KNX Database

Universal dimming actuator REG-K/4x230/250W MTN649325

Schneider Electric Industries SAS · Order number MTN649325 · 4.6 Dimming Actuator › 4.6.01 DIN rail mounted REG-K

MTN649325

Download .knxprod Universal dimming 3244/1.0 1.0 · 174 KB

Product

ManufacturerSchneider Electric Industries SAS
Product nameUniversal dimming actuator REG-K/4x230/250W
Order numberMTN649325
HardwareUniversal-Dimmaktor Multiphase REG-K
MediumTwisted Pair
Rail mountedYes
RegistrationCertified
Languagesen-US, de-DE, fr-FR, da-DK, nl-NL, it-IT, sv-SE, es-ES
Catalog entryM-0064_H-MTN649325-1-O000C_HP-3244-10-C229-O000C_CI-MTN649325-1
FingerprintC229
SHA-2565a4e49278664aee84390b9f14cd3eb68054c82b5a839fa4be4f363c45561ef96
First seen2026-11-25
Markets59 markets

Application program: Universal dimming 3244/1.0 1.0

Application number$3244
Version1.0
Mask versionMV-0021 (2.1)
KNX Data SecureNo
Parameters697
Group objects65
Group objects (65)
NoNameFunctionSizeDPTFlags
0Switching objectChannel 1, General1 BitCW
1Dimming objectChannel 1, General4 BitCW
2Value objectChannel 1, General1 ByteCW
3Set objectChannel 1, Dimming speed1 ByteCW
4Dimming time reductionChannel 1, Dimming speed1 ByteCW
5Staircase lighting objectChannel 1, Staircase lighting1 BitCW
6Logic objectChannel 1, Higher level funct.1 BitCW
6Priority controlChannel 1, Higher level funct.2 BitCW
7Disable objectChannel 1, Higher level funct.1 BitCW
8Status feedback switchChannel 1, Status feedback1 BitCT
8Status switchChannel 1, Status1 BitCR
9Status feedback value object/brightness valueChannel 1, Status feedback1 ByteCT
9Status value object/brightness valueChannel 1, Status1 ByteCR
10Switching objectChannel 2, general1 BitCW
11Dimming objectChannel 2, general4 BitCW
12Value objectChannel 2, general1 ByteCW
13Set objectChannel 2, dimming speed1 ByteCW
14Dimming time reductionChannel 2, dimming speed1 ByteCW
15Staircase lighting objectChannel 2, Staircase lighting1 BitCW
16Logic objectChannel 2, higher level funct.1 BitCW
16Priority controlChannel 2, higher level funct.2 BitCW
17Disable objectChannel 2, higher level funct.1 BitCW
18Status feedback switchChannel 2, status feedback1 BitCT
18Status switchChannel 2, status1 BitCR
19Status feedback value object/brightness valueChannel 2, status feedback1 ByteCT
19Status value object/brightness valueChannel 2, status1 ByteCR
20Switching objectChannel 3, general1 BitCW
21Dimming objectChannel 3, general4 BitCW
22Value objectChannel 3, general1 ByteCW
23Set objectChannel 3, dimming speed1 ByteCW
24Dimming time reductionChannel 3, dimming speed1 ByteCW
25Staircase lighting objectChannel 3, Staircase lighting1 BitCW
26Logic objectChannel 3, higher level funct.1 BitCW
26Priority controlChannel 3, higher level funct.2 BitCW
27Disable objectChannel 3, higher level funct.1 BitCW
28Status feedback switchChannel 3, status feedback1 BitCT
28Status switchChannel 3, status1 BitCR
29Status feedback value object/brightness valueChannel 3, status feedback1 ByteCT
29Status value object/brightness valueChannel 3, status1 ByteCR
30Switching objectChannel 4, general1 BitCW
31Dimming objectChannel 4, general4 BitCW
32Value objectChannel 4, general1 ByteCW
33Set objectChannel 4, dimming speed1 ByteCW
34Dimming time reductionChannel 4, dimming speed1 ByteCW
35Staircase lighting objectChannel 4, Staircase lighting1 BitCW
36Logic objectChannel 4, higher level funct.1 BitCW
36Priority controlChannel 4, higher level funct.2 BitCW
37Disable objectChannel 4, higher level funct.1 BitCW
38Status feedback switchChannel 4, status feedback1 BitCT
38Status switchChannel 4, status1 BitCR
39Status feedback value object/brightness valueChannel 4, status feedback1 ByteCT
39Status value object/brightness valueChannel 4, status1 ByteCR
40Scene objectScenes1 ByteCW
41Recall scene 1/2Scene extension unit1 BitCW
42Recall scene 3/4Scene extension unit1 BitCW
43Save scene 1/2Scene extension unit1 BitCW
44Save scene 3/4Scene extension unit1 BitCW
45Switching object centralCentral function1 BitCW
46Central dimming objectCentral function4 BitCW
47Central value objectCentral function1 ByteCW
48Status feedback errorStatus feedback1 BitCT
48Status errorStatus1 BitCR
49Disable channel operationOperation1 BitCRW
50Disable extension inputsOperation1 BitCRW
51Factor for identical dimming timeSame dimming time1 ByteCW
Parameters (205)
ParameterTypeDefault
GenerallistDummy
Internal ETS identification highunsignedInt 66…10068
Internal ETS identification lowunsignedInt 50…5050
Internal ETS version highunsignedInt 64…6464
Internal ETS version lowunsignedInt 0…00
Channel 1listDeactivated
Channel 2listDeactivated
Channel 3listDeactivated
Channel 4listDeactivated
SceneslistDisabled
Extension unit sceneslistDisabled
Central functionlistDisabled
Switching object centrallistActivated
Central dimming objectlistDeactivated
Central value objectlistDeactivated
Same dimming time at central function and sceneslistDisabled
Channel operationlistEnabled
Extension inputslistEnabled
Status errorlistDeactivated
Same dimming timelistDummy
Time base for same dimming timelist1 s
Time factor for same dimming time 1-255unsignedInt 1…2555
Time factor for same dimming time changeable via buslistDeactivated
1: GenerallistDummy
Minimum dimming value in %unsignedInt 1…10015
Maximum dimming value in %unsignedInt 1…100100
Starting behaviourlistMax. brightness
Initial brightness in %unsignedInt 5…100100
Base dimming curvelistIncandescent lamps
Dimming object switches channellistOnly ON, not OFF
Value object switches channellistON and OFF
Extension input influenceslistSwitching object
Extension inputlistEnabled
Delay timeslistDisabled
Staircase lighting functionlistDeactivated
Switching object effectivelistUnchanged
Higher level functionlistDeactivated
Disable functionlistDeactivated
Behaviour on bus voltage recovery and downloadlistNo reaction
Status switchlistDeactivated
Status value object/brightness valuelistDeactivated
1: Base dimming curvelistDummy
1st threshold value in %unsignedInt 0…10025
2nd threshold value in %unsignedInt 0…10050
3rd threshold value in %unsignedInt 0…10075
Time base of 1st dimming sectionlist100 ms
Time factor of 1st dimming section (1-255)unsignedInt 1…255230
Time base of 2nd dimming sectionlist100 ms
Time factor of 2nd dimming section (1-255)unsignedInt 1…255180
Time base of 3rd dimming sectionlist100 ms
Time factor of 3rd dimming section (1-255)unsignedInt 1…255120
Time base of 4th dimming sectionlist100 ms
Time factor of 4th dimming section (1-255)unsignedInt 1…25570
1: Dimming time reductionlistDummy
Dimming time reduction object for dimming curvelistDeactivated
Format of dimming time reductionlist1-100 %
For switching telegrams and staircase lighting switch on atlist2 %
For switching telegrams and staircase lighting switch on at x/2.55 %unsignedInt 1…2555
For dimming telegrams tolist6 %
For dimming telegrams to x/2.55 %unsignedInt 1…25516
For staircase lighting switch off atlist50 %
For staircase lighting switch off at x/2.55 %unsignedInt 1…255128
For value telegrams atlist20 %
For value telegrams at x/2.55 %unsignedInt 1…25551
For scene telegrams atlist32 %
For scene telegrams at x/2.55 %unsignedInt 1…25582
For higher level functions atlist2 %
For higher level functions at x/2.55 %unsignedInt 1…2555
Set 1 - 3listDisabled
For switching telegrams and staircase lighting switch on atlist6 %
For switching telegrams and staircase lighting switch on at x/2.55 %unsignedInt 1…25515
For dimming telegrams tolist20 %
For dimming telegrams to x/2.55 %unsignedInt 1…25551
For staircase lighting switch off atlist70 %
For staircase lighting switch off at x/2.55 %unsignedInt 1…255179
For value telegrams atlist30 %
For value telegrams at x/2.55 %unsignedInt 1…25577
For scene telegrams atlist70 %
For scene telegrams at x/2.55 %unsignedInt 1…255179
For higher level functions atlist5 %
For higher level functions at x/2.55 %unsignedInt 1…25513
For switching telegrams and staircase lighting switch on atlist3 %
For switching telegrams and staircase lighting switch on at x/2.55 %unsignedInt 1…2558
For dimming telegrams tolist15 %
For dimming telegrams to x/2.55 %unsignedInt 1…25538
For staircase lighting switch off atlist40 %
For staircase lighting switch off at x/2.55 %unsignedInt 1…255102
For value telegrams atlist15 %
For value telegrams at x/2.55 %unsignedInt 1…25538
For scene telegrams atlist25 %
For scene telegrams at x/2.55 %unsignedInt 1…25564
For higher level functions atlist3 %
For higher level functions at x/2.55 %unsignedInt 1…2558
For switching telegrams and staircase lighting switch on atlist1 %
For switching telegrams and staircase lighting switch on at x/2.55 %unsignedInt 1…2553
For dimming telegrams tolist7 %
For dimming telegrams to x/2.55 %unsignedInt 1…25518
For staircase lighting switch off atlist25 %
For staircase lighting switch off at x/2.55 %unsignedInt 1…25564
For value telegrams atlist10 %
For value telegrams at x/2.55 %unsignedInt 1…25526
For scene telegrams atlist20 %
For scene telegrams at x/2.55 %unsignedInt 1…25551
For higher level functions atlist1 %
For higher level functions at x/2.55 %unsignedInt 1…2553
1: Delay timeslistDummy
ON delaylistDeactivated
Output during ON delaylistSwitched off
Time base for ON delaylist1 min.
Time factor for ON delay (1-255)unsignedInt 1…2553
OFF delaylistDeactivated
Time base for OFF delaylist1 min.
Time factor for OFF delay (1-255)unsignedInt 1…2553
1: Staircase timerlistDummy
Staircase lighting functionlistNot retriggerable with manual OFF
Time base for staircase timerlist1 min.
Max. number of time accumulations (1-255)unsignedInt 1…2553
Time factor for staircase timer (1-255)unsignedInt 1…2553
Staircase lighting object effectivelistUnchanged
Staircase lighting objectlistUnchanged
Disconnection warning for staircase timerlistDeactivated
Warning time for staircase timer in seconds (1-255)unsignedInt 1…25530
1: SceneslistDummy
Overwrite scene values in the actuator during downloadlistActivated
Same dimming timelistDeactivated
Scene 1listDeactivated
Scene 1: Scene number (0-63)unsignedInt 0…630
Scene 1: Brightness value in %unsignedInt 0…10015
Scene 2listDeactivated
Scene 2: Scene number (0-63)unsignedInt 0…631
Scene 2: Brightness value in %unsignedInt 0…10035
Scene 3listDeactivated
Scene 3: Scene number (0-63)unsignedInt 0…632
Scene 3: Brightness value in %unsignedInt 0…10050
Scene 4listDeactivated
Scene 4: Scene number (0-63)unsignedInt 0…633
Scene 4: Brightness value in %unsignedInt 0…10065
Scene 5listDeactivated
Scene 5: Scene number (0-63)unsignedInt 0…634
Scene 5: Brightness value in %unsignedInt 0…10080
Scene 6listDeactivated
Scene 6: Scene number (0-63)unsignedInt 0…635
Scene 6: Brightness value in %unsignedInt 0…10080
Scene 7listDeactivated
Scene 7: Scene number (0-63)unsignedInt 0…636
Scene 7: Brightness value in %unsignedInt 0…10080
Scene 8listDeactivated
Scene 8: Scene number (0-63)unsignedInt 0…637
Scene 8: Brightness value in %unsignedInt 0…10080
1: Central functionlistDummy
Function at switching object central = 0listSwitch off
Desired brightness at switching object central = 0 in %unsignedInt 5…100100
Function at switching object central = 1listSwitch on at selectable brightness
Desired brightness at switching object central = 1 in %unsignedInt 5…100100
1: Logic operationlistDummy
Logic operationlistOR
Logic object effectivelistUnchanged
Value of logic object after bus voltage recovery and downloadlist1
Brightness at logic object "0" in %unsignedInt 0…1000
Brightness at logic object "1" in %unsignedInt 0…1000
1: Priority controllistDummy
Behaviour at start of priority control "ON"listSwitch on at selectable brightness
Desired brightness at start of priority control "ON" in %unsignedInt 5…100100
Behaviour at start of priority control "OFF"listSwitch off
Desired brightness at start of priority control "OFF" in %unsignedInt 5…100100
Behaviour at end of priority controllistFollows secondary functions
Desired brightness at end of priority control in %unsignedInt 5…100100
Behaviour of priority control after bus voltage recoverylistInactive
1: Disable functionlistDummy
LockinglistAt object value "1"
Behaviour at the start of lockinglistNo reaction
Desired brightness at start of disable function in %unsignedInt 5…100100
Behaviour at the end of lockinglistNo reaction
Desired brightness at end of disable function in %unsignedInt 5…100100
Status of locking after bus voltage recoverylistInactive
2: GenerallistDummy
2: Base dimming curvelistDummy
2: Dimming time reductionlistDummy
2: Delay timeslistDummy
2: Staircase timerlistDummy
2: SceneslistDummy
2: Central functionlistDummy
2: Logic operationlistDummy
2: Priority controllistDummy
2: Disable functionlistDummy
3: GenerallistDummy
3: Base dimming curvelistDummy
3: Dimming time reductionlistDummy
3: Delay timeslistDummy
3: Staircase timerlistDummy
3: SceneslistDummy
3: Central functionlistDummy
3: Logic operationlistDummy
3: Priority controllistDummy
3: Disable functionlistDummy
4: GenerallistDummy
4: Base dimming curvelistDummy
4: Dimming time reductionlistDummy
4: Delay timeslistDummy
4: Staircase timerlistDummy
4: SceneslistDummy
4: Central functionlistDummy
4: Logic operationlistDummy
4: Priority controllistDummy
4: Disable functionlistDummy

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Universal dimming 3244/1.0 1.0 latest$3244C2292026-11-25174 KBDownload

About this file

This is the official ETS product database for the Schneider Electric Industries SAS Universal dimming actuator REG-K/4x230/250W (MTN649325), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Schneider Electric Industries SAS

All Schneider Electric Industries SAS products