Analogue input REG-K/4-gang MTN682191
Schneider Electric Industries SAS · Order number MTN682191 · 2.8 Analogue Input › 2.8.01 DIN rail mounted REG-K
MTN682191
Download .knxprod Analogue output floating point/value B00A/0.1 0.1 · 125 KB
Product
| Manufacturer | Schneider Electric Industries SAS |
|---|---|
| Product name | Analogue input REG-K/4-gang |
| Order number | MTN682191 |
| Hardware | Analogeingang REG-K/4-fach |
| Medium | Twisted Pair |
| Rail mounted | Yes |
| Registration | Certified |
| Languages | en-US, de-DE, fr-FR, da-DK, nl-NL, it-IT, sv-SE, es-ES |
| Catalog entry | M-0064_H-MTN682191-1-O00F4_HP-B00A-01-9CA4-O00F4_CI-MTN682191-1 |
| Fingerprint | 9CA4 |
| SHA-256 | 3702b827fcd509178fab90fb69a60d552b6292cf498435d3f7248ea2ddf5259d |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Analogue output floating point/value B00A/0.1 0.1
| Application number | $B00A |
|---|---|
| Version | 0.1 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 549 |
| Group objects | 74 |
Group objects (74)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Alarm object | Analog input | 1 Bit | CTU | |
| 1 | Measuring value input 1 | Analog input | 2 Bytes | CTU | |
| 1 | Measuring value input 1 | Analog input | 1 Byte | CTU | |
| 2 | Measuring value input 2 | Analog input | 2 Bytes | CTU | |
| 2 | Measuring value input 2 | Analog input | 1 Byte | CTU | |
| 3 | Measuring value input 3 | Analog input | 2 Bytes | CTU | |
| 3 | Measuring value input 3 | Analog input | 1 Byte | CTU | |
| 4 | Measuring value input 4 | Analog input | 2 Bytes | CTU | |
| 4 | Measuring value input 4 | Analog input | 1 Byte | CTU | |
| 5 | Limit value 1 input 1 | Analog input | 1 Bit | CTU | |
| 6 | Limit value 2 input 1 | Analog input | 1 Bit | CTU | |
| 7 | Limit value 1 input 2 | Analog input | 1 Bit | CTU | |
| 8 | Limit value 2 input 2 | Analog input | 1 Bit | CTU | |
| 9 | Limit value 1 input 3 | Analog input | 1 Bit | CTU | |
| 10 | Limit value 2 input 3 | Analog input | 1 Bit | CTU | |
| 11 | Limit value 1 input 4 | Analog input | 1 Bit | CTU | |
| 12 | Limit value 2 input 4 | Analog input | 1 Bit | CTU | |
| 13 | External limit value 1 input 1 | Analog input | 1 Byte | CWU | |
| 13 | External limit value 1 input 1 | Analog input | 2 Bytes | CWU | |
| 14 | External limit value 2 input 1 | Analog input | 2 Bytes | CWU | |
| 14 | External limit value 2 input 1 | Analog input | 1 Byte | CWU | |
| 15 | External limit value 1 input 2 | Analog input | 1 Byte | CWU | |
| 15 | External limit value 1 input 2 | Analog input | 2 Bytes | CWU | |
| 16 | External limit value 2 input 2 | Analog input | 2 Bytes | CWU | |
| 16 | External limit value 2 input 2 | Analog input | 1 Byte | CWU | |
| 17 | External limit value 1 input 3 | Analog input | 1 Byte | CWU | |
| 17 | External limit value 1 input 3 | Analog input | 2 Bytes | CWU | |
| 18 | External limit value 2 input 3 | Analog input | 2 Bytes | CWU | |
| 18 | External limit value 2 input 3 | Analog input | 1 Byte | CWU | |
| 19 | External limit value 1 input 4 | Analog input | 1 Byte | CWU | |
| 19 | External limit value 1 input 4 | Analog input | 2 Bytes | CWU | |
| 20 | External limit value 2 input 4 | Analog input | 2 Bytes | CWU | |
| 20 | External limit value 2 input 4 | Analog input | 1 Byte | CWU | |
| 21 | Open-circuit monitoring input 1 | Analog input | 1 Bit | CTU | |
| 22 | Open-circuit monitoring input 2 | Analog input | 1 Bit | CTU | |
| 23 | Open-circuit monitoring input 3 | Analog input | 1 Bit | CTU | |
| 24 | Open-circuit monitoring input 4 | Analog input | 1 Bit | CTU | |
| 25 | Alarm object | Extension module | 1 Bit | CTU | |
| 26 | Measuring value input 5 | Extension module | 2 Bytes | CTU | |
| 26 | Measuring value input 5 | Extension module | 1 Byte | CTU | |
| 27 | Measuring value input 6 | Extension module | 2 Bytes | CTU | |
| 27 | Measuring value input 6 | Extension module | 1 Byte | CTU | |
| 28 | Measuring value input 7 | Extension module | 2 Bytes | CTU | |
| 28 | Measuring value input 7 | Extension module | 1 Byte | CTU | |
| 29 | Measuring value input 8 | Extension module | 2 Bytes | CTU | |
| 29 | Measuring value input 8 | Extension module | 1 Byte | CTU | |
| 30 | Limit value 1 input 5 | Extension module | 1 Bit | CTU | |
| 31 | Limit value 2 input 5 | Extension module | 1 Bit | CTU | |
| 32 | Limit value 1 input 6 | Extension module | 1 Bit | CTU | |
| 33 | Limit value 2 input 6 | Extension module | 1 Bit | CTU | |
| 34 | Limit value 1 input 7 | Extension module | 1 Bit | CTU | |
| 35 | Limit value 2 input 7 | Extension module | 1 Bit | CTU | |
| 36 | Limit value 1 input 8 | Extension module | 1 Bit | CTU | |
| 37 | Limit value 2 input 8 | Extension module | 1 Bit | CTU | |
| 38 | External limit value 1 input 5 | Extension module | 1 Byte | CWU | |
| 38 | External limit value 1 input 5 | Extension module | 2 Bytes | CWU | |
| 39 | External limit value 2 input 5 | Extension module | 2 Bytes | CWU | |
| 39 | External limit value 2 input 5 | Extension module | 1 Byte | CWU | |
| 40 | External limit value 1 input 6 | Extension module | 1 Byte | CWU | |
| 40 | External limit value 1 input 6 | Extension module | 2 Bytes | CWU | |
| 41 | External limit value 2 input 6 | Extension module | 2 Bytes | CWU | |
| 41 | External limit value 2 input 6 | Extension module | 1 Byte | CWU | |
| 42 | External limit value 1 input 7 | Extension module | 1 Byte | CWU | |
| 42 | External limit value 1 input 7 | Extension module | 2 Bytes | CWU | |
| 43 | External limit value 2 input 7 | Extension module | 2 Bytes | CWU | |
| 43 | External limit value 2 input 7 | Extension module | 1 Byte | CWU | |
| 44 | External limit value 1 input 8 | Extension module | 1 Byte | CWU | |
| 44 | External limit value 1 input 8 | Extension module | 2 Bytes | CWU | |
| 45 | External limit value 2 input 8 | Extension module | 2 Bytes | CWU | |
| 45 | External limit value 2 input 8 | Extension module | 1 Byte | CWU | |
| 46 | Open-circuit monitoring input 5 | Extension module | 1 Bit | CTU | |
| 47 | Open-circuit monitoring input 6 | Extension module | 1 Bit | CTU | |
| 48 | Open-circuit monitoring input 7 | Extension module | 1 Bit | CTU | |
| 49 | Open-circuit monitoring input 8 | Extension module | 1 Bit | CTU |
Parameters (57)
| Parameter | Type | Default |
|---|---|---|
| General parameters | list | no |
| Signal input 1 | list | no sensor |
| Open-circuit detection input 1 | list | no detection |
| Signal input 2 | list | no sensor |
| Open-circuit detection input 2 | list | no detection |
| Signal input 3 | list | no sensor |
| Open-circuit detection input 3 | list | no detection |
| Signal input 4 | list | no sensor |
| Open-circuit detection input 4 | list | no detection |
| Alarm analog input | list | no transmission |
| Extension module | list | no |
| Signal input 5 | list | no sensor |
| Open-circuit detection input 5 | list | no detection |
| Signal input 6 | list | no sensor |
| Open-circuit detection input 6 | list | no detection |
| Signal input 7 | list | no sensor |
| Open-circuit detection input 7 | list | no detection |
| Signal input 8 | list | no sensor |
| Open-circuit detection input 8 | list | no detection |
| Alarm extension module | list | no transmission |
| Measuring value 1 | list | no |
| Measuring value transmission format | list | 16 bit EIS5 |
| Measuring value for 0% of measuring signal (-32768...32767) | signedInt -32768…32767 | 0 |
| Base value 0% of measuring value (0...255) | signedInt 0…255 | 0 |
| Measuring value for 100% of measuring signal (-32768...32767) | signedInt -32768…32767 | 100 |
| Base value 100% of measuring value (0...255) | signedInt 0…255 | 255 |
| Measuring range scaling factor | list | * 0.01 |
| Transmit measuring value in the event of a change by | list | 3% |
| Measuring value cycl. transm. factor (base 10s, 0 = no cyclical transmission) | unsignedInt 0…120 | 0 |
| Measuring value 2 | list | no |
| Measuring value for 100% of measuring signal (-32768...32767) | signedInt -32768…32767 | 1000 |
| Measuring value 3 | list | no |
| Measuring value 4 | list | no |
| Measuring value 5 | list | no |
| Measuring value 6 | list | no |
| Measuring value 7 | list | no |
| Measuring value 8 | list | no |
| Input 1 | list | no |
| Limit value 1 (in % of measuring range) | unsignedInt 0…100 | 20 |
| Limit value hysteresis 1 | unsignedInt 0…100 | 10 |
| Limit value (LV) activation 1 | list | below LV = ON, above LV+hysteresis=OFF |
| External limit value LV 1 | list | no |
| Format of ext. limit value obj. LV 1 | list | 16 bit EIS5 |
| Limit value 1 cycl. transm. factor (base 10s, 0 = no cyclical transmission) | unsignedInt 0…120 | 0 |
| Limit value 2 (in % of measuring range) | unsignedInt 0…100 | 80 |
| Limit value hysteresis 2 | unsignedInt 0…100 | 10 |
| Limit value (LV) activation 2 | list | above LV = ON, below LV-hysteresis=OFF |
| External limit value LV 2 | list | no |
| Format of ext. limit value obj. LV 2 | list | 16 bit EIS5 |
| Limit value 2 cycl. transm. factor (base 10s, 0 = no cyclical transmission) | unsignedInt 0…120 | 0 |
| Input 2 | list | no |
| Input 3 | list | no |
| Input 4 | list | no |
| Input 5 | list | no |
| Input 6 | list | no |
| Input 7 | list | no |
| Input 8 | list | no |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Analogue output floating point/value B00A/0.1 0.1 latest | $B00A | 9CA4 | 2026-11-25 | 125 KB | Download |
About this file
This is the official ETS product database for the Schneider Electric Industries SAS Analogue input REG-K/4-gang (MTN682191), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Schneider Electric Industries SAS
- KNX FUGA Multif. push-button, display, RTCU, PI 507Dx042
- KNX FUGA Movement detector 180 507Dx350
- KNX FUGA Push-button 4 switch + LED 507Dx611
- KNX OPUS Multif. push-button, display, RTCU, PI 507Nx042
- KNX OPUS Movement detector 180 507Nx350
- KNX OPUS Push-button 4 switch + LED 507Nx611
- KNX Presence 507Z6352
- KNX Presence Basic 507Z6353
- KNX Presence with light control + IR 507Z6354
- KNX Push-button, 1-gang ALB4x150
- KNX Push-button, 2-gang ALB4x151
- KNX 1-gang push-button with IR receiver ALB4x152