| 0 | GroupA-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 0 | GroupA-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 0 | GroupA-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 0 | GroupA-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 0 | GroupA-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 0 | GroupA-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 0 | GroupA-AC | Power out | 1 Bit | 1.1 switch | CT |
| 0 | GroupA-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 1 | GroupA-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 1 | GroupA-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 1 | GroupA-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 1 | GroupA-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 1 | GroupA-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 1 | GroupA-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 1 | GroupA-AC | Power in | 1 Bit | 1.1 switch | CW |
| 1 | GroupA-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 2 | GroupA-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 2 | GroupA-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 2 | GroupA-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 2 | GroupA-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 2 | GroupA-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 2 | GroupA-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 2 | GroupA-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 2 | GroupA-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 3 | GroupA-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 3 | GroupA-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 3 | GroupA-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 3 | GroupA-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 3 | GroupA-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 3 | GroupA-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 3 | GroupA-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 3 | GroupA-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 4 | GroupA-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 4 | GroupA-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 4 | GroupA-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 4 | GroupA-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 4 | GroupA-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 4 | GroupA-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 4 | GroupA-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 4 | GroupA-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 5 | GroupA-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 5 | GroupA-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 5 | GroupA-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 5 | GroupA-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 5 | GroupA-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 5 | GroupA-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 5 | GroupA-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 5 | GroupA-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 5 | GroupA-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 6 | GroupA-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 6 | GroupA-Switch 4 | Switch out | 1 Bit | 1.1 switch | CT |
| 6 | GroupA-Dimmer 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 6 | GroupA-Curtain 4 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 6 | GroupA-ColorTemp 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 6 | GroupA-FloorHeating 2 | Power out | 1 Bit | 1.1 switch | CT |
| 6 | GroupA-Vent 2 | Power out | 1 Bit | 1.1 switch | CT |
| 6 | GroupA-AQ | PM2.5 in | 2 Bytes | 7.1 pulses | CW |
| 6 | GroupA-AQ | PM2.5 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 7 | GroupA-AC | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 7 | GroupA-Switch 4 | Switch in | 1 Bit | 1.1 switch | CW |
| 7 | GroupA-Dimmer 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 7 | GroupA-Curtain 4 | Stop out | 1 Bit | 1.17 trigger | CT |
| 7 | GroupA-ColorTemp 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 7 | GroupA-FloorHeating 2 | Power in | 1 Bit | 1.1 switch | CW |
| 7 | GroupA-Vent 2 | Power in | 1 Bit | 1.1 switch | CW |
| 7 | GroupA-AQ | PM10 in | 2 Bytes | 7.1 pulses | CW |
| 7 | GroupA-AQ | PM10 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 8 | GroupA-FloorHeating 2 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 8 | GroupA-Switch 5 | Switch out | 1 Bit | 1.1 switch | CT |
| 8 | GroupA-Dimmer 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 8 | GroupA-Curtain 5 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 8 | GroupA-ColorTemp 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 8 | GroupA-Vent 2 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 8 | GroupA-AC | Swing out | 1 Bit | 1.10 start/stop | CT |
| 9 | GroupA-FloorHeating 2 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 9 | GroupA-Switch 5 | Switch in | 1 Bit | 1.1 switch | CW |
| 9 | GroupA-Dimmer 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 9 | GroupA-Curtain 5 | Stop out | 1 Bit | 1.17 trigger | CT |
| 9 | GroupA-ColorTemp 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 9 | GroupA-Vent 2 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 9 | GroupA-AC | Swing in | 1 Bit | 1.10 start/stop | CW |
| 10 | GroupA-ColorTemp 2 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 10 | GroupA-Switch 6 | Switch out | 1 Bit | 1.1 switch | CT |
| 10 | GroupA-Dimmer 3 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 10 | GroupA-Curtain 6 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 10 | GroupA-FloorHeating 2 | Heating control out | 1 Bit | 1.1 switch | CT |
| 10 | GroupA-Vent 2 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 10 | GroupA-AC | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 11 | GroupA-ColorTemp 2 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 11 | GroupA-Switch 6 | Switch in | 1 Bit | 1.1 switch | CW |
| 11 | GroupA-Dimmer 3 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CT |
| 11 | GroupA-Curtain 6 | Stop out | 1 Bit | 1.17 trigger | CT |
| 11 | GroupA-FloorHeating 2 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 11 | GroupA-Vent 2 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 11 | GroupA-AC | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 12 | GroupB-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 12 | GroupB-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 12 | GroupB-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 12 | GroupB-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 12 | GroupB-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 12 | GroupB-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 12 | GroupB-AC | Power out | 1 Bit | 1.1 switch | CT |
| 12 | GroupB-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 13 | GroupB-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 13 | GroupB-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 13 | GroupB-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 13 | GroupB-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 13 | GroupB-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 13 | GroupB-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 13 | GroupB-AC | Power in | 1 Bit | 1.1 switch | CW |
| 13 | GroupB-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 14 | GroupB-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 14 | GroupB-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 14 | GroupB-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 14 | GroupB-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 14 | GroupB-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 14 | GroupB-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 14 | GroupB-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 14 | GroupB-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 15 | GroupB-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 15 | GroupB-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 15 | GroupB-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 15 | GroupB-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 15 | GroupB-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 15 | GroupB-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 15 | GroupB-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 15 | GroupB-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 16 | GroupB-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 16 | GroupB-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 16 | GroupB-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 16 | GroupB-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 16 | GroupB-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 16 | GroupB-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 16 | GroupB-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 16 | GroupB-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 17 | GroupB-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 17 | GroupB-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 17 | GroupB-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 17 | GroupB-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 17 | GroupB-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 17 | GroupB-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 17 | GroupB-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 17 | GroupB-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 17 | GroupB-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 18 | GroupB-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 18 | GroupB-Switch 4 | Switch out | 1 Bit | 1.1 switch | CT |
| 18 | GroupB-Curtain 4 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 18 | GroupB-Dimmer 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 18 | GroupB-ColorTemp 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 18 | GroupB-FloorHeating 2 | Power out | 1 Bit | 1.1 switch | CT |
| 18 | GroupB-Vent 2 | Power out | 1 Bit | 1.1 switch | CT |
| 18 | GroupB-AQ | PM2.5 in | 2 Bytes | 7.1 pulses | CW |
| 18 | GroupB-AQ | PM2.5 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 19 | GroupB-AC | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 19 | GroupB-Switch 4 | Switch in | 1 Bit | 1.1 switch | CW |
| 19 | GroupB-Curtain 4 | Stop out | 1 Bit | 1.17 trigger | CT |
| 19 | GroupB-Dimmer 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 19 | GroupB-ColorTemp 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 19 | GroupB-FloorHeating 2 | Power in | 1 Bit | 1.1 switch | CW |
| 19 | GroupB-Vent 2 | Power in | 1 Bit | 1.1 switch | CW |
| 19 | GroupB-AQ | PM10 in | 2 Bytes | 7.1 pulses | CW |
| 19 | GroupB-AQ | PM10 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 20 | GroupB-FloorHeating 2 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 20 | GroupB-Switch 5 | Switch out | 1 Bit | 1.1 switch | CT |
| 20 | GroupB-Curtain 5 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 20 | GroupB-Dimmer 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 20 | GroupB-ColorTemp 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 20 | GroupB-Vent 2 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 20 | GroupB-AC | Swing out | 1 Bit | 1.10 start/stop | CT |
| 21 | GroupB-FloorHeating 2 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 21 | GroupB-Switch 5 | Switch in | 1 Bit | 1.1 switch | CW |
| 21 | GroupB-Curtain 5 | Stop out | 1 Bit | 1.17 trigger | CT |
| 21 | GroupB-Dimmer 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 21 | GroupB-ColorTemp 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 21 | GroupB-Vent 2 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 21 | GroupB-AC | Swing in | 1 Bit | 1.10 start/stop | CW |
| 22 | GroupB-ColorTemp 2 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 22 | GroupB-Switch 6 | Switch out | 1 Bit | 1.1 switch | CT |
| 22 | GroupB-Curtain 6 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 22 | GroupB-Dimmer 3 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 22 | GroupB-FloorHeating 2 | Heating control out | 1 Bit | 1.1 switch | CT |
| 22 | GroupB-Vent 2 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 22 | GroupB-AC | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 23 | GroupB-ColorTemp 2 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 23 | GroupB-Switch 6 | Switch in | 1 Bit | 1.1 switch | CW |
| 23 | GroupB-Curtain 6 | Stop out | 1 Bit | 1.17 trigger | CT |
| 23 | GroupB-Dimmer 3 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 23 | GroupB-FloorHeating 2 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 23 | GroupB-Vent 2 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 23 | GroupB-AC | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 24 | GroupC-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 24 | GroupC-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 24 | GroupC-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 24 | GroupC-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 24 | GroupC-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 24 | GroupC-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 24 | GroupC-AC | Power out | 1 Bit | 1.1 switch | CT |
| 24 | GroupC-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 25 | GroupC-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 25 | GroupC-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 25 | GroupC-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 25 | GroupC-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 25 | GroupC-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 25 | GroupC-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 25 | GroupC-AC | Power in | 1 Bit | 1.1 switch | CW |
| 25 | GroupC-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 26 | GroupC-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 26 | GroupC-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 26 | GroupC-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 26 | GroupC-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 26 | GroupC-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 26 | GroupC-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 26 | GroupC-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 26 | GroupC-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 27 | GroupC-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 27 | GroupC-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 27 | GroupC-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 27 | GroupC-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 27 | GroupC-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 27 | GroupC-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 27 | GroupC-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 27 | GroupC-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 28 | GroupC-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 28 | GroupC-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 28 | GroupC-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 28 | GroupC-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 28 | GroupC-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 28 | GroupC-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 28 | GroupC-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 28 | GroupC-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 29 | GroupC-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 29 | GroupC-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 29 | GroupC-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 29 | GroupC-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 29 | GroupC-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 29 | GroupC-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 29 | GroupC-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 29 | GroupC-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 29 | GroupC-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 30 | GroupC-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 30 | GroupC-Switch 4 | Switch out | 1 Bit | 1.1 switch | CT |
| 30 | GroupC-Curtain 4 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 30 | GroupC-Dimmer 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 30 | GroupC-ColorTemp 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 30 | GroupC-FloorHeating 2 | Power out | 1 Bit | 1.1 switch | CT |
| 30 | GroupC-Vent 2 | Power out | 1 Bit | 1.1 switch | CT |
| 30 | GroupC-AQ | PM2.5 in | 2 Bytes | 7.1 pulses | CW |
| 30 | GroupC-AQ | PM2.5 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 31 | GroupC-AC | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 31 | GroupC-Switch 4 | Switch in | 1 Bit | 1.1 switch | CW |
| 31 | GroupC-Curtain 4 | Stop out | 1 Bit | 1.17 trigger | CT |
| 31 | GroupC-Dimmer 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 31 | GroupC-ColorTemp 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 31 | GroupC-FloorHeating 2 | Power in | 1 Bit | 1.1 switch | CW |
| 31 | GroupC-Vent 2 | Power in | 1 Bit | 1.1 switch | CW |
| 31 | GroupC-AQ | PM10 in | 2 Bytes | 7.1 pulses | CW |
| 31 | GroupC-AQ | PM10 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 32 | GroupC-FloorHeating 2 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 32 | GroupC-Switch 5 | Switch out | 1 Bit | 1.1 switch | CT |
| 32 | GroupC-Curtain 5 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 32 | GroupC-Dimmer 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 32 | GroupC-ColorTemp 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 32 | GroupC-Vent 2 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 32 | GroupC-AC | Swing out | 1 Bit | 1.10 start/stop | CT |
| 33 | GroupC-FloorHeating 2 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 33 | GroupC-Switch 5 | Switch in | 1 Bit | 1.1 switch | CW |
| 33 | GroupC-Curtain 5 | Stop out | 1 Bit | 1.17 trigger | CT |
| 33 | GroupC-Dimmer 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 33 | GroupC-ColorTemp 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 33 | GroupC-Vent 2 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 33 | GroupC-AC | Swing in | 1 Bit | 1.10 start/stop | CW |
| 34 | GroupC-ColorTemp 2 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 34 | GroupC-Switch 6 | Switch out | 1 Bit | 1.1 switch | CT |
| 34 | GroupC-Curtain 6 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 34 | GroupC-Dimmer 3 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 34 | GroupC-FloorHeating 2 | Heating control out | 1 Bit | 1.1 switch | CT |
| 34 | GroupC-Vent 2 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 34 | GroupC-AC | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 35 | GroupC-ColorTemp 2 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 35 | GroupC-Switch 6 | Switch in | 1 Bit | 1.1 switch | CW |
| 35 | GroupC-Curtain 6 | Stop out | 1 Bit | 1.17 trigger | CT |
| 35 | GroupC-Dimmer 3 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 35 | GroupC-FloorHeating 2 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 35 | GroupC-Vent 2 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 35 | GroupC-AC | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 36 | GroupD-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 36 | GroupD-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 36 | GroupD-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 36 | GroupD-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 36 | GroupD-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 36 | GroupD-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 36 | GroupD-AC | Power out | 1 Bit | 1.1 switch | CT |
| 36 | GroupD-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 37 | GroupD-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 37 | GroupD-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 37 | GroupD-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 37 | GroupD-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 37 | GroupD-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 37 | GroupD-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 37 | GroupD-AC | Power in | 1 Bit | 1.1 switch | CW |
| 37 | GroupD-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 38 | GroupD-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 38 | GroupD-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 38 | GroupD-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 38 | GroupD-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 38 | GroupD-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 38 | GroupD-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 38 | GroupD-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 38 | GroupD-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 39 | GroupD-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 39 | GroupD-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 39 | GroupD-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 39 | GroupD-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 39 | GroupD-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 39 | GroupD-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 39 | GroupD-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 39 | GroupD-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 40 | GroupD-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 40 | GroupD-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 40 | GroupD-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 40 | GroupD-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 40 | GroupD-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 40 | GroupD-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 40 | GroupD-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 40 | GroupD-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 41 | GroupD-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 41 | GroupD-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 41 | GroupD-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 41 | GroupD-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 41 | GroupD-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 41 | GroupD-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 41 | GroupD-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 41 | GroupD-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 41 | GroupD-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 42 | GroupD-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 42 | GroupD-Switch 4 | Switch out | 1 Bit | 1.1 switch | CT |
| 42 | GroupD-Curtain 4 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 42 | GroupD-Dimmer 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 42 | GroupD-ColorTemp 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 42 | GroupD-FloorHeating 2 | Power out | 1 Bit | 1.1 switch | CT |
| 42 | GroupD-Vent 2 | Power out | 1 Bit | 1.1 switch | CT |
| 42 | GroupD-AQ | PM2.5 in | 2 Bytes | 7.1 pulses | CW |
| 42 | GroupD-AQ | PM2.5 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 43 | GroupD-AC | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 43 | GroupD-Switch 4 | Switch in | 1 Bit | 1.1 switch | CW |
| 43 | GroupD-Curtain 4 | Stop out | 1 Bit | 1.17 trigger | CT |
| 43 | GroupD-Dimmer 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 43 | GroupD-ColorTemp 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 43 | GroupD-FloorHeating 2 | Power in | 1 Bit | 1.1 switch | CW |
| 43 | GroupD-Vent 2 | Power in | 1 Bit | 1.1 switch | CW |
| 43 | GroupD-AQ | PM10 in | 2 Bytes | 7.1 pulses | CW |
| 43 | GroupD-AQ | PM10 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 44 | GroupD-FloorHeating 2 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 44 | GroupD-Switch 5 | Switch out | 1 Bit | 1.1 switch | CT |
| 44 | GroupD-Curtain 5 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 44 | GroupD-Dimmer 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 44 | GroupD-ColorTemp 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 44 | GroupD-Vent 2 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 44 | GroupD-AC | Swing out | 1 Bit | 1.10 start/stop | CT |
| 45 | GroupD-FloorHeating 2 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 45 | GroupD-Switch 5 | Switch in | 1 Bit | 1.1 switch | CW |
| 45 | GroupD-Curtain 5 | Stop out | 1 Bit | 1.17 trigger | CT |
| 45 | GroupD-Dimmer 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 45 | GroupD-ColorTemp 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 45 | GroupD-Vent 2 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 45 | GroupD-AC | Swing in | 1 Bit | 1.10 start/stop | CW |
| 46 | GroupD-ColorTemp 2 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 46 | GroupD-Switch 6 | Switch out | 1 Bit | 1.1 switch | CT |
| 46 | GroupD-Curtain 6 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 46 | GroupD-Dimmer 3 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 46 | GroupD-FloorHeating 2 | Heating control out | 1 Bit | 1.1 switch | CT |
| 46 | GroupD-Vent 2 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 46 | GroupD-AC | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 47 | GroupD-ColorTemp 2 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 47 | GroupD-Switch 6 | Switch in | 1 Bit | 1.1 switch | CW |
| 47 | GroupD-Curtain 6 | Stop out | 1 Bit | 1.17 trigger | CT |
| 47 | GroupD-Dimmer 3 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 47 | GroupD-FloorHeating 2 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 47 | GroupD-Vent 2 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 47 | GroupD-AC | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 48 | GroupE-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 48 | GroupE-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 48 | GroupE-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 48 | GroupE-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 48 | GroupE-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 48 | GroupE-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 48 | GroupE-AC | Power out | 1 Bit | 1.1 switch | CT |
| 48 | GroupE-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 49 | GroupE-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 49 | GroupE-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 49 | GroupE-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 49 | GroupE-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 49 | GroupE-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 49 | GroupE-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 49 | GroupE-AC | Power in | 1 Bit | 1.1 switch | CW |
| 49 | GroupE-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 50 | GroupE-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 50 | GroupE-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 50 | GroupE-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 50 | GroupE-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 50 | GroupE-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 50 | GroupE-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 50 | GroupE-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 50 | GroupE-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 51 | GroupE-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 51 | GroupE-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 51 | GroupE-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 51 | GroupE-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 51 | GroupE-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 51 | GroupE-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 51 | GroupE-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 51 | GroupE-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 52 | GroupE-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 52 | GroupE-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 52 | GroupE-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 52 | GroupE-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 52 | GroupE-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 52 | GroupE-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 52 | GroupE-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 52 | GroupE-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 53 | GroupE-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 53 | GroupE-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 53 | GroupE-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 53 | GroupE-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 53 | GroupE-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 53 | GroupE-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 53 | GroupE-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 53 | GroupE-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 53 | GroupE-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 54 | GroupE-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 54 | GroupE-Switch 4 | Switch out | 1 Bit | 1.1 switch | CT |
| 54 | GroupE-Curtain 4 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 54 | GroupE-Dimmer 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 54 | GroupE-ColorTemp 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 54 | GroupE-FloorHeating 2 | Power out | 1 Bit | 1.1 switch | CT |
| 54 | GroupE-Vent 2 | Power out | 1 Bit | 1.1 switch | CT |
| 54 | GroupE-AQ | PM2.5 in | 2 Bytes | 7.1 pulses | CW |
| 54 | GroupE-AQ | PM2.5 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 55 | GroupE-AC | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 55 | GroupE-Switch 4 | Switch in | 1 Bit | 1.1 switch | CW |
| 55 | GroupE-Curtain 4 | Stop out | 1 Bit | 1.17 trigger | CT |
| 55 | GroupE-Dimmer 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 55 | GroupE-ColorTemp 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 55 | GroupE-FloorHeating 2 | Power in | 1 Bit | 1.1 switch | CW |
| 55 | GroupE-Vent 2 | Power in | 1 Bit | 1.1 switch | CW |
| 55 | GroupE-AQ | PM10 in | 2 Bytes | 7.1 pulses | CW |
| 55 | GroupE-AQ | PM10 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 56 | GroupE-FloorHeating 2 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 56 | GroupE-Switch 5 | Switch out | 1 Bit | 1.1 switch | CT |
| 56 | GroupE-Curtain 5 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 56 | GroupE-Dimmer 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 56 | GroupE-ColorTemp 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 56 | GroupE-Vent 2 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 56 | GroupE-AC | Swing out | 1 Bit | 1.10 start/stop | CT |
| 57 | GroupE-FloorHeating 2 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 57 | GroupE-Switch 5 | Switch in | 1 Bit | 1.1 switch | CW |
| 57 | GroupE-Curtain 5 | Stop out | 1 Bit | 1.17 trigger | CT |
| 57 | GroupE-Dimmer 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 57 | GroupE-ColorTemp 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 57 | GroupE-Vent 2 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 57 | GroupE-AC | Swing in | 1 Bit | 1.10 start/stop | CW |
| 58 | GroupE-ColorTemp 2 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 58 | GroupE-Switch 6 | Switch out | 1 Bit | 1.1 switch | CT |
| 58 | GroupE-Curtain 6 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 58 | GroupE-Dimmer 3 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 58 | GroupE-FloorHeating 2 | Heating control out | 1 Bit | 1.1 switch | CT |
| 58 | GroupE-Vent 2 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 58 | GroupE-AC | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 59 | GroupE-ColorTemp 2 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 59 | GroupE-Switch 6 | Switch in | 1 Bit | 1.1 switch | CW |
| 59 | GroupE-Curtain 6 | Stop out | 1 Bit | 1.17 trigger | CT |
| 59 | GroupE-Dimmer 3 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 59 | GroupE-FloorHeating 2 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 59 | GroupE-Vent 2 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 59 | GroupE-AC | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 60 | GroupF-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 60 | GroupF-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 60 | GroupF-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 60 | GroupF-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 60 | GroupF-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 60 | GroupF-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 60 | GroupF-AC | Power out | 1 Bit | 1.1 switch | CT |
| 60 | GroupF-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 61 | GroupF-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 61 | GroupF-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 61 | GroupF-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 61 | GroupF-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 61 | GroupF-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 61 | GroupF-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 61 | GroupF-AC | Power in | 1 Bit | 1.1 switch | CW |
| 61 | GroupF-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 62 | GroupF-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 62 | GroupF-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 62 | GroupF-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 62 | GroupF-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 62 | GroupF-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 62 | GroupF-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 62 | GroupF-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 62 | GroupF-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 63 | GroupF-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 63 | GroupF-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 63 | GroupF-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 63 | GroupF-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 63 | GroupF-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 63 | GroupF-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 63 | GroupF-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 63 | GroupF-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 64 | GroupF-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 64 | GroupF-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 64 | GroupF-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 64 | GroupF-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 64 | GroupF-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 64 | GroupF-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 64 | GroupF-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 64 | GroupF-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 65 | GroupF-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 65 | GroupF-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 65 | GroupF-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 65 | GroupF-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 65 | GroupF-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 65 | GroupF-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 65 | GroupF-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 65 | GroupF-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 65 | GroupF-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 66 | GroupF-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 66 | GroupF-Switch 4 | Switch out | 1 Bit | 1.1 switch | CT |
| 66 | GroupF-Curtain 4 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 66 | GroupF-Dimmer 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 66 | GroupF-ColorTemp 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 66 | GroupF-FloorHeating 2 | Power out | 1 Bit | 1.1 switch | CT |
| 66 | GroupF-Vent 2 | Power out | 1 Bit | 1.1 switch | CT |
| 66 | GroupF-AQ | PM2.5 in | 2 Bytes | 7.1 pulses | CW |
| 66 | GroupF-AQ | PM2.5 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 67 | GroupF-AC | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 67 | GroupF-Switch 4 | Switch in | 1 Bit | 1.1 switch | CW |
| 67 | GroupF-Curtain 4 | Stop out | 1 Bit | 1.17 trigger | CT |
| 67 | GroupF-Dimmer 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 67 | GroupF-ColorTemp 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 67 | GroupF-FloorHeating 2 | Power in | 1 Bit | 1.1 switch | CW |
| 67 | GroupF-Vent 2 | Power in | 1 Bit | 1.1 switch | CW |
| 67 | GroupF-AQ | PM10 in | 2 Bytes | 7.1 pulses | CW |
| 67 | GroupF-AQ | PM10 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 68 | GroupF-FloorHeating 2 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 68 | GroupF-Switch 5 | Switch out | 1 Bit | 1.1 switch | CT |
| 68 | GroupF-Curtain 5 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 68 | GroupF-Dimmer 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 68 | GroupF-ColorTemp 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 68 | GroupF-Vent 2 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 68 | GroupF-AC | Swing out | 1 Bit | 1.10 start/stop | CT |
| 69 | GroupF-FloorHeating 2 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 69 | GroupF-Switch 5 | Switch in | 1 Bit | 1.1 switch | CW |
| 69 | GroupF-Curtain 5 | Stop out | 1 Bit | 1.17 trigger | CT |
| 69 | GroupF-Dimmer 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 69 | GroupF-ColorTemp 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 69 | GroupF-Vent 2 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 69 | GroupF-AC | Swing in | 1 Bit | 1.10 start/stop | CW |
| 70 | GroupF-ColorTemp 2 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 70 | GroupF-Switch 6 | Switch out | 1 Bit | 1.1 switch | CT |
| 70 | GroupF-Curtain 6 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 70 | GroupF-Dimmer 3 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 70 | GroupF-FloorHeating 2 | Heating control out | 1 Bit | 1.1 switch | CT |
| 70 | GroupF-Vent 2 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 70 | GroupF-AC | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 71 | GroupF-ColorTemp 2 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 71 | GroupF-Switch 6 | Switch in | 1 Bit | 1.1 switch | CW |
| 71 | GroupF-Curtain 6 | Stop out | 1 Bit | 1.17 trigger | CT |
| 71 | GroupF-Dimmer 3 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 71 | GroupF-FloorHeating 2 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 71 | GroupF-Vent 2 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 71 | GroupF-AC | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 72 | GroupG-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 72 | GroupG-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 72 | GroupG-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 72 | GroupG-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 72 | GroupG-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 72 | GroupG-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 72 | GroupG-AC | Power out | 1 Bit | 1.1 switch | CT |
| 72 | GroupG-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 73 | GroupG-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 73 | GroupG-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 73 | GroupG-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 73 | GroupG-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 73 | GroupG-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 73 | GroupG-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 73 | GroupG-AC | Power in | 1 Bit | 1.1 switch | CW |
| 73 | GroupG-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 74 | GroupG-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 74 | GroupG-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 74 | GroupG-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 74 | GroupG-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 74 | GroupG-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 74 | GroupG-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 74 | GroupG-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 74 | GroupG-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 75 | GroupG-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 75 | GroupG-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 75 | GroupG-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 75 | GroupG-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 75 | GroupG-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 75 | GroupG-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 75 | GroupG-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 75 | GroupG-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 76 | GroupG-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 76 | GroupG-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 76 | GroupG-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 76 | GroupG-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 76 | GroupG-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 76 | GroupG-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 76 | GroupG-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 76 | GroupG-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 77 | GroupG-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 77 | GroupG-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 77 | GroupG-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 77 | GroupG-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 77 | GroupG-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 77 | GroupG-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 77 | GroupG-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 77 | GroupG-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 77 | GroupG-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 78 | GroupG-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 78 | GroupG-Switch 4 | Switch out | 1 Bit | 1.1 switch | CT |
| 78 | GroupG-Curtain 4 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 78 | GroupG-Dimmer 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 78 | GroupG-ColorTemp 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 78 | GroupG-FloorHeating 2 | Power out | 1 Bit | 1.1 switch | CT |
| 78 | GroupG-Vent 2 | Power out | 1 Bit | 1.1 switch | CT |
| 78 | GroupG-AQ | PM2.5 in | 2 Bytes | 7.1 pulses | CW |
| 78 | GroupG-AQ | PM2.5 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 79 | GroupG-AC | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 79 | GroupG-Switch 4 | Switch in | 1 Bit | 1.1 switch | CW |
| 79 | GroupG-Curtain 4 | Stop out | 1 Bit | 1.17 trigger | CT |
| 79 | GroupG-Dimmer 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 79 | GroupG-ColorTemp 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 79 | GroupG-FloorHeating 2 | Power in | 1 Bit | 1.1 switch | CW |
| 79 | GroupG-Vent 2 | Power in | 1 Bit | 1.1 switch | CW |
| 79 | GroupG-AQ | PM10 in | 2 Bytes | 7.1 pulses | CW |
| 79 | GroupG-AQ | PM10 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 80 | GroupG-FloorHeating 2 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 80 | GroupG-Switch 5 | Switch out | 1 Bit | 1.1 switch | CT |
| 80 | GroupG-Curtain 5 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 80 | GroupG-Dimmer 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 80 | GroupG-ColorTemp 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 80 | GroupG-Vent 2 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 80 | GroupG-AC | Swing out | 1 Bit | 1.10 start/stop | CT |
| 81 | GroupG-FloorHeating 2 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 81 | GroupG-Switch 5 | Switch in | 1 Bit | 1.1 switch | CW |
| 81 | GroupG-Curtain 5 | Stop out | 1 Bit | 1.17 trigger | CT |
| 81 | GroupG-Dimmer 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 81 | GroupG-ColorTemp 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 81 | GroupG-Vent 2 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 81 | GroupG-AC | Swing in | 1 Bit | 1.10 start/stop | CW |
| 82 | GroupG-ColorTemp 2 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 82 | GroupG-Switch 6 | Switch out | 1 Bit | 1.1 switch | CT |
| 82 | GroupG-Curtain 6 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 82 | GroupG-Dimmer 3 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 82 | GroupG-FloorHeating 2 | Heating control out | 1 Bit | 1.1 switch | CT |
| 82 | GroupG-Vent 2 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 82 | GroupG-AC | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 83 | GroupG-ColorTemp 2 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 83 | GroupG-Switch 6 | Switch in | 1 Bit | 1.1 switch | CW |
| 83 | GroupG-Curtain 6 | Stop out | 1 Bit | 1.17 trigger | CT |
| 83 | GroupG-Dimmer 3 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 83 | GroupG-FloorHeating 2 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 83 | GroupG-Vent 2 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 83 | GroupG-AC | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 84 | GroupH-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 84 | GroupH-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 84 | GroupH-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 84 | GroupH-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 84 | GroupH-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 84 | GroupH-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 84 | GroupH-AC | Power out | 1 Bit | 1.1 switch | CT |
| 84 | GroupH-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 85 | GroupH-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 85 | GroupH-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 85 | GroupH-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 85 | GroupH-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 85 | GroupH-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 85 | GroupH-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 85 | GroupH-AC | Power in | 1 Bit | 1.1 switch | CW |
| 85 | GroupH-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 86 | GroupH-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 86 | GroupH-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 86 | GroupH-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 86 | GroupH-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 86 | GroupH-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 86 | GroupH-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 86 | GroupH-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 86 | GroupH-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 87 | GroupH-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 87 | GroupH-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 87 | GroupH-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 87 | GroupH-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 87 | GroupH-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 87 | GroupH-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 87 | GroupH-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 87 | GroupH-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 88 | GroupH-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 88 | GroupH-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 88 | GroupH-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 88 | GroupH-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 88 | GroupH-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 88 | GroupH-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 88 | GroupH-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 88 | GroupH-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 89 | GroupH-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 89 | GroupH-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 89 | GroupH-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 89 | GroupH-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 89 | GroupH-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 89 | GroupH-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 89 | GroupH-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 89 | GroupH-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 89 | GroupH-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 90 | GroupH-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 90 | GroupH-Switch 4 | Switch out | 1 Bit | 1.1 switch | CT |
| 90 | GroupH-Curtain 4 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 90 | GroupH-Dimmer 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 90 | GroupH-ColorTemp 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 90 | GroupH-FloorHeating 2 | Power out | 1 Bit | 1.1 switch | CT |
| 90 | GroupH-Vent 2 | Power out | 1 Bit | 1.1 switch | CT |
| 90 | GroupH-AQ | PM2.5 in | 2 Bytes | 7.1 pulses | CW |
| 90 | GroupH-AQ | PM2.5 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 91 | GroupH-AC | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 91 | GroupH-Switch 4 | Switch in | 1 Bit | 1.1 switch | CW |
| 91 | GroupH-Curtain 4 | Stop out | 1 Bit | 1.17 trigger | CT |
| 91 | GroupH-Dimmer 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 91 | GroupH-ColorTemp 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 91 | GroupH-FloorHeating 2 | Power in | 1 Bit | 1.1 switch | CW |
| 91 | GroupH-Vent 2 | Power in | 1 Bit | 1.1 switch | CW |
| 91 | GroupH-AQ | PM10 in | 2 Bytes | 7.1 pulses | CW |
| 91 | GroupH-AQ | PM10 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 92 | GroupH-FloorHeating 2 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 92 | GroupH-Switch 5 | Switch out | 1 Bit | 1.1 switch | CT |
| 92 | GroupH-Curtain 5 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 92 | GroupH-Dimmer 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 92 | GroupH-ColorTemp 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 92 | GroupH-Vent 2 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 92 | GroupH-AC | Swing out | 1 Bit | 1.10 start/stop | CT |
| 93 | GroupH-FloorHeating 2 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 93 | GroupH-Switch 5 | Switch in | 1 Bit | 1.1 switch | CW |
| 93 | GroupH-Curtain 5 | Stop out | 1 Bit | 1.17 trigger | CT |
| 93 | GroupH-Dimmer 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 93 | GroupH-ColorTemp 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 93 | GroupH-Vent 2 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 93 | GroupH-AC | Swing in | 1 Bit | 1.10 start/stop | CW |
| 94 | GroupH-ColorTemp 2 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 94 | GroupH-Switch 6 | Switch out | 1 Bit | 1.1 switch | CT |
| 94 | GroupH-Curtain 6 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 94 | GroupH-Dimmer 3 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 94 | GroupH-FloorHeating 2 | Heating control out | 1 Bit | 1.1 switch | CT |
| 94 | GroupH-Vent 2 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 94 | GroupH-AC | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 95 | GroupH-ColorTemp 2 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 95 | GroupH-Switch 6 | Switch in | 1 Bit | 1.1 switch | CW |
| 95 | GroupH-Curtain 6 | Stop out | 1 Bit | 1.17 trigger | CT |
| 95 | GroupH-Dimmer 3 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 95 | GroupH-FloorHeating 2 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 95 | GroupH-Vent 2 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 95 | GroupH-AC | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 96 | GroupI-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 96 | GroupI-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 96 | GroupI-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 96 | GroupI-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 96 | GroupI-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 96 | GroupI-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 96 | GroupI-AC | Power out | 1 Bit | 1.1 switch | CT |
| 96 | GroupI-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 97 | GroupI-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 97 | GroupI-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 97 | GroupI-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 97 | GroupI-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 97 | GroupI-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 97 | GroupI-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 97 | GroupI-AC | Power in | 1 Bit | 1.1 switch | CW |
| 97 | GroupI-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 98 | GroupI-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 98 | GroupI-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 98 | GroupI-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 98 | GroupI-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 98 | GroupI-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 98 | GroupI-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 98 | GroupI-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 98 | GroupI-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 99 | GroupI-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 99 | GroupI-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 99 | GroupI-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 99 | GroupI-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 99 | GroupI-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 99 | GroupI-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 99 | GroupI-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 99 | GroupI-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 100 | GroupI-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 100 | GroupI-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 100 | GroupI-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 100 | GroupI-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 100 | GroupI-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 100 | GroupI-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 100 | GroupI-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 100 | GroupI-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 101 | GroupI-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 101 | GroupI-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 101 | GroupI-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 101 | GroupI-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 101 | GroupI-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 101 | GroupI-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 101 | GroupI-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 101 | GroupI-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 101 | GroupI-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 102 | GroupI-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 102 | GroupI-Switch 4 | Switch out | 1 Bit | 1.1 switch | CT |
| 102 | GroupI-Curtain 4 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 102 | GroupI-Dimmer 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 102 | GroupI-ColorTemp 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 102 | GroupI-FloorHeating 2 | Power out | 1 Bit | 1.1 switch | CT |
| 102 | GroupI-Vent 2 | Power out | 1 Bit | 1.1 switch | CT |
| 102 | GroupI-AQ | PM2.5 in | 2 Bytes | 7.1 pulses | CW |
| 102 | GroupI-AQ | PM2.5 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 103 | GroupI-AC | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 103 | GroupI-Switch 4 | Switch in | 1 Bit | 1.1 switch | CW |
| 103 | GroupI-Curtain 4 | Stop out | 1 Bit | 1.17 trigger | CT |
| 103 | GroupI-Dimmer 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 103 | GroupI-ColorTemp 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 103 | GroupI-FloorHeating 2 | Power in | 1 Bit | 1.1 switch | CW |
| 103 | GroupI-Vent 2 | Power in | 1 Bit | 1.1 switch | CW |
| 103 | GroupI-AQ | PM10 in | 2 Bytes | 7.1 pulses | CW |
| 103 | GroupI-AQ | PM10 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 104 | GroupI-FloorHeating 2 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 104 | GroupI-Switch 5 | Switch out | 1 Bit | 1.1 switch | CT |
| 104 | GroupI-Curtain 5 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 104 | GroupI-Dimmer 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 104 | GroupI-ColorTemp 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 104 | GroupI-Vent 2 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 104 | GroupI-AC | Swing out | 1 Bit | 1.10 start/stop | CT |
| 105 | GroupI-FloorHeating 2 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 105 | GroupI-Switch 5 | Switch in | 1 Bit | 1.1 switch | CW |
| 105 | GroupI-Curtain 5 | Stop out | 1 Bit | 1.17 trigger | CT |
| 105 | GroupI-Dimmer 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 105 | GroupI-ColorTemp 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 105 | GroupI-Vent 2 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 105 | GroupI-AC | Swing in | 1 Bit | 1.10 start/stop | CW |
| 106 | GroupI-ColorTemp 2 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 106 | GroupI-Switch 6 | Switch out | 1 Bit | 1.1 switch | CT |
| 106 | GroupI-Curtain 6 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 106 | GroupI-Dimmer 3 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 106 | GroupI-FloorHeating 2 | Heating control out | 1 Bit | 1.1 switch | CT |
| 106 | GroupI-Vent 2 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 106 | GroupI-AC | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 107 | GroupI-ColorTemp 2 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 107 | GroupI-Switch 6 | Switch in | 1 Bit | 1.1 switch | CW |
| 107 | GroupI-Curtain 6 | Stop out | 1 Bit | 1.17 trigger | CT |
| 107 | GroupI-Dimmer 3 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 107 | GroupI-FloorHeating 2 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 107 | GroupI-Vent 2 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 107 | GroupI-AC | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 108 | GroupJ-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 108 | GroupJ-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 108 | GroupJ-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 108 | GroupJ-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 108 | GroupJ-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 108 | GroupJ-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 108 | GroupJ-AC | Power out | 1 Bit | 1.1 switch | CT |
| 108 | GroupJ-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 109 | GroupJ-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 109 | GroupJ-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 109 | GroupJ-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 109 | GroupJ-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 109 | GroupJ-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 109 | GroupJ-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 109 | GroupJ-AC | Power in | 1 Bit | 1.1 switch | CW |
| 109 | GroupJ-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 110 | GroupJ-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 110 | GroupJ-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 110 | GroupJ-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 110 | GroupJ-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 110 | GroupJ-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 110 | GroupJ-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 110 | GroupJ-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 110 | GroupJ-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 111 | GroupJ-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 111 | GroupJ-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 111 | GroupJ-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 111 | GroupJ-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 111 | GroupJ-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 111 | GroupJ-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 111 | GroupJ-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 111 | GroupJ-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 112 | GroupJ-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 112 | GroupJ-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 112 | GroupJ-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 112 | GroupJ-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 112 | GroupJ-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 112 | GroupJ-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 112 | GroupJ-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 112 | GroupJ-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 113 | GroupJ-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 113 | GroupJ-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 113 | GroupJ-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 113 | GroupJ-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 113 | GroupJ-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 113 | GroupJ-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 113 | GroupJ-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 113 | GroupJ-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 113 | GroupJ-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 114 | GroupJ-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 114 | GroupJ-Switch 4 | Switch out | 1 Bit | 1.1 switch | CT |
| 114 | GroupJ-Curtain 4 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 114 | GroupJ-Dimmer 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 114 | GroupJ-ColorTemp 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 114 | GroupJ-FloorHeating 2 | Power out | 1 Bit | 1.1 switch | CT |
| 114 | GroupJ-Vent 2 | Power out | 1 Bit | 1.1 switch | CT |
| 114 | GroupJ-AQ | PM2.5 in | 2 Bytes | 7.1 pulses | CW |
| 114 | GroupJ-AQ | PM2.5 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 115 | GroupJ-AC | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 115 | GroupJ-Switch 4 | Switch in | 1 Bit | 1.1 switch | CW |
| 115 | GroupJ-Curtain 4 | Stop out | 1 Bit | 1.17 trigger | CT |
| 115 | GroupJ-Dimmer 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 115 | GroupJ-ColorTemp 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 115 | GroupJ-FloorHeating 2 | Power in | 1 Bit | 1.1 switch | CW |
| 115 | GroupJ-Vent 2 | Power in | 1 Bit | 1.1 switch | CW |
| 115 | GroupJ-AQ | PM10 in | 2 Bytes | 7.1 pulses | CW |
| 115 | GroupJ-AQ | PM10 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 116 | GroupJ-FloorHeating 2 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 116 | GroupJ-Switch 5 | Switch out | 1 Bit | 1.1 switch | CT |
| 116 | GroupJ-Curtain 5 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 116 | GroupJ-Dimmer 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 116 | GroupJ-ColorTemp 2 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 116 | GroupJ-Vent 2 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 116 | GroupJ-AC | Swing out | 1 Bit | 1.10 start/stop | CT |
| 117 | GroupJ-FloorHeating 2 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 117 | GroupJ-Switch 5 | Switch in | 1 Bit | 1.1 switch | CW |
| 117 | GroupJ-Curtain 5 | Stop out | 1 Bit | 1.17 trigger | CT |
| 117 | GroupJ-Dimmer 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 117 | GroupJ-ColorTemp 2 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 117 | GroupJ-Vent 2 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 117 | GroupJ-AC | Swing in | 1 Bit | 1.10 start/stop | CW |
| 118 | GroupJ-ColorTemp 2 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 118 | GroupJ-Switch 6 | Switch out | 1 Bit | 1.1 switch | CT |
| 118 | GroupJ-Curtain 6 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 118 | GroupJ-Dimmer 3 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 118 | GroupJ-FloorHeating 2 | Heating control out | 1 Bit | 1.1 switch | CT |
| 118 | GroupJ-Vent 2 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 118 | GroupJ-AC | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 119 | GroupJ-ColorTemp 2 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 119 | GroupJ-Switch 6 | Switch in | 1 Bit | 1.1 switch | CW |
| 119 | GroupJ-Curtain 6 | Stop out | 1 Bit | 1.17 trigger | CT |
| 119 | GroupJ-Dimmer 3 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 119 | GroupJ-FloorHeating 2 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 119 | GroupJ-Vent 2 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 119 | GroupJ-AC | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 120 | GroupK-Switch 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 120 | GroupK-Curtain 1 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 120 | GroupK-Dimmer 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 120 | GroupK-ColorTemp 1 | Switch out | 1 Bit | 1.1 switch | CT |
| 120 | GroupK-FloorHeating 1 | Power out | 1 Bit | 1.1 switch | CT |
| 120 | GroupK-Vent 1 | Power out | 1 Bit | 1.1 switch | CT |
| 120 | GroupK-AC | Power out | 1 Bit | 1.1 switch | CT |
| 120 | GroupK-AQ | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 121 | GroupK-Switch 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 121 | GroupK-Curtain 1 | Stop out | 1 Bit | 1.17 trigger | CT |
| 121 | GroupK-Dimmer 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 121 | GroupK-ColorTemp 1 | Switch in | 1 Bit | 1.1 switch | CW |
| 121 | GroupK-FloorHeating 1 | Power in | 1 Bit | 1.1 switch | CW |
| 121 | GroupK-Vent 1 | Power in | 1 Bit | 1.1 switch | CW |
| 121 | GroupK-AC | Power in | 1 Bit | 1.1 switch | CW |
| 121 | GroupK-AQ | Humidity in | 2 Bytes | 9.7 humidity (%) | CW |
| 122 | GroupK-FloorHeating 1 | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |
| 122 | GroupK-Switch 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 122 | GroupK-Curtain 2 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 122 | GroupK-Dimmer 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 122 | GroupK-ColorTemp 1 | Brightness out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 122 | GroupK-Vent 1 | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 122 | GroupK-AC | Mode out | 1 Byte | 20.105 HVAC control mode | CT |
| 122 | GroupK-AQ | CO2 in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 123 | GroupK-FloorHeating 1 | Set Point in | 2 Bytes | 9.1 temperature (°C) | CW |
| 123 | GroupK-Switch 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 123 | GroupK-Curtain 2 | Stop out | 1 Bit | 1.17 trigger | CT |
| 123 | GroupK-Dimmer 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 123 | GroupK-ColorTemp 1 | Brightness in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 123 | GroupK-Vent 1 | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 123 | GroupK-AC | Mode in | 1 Byte | 20.105 HVAC control mode | CW |
| 123 | GroupK-AQ | HCHO in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 124 | GroupK-ColorTemp 1 | Color Temperature out | 2 Bytes | 7.600 absolute colour temperature (K) | CT |
| 124 | GroupK-Switch 3 | Switch out | 1 Bit | 1.1 switch | CT |
| 124 | GroupK-Curtain 3 | OpenClose out | 1 Bit | 1.9 open/close | CT |
| 124 | GroupK-Dimmer 2 | Switch out | 1 Bit | 1.1 switch | CT |
| 124 | GroupK-FloorHeating 1 | Heating control out | 1 Bit | 1.1 switch | CT |
| 124 | GroupK-Vent 1 | Fan Manual out | 1 Bit | 1.3 enable | CT |
| 124 | GroupK-AC | Fan Speed out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 124 | GroupK-AQ | VOC in | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 125 | GroupK-ColorTemp 1 | Color Temperature in | 2 Bytes | 7.600 absolute colour temperature (K) | CW |
| 125 | GroupK-Switch 3 | Switch in | 1 Bit | 1.1 switch | CW |
| 125 | GroupK-Curtain 3 | Stop out | 1 Bit | 1.17 trigger | CT |
| 125 | GroupK-Dimmer 2 | Switch in | 1 Bit | 1.1 switch | CW |
| 125 | GroupK-FloorHeating 1 | Temperature in | 2 Bytes | 9.1 temperature (°C) | CW |
| 125 | GroupK-Vent 1 | Fan Manual in | 1 Bit | 1.3 enable | CW |
| 125 | GroupK-AC | Fan Speed in | 1 Byte | 5.1 percentage (0..100%) | CW |
| 125 | GroupK-AQ | PM1.0 in | 2 Bytes | 7.1 pulses | CW |
| 125 | GroupK-AQ | PM1.0 in | 2 Bytes | 9.30 concentration (µg/m³) | CW |
| 126 | GroupK-AC | Set Point out | 2 Bytes | 9.1 temperature (°C) | CT |