KNX Database
Panasonic WRKT5512E-XXX 2 Gang Dimming Actuator 300W  DM102

2 Gang Dimming Actuator 300W DM102 WRKT5512E-XXX

Panasonic · Order number WRKT5512E-XXX · Lighting › Dimmer

2 Channels Dimming Actuator 300W

Download .knxprod Dim-Act-2Ch 1.0 · 77 KB

Product

ManufacturerPanasonic
Product name2 Gang Dimming Actuator 300W DM102
Order numberWRKT5512E-XXX
HardwareHW 2 Ch Dimming Actuator
MediumTwisted Pair
Rail mountedYes
RegistrationCertified · 2018-06-08
Catalog entryM-008B_H-805486.2DP-1_HP-0304-10-4F94_CI-WRKT5512E.2DXXX-1
Fingerprint4F94
SHA-256e3a95345eb15c874a3ce6ba7769eaabd0e7ad9df86f5d3864f856945e1acbaf1
First seen2026-11-25
Markets59 markets

Application program: Dim-Act-2Ch 1.0

Application number$0304
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters127
Group objects36
Group objects (36)
NoNameFunctionSizeDPTFlags
0Channel 1 SwitchingSwitch On/Off1 Bit1.1 switchCWU
1Channel 1 DimmingRelative dimming4 Bit3.7 dimming controlCRWU
2Channel 1 DimmingAbsolute dimming1 Byte5.1 percentage (0..100%)CWU
3Channel 1 SwitchingSoft switching1 Bit1.1 switchCWU
4Channel 1 FeedbackSwitch On Off feedback1 Bit1.1 switchCRTU
5Channel 1 FeedbackBrightness feedback1 Byte5.1 percentage (0..100%)CRTU
6Channel 1 SupplementaryDisable1 Bit1.1 switchCRWU
7Channel 1 SupplementaryForced position2 Bit2.1 switch controlCRWU
8Channel 1 LogicOR1 Bit1.1 switchCRWU
8Channel 1 LogicAND1 Bit1.1 switchCRWU
9Channel 1 WarningShort circuit / High load1 Bit1.5 alarmCRTU
10Channel 1 WarningOver temperature1 Bit1.5 alarmCRTU
11Channel 1 WarningOverload1 Bit1.5 alarmCRTU
12Channel 1 CounterOperating hours counter (h)2 Bytes7.7 time (h)CRTU
13Channel 1 CounterRestart hours counters1 Bit1.1 switchCWU
14Channel 1 StatusChannel Status1 Bit1.3 enableCRTU
15Channel 1 CounterOperating hours counter (s)4 Bytes13.100 time lag (s)CRTU
17Channel 2 SwitchingSwitch On/Off1 Bit1.1 switchCWU
18Channel 2 DimmingRelative dimming4 Bit3.7 dimming controlCRWU
19Channel 2 DimmingAbsolute dimming1 Byte5.1 percentage (0..100%)CWU
20Channel 2 SwitchingSoft switching1 Bit1.1 switchCWU
21Channel 2 FeedbackSwitch On Off feedback1 Bit1.1 switchCRTU
22Channel 2 FeedbackBrightness feedback1 Byte5.1 percentage (0..100%)CRTU
23Channel 2 SupplementaryDisable1 Bit1.1 switchCRWU
24Channel 2 SupplementaryForced position2 Bit2.1 switch controlCRWU
25Channel 2 LogicOR1 Bit1.1 switchCRWU
25Channel 2 LogicAND1 Bit1.1 switchCRWU
26Channel 2 WarningShort circuit / High load1 Bit1.5 alarmCRTU
27Channel 2 WarningOver temperature1 Bit1.5 alarmCRTU
28Channel 2 WarningOverload1 Bit1.5 alarmCRTU
29Channel 2 CounterOperating hours counter (h)2 Bytes7.7 time (h)CRTU
30Channel 2 CounterRestart hours counters1 Bit1.1 switchCWU
31Channel 2 StatusChannel Status1 Bit1.3 enableCRTU
32Channel 2 CounterOperating hours counter (s)4 Bytes13.100 time lag (s)CRTU
68Central SwitchingSwitch On/Off1 Bit1.1 switchCWU
69Access/Save SceneDimming1 Byte18.1 scene controlCRWU
Parameters (67)
ParameterTypeDefault
Cycle time for sending of feedback objectslist5 min.
Delay for feedbacks after bus voltage returnlist5 min.
Report operating hours at changeunsignedInt 1…650001
Feedback cycle time for operating hours counterlist5 min.
Manual controllistYes
Blinking ratelist1 sec.
Type of connected loadlistUniversal
Minimum brightness (%)unsignedInt 1…451
Response when receiving a dimming valuelistImmediate ON
Maximum brightness (%)unsignedInt 50…100100
Switch-ON brightnesslistMinimum brightness
Assignment to Central Switching?listNo
Behaviour after bus failurelistNo change
Behaviour after restoration of the bus/mains powerlistSame as before bus failure
Time for Soft ON (sec.)unsignedInt 0…6010
Dimming value after Soft ON (%)unsignedInt 10…100100
Time between Soft ON and Soft OFFlistUntil "Soft Off" telegram
Time for Soft OFF (sec.)unsignedInt 0…6010
Characteristic curvelistLinear
Dimming time between Min. to Max. brigthness (sec.)unsignedInt 1…6010
1st area dimming time (sec.)unsignedInt 1…6010
Brigthness value for the 1st area (%)unsignedInt 1…10020
2nd area dimming time (sec.)unsignedInt 1…6010
Brigthness value for the 2nd area (%)unsignedInt 1…10060
3rd area dimming time (sec.)unsignedInt 1…6010
Sending switch on off feedbacklistNo
Sending brigthness feedbacklistNo
Operating hours counterlistDisable
Transmit operating hours cyclicallylistNo
Send overtemperature errorlistNo
Send short circuit errorlistNo
Send overload errorlistNo
Scene1 activatable by scene numberlistScene number 1
Storage function for scene1listNo
Scene1 after download (%)unsignedInt 0…10010
Scene2 after download (%)unsignedInt 0…10020
Storage function for scene2listNo
Scene2 activatable by scene numberlistScene number 2
Scene3 activatable by scene numberlistScene number 3
Storage function for scene3listNo
Scene3 after download (%)unsignedInt 0…10030
Scene4 after download (%)unsignedInt 0…10040
Storage function for scene4listNo
Scene4 activatable by scene numberlistScene number 4
Scene5 activatable by scene numberlistScene number 5
Storage function for scene5listNo
Scene5 after download (%)unsignedInt 0…10050
Scene6 after download (%)unsignedInt 0…10060
Storage function for scene6listNo
Scene6 activatable by scene numberlistScene number 6
Scene7 activatable by scene numberlistScene number 7
Storage function for scene7listNo
Scene7 after download (%)unsignedInt 0…10070
Scene8 after download (%)unsignedInt 0…10080
Storage function for scene8listNo
Scene8 activatable by scene numberlistScene number 8
Selection of supplementary functionlistNo supplementary function
Behaviour at the beginning of the disabling functionlistSwitch off
Behaviour at the end of the disabling functionlistSwitch off
Brightness for forced position "active, switch on"listMinimum brightness
Brigthness for forced position "end inactive"listNo reaction
Logic operation function ?listNo logic function
Behaviour when recalling a scenelistImmediate ON
Brigthness for forced position "active, switch off"listSwitch Off
Automatic switch off at minimum brigthnesslistNo
Cycle time for sending of error and status objectslist5 min.
Send channel statuslistNo

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Dim-Act-2Ch 1.0 latest$03044F942026-11-2577 KBDownload

About this file

This is the official ETS product database for the Panasonic 2 Gang Dimming Actuator 300W DM102 (WRKT5512E-XXX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Panasonic

All Panasonic products