KNX Database
Optimus OPT-MSx-212 OPT-MSx-212 Advanced Multi Sensor

OPT-MSx-212 Advanced Multi Sensor OPT-MSx-212

Optimus · Order number OPT-MSx-212 · Physical Sensor › Movement

Multi Sensor, PIR

Download .knxprod Motion, Brightness, Temperature, Humidity, Air Quality, Room Temperature Controller, Logic Controller 1.2 · 270 KB

Product

ManufacturerOptimus
Product nameOPT-MSx-212 Advanced Multi Sensor
Order numberOPT-MSx-212
HardwareOPT-MSx-212
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2024-10-22
Languagestr-TR, en-US
Catalog entryM-0234_H-103100-18_HP-AC20-12-3C8C_CI-OPT.2DMSx.2D212-3
Fingerprint3C8C
SHA-2560a4208fbb6014d421d3b558e460332fe79effe75400261850320218a3b5ab079
First seen2026-11-25
Markets69 markets

Application program: Motion, Brightness, Temperature, Humidity, Air Quality, Room Temperature Controller, Logic Controller 1.2

Application number$AC20
Version1.2
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters1234
Group objects373
Group objects (373)
NoNameFunctionSizeDPTFlags
0Movement Application - {{Number}}Enable Input1 Bit1.3 enableCW
0Constant Brightness Control - {{Number}}Enable Input1 Bit1.3 enableCRWT
0HVAC ApplicationEnable Input1 Bit1.3 enableCW
0Sensor | BrightnessEnable Input1 Bit1.3 enableCW
0Sensor | TemperatureEnable Input1 Bit1.3 enableCW
0Sensor | HumidityEnable Input1 Bit1.3 enableCW
0Sensor | Air QualityEnable Input1 Bit1.3 enableCW
0LA - {{Number}} | Inactivity MonitorStart/Stop Monitoring1 Bit1.10 start/stopCRWT
0LA - {{Number}} | Filter/DelayInput1 Bit1.1 switchCW
0LA - {{Number}} | Filter/DelayInput1 Byte5.10 counter pulses (0..255)CW
0LA - {{Number}} | Filter/DelayInput1 Byte6.10 counter pulses (-128..127)CW
0LA - {{Number}} | Filter/DelayInput1 Byte5.1 percentage (0..100%)CW
0LA - {{Number}} | Filter/DelayInput2 Bytes7.1 pulsesCW
0LA - {{Number}} | Filter/DelayInput2 Bytes8.1 pulses differenceCW
0LA - {{Number}} | Filter/DelayInput2 Bytes9.1 temperature (°C)CW
0LA - {{Number}} | Filter/DelayInput4 Bytes12.1 counter pulses (unsigned)CW
0LA - {{Number}} | Filter/DelayInput4 Bytes13.1 counter pulses (signed)CW
0LA - {{Number}} | Filter/DelayInput4 BytesDPT.14CW
0LA - {{Number}} | PresetCall Preset1 Bit1.22 sceneCW
0LA - {{Number}} | Logic GateInput - 11 Bit1.1 switchCW
0LA - {{Number}} | GateInput1 Bit1.1 switchCW
0LA - {{Number}} | GateInput4 BitDPT.3CW
0LA - {{Number}} | GateInput1 Byte5.10 counter pulses (0..255)CW
0LA - {{Number}} | GateInput1 Byte6.10 counter pulses (-128..127)CW
0LA - {{Number}} | GateInput1 Byte5.1 percentage (0..100%)CW
0LA - {{Number}} | GateInput2 Bytes7.1 pulsesCW
0LA - {{Number}} | GateInput2 Bytes8.1 pulses differenceCW
0LA - {{Number}} | GateInput2 Bytes9.1 temperature (°C)CW
0LA - {{Number}} | ThresholdInput1 Byte5.10 counter pulses (0..255)CW
0LA - {{Number}} | ThresholdInput1 Byte6.10 counter pulses (-128..127)CW
0LA - {{Number}} | ThresholdInput1 Byte5.1 percentage (0..100%)CW
0LA - {{Number}} | ThresholdInput2 Bytes7.1 pulsesCW
0LA - {{Number}} | ThresholdInput2 Bytes8.1 pulses differenceCW
0LA - {{Number}} | ThresholdInput2 Bytes9.1 temperature (°C)CW
0LA - {{Number}} | ThresholdInput4 Bytes12.1 counter pulses (unsigned)CW
0LA - {{Number}} | ThresholdInput4 Bytes13.1 counter pulses (signed)CW
0LA - {{Number}} | ThresholdInput4 BytesDPT.14CW
0LA - {{Number}} | SceneLight Scene Number1 Byte18.1 scene controlCW
0Output - {{Number}} | SwitchSwitch1 Bit1.1 switchCW
0Output - 1...2 | Shutter/BlindMove1 Bit1.8 up/downCW
0Output - 1...2 | 3-Point ValveHeating Valve Control Value1 Byte5.1 percentage (0..100%)CW
0Output - 1...2 | 3-Point ValveCooling Valve Control Value1 Byte5.1 percentage (0..100%)CW
1Movement Application - {{Number}}Slave Output1 Bit1.1 switchCT
1Constant Brightness Control - {{Number}}Start Stop1 Bit1.10 start/stopCRWT
1HVAC ApplicationSlave Input1 Bit1.1 switchCW
1Sensor | BrightnessValue Output2 Bytes9.4 lux (Lux)CRT
1Sensor | TemperatureValue Output2 Bytes9.1 temperature (°C)CRT
1Sensor | HumiditySensor Output2 Bytes9.7 humidity (%)CRT
1Sensor | Air QualitySensor Output (VOC Index)2 Bytes7.1 pulsesCRT
1LA - {{Number}} | Inactivity MonitorMovement Input1 Bit1.1 switchCW
1LA - {{Number}} | Filter/DelayOutput1 Bit1.1 switchCT
1LA - {{Number}} | Filter/DelayOutput1 Byte5.10 counter pulses (0..255)CT
1LA - {{Number}} | Filter/DelayOutput1 Byte6.10 counter pulses (-128..127)CT
1LA - {{Number}} | Filter/DelayOutput1 Byte5.1 percentage (0..100%)CT
1LA - {{Number}} | Filter/DelayOutput2 Bytes7.1 pulsesCT
1LA - {{Number}} | Filter/DelayOutput2 Bytes8.1 pulses differenceCT
1LA - {{Number}} | Filter/DelayOutput2 Bytes9.1 temperature (°C)CT
1LA - {{Number}} | Filter/DelayOutput4 Bytes12.1 counter pulses (unsigned)CT
1LA - {{Number}} | Filter/DelayOutput4 Bytes13.1 counter pulses (signed)CT
1LA - {{Number}} | Filter/DelayOutput4 BytesDPT.14CT
1LA - {{Number}} | PresetOutput - 11 Bit1.1 switchCT
1LA - {{Number}} | PresetOutput - 11 Byte5.10 counter pulses (0..255)CT
1LA - {{Number}} | PresetOutput - 12 Bytes7.1 pulsesCT
1LA - {{Number}} | PresetOutput - 12 Bytes8.1 pulses differenceCT
1LA - {{Number}} | PresetOutput - 12 Bytes9.1 temperature (°C)CT
1LA - {{Number}} | Logic GateInput - 21 Bit1.1 switchCW
1LA - {{Number}} | GateControl Input1 Bit1.3 enableCW
1LA - {{Number}} | ThresholdOutput1 Bit1.1 switchCT
1LA - {{Number}} | ThresholdOutput1 Byte5.10 counter pulses (0..255)CT
1LA - {{Number}} | ThresholdOutput1 Byte6.10 counter pulses (-128..127)CT
1LA - {{Number}} | ThresholdOutput1 Byte5.1 percentage (0..100%)CT
1LA - {{Number}} | SceneChannel - 1 Output1 Bit1.1 switchCT
1LA - {{Number}} | SceneChannel - 1 Output1 Bit1.8 up/downCT
1LA - {{Number}} | SceneChannel - 1 Output1 Byte5.10 counter pulses (0..255)CT
1LA - {{Number}} | SceneChannel - 1 Output1 Byte5.1 percentage (0..100%)CT
1LA - {{Number}} | SceneChannel - 1 Output2 Bytes9.1 temperature (°C)CT
1Input - {{Number}} | Value SenderPress Output1 Bit1.1 switchCT
1Input - {{Number}} | Value SenderPress Output1 Byte5.10 counter pulses (0..255)CT
1Input - {{Number}} | Value SenderPress Output1 Byte6.10 counter pulses (-128..127)CT
1Input - {{Number}} | Value SenderPress Output1 Byte5.1 percentage (0..100%)CT
1Input - {{Number}} | Value SenderPress Output1 Byte17.1 scene numberCT
1Input - {{Number}} | Value SenderPress Output1 Byte20.102 HVAC modeCT
1Input - {{Number}} | Value SenderPress Output2 Bytes7.1 pulsesCT
1Input - {{Number}} | Value SenderPress Output2 Bytes8.1 pulses differenceCT
1Input - {{Number}} | Value SenderPress Output2 Bytes9.1 temperature (°C)CT
1Input - {{Number}} | Value SenderOutput (Short Press)1 Bit1.1 switchCT
1Input - {{Number}} | Value SenderOutput (Short Press)1 Byte5.10 counter pulses (0..255)CT
1Input - {{Number}} | Value SenderOutput (Short Press)1 Byte6.10 counter pulses (-128..127)CT
1Input - {{Number}} | Value SenderOutput (Short Press)1 Byte5.1 percentage (0..100%)CT
1Input - {{Number}} | Value SenderOutput (Short Press)1 Byte17.1 scene numberCT
1Input - {{Number}} | Value SenderOutput (Short Press)1 Byte20.102 HVAC modeCT
1Input - {{Number}} | Value SenderOutput (Short Press)2 Bytes7.1 pulsesCT
1Input - {{Number}} | Value SenderOutput (Short Press)2 Bytes8.1 pulses differenceCT
1Input - {{Number}} | Value SenderOutput (Short Press)2 Bytes9.1 temperature (°C)CT
1Input - {{Number}} | Shutter/BlindMove1 Bit1.8 up/downCT
1Output - {{Number}} | SwitchStatus1 Bit1.1 switchCRT
1Output - 1...2 | Shutter/BlindStop/Step1 Bit1.7 stepCW
1Output - 1...2 | 3-Point ValveHeating Valve Status Value1 Byte5.1 percentage (0..100%)CT
1Output - 1...2 | 3-Point ValveCooling Valve Status Value1 Byte5.1 percentage (0..100%)CT
2Movement Application - {{Number}}Slave Input1 Bit1.1 switchCW
2Constant Brightness Control - {{Number}}External Movement Input1 Bit1.1 switchCW
2HVAC ApplicationDetection Timeout2 Bytes7.5 time (s)CRW
2RTC | MasterFan Speed Request1 Byte5.1 percentage (0..100%)CW
2Sensor | BrightnessTreshold Value2 Bytes9.4 lux (Lux)CRT
2Sensor | BrightnessTreshold Value2 Bytes9.4 lux (Lux)CRWT
2Sensor | TemperatureTreshold Value2 Bytes9.1 temperature (°C)CRT
2Sensor | TemperatureTreshold Value2 Bytes9.1 temperature (°C)CRWT
2Sensor | HumidityTreshold Status1 Bit1.1 switchCT
2Sensor | HumidityTreshold Status1 Byte5.10 counter pulses (0..255)CT
2Sensor | HumidityTreshold Status1 Byte5.1 percentage (0..100%)CT
2Sensor | HumidityTreshold Status1 Byte17.1 scene numberCT
2Sensor | HumidityTreshold Status1 Byte20.102 HVAC modeCT
2Sensor | HumidityTreshold Status2 Bytes9.1 temperature (°C)CT
2Sensor | Air QualitySensor Output (ppm)2 Bytes9.8 parts/million (ppm)CRT
2LA - {{Number}} | Inactivity MonitorAction at Detection1 Bit1.1 switchCT
2LA - {{Number}} | Inactivity MonitorAction at Detection1 Byte5.10 counter pulses (0..255)CT
2LA - {{Number}} | Inactivity MonitorAction at Detection1 Byte5.1 percentage (0..100%)CT
2LA - {{Number}} | Inactivity MonitorAction at Detection1 Byte17.1 scene numberCT
2LA - {{Number}} | Inactivity MonitorAction at Detection1 Byte20.102 HVAC modeCT
2LA - {{Number}} | Inactivity MonitorAction at Detection2 Bytes9.1 temperature (°C)CT
2LA - {{Number}} | Filter/DelayDelay Time2 Bytes7.4 time (100 ms)CRWT
2LA - {{Number}} | Filter/DelayDelay Time2 Bytes7.5 time (s)CRWT
2LA - {{Number}} | PresetOutput - 21 Bit1.1 switchCT
2LA - {{Number}} | PresetOutput - 21 Byte5.10 counter pulses (0..255)CT
2LA - {{Number}} | PresetOutput - 22 Bytes7.1 pulsesCT
2LA - {{Number}} | PresetOutput - 22 Bytes8.1 pulses differenceCT
2LA - {{Number}} | PresetOutput - 22 Bytes9.1 temperature (°C)CT
2LA - {{Number}} | Logic GateInput - 31 Bit1.1 switchCW
2LA - {{Number}} | GateOutput1 Bit1.1 switchCT
2LA - {{Number}} | GateOutput4 BitDPT.3CT
2LA - {{Number}} | GateOutput1 Byte5.10 counter pulses (0..255)CT
2LA - {{Number}} | GateOutput1 Byte6.10 counter pulses (-128..127)CT
2LA - {{Number}} | GateOutput1 Byte5.1 percentage (0..100%)CT
2LA - {{Number}} | GateOutput2 Bytes7.1 pulsesCT
2LA - {{Number}} | GateOutput2 Bytes8.1 pulses differenceCT
2LA - {{Number}} | GateOutput2 Bytes9.1 temperature (°C)CT
2LA - {{Number}} | SceneChannel - 2 Output1 Bit1.1 switchCT
2LA - {{Number}} | SceneChannel - 2 Output1 Bit1.8 up/downCT
2LA - {{Number}} | SceneChannel - 2 Output1 Byte5.10 counter pulses (0..255)CT
2LA - {{Number}} | SceneChannel - 2 Output1 Byte5.1 percentage (0..100%)CT
2LA - {{Number}} | SceneChannel - 2 Output2 Bytes9.1 temperature (°C)CT
2Input - {{Number}} | Value SenderRelease Output1 Bit1.1 switchCT
2Input - {{Number}} | Value SenderRelease Output1 Byte5.10 counter pulses (0..255)CT
2Input - {{Number}} | Value SenderRelease Output1 Byte6.10 counter pulses (-128..127)CT
2Input - {{Number}} | Value SenderRelease Output1 Byte5.1 percentage (0..100%)CT
2Input - {{Number}} | Value SenderRelease Output1 Byte17.1 scene numberCT
2Input - {{Number}} | Value SenderRelease Output1 Byte20.102 HVAC modeCT
2Input - {{Number}} | Value SenderRelease Output2 Bytes7.1 pulsesCT
2Input - {{Number}} | Value SenderRelease Output2 Bytes8.1 pulses differenceCT
2Input - {{Number}} | Value SenderRelease Output2 Bytes9.1 temperature (°C)CT
2Input - {{Number}} | Value SenderOutput (Long Press)1 Bit1.1 switchCT
2Input - {{Number}} | Value SenderOutput (Long Press)1 Byte5.10 counter pulses (0..255)CT
2Input - {{Number}} | Value SenderOutput (Long Press)1 Byte6.10 counter pulses (-128..127)CT
2Input - {{Number}} | Value SenderOutput (Long Press)1 Byte5.1 percentage (0..100%)CT
2Input - {{Number}} | Value SenderOutput (Long Press)1 Byte17.1 scene numberCT
2Input - {{Number}} | Value SenderOutput (Long Press)1 Byte20.102 HVAC modeCT
2Input - {{Number}} | Value SenderOutput (Long Press)2 Bytes7.1 pulsesCT
2Input - {{Number}} | Value SenderOutput (Long Press)2 Bytes8.1 pulses differenceCT
2Input - {{Number}} | Value SenderOutput (Long Press)2 Bytes9.1 temperature (°C)CT
2Input - {{Number}} | Shutter/BlindStop1 Bit1.7 stepCT
2Output - {{Number}} | SwitchThreshold Input1 Byte5.1 percentage (0..100%)CW
2Output - 1...2 | Shutter/BlindScene1 Byte17.1 scene numberCW
3Movement Application - {{Number}}Detection Timeout2 Bytes7.5 time (s)CRW
3Constant Brightness Control - {{Number}}Detection Timeout2 Bytes7.5 time (s)CRWT
3HVAC ApplicationOutput1 Bit1.1 switchCT
3HVAC ApplicationOutput1 Byte5.10 counter pulses (0..255)CT
3HVAC ApplicationOutput1 Byte5.1 percentage (0..100%)CT
3HVAC ApplicationOutput1 Byte17.1 scene numberCT
3HVAC ApplicationOutput1 Byte20.102 HVAC modeCT
3HVAC ApplicationOutput2 Bytes9.1 temperature (°C)CT
3RTC | MasterConfirmed Fan Speed Status1 Byte5.1 percentage (0..100%)CRT
3Sensor | BrightnessTreshold Status1 Bit1.1 switchCT
3Sensor | BrightnessTreshold Status1 Byte5.10 counter pulses (0..255)CT
3Sensor | BrightnessTreshold Status1 Byte5.1 percentage (0..100%)CT
3Sensor | BrightnessTreshold Status1 Byte17.1 scene numberCT
3Sensor | BrightnessTreshold Status1 Byte20.102 HVAC modeCT
3Sensor | BrightnessTreshold Status2 Bytes9.1 temperature (°C)CT
3Sensor | TemperatureTreshold Status1 Bit1.1 switchCT
3Sensor | TemperatureTreshold Status1 Byte5.10 counter pulses (0..255)CT
3Sensor | TemperatureTreshold Status1 Byte5.1 percentage (0..100%)CT
3Sensor | TemperatureTreshold Status1 Byte17.1 scene numberCT
3Sensor | TemperatureTreshold Status1 Byte20.102 HVAC modeCT
3Sensor | TemperatureTreshold Status2 Bytes9.1 temperature (°C)CT
3Sensor | Air QualityTreshold Status1 Bit1.1 switchCT
3Sensor | Air QualityTreshold Status1 Byte5.10 counter pulses (0..255)CT
3Sensor | Air QualityTreshold Status1 Byte5.1 percentage (0..100%)CT
3Sensor | Air QualityTreshold Status1 Byte17.1 scene numberCT
3Sensor | Air QualityTreshold Status1 Byte20.102 HVAC modeCT
3Sensor | Air QualityTreshold Status2 Bytes9.1 temperature (°C)CT
3LA - {{Number}} | Inactivity MonitorAction End of Monitoring Time1 Bit1.1 switchCT
3LA - {{Number}} | Inactivity MonitorAction End of Monitoring Time1 Byte5.10 counter pulses (0..255)CT
3LA - {{Number}} | Inactivity MonitorAction End of Monitoring Time1 Byte5.1 percentage (0..100%)CT
3LA - {{Number}} | Inactivity MonitorAction End of Monitoring Time1 Byte17.1 scene numberCT
3LA - {{Number}} | Inactivity MonitorAction End of Monitoring Time1 Byte20.102 HVAC modeCT
3LA - {{Number}} | Inactivity MonitorAction End of Monitoring Time2 Bytes9.1 temperature (°C)CT
3LA - {{Number}} | PresetOutput - 31 Bit1.1 switchCT
3LA - {{Number}} | PresetOutput - 31 Byte5.10 counter pulses (0..255)CT
3LA - {{Number}} | PresetOutput - 32 Bytes7.1 pulsesCT
3LA - {{Number}} | PresetOutput - 32 Bytes8.1 pulses differenceCT
3LA - {{Number}} | PresetOutput - 32 Bytes9.1 temperature (°C)CT
3LA - {{Number}} | Logic GateInput - 41 Bit1.1 switchCW
3LA - {{Number}} | SceneChannel - 3 Output1 Bit1.1 switchCT
3LA - {{Number}} | SceneChannel - 3 Output1 Bit1.8 up/downCT
3LA - {{Number}} | SceneChannel - 3 Output1 Byte5.10 counter pulses (0..255)CT
3LA - {{Number}} | SceneChannel - 3 Output1 Byte5.1 percentage (0..100%)CT
3LA - {{Number}} | SceneChannel - 3 Output2 Bytes9.1 temperature (°C)CT
3Output - {{Number}} | SwitchPermanent ON1 Bit1.1 switchCW
3Output - 1...2 | Shutter/BlindMove to Position1 Byte5.1 percentage (0..100%)CW
4Movement Application - {{Number}}Activate Night Mode1 Bit1.1 switchCW
4Constant Brightness Control - {{Number}}Brightness Setpoint1 Bit1.1 switchCW
4LA - {{Number}} | PresetOutput - 41 Bit1.1 switchCT
4LA - {{Number}} | PresetOutput - 41 Byte5.10 counter pulses (0..255)CT
4LA - {{Number}} | PresetOutput - 42 Bytes7.1 pulsesCT
4LA - {{Number}} | PresetOutput - 42 Bytes8.1 pulses differenceCT
4LA - {{Number}} | PresetOutput - 42 Bytes9.1 temperature (°C)CT
4LA - {{Number}} | Logic GateInput - 51 Bit1.1 switchCW
4LA - {{Number}} | SceneChannel - 4 Output1 Bit1.1 switchCT
4LA - {{Number}} | SceneChannel - 4 Output1 Bit1.8 up/downCT
4LA - {{Number}} | SceneChannel - 4 Output1 Byte5.10 counter pulses (0..255)CT
4LA - {{Number}} | SceneChannel - 4 Output1 Byte5.1 percentage (0..100%)CT
4LA - {{Number}} | SceneChannel - 4 Output2 Bytes9.1 temperature (°C)CT
4Output - {{Number}} | SwitchScene1 Byte17.1 scene numberCW
4Output - 1...2 | Shutter/BlindPosition Status1 Byte5.1 percentage (0..100%)CT
5Movement Application - {{Number}}Detection Night Timeout2 Bytes7.5 time (s)CRW
5Constant Brightness Control - {{Number}}Brightness Set Value2 Bytes9.4 lux (Lux)CRWT
5LA - {{Number}} | Logic GateInput - 61 Bit1.1 switchCW
5LA - {{Number}} | SceneChannel - 5 Output1 Bit1.1 switchCT
5LA - {{Number}} | SceneChannel - 5 Output1 Bit1.8 up/downCT
5LA - {{Number}} | SceneChannel - 5 Output1 Byte5.10 counter pulses (0..255)CT
5LA - {{Number}} | SceneChannel - 5 Output1 Byte5.1 percentage (0..100%)CT
5LA - {{Number}} | SceneChannel - 5 Output2 Bytes9.1 temperature (°C)CT
6Movement Application - {{Number}}Internal Brightness Threshold2 Bytes9.4 lux (Lux)CW
6Constant Brightness Control - {{Number}}External Brightness Value2 Bytes9.4 lux (Lux)CW
6RTC | MasterRequest Fan Auto1 Bit1.1 switchCW
6LA - {{Number}} | Logic GateInput - 71 Bit1.1 switchCW
6LA - {{Number}} | SceneChannel - 6 Output1 Bit1.1 switchCT
6LA - {{Number}} | SceneChannel - 6 Output1 Bit1.8 up/downCT
6LA - {{Number}} | SceneChannel - 6 Output1 Byte5.10 counter pulses (0..255)CT
6LA - {{Number}} | SceneChannel - 6 Output1 Byte5.1 percentage (0..100%)CT
6LA - {{Number}} | SceneChannel - 6 Output2 Bytes9.1 temperature (°C)CT
7Movement Application - {{Number}}External Brightness2 Bytes9.4 lux (Lux)CW
7Constant Brightness Control - {{Number}}Stop 1 Bit1 Bit1.1 switchCW
7RTC | MasterConfirmed Fan Auto1 Bit1.1 switchCRT
7LA - {{Number}} | Logic GateInput - 81 Bit1.1 switchCW
7LA - {{Number}} | SceneChannel - 7 Output1 Bit1.1 switchCT
7LA - {{Number}} | SceneChannel - 7 Output1 Bit1.8 up/downCT
7LA - {{Number}} | SceneChannel - 7 Output1 Byte5.10 counter pulses (0..255)CT
7LA - {{Number}} | SceneChannel - 7 Output1 Byte5.1 percentage (0..100%)CT
7LA - {{Number}} | SceneChannel - 7 Output2 Bytes9.1 temperature (°C)CT
8Movement Application - {{Number}}External Brightness Threshold2 Bytes9.4 lux (Lux)CW
8Constant Brightness Control - {{Number}}Stop 4 Bit4 Bit3.7 dimming controlCW
8LA - {{Number}} | Logic GateOutput1 Bit1.1 switchCT
8LA - {{Number}} | Logic GateOutput1 Byte5.10 counter pulses (0..255)CT
8LA - {{Number}} | SceneChannel - 8 Output1 Bit1.1 switchCT
8LA - {{Number}} | SceneChannel - 8 Output1 Bit1.8 up/downCT
8LA - {{Number}} | SceneChannel - 8 Output1 Byte5.10 counter pulses (0..255)CT
8LA - {{Number}} | SceneChannel - 8 Output1 Byte5.1 percentage (0..100%)CT
8LA - {{Number}} | SceneChannel - 8 Output2 Bytes9.1 temperature (°C)CT
9Movement Application - {{Number}}Test Mode1 Bit1.1 switchCW
9Constant Brightness Control - {{Number}}Stop 1 Byte1 Byte5.10 counter pulses (0..255)CW
9Constant Brightness Control - {{Number}}Stop 1 Byte1 Byte5.1 percentage (0..100%)CW
9LA - {{Number}} | SceneChannel - 1 Status1 Bit1.1 switchCWU
9LA - {{Number}} | SceneChannel - 1 Status1 Bit1.8 up/downCWU
9LA - {{Number}} | SceneChannel - 1 Status1 Byte5.10 counter pulses (0..255)CWU
9LA - {{Number}} | SceneChannel - 1 Status1 Byte5.1 percentage (0..100%)CWU
9LA - {{Number}} | SceneChannel - 1 Status2 Bytes9.1 temperature (°C)CWU
10Movement Application - {{Number}}Actuator Status1 Bit1.1 switchCW
10Constant Brightness Control - {{Number}}Output - 11 Byte5.10 counter pulses (0..255)CT
10Constant Brightness Control - {{Number}}Output - 11 Byte5.1 percentage (0..100%)CT
10RTC | GeneralHVAC Operating Mode1 Byte20.102 HVAC modeCRWT
10LA - {{Number}} | SceneChannel - 2 Status1 Bit1.1 switchCWU
10LA - {{Number}} | SceneChannel - 2 Status1 Bit1.8 up/downCWU
10LA - {{Number}} | SceneChannel - 2 Status1 Byte5.10 counter pulses (0..255)CWU
10LA - {{Number}} | SceneChannel - 2 Status1 Byte5.1 percentage (0..100%)CWU
10LA - {{Number}} | SceneChannel - 2 Status2 Bytes9.1 temperature (°C)CWU
10Input - 1Enable Object1 Bit1.3 enableCW
11Movement Application - {{Number}}External Button1 Bit1.1 switchCW
11Constant Brightness Control - {{Number}}Output - 21 Byte5.10 counter pulses (0..255)CT
11Constant Brightness Control - {{Number}}Output - 21 Byte5.1 percentage (0..100%)CT
11RTC | GeneralComfort Operating Mode Select1 Bit1.1 switchCRWT
11LA - {{Number}} | SceneChannel - 3 Status1 Bit1.1 switchCWU
11LA - {{Number}} | SceneChannel - 3 Status1 Bit1.8 up/downCWU
11LA - {{Number}} | SceneChannel - 3 Status1 Byte5.10 counter pulses (0..255)CWU
11LA - {{Number}} | SceneChannel - 3 Status1 Byte5.1 percentage (0..100%)CWU
11LA - {{Number}} | SceneChannel - 3 Status2 Bytes9.1 temperature (°C)CWU
12Movement Application - {{Number}}Output - 11 Bit1.1 switchCT
12Movement Application - {{Number}}Output - 11 Byte5.10 counter pulses (0..255)CT
12Movement Application - {{Number}}Output - 11 Byte5.1 percentage (0..100%)CT
12Movement Application - {{Number}}Output - 11 Byte17.1 scene numberCT
12Movement Application - {{Number}}Output - 11 Byte20.102 HVAC modeCT
12Movement Application - {{Number}}Output - 12 Bytes9.1 temperature (°C)CT
12Constant Brightness Control - {{Number}}Output - 31 Byte5.10 counter pulses (0..255)CT
12Constant Brightness Control - {{Number}}Output - 31 Byte5.1 percentage (0..100%)CT
12RTC | GeneralStandby Operation Mode Select1 Bit1.1 switchCRWT
12LA - {{Number}} | SceneChannel - 4 Status1 Bit1.1 switchCWU
12LA - {{Number}} | SceneChannel - 4 Status1 Bit1.8 up/downCWU
12LA - {{Number}} | SceneChannel - 4 Status1 Byte5.10 counter pulses (0..255)CWU
12LA - {{Number}} | SceneChannel - 4 Status1 Byte5.1 percentage (0..100%)CWU
12LA - {{Number}} | SceneChannel - 4 Status2 Bytes9.1 temperature (°C)CWU
13Movement Application - {{Number}}Output - 21 Bit1.1 switchCT
13Movement Application - {{Number}}Output - 21 Byte5.10 counter pulses (0..255)CT
13Movement Application - {{Number}}Output - 21 Byte5.1 percentage (0..100%)CT
13Movement Application - {{Number}}Output - 21 Byte17.1 scene numberCT
13Movement Application - {{Number}}Output - 21 Byte20.102 HVAC modeCT
13Movement Application - {{Number}}Output - 22 Bytes9.1 temperature (°C)CT
13RTC | GeneralECO Operating Mode Select1 Bit1.1 switchCRWT
13LA - {{Number}} | SceneChannel - 5 Status1 Bit1.1 switchCWU
13LA - {{Number}} | SceneChannel - 5 Status1 Bit1.8 up/downCWU
13LA - {{Number}} | SceneChannel - 5 Status1 Byte5.10 counter pulses (0..255)CWU
13LA - {{Number}} | SceneChannel - 5 Status1 Byte5.1 percentage (0..100%)CWU
13LA - {{Number}} | SceneChannel - 5 Status2 Bytes9.1 temperature (°C)CWU
14RTC | GeneralProtection Operating Mode Select1 Bit1.1 switchCRWT
14LA - {{Number}} | SceneChannel - 6 Status1 Bit1.1 switchCWU
14LA - {{Number}} | SceneChannel - 6 Status1 Bit1.8 up/downCWU
14LA - {{Number}} | SceneChannel - 6 Status1 Byte5.10 counter pulses (0..255)CWU
14LA - {{Number}} | SceneChannel - 6 Status1 Byte5.1 percentage (0..100%)CWU
14LA - {{Number}} | SceneChannel - 6 Status2 Bytes9.1 temperature (°C)CWU
15RTC | GeneralForced Operating Mode1 Byte20.102 HVAC modeCW
15LA - {{Number}} | SceneChannel - 7 Status1 Bit1.1 switchCWU
15LA - {{Number}} | SceneChannel - 7 Status1 Bit1.8 up/downCWU
15LA - {{Number}} | SceneChannel - 7 Status1 Byte5.10 counter pulses (0..255)CWU
15LA - {{Number}} | SceneChannel - 7 Status1 Byte5.1 percentage (0..100%)CWU
15LA - {{Number}} | SceneChannel - 7 Status2 Bytes9.1 temperature (°C)CWU
16RTC | GeneralPresence Detector Input1 Bit1.1 switchCW
16LA - {{Number}} | SceneChannel - 8 Status1 Bit1.1 switchCWU
16LA - {{Number}} | SceneChannel - 8 Status1 Bit1.8 up/downCWU
16LA - {{Number}} | SceneChannel - 8 Status1 Byte5.10 counter pulses (0..255)CWU
16LA - {{Number}} | SceneChannel - 8 Status1 Byte5.1 percentage (0..100%)CWU
16LA - {{Number}} | SceneChannel - 8 Status2 Bytes9.1 temperature (°C)CWU
17RTC | GeneralWindows Contact Input1 Bit1.1 switchCW
18RTC | GeneralRTC Controller RHCC Status2 Bytes22.101 RHCC statusCRT
19RTC | GeneralController HVAC Status1 Byte20.102 HVAC modeCRT
20RTC | SetpointSet Temperature Output2 Bytes9.1 temperature (°C)CRT
20Input - 2Enable Object1 Bit1.3 enableCW
21RTC | SetpointSet Temperature Request2 Bytes9.1 temperature (°C)CW
22RTC | Temperature ReadingInternal Temperature2 Bytes9.1 temperature (°C)CRT
23RTC | Temperature ReadingActual Temperature Error1 Bit1.5 alarmCT
24RTC | Temperature ReadingExternal Temperature2 Bytes9.1 temperature (°C)CW
25RTC | Temperature ReadingTemperature Output2 Bytes9.1 temperature (°C)CRT
26RTC | Temperature ReadingFault Temperature Reading1 Bit1.5 alarmCRT
27RTC | Temperature ReadingInstantaneous Temperature Change1 Bit1.5 alarmCRT
28RTC | Heating/CoolingHVAC Control Mode Input1 Byte20.105 HVAC control modeCW
29RTC | Heating/CoolingHVAC Control Mode Status1 Byte20.105 HVAC control modeCRT
30RTC | Heating/CoolingHVAC Changeover Mode Select 1 Byte20.107 changeover modeCW
30Input - 3Enable Object1 Bit1.3 enableCW
31RTC | Heating/CoolingHVAC Changeover Mode Status 1 Byte20.107 changeover modeCRT
32RTC | Heating/CoolingHeating Cooling Select1 Bit1.100 cooling/heatingCW
33RTC | Heating/CoolingHeating Cooling Control Value1 Bit1.1 switchCT
33RTC | Heating/CoolingHeating Cooling Control Value1 Byte5.1 percentage (0..100%)CT
34RTC | HeatingHeating Control Value1 Bit1.1 switchCT
34RTC | HeatingHeating Control Value1 Byte5.1 percentage (0..100%)CT
35RTC | HeatingAdditional Heating Stage1 Bit1.1 switchCT
35RTC | HeatingAdditional Heating Stage1 Byte5.1 percentage (0..100%)CT
36RTC | CoolingCooling Control Value1 Bit1.1 switchCT
36RTC | CoolingCooling Control Value1 Byte5.1 percentage (0..100%)CT
37RTC | CoolingAdditional Cooling Stage1 Bit1.1 switchCT
37RTC | CoolingAdditional Cooling Stage1 Byte5.1 percentage (0..100%)CT
38RTC | Heating/CoolingHeating/Cooling Select Status1 Bit1.100 cooling/heatingCRT
39RTC | HeatingHeating Status1 Bit1.2 booleanCT
40RTC | CoolingCooling Status1 Bit1.2 booleanCT
70RTC | Fan CoilFan Speed Auto Control1 Bit1.1 switchCW
71RTC | Fan CoilFan Speed Manual Control1 Bit1.1 switchCW
72RTC | Fan CoilFan Auto / Manual Status1 Bit1.1 switchCRT
73RTC | Fan CoilFan Speed Set1 Byte5.1 percentage (0..100%)CT
73RTC | Fan CoilFan Speed Set1 Byte5.100 fan stage (0..255)CT
74RTC | Fan CoilFan Speed 11 Bit1.1 switchCT
75RTC | Fan CoilFan Speed 21 Bit1.1 switchCT
76RTC | Fan CoilFan Speed 31 Bit1.1 switchCT
77RTC | Fan CoilFan Speed 41 Bit1.1 switchCT
78RTC | Fan CoilFan Speed 51 Bit1.1 switchCT
79RTC | Fan CoilFan Speed Step Control1 Bit1.1 switchCW
80RTC | Fan CoilFan Speed Status1 Byte5.1 percentage (0..100%)CW
80RTC | Fan CoilFan Speed Status1 Byte5.100 fan stage (0..255)CW
Parameters (379)
ParameterTypeDefault
Start Up Delaytime10
ModellistOPT-MSS-212 Standard
AccesorylistNone
Movement Application - 1unsignedInt 0…10
Movement Application - 2unsignedInt 0…10
Constant Brightness Control - 1unsignedInt 0…10
Constant Brightness Control - 2unsignedInt 0…10
HVAC ApplicationunsignedInt 0…10
Sensor SelectlistBoth Sensors
Movement Sensor SensitivitylistMedium
Device ModelistMaster
Cyclic Send Periodtime300
Detection Timeouttime300
Detection Timeout ObjectunsignedInt 0…10
Detection Night ModeunsignedInt 0…10
Detection Night Timeouttime300
Detection Night Timeout ObjectunsignedInt 0…10
Brigthness SourcelistBrigthness Independent
Light Level TresholdunsignedInt 10…1000400
Light Level Treshold ObjectunsignedInt 0…10
External Light Level ThresholdunsignedInt 10…1000400
External Light Level Threshold ObjectunsignedInt 0…10
Operating ModelistAuto
Slave InputlistNo
Slave Input Depend on BrightnesslistNo
Test Mode ObjectlistNo
Actuator Status ObjectlistNo
Pause Timetime10
External Push Button ObjectunsignedInt 0…10
Switch ON withlistON Telegram
Enable ObjectunsignedInt 0…10
Enable withlistON Telegram
Initial PositionlistEnable
Reaction When EnabledlistSend Current Status
Reaction When DisabledlistDo Not Send Telegram
Data Typelist1-Bit
Action at DetectionlistSend Value
Send ValuelistON Telegram
Send ValueunsignedInt 0…255255
Send ValueunsignedInt 0…100100
Send ValuelistScene 1
Send ValuelistComfort
Send Valuefloat -273…67000023
Use Second OutputunsignedInt 0…10
Action End Of DetectionlistSend Value
Send ValuelistOFF Telegram
Send ValueunsignedInt 0…2550
Send ValueunsignedInt 0…1000
Send ValuelistScene 2
Send ValuelistStandby
Send Valuefloat -273…67000020
Repeat TelegramunsignedInt 0…10
Repeat Cyclictime60
Two Stage OffunsignedInt 0…10
Two Stage Off Brightness ValueunsignedInt 0…2550
Two Stage Off Brightness Delay Timetime10
Common Repeat Cyclictime60
Two Stage Off Brightness ValueunsignedInt 0…1000
Brightness SourcelistInternal
Operating ModelistMovement Independent
Output Typelist1-Byte Unsigned
Set BrightnessunsignedInt 10…1000200
ToleranceunsignedInt 10…10010
Upper LimitunsignedInt 0…255255
Upper LimitunsignedInt 0…100100
Lower LimitunsignedInt 0…2550
Lower LimitunsignedInt 0…1000
Starting Control fromunsignedInt 0…255127
Starting Control fromunsignedInt 0…10050
Increment StepunsignedInt 1…155
Decrement StepunsignedInt 1…155
Control Speedtime10
Brightness Set Value ObjectlistNo
Save Brightness Setpoint ObjectlistNo
AutoStart After Boot (w/o Movement)listNo
Second OutputlistNo
GainunsignedInt 10…255100
Bottom LimitunsignedInt 0…2550
Bottom LimitunsignedInt 0…1000
Third OutputlistNo
Movement SourcelistInternal
Internal Movement SensitivitylistMedium
Movement Timeouttime300
Movement Timeout ObjectunsignedInt 0…10
End of Movement Output ValueunsignedInt 0…2550
End of Movement Output ValueunsignedInt 0…1000
Manual Control Timetime10
Enable ObjectlistNo
Reaction Value When EnablelistParametric Value
Reaction Value When DisabledlistNo Telegram
Slave InputunsignedInt 0…10
Validation Delaylist30sec
Minimum number of motion detections during delay for Switch ONlistFirst
Detection Time ObjectunsignedInt 0…10
Output Data Typelist1-Bit
Action at DetectionlistNo Reaction
Action End Of DetectionlistNo Reaction
Room Temperature ControllerunsignedInt 0…10
Room Temperature Controller ModelistMaster
Control FunctionlistHeating
Operating Mode After ResetlistPrevious
Temperature SourcelistInternal Sensor
External Temperature Reading OffsetsignedInt -128…1270
Monitoring Time (0=No Monitoring)time0
Weight (Internal/External)unsignedInt 0…1000
PeriodicallyunsignedInt 0…11
Cycle Timetime15
On ChangeunsignedInt 0…11
Change RatiounsignedInt 1…502
Instantaneous Temperature ChangelistNo
Monitoring Timetime1
Temperature DifferenceunsignedInt 1…151
Control Value Typelist2-Point 1-Bit ON/OFF
Status Heating ObjectlistNo
Control DirectionlistNormal
HysteresisunsignedInt 3…25510
Cyclic Sending of Control Valuetime1
Heating TypelistArea 4°C 200min
P ValueunsignedInt 10…10015
I Valuetime100
PWM Cycletime15
Min Control ValueunsignedInt 0…2550
Max Control ValueunsignedInt 1…255255
Change Amountlist2%
Cyclic Sendingtime1
Status Cooling ObjectlistNo
Cyclic Sending of Control Valtime1
Cooling TypelistArea 4°C 200min
Switchover Heating/CoolinglistOnly from Bus
Control Function After ResetlistPrevious
Control Value(s)list1-Common Object
Setpoint TemperatureunsignedInt 10…4024
Deadzonelist1
Standby ReducingunsignedInt 0…202
Economy ReducingunsignedInt 0…204
Frost Protection TempunsignedInt 5…157
Standby IncreasingunsignedInt 0…202
Economy IncreasingunsignedInt 0…204
Heat Protection TempunsignedInt 30…4532
Maximum range at heatingunsignedInt 0…105
Maximum range at coolingunsignedInt 0…105
Remember manual adjustmentunsignedInt 0…10
Reset manual change when change the operating modeunsignedInt 0…10
Default Setpoint TemperatureunsignedInt 16…3024
Send Value for Fan Auto/Manuallist1: Auto 0: Manual
Number of Fan Levelslist2
Output Format of Levellist0...5 (DPT:5.100)
1 Bit Fan OutputslistDisable
Send Outputs at also Automatic ModeunsignedInt 0…10
Minimum Fan Speed LevellistOFF
Receive Fan Speed StatusunsignedInt 0…10
Fan Speed 1 Start AtunsignedInt 1…25525
Fan Speed 2 Start AtunsignedInt 1…25577
Fan Speed 3 Start AtunsignedInt 1…255128
Fan Speed 4 Start AtunsignedInt 1…255180
Fan Speed 5 Start AtunsignedInt 1…255225
Fan Stage Limit at ECO/Night ModelistNone
Fan Speed Step Control ObjectunsignedInt 0…10
Fan Coil EnablelistOFF Telegram
Internal Temperature Reading OffsetsignedInt -128…1270
Send SetpointlistWhile Change
Cyclic Send Setpointtime1
Additional Control Typelist2-Point 1-Bit ON/OFF
Additional Heating StageunsignedInt 0…10
Temperature DifferenceunsignedInt 0…25510
Additional Cooling StageunsignedInt 0…10
Fan Coil HeatinglistOFF Telegram
Fan Coil CoolinglistOFF Telegram
Minimum SetpointunsignedInt 16…2618
Maximum SetpointunsignedInt 20…3028
Fan Speed 2 Start AtunsignedInt 1…255102
Fan Speed 3 Start AtunsignedInt 1…255180
Fan Speed 2 Start AtunsignedInt 1…255128
Switch to comfort mode when set temperature changedunsignedInt 0…10
Brightness DetectionunsignedInt 0…10
Temperature DetectionunsignedInt 0…10
Humidity DetectionunsignedInt 0…10
Air Quality DetectionunsignedInt 0…10
CalibrationunsignedInt 10…200100
Offset (+/- )signedInt -128…1270
PeriodicallyunsignedInt 0…10
Cycle Timetime2
On ChangeunsignedInt 0…10
Change RatiounsignedInt 10…1000100
Threshold ControlunsignedInt 0…10
Threshold ValueunsignedInt 10…1000100
External Threshold ObjectunsignedInt 0…10
Hysteresislist2
Above ThresholdlistNo Reaction
Below ThresholdlistNo Reaction
OffsetsignedInt -128…1270
Change RatiounsignedInt 1…501
Threshold ValuesignedInt -10…500
Hysteresislist0.5
OffsetsignedInt -20…500
Control Point(s)list1-Point
Threshold Point 1 ValueunsignedInt 10…9010
Common Hysteresis (±)list0
Send ValuelistAuto
Send Valuefloat -273…6700001
Threshold Point 2= Point 1+list10
Between Point 1 and Point 2listNo Reaction
Above Threshold Point-2listNo Reaction
Threshold Point 3= Point 2+list10
Between Point 2 and Point 3listNo Reaction
Above Threshold Point-3listNo Reaction
Change Ratiolist30
Threshold Point 1 Valuelist150
Threshold Point 2= Point 1+list50
Threshold Point 3= Point 2+list50
Logic 1listNo Logic
Logic 2listNo Logic
Logic 3listNo Logic
Logic 4listNo Logic
Logic 5listNo Logic
Monitoring Timetime300
Start Delaytime5
Auto RepeatlistNever
Action End of Monitoring TimelistNo Reaction
Send Valuefloat -273…67000021
Input/Output Data Typelist1-Bit
Delay Time Steplist1-Second Step
Delay Timetime0
Delay Time Write ObjectlistNo
Filter FunctionlistNo Filter
Filter CriterialistEqual
Criteria ValuelistOFF Telegram
Criteria ValueunsignedInt 0…2550
Criteria ValueunsignedInt 0…1000
Criteria ValuesignedInt -128…1270
Criteria Valuefloat -273…327670
Criteria ValuesignedInt -32768…327670
Criteria ValueunsignedInt 0…655350
Criteria Valuefloat -2147483648…21474836470
Criteria ValuesignedInt -2147483648…21474836470
Criteria ValueunsignedInt 0…42949672950
Output Countlist1
Output 1 Data Typelist1-Bit
Output 2 Data Typelist1-Bit
Output 3 Data Typelist1-Bit
Output 4 Data Typelist1-Bit
Output 1listNo Reaction
Output 2listNo Reaction
Output 3listNo Reaction
Output 4listNo Reaction
Send ValueunsignedInt 0…6553565535
Send ValuesignedInt -32768…3276732767
Send Valuefloat -273…327670
Send ValueunsignedInt 0…655350
Send ValuesignedInt -32768…327670
Delay Between TelegramslistNo Delay
Number of Inputlist2
Logic OperatorlistAND
Logic OperatorlistNOT
Logic InputlistNormal
Send Output Valuelistin Every Calculation
Output value when logic is Truelist1
Output value when logic is TrueunsignedInt 0…255255
Output value when logic is Falselist0
Output value when logic is FalseunsignedInt 0…2550
Initial ValuelistValue=0
Control Input BehaviourlistNormal
Initial Value of Control InputlistEnable
Send Last Value When Gate EnabledunsignedInt 0…10
Input Data Typelist1-Byte Unsigned
Threshold Countlist1
Threshold 1unsignedInt 0…2550
Threshold 1signedInt -128…1270
Threshold 1unsignedInt 0…1000
Threshold 1unsignedInt 0…655350
Threshold 1signedInt -32768…327670
Threshold 1float -273…327671
Threshold 1unsignedInt 0…42949672950
Threshold 1signedInt -2147483648…21474836470
Threshold 1float -2147483648…21474836471
Less Than ThresholdunsignedInt 0…10
Send ValuesignedInt -128…1270
Less Than Threshold 1unsignedInt 0…10
Greater Than (or Equal) ThresholdunsignedInt 0…10
Greater Than (or Equal) Threshold 1 and Less Than Threshold 2unsignedInt 0…10
Threshold 2unsignedInt 0…2550
Threshold 2signedInt -128…1270
Threshold 2unsignedInt 0…1000
Threshold 2unsignedInt 0…655350
Threshold 2signedInt -32768…327670
Threshold 2float -273…327671
Threshold 2unsignedInt 0…42949672950
Threshold 2signedInt -2147483648…21474836470
Threshold 2float -2147483648…21474836471
Greater Than (or Equal) Threshold 2unsignedInt 0…10
Greater Than (or Equal) Threshold 2 and Less Than Threshold 3unsignedInt 0…10
Threshold 3unsignedInt 0…2550
Threshold 3signedInt -128…1270
Threshold 3unsignedInt 0…1000
Threshold 3unsignedInt 0…655350
Threshold 3signedInt -32768…327670
Threshold 3float -273…327671
Threshold 3unsignedInt 0…42949672950
Threshold 3signedInt -2147483648…21474836470
Threshold 3float -2147483648…21474836471
Greater Than (or Equal) Threshold 3unsignedInt 0…10
Scene NametextScene
Scene Countlist1
Number of Channellist1
Delay Between Telegramstime1
Channel 1list1-Bit Switch
Channel 2list1-Bit Switch
Channel 3list1-Bit Switch
Channel 4list1-Bit Switch
Channel 5list1-Bit Switch
Channel 6list1-Bit Switch
Channel 7list1-Bit Switch
Channel 8list1-Bit Switch
Scene NumberlistScene 1
Scene can be SavedlistNot Allowed
Channel 1listBypass
Send ValuelistUp
Channel 2listBypass
Channel 3listBypass
Channel 4listBypass
Channel 5listBypass
Channel 6listBypass
Channel 7listBypass
Channel 8listBypass
Scene NumberlistScene 2
Scene NumberlistScene 3
Scene NumberlistScene 4
Scene NumberlistScene 5
Scene NumberlistScene 6
Scene NumberlistScene 7
Scene NumberlistScene 8
Overwrite Parameters at DownloadunsignedInt 0…10
Input FunctionlistNo Function
Debounce Timelist50
Initial StatelistEnable
Digital Input FunctionlistNo Function
Button TypelistSwitch Button
Read Input and Send Status After StartunsignedInt 0…10
Time for Long Operationlist0.25
When PushedlistNo Reaction
When PressedlistNo Reaction
Send ValuesignedInt -128…127100
Send ValuesignedInt -32768…32767100
When ReleasedlistNo Reaction
Long Press DetectionlistNo Reaction
Contact TypelistNormally Open
Operation withlist1 Button
FunctionlistUp/Stop/Down/Stop
BehaviourlistShort Press: Stop/Step, Long Press: Move
BehaviourlistMove Up
Short PreslistStop/Step Up
Long PresslistMove Up
Output OperationlistNo Function
Output TypelistNormally Open
Reaction Bus Voltage FailurelistNo Reaction
Receive Data in 8 BitlistNo
Treshold (Included)unsignedInt 1…25524
Send StatuslistAfter a Change
Time FunctionlistNo Reaction
Switch ON Delaytime0
Switch OFF Delaytime0
Lighting Timetime0
SceneslistDisable
Scene 1 NumberlistScene 1
Scene 1 StatelistNo Reaction
Scene 2 NumberlistScene 1
Scene 2 StatelistNo Reaction
Scene 3 NumberlistScene 1
Scene 3 StatelistNo Reaction
Scene 4 NumberlistScene 1
Scene 4 StatelistNo Reaction
Scene 5 NumberlistScene 1
Scene 5 StatelistNo Reaction
Travel Timetime1
Slat OperationlistDisable
Slat Step Timelist250
Pause Timelist250
Drive Timetime1
Valve NamelistCooling Valve

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Motion, Brightness, Temperature, Humidity, Air Quality, Room Temperature Controller, Logic Controller 1.2 latest$AC203C8C2026-11-25270 KBDownload

About this file

This is the official ETS product database for the Optimus OPT-MSx-212 Advanced Multi Sensor (OPT-MSx-212), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.