue4 Bytes14.56 power (W)CW
92B Override 5, Central Control, ControlValue4 Bytes14.56 power (W)CW
92B Override 5, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
93B Override 5, Forced ControlOn / Off2 Bit2.1 switch controlCW
94B Override 5, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
94B Override 5, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
94B Override 5, Lock, StatusOn / Off1 Bit1.2 booleanCRT
94B Override 5, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
94B Override 5, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
94B Override 5, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
95B Override 6, Permanent OFFOn / Off1 Bit1.3 enableCW
95B Override 6, Manual ONOn / Off1 Bit1.3 enableCW
95B Override 6, LockOn / Off1 Bit1.3 enableCW
95B Override 6, Central ControlOn / Off1 Bit1.3 enableCW
95B Override 6, User-defined ControlOn / Off1 Bit1.3 enableCW
96B Override 6, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
96B Override 6, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
96B Override 6, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
96B Override 6, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
96B Override 6, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
96B Override 6, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
96B Override 6, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
96B Override 6, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
96B Override 6, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
96B Override 6, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
96B Override 6, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
96B Override 6, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
96B Override 6, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
96B Override 6, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
96B Override 6, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
96B Override 6, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
96B Override 6, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
96B Override 6, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
96B Override 6, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
96B Override 6, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
96B Override 6, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
96B Override 6, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
96B Override 6, Lock, ControlValue2 Bytes9.21 current (mA)CW
96B Override 6, Central Control, ControlValue2 Bytes9.21 current (mA)CW
96B Override 6, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
96B Override 6, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
96B Override 6, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
96B Override 6, Lock, ControlValue2 Bytes9.24 power (kW)CW
96B Override 6, Central Control, ControlValue2 Bytes9.24 power (kW)CW
96B Override 6, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
96B Override 6, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
96B Override 6, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
96B Override 6, Lock, ControlValue4 Bytes14.56 power (W)CW
96B Override 6, Central Control, ControlValue4 Bytes14.56 power (W)CW
96B Override 6, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
97B Override 6, Forced ControlOn / Off2 Bit2.1 switch controlCW
98B Override 6, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
98B Override 6, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
98B Override 6, Lock, StatusOn / Off1 Bit1.2 booleanCRT
98B Override 6, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
98B Override 6, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
98B Override 6, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
99B Override 7, Permanent OFFOn / Off1 Bit1.3 enableCW
99B Override 7, Manual ONOn / Off1 Bit1.3 enableCW
99B Override 7, LockOn / Off1 Bit1.3 enableCW
99B Override 7, Central ControlOn / Off1 Bit1.3 enableCW
99B Override 7, User-defined ControlOn / Off1 Bit1.3 enableCW
100B Override 7, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
100B Override 7, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
100B Override 7, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
100B Override 7, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
100B Override 7, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
100B Override 7, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
100B Override 7, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
100B Override 7, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
100B Override 7, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
100B Override 7, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
100B Override 7, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
100B Override 7, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
100B Override 7, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
100B Override 7, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
100B Override 7, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
100B Override 7, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
100B Override 7, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
100B Override 7, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
100B Override 7, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
100B Override 7, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
100B Override 7, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
100B Override 7, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
100B Override 7, Lock, ControlValue2 Bytes9.21 current (mA)CW
100B Override 7, Central Control, ControlValue2 Bytes9.21 current (mA)CW
100B Override 7, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
100B Override 7, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
100B Override 7, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
100B Override 7, Lock, ControlValue2 Bytes9.24 power (kW)CW
100B Override 7, Central Control, ControlValue2 Bytes9.24 power (kW)CW
100B Override 7, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
100B Override 7, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
100B Override 7, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
100B Override 7, Lock, ControlValue4 Bytes14.56 power (W)CW
100B Override 7, Central Control, ControlValue4 Bytes14.56 power (W)CW
100B Override 7, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
101B Override 7, Forced ControlOn / Off2 Bit2.1 switch controlCW
102B Override 7, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
102B Override 7, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
102B Override 7, Lock, StatusOn / Off1 Bit1.2 booleanCRT
102B Override 7, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
102B Override 7, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
102B Override 7, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
103B Overrides status1 = Active1 Bit1.2 booleanCRT
104B Number of switching cyclesValue (in cycles)4 Bytes12.1 counter pulses (unsigned)CRT
105B Number for switching cyclesSet Value (in cycles)4 Bytes12.1 counter pulses (unsigned)CW
106B Threshold for switching cyclesSet / Request Value (in cycles)4 Bytes12.1 counter pulses (unsigned)CRW
107B Exceedance of threshold for switching cyclesOn / Off1 Bit1.2 booleanCRT
108B Operating hoursValue (in hours)4 Bytes12.1 counter pulses (unsigned)CRT
109B Operating hoursValue (in seconds)4 Bytes13.100 time lag (s)CRT
110B Operating hoursSet Value4 Bytes12.1 counter pulses (unsigned)CW
111B Threshold for operating hoursSet / Request Value4 Bytes12.1 counter pulses (unsigned)CRW
112B Exceedance of threshold for operating hoursOn / Off1 Bit1.2 booleanCRT
113B Load Check-measured valueCurrent (mA)2 Bytes7.12 current (mA)CRT
114B Load Check-measured valueCurrent (A)4 Bytes14.19 electric current (A)CRT
115B Load Check-Normal value storeOn1 Bit1.3 enableCW
116B Load Check-Normal value recallCurrent (mA)2 Bytes7.12 current (mA)CRT
117B Load Check-Normal value recallCurrent (A)4 Bytes14.19 electric current (A)CRT
118B Load Check-Exceedance of load check limit valueOn / Off1 Bit1.2 booleanCRT
119B Load Check-Shortfall of load check limit valueOn / Off1 Bit1.2 booleanCRT
120B Load Check-Contact FailureOn / Off1 Bit1.2 booleanCRT
121C SwitchingOn / Off1 Bit1.1 switchCW
122C Control ValueValue1 Byte5.10 counter pulses (0..255)CW
122C Control ValueValue2 Bytes9.1 temperature (°C)CW
122C Control ValueValue1 Byte5.1 percentage (0..100%)CW
122C Control ValueValue2 Bytes9.4 lux (Lux)CW
122C Control ValueValue2 Bytes9.21 current (mA)CW
122C Control ValueValue2 Bytes9.24 power (kW)CW
122C Control ValueValue4 Bytes14.56 power (W)CW
123C Status switchingOn / Off1 Bit1.1 switchCRT
124C Logic operation 1On / Off1 Bit1.1 switchCW
125C Logic operation 2On / Off1 Bit1.1 switchCW
126C Central SwitchingOn / Off1 Bit1.1 switchCW
127C 8-bit scenerecall / store 1 Byte18.1 scene controlCW
128C Night modeOn / Off1 Bit1.3 enableCW
129C Night mode timerON time (seconds)2 Bytes7.5 time (s)CRW
130C Day mode timerON time 1 (seconds)2 Bytes7.5 time (s)CRW
131C Forced controlOn / Off2 Bit2.1 switch controlCW
132C Pre-warning expiration of timer periodOn / Off1 Bit1.1 switchCRT
133C Lock TimerOn / Off1 Bit1.3 enableCW
134C Override 1, Permanent OFFOn / Off1 Bit1.3 enableCW
134C Override 1, Manual ONOn / Off1 Bit1.3 enableCW
134C Override 1, LockOn / Off1 Bit1.3 enableCW
134C Override 1, Central ControlOn / Off1 Bit1.3 enableCW
134C Override 1, User-defined ControlOn / Off1 Bit1.3 enableCW
135C Override 1, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
135C Override 1, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
135C Override 1, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
135C Override 1, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
135C Override 1, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
135C Override 1, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
135C Override 1, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
135C Override 1, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
135C Override 1, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
135C Override 1, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
135C Override 1, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
135C Override 1, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
135C Override 1, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
135C Override 1, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
135C Override 1, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
135C Override 1, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
135C Override 1, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
135C Override 1, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
135C Override 1, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
135C Override 1, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
135C Override 1, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
135C Override 1, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
135C Override 1, Lock, ControlValue2 Bytes9.21 current (mA)CW
135C Override 1, Central Control, ControlValue2 Bytes9.21 current (mA)CW
135C Override 1, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
135C Override 1, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
135C Override 1, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
135C Override 1, Lock, ControlValue2 Bytes9.24 power (kW)CW
135C Override 1, Central Control, ControlValue2 Bytes9.24 power (kW)CW
135C Override 1, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
135C Override 1, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
135C Override 1, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
135C Override 1, Lock, ControlValue4 Bytes14.56 power (W)CW
135C Override 1, Central Control, ControlValue4 Bytes14.56 power (W)CW
135C Override 1, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
136C Override 1, Forced ControlOn / Off2 Bit2.1 switch controlCW
137C Override 1, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
137C Override 1, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
137C Override 1, Lock, StatusOn / Off1 Bit1.2 booleanCRT
137C Override 1, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
137C Override 1, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
137C Override 1, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
138C Override 2, Permanent OFFOn / Off1 Bit1.3 enableCW
138C Override 2, Manual ONOn / Off1 Bit1.3 enableCW
138C Override 2, LockOn / Off1 Bit1.3 enableCW
138C Override 2, Central ControlOn / Off1 Bit1.3 enableCW
138C Override 2, User-defined ControlOn / Off1 Bit1.3 enableCW
139C Override 2, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
139C Override 2, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
139C Override 2, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
139C Override 2, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
139C Override 2, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
139C Override 2, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
139C Override 2, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
139C Override 2, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
139C Override 2, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
139C Override 2, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
139C Override 2, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
139C Override 2, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
139C Override 2, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
139C Override 2, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
139C Override 2, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
139C Override 2, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
139C Override 2, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
139C Override 2, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
139C Override 2, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
139C Override 2, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
139C Override 2, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
139C Override 2, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
139C Override 2, Lock, ControlValue2 Bytes9.21 current (mA)CW
139C Override 2, Central Control, ControlValue2 Bytes9.21 current (mA)CW
139C Override 2, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
139C Override 2, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
139C Override 2, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
139C Override 2, Lock, ControlValue2 Bytes9.24 power (kW)CW
139C Override 2, Central Control, ControlValue2 Bytes9.24 power (kW)CW
139C Override 2, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
139C Override 2, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
139C Override 2, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
139C Override 2, Lock, ControlValue4 Bytes14.56 power (W)CW
139C Override 2, Central Control, ControlValue4 Bytes14.56 power (W)CW
139C Override 2, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
140C Override 2, Forced ControlOn / Off2 Bit2.1 switch controlCW
141C Override 2, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
141C Override 2, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
141C Override 2, Lock, StatusOn / Off1 Bit1.2 booleanCRT
141C Override 2, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
141C Override 2, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
141C Override 2, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
142C Override 3, Permanent OFFOn / Off1 Bit1.3 enableCW
142C Override 3, Manual ONOn / Off1 Bit1.3 enableCW
142C Override 3, LockOn / Off1 Bit1.3 enableCW
142C Override 3, Central ControlOn / Off1 Bit1.3 enableCW
142C Override 3, User-defined ControlOn / Off1 Bit1.3 enableCW
143C Override 3, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
143C Override 3, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
143C Override 3, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
143C Override 3, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
143C Override 3, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
143C Override 3, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
143C Override 3, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
143C Override 3, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
143C Override 3, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
143C Override 3, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
143C Override 3, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
143C Override 3, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
143C Override 3, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
143C Override 3, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
143C Override 3, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
143C Override 3, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
143C Override 3, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
143C Override 3, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
143C Override 3, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
143C Override 3, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
143C Override 3, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
143C Override 3, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
143C Override 3, Lock, ControlValue2 Bytes9.21 current (mA)CW
143C Override 3, Central Control, ControlValue2 Bytes9.21 current (mA)CW
143C Override 3, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
143C Override 3, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
143C Override 3, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
143C Override 3, Lock, ControlValue2 Bytes9.24 power (kW)CW
143C Override 3, Central Control, ControlValue2 Bytes9.24 power (kW)CW
143C Override 3, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
143C Override 3, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
143C Override 3, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
143C Override 3, Lock, ControlValue4 Bytes14.56 power (W)CW
143C Override 3, Central Control, ControlValue4 Bytes14.56 power (W)CW
143C Override 3, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
144C Override 3, Forced ControlOn / Off2 Bit2.1 switch controlCW
145C Override 3, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
145C Override 3, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
145C Override 3, Lock, StatusOn / Off1 Bit1.2 booleanCRT
145C Override 3, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
145C Override 3, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
145C Override 3, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
146C Override 4, Permanent OFFOn / Off1 Bit1.3 enableCW
146C Override 4, Manual ONOn / Off1 Bit1.3 enableCW
146C Override 4, LockOn / Off1 Bit1.3 enableCW
146C Override 4, Central ControlOn / Off1 Bit1.3 enableCW
146C Override 4, User-defined ControlOn / Off1 Bit1.3 enableCW
147C Override 4, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
147C Override 4, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
147C Override 4, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
147C Override 4, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
147C Override 4, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
147C Override 4, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
147C Override 4, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
147C Override 4, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
147C Override 4, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
147C Override 4, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
147C Override 4, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
147C Override 4, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
147C Override 4, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
147C Override 4, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
147C Override 4, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
147C Override 4, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
147C Override 4, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
147C Override 4, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
147C Override 4, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
147C Override 4, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
147C Override 4, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
147C Override 4, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
147C Override 4, Lock, ControlValue2 Bytes9.21 current (mA)CW
147C Override 4, Central Control, ControlValue2 Bytes9.21 current (mA)CW
147C Override 4, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
147C Override 4, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
147C Override 4, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
147C Override 4, Lock, ControlValue2 Bytes9.24 power (kW)CW
147C Override 4, Central Control, ControlValue2 Bytes9.24 power (kW)CW
147C Override 4, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
147C Override 4, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
147C Override 4, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
147C Override 4, Lock, ControlValue4 Bytes14.56 power (W)CW
147C Override 4, Central Control, ControlValue4 Bytes14.56 power (W)CW
147C Override 4, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
148C Override 4, Forced ControlOn / Off2 Bit2.1 switch controlCW
149C Override 4, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
149C Override 4, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
149C Override 4, Lock, StatusOn / Off1 Bit1.2 booleanCRT
149C Override 4, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
149C Override 4, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
149C Override 4, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
150C Override 5, Permanent OFFOn / Off1 Bit1.3 enableCW
150C Override 5, Manual ONOn / Off1 Bit1.3 enableCW
150C Override 5, LockOn / Off1 Bit1.3 enableCW
150C Override 5, Central ControlOn / Off1 Bit1.3 enableCW
150C Override 5, User-defined ControlOn / Off1 Bit1.3 enableCW
151C Override 5, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
151C Override 5, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
151C Override 5, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
151C Override 5, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
151C Override 5, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
151C Override 5, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
151C Override 5, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW
151C Override 5, Lock, ControlValue2 Bytes9.1 temperature (°C)CW
151C Override 5, Central Control, ControlValue2 Bytes9.1 temperature (°C)CW
151C Override 5, User-defined Control, Control ValueValue2 Bytes9.1 temperature (°C)CW
151C Override 5, Permanent OFF, Control ValueValue1 Byte5.1 percentage (0..100%)CW
151C Override 5, Manual ON, Control ValueValue1 Byte5.1 percentage (0..100%)CW
151C Override 5, Lock, ControlValue1 Byte5.1 percentage (0..100%)CW
151C Override 5, Central Control, ControlValue1 Byte5.1 percentage (0..100%)CW
151C Override 5, User-defined Control, Control ValueValue1 Byte5.1 percentage (0..100%)CW
151C Override 5, Permanent OFF, Control ValueValue2 Bytes9.4 lux (Lux)CW
151C Override 5, Manual ON, Control ValueValue2 Bytes9.4 lux (Lux)CW
151C Override 5, Lock, ControlValue2 Bytes9.4 lux (Lux)CW
151C Override 5, Central Control, ControlValue2 Bytes9.4 lux (Lux)CW
151C Override 5, User-defined Control, Control ValueValue2 Bytes9.4 lux (Lux)CW
151C Override 5, Permanent OFF, Control ValueValue2 Bytes9.21 current (mA)CW
151C Override 5, Manual ON, Control ValueValue2 Bytes9.21 current (mA)CW
151C Override 5, Lock, ControlValue2 Bytes9.21 current (mA)CW
151C Override 5, Central Control, ControlValue2 Bytes9.21 current (mA)CW
151C Override 5, User-defined Control, Control ValueValue2 Bytes9.21 current (mA)CW
151C Override 5, Permanent OFF, Control ValueValue2 Bytes9.24 power (kW)CW
151C Override 5, Manual ON, Control ValueValue2 Bytes9.24 power (kW)CW
151C Override 5, Lock, ControlValue2 Bytes9.24 power (kW)CW
151C Override 5, Central Control, ControlValue2 Bytes9.24 power (kW)CW
151C Override 5, User-defined Control, Control ValueValue2 Bytes9.24 power (kW)CW
151C Override 5, Permanent OFF, Control ValueValue4 Bytes14.56 power (W)CW
151C Override 5, Manual ON, Control ValueValue4 Bytes14.56 power (W)CW
151C Override 5, Lock, ControlValue4 Bytes14.56 power (W)CW
151C Override 5, Central Control, ControlValue4 Bytes14.56 power (W)CW
151C Override 5, User-defined Control, Control ValueValue4 Bytes14.56 power (W)CW
152C Override 5, Forced ControlOn / Off2 Bit2.1 switch controlCW
153C Override 5, Permanent-OFF, StatusOn / Off1 Bit1.2 booleanCRT
153C Override 5, Manual ON, StatusOn / Off1 Bit1.2 booleanCRT
153C Override 5, Lock, StatusOn / Off1 Bit1.2 booleanCRT
153C Override 5, Central Control, StatusOn / Off1 Bit1.2 booleanCRT
153C Override 5, User-defined Control, StatusOn / Off1 Bit1.2 booleanCRT
153C Override 5, Forced Control, StatusOn / Off1 Bit1.2 booleanCRT
154C Override 6, Permanent OFFOn / Off1 Bit1.3 enableCW
154C Override 6, Manual ONOn / Off1 Bit1.3 enableCW
154C Override 6, LockOn / Off1 Bit1.3 enableCW
154C Override 6, Central ControlOn / Off1 Bit1.3 enableCW
154C Override 6, User-defined ControlOn / Off1 Bit1.3 enableCW
155C Override 6, Permanent OFF, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
155C Override 6, Manual ON, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
155C Override 6, Lock, ControlValue1 Byte5.10 counter pulses (0..255)CW
155C Override 6, Central Control, ControlValue1 Byte5.10 counter pulses (0..255)CW
155C Override 6, User-defined Control, Control ValueValue1 Byte5.10 counter pulses (0..255)CW
155C Override 6, Permanent OFF, Control ValueValue2 Bytes9.1 temperature (°C)CW
155C Override 6, Manual ON, Control ValueValue2 Bytes9.1 temperature (°C)CW

First 1000 of 4394 group objects shown. Download the .knxprod for the full list.

Parameters (135)
ParameterTypeDefault
Cyclical transmission of device function (0=in operation)listDisable
Send status of device function inverted (1=in operation)listNo
Cyclical transmission periodtime120
Specific transmission time for status objects after bus voltage recoverytime15
Transmission delay between status objectstime1
Behaviour after downloadlistUse device parameter
Function Channel AlistSwitching
Function Channel BlistSwitching
Function Channel ClistSwitching
Function Channel DlistSwitching
Function Channel ElistSwitching
Function Channel FlistSwitching
Function Channel GlistSwitching
Function Channel HlistSwitching
Function Channel IlistSwitching
Function Channel JlistSwitching
Function Channel KlistSwitching
Function Channel LlistSwitching
not_visiblelistas before bus voltage failure
Last variantlistnot_visible
Warning before switching OfflistNo
8-bit scenes configurable by userlistDisable
not_visiblelistDeactivate timer
Limit night mode timerlistEnable
Exceedance of load check limit valuelistDisable
Shortfall of load check imit valuelistDisable
Value change since last sent (mA)unsignedInt 0…655350
Load ChecklistDisable
not_visibleunsignedInt 0…6553520
Override 1listDeactivated
enablelistDisable
Start value / behavior of override input on bus voltage recoverylistDeactivated
Restart timer on deactivation of overridelistEnable
Behavior on override activationlistno change
Behavior on override deactivationlistupdated value
Power up value (%)listOn
Invert Override ControllistNo
Monitoring Timetime0
Override Durationtime0
Status OverridelistEnable
Value at activation (%)unsignedInt 0…255255
Override 2listDeactivated
Override 3listDeactivated
Override 4listDeactivated
Override 5listDeactivated
Override 6listDeactivated
Override 7listDeactivated
not_visiblelistFalse
not_visiblelistnot_visible
not_visibleunsignedInt 0…2551
not_visibleunsignedInt 0…655351
Operation ModelistNormal mode
Relay modelistNormally Open
Control Value InputlistDisable
Central SwitchinglistDisable
8-bit scene controllistDisable
Overrides statuslistEnable
Send status on requestlistDisable
Send status on change of statuslistEnable
Send status cyclicallytime0
Status objectlistEnable
Switching state on bus voltage failurelistno change
Initial value after bus voltage recoverylistLast status of the switching value
Counting of switching cycleslistDisable
Counting of operating hourslistDisable
ON delaytime0
OFF delaytime0
ON delay (central switching)time0
OFF delay (central switching)time0
Night modelistDisable
ON time during night modetime1800
Retriggering possibleunsignedInt 0…51
Warning periodtime30
Warning signal periodtime1
Change ON time in night mode via objectlistDisable
Blocking characteritics for timer modelistDeactivate timer
ON time 1 during day modetime900
Change ON 1 time during day mode via objectlistDisable
Number of flashing cycles (0 = indefinite)unsignedInt 0…100005
ON time flashingtime1
OFF time flashingtime1
Data TypelistPercentage (%)
Threshold for Off (<=)unsignedInt 0…2550
Threshold for On (>=)unsignedInt 0…2551
Threshold for Off (<=)float -671088.6…670760.90
Threshold for On (>=)float -671088.6…670760.91
Threshold for On (>=)unsignedInt 0…2553
Threshold for Off (<=)unsignedInt 0…1000
Threshold for On (>=)unsignedInt 0…1001
Threshold for Off (<=)float -3.402823e+38…3.402823e+380
Threshold for On (>=)float -3.402823e+38…3.402823e+381
Logic operation 1listNo logic operation
Invert logical inputlistNo
Invert logical outputlistNo
Initial value of logic operation object after bus voltage recoverylistas before bus voltage failure
Logic operation 2listNo logic operation
Link 1 with scene [1…64] (0 = disable)unsignedInt 0…640
dummy_not_visibleunsignedInt 0…255192
Delete learned scenelistDisable
Predefine scenelistDisable
Predefined switching value for scenelistOff
Link 2 with scene [1…64] (0 = disable)unsignedInt 0…640
Link 3 with scene [1…64] (0 = disable)unsignedInt 0…640
Link 4 with scene [1…64] (0 = disable)unsignedInt 0…640
Link 5 with scene [1…64] (0 = disable)unsignedInt 0…640
Link 6 with scene [1…64] (0 = disable)unsignedInt 0…640
Link 7 with scene [1…64] (0 = disable)unsignedInt 0…640
Link 8 with scene [1…64] (0 = disable)unsignedInt 0…640
Control Value Input Data TypelistPercentage (%)
Current unitlistA
Scaling factor (value * 0,001)unsignedInt 1…655351000
Value offset (mA)signedInt -32768…327670
Load Check measured valuelistDisable
Send status on change of statuslistDisable
Value change since last sent (mA)unsignedInt 0…6553530
Blocktime for sending of statustime0
Load Check monitoringlistNo
Load Check normal value (mA)unsignedInt 0…65535150
Dead timetime10
Load Check offset above limit (mA)unsignedInt 0…6553515
Load Check hysteresis above limit (%)unsignedInt 0…10010
Load Check hysteresis above limit (mA)unsignedInt 0…25526
Load Check offset below limit (mA)unsignedInt 0…6553515
Load Check hysteresis below limit (%)unsignedInt 0…10010
Load Check hysteresis below limit (mA)unsignedInt 0…25526
Normal value recalllistDisable
Contact FailurelistDisable
Value change since last sent (cycles)unsignedInt 0…42949672951
Threshold monitoringlistDisable
Threshold for switching cyclesunsignedInt 0…42949672951000
Counting of operating hours inlisthours
Value change since last sent (hours)unsignedInt 0…42949672951
Value change since last sent (seconds)unsignedInt 0…42949672953600
Measure if load current flowlistDisable
Threshold for operating hoursunsignedInt 0…42949672951000

Version history

ApplicationApp noFingerprintFirst seenSizeFile
07 B0 A12 Switching Actuator 12-fold 9A0303 0.3 latest$9A03982D2026-11-251.6 MBDownload

About this file

This is the official ETS product database for the Schrack Technik GmbH Switching Actuator KXSK0CRC-- (KXSK0CRC--), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Schrack Technik GmbH

All Schrack Technik GmbH products