KNX Database

EP-KJ-D1/EP-KJ-D2

NEXhome · Order number EP-KJ-D1/EP-KJ-D2 · K270/K3174

Download .knxprod EP-KJ-D1/EP-KJ-D2 1.0 · 128 KB

Product

ManufacturerNEXhome
Product nameEP-KJ-D1/EP-KJ-D2
Order numberEP-KJ-D1/EP-KJ-D2
HardwareEP-KJ-D1/EP-KJ-D2
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationRegistered · 2024-01-25
Languagesen-US
Catalog entryM-02A4_H-02A4E4003220-16_HP-E400-10-DAE0_CI-EP.2DKJ.2DD1.2FEP.2DKJ.2DD2-1
FingerprintDAE0
SHA-256605b4aeef15cb2939bde50a76a4e91667f0f3f3205784122d0db4a7686851348
First seen2026-11-25
MarketsChina, Singapore, USA, United Arab Emirates

Application program: EP-KJ-D1/EP-KJ-D2 1.0

Application number$E400
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version5.0
Parameters249
Group objects142
Group objects (142)
NoNameFunctionSizeDPTFlags
0SW 1Switch Out1 Bit1.1 switchCT
1SW 1Switch In1 Bit1.1 switchCW
2SW 2Switch Out1 Bit1.1 switchCT
3SW 2Switch In1 Bit1.1 switchCW
4SW 3Switch Out1 Bit1.1 switchCT
5SW 3Switch In1 Bit1.1 switchCW
6SW 4Switch Out1 Bit1.1 switchCT
7SW 4Switch In1 Bit1.1 switchCW
8SW 5Switch Out1 Bit1.1 switchCT
9SW 5Switch In1 Bit1.1 switchCW
10SW 6Switch Out1 Bit1.1 switchCT
11SW 6Switch In1 Bit1.1 switchCW
12SW 7Switch Out1 Bit1.1 switchCT
13SW 7Switch In1 Bit1.1 switchCW
14SW 8Switch Out1 Bit1.1 switchCT
15SW 8Switch In1 Bit1.1 switchCW
16SW 9Switch Out1 Bit1.1 switchCT
17SW 9Switch In1 Bit1.1 switchCW
18DIM 1Switch Out1 Bit1.1 switchCT
19DIM 1Switch In1 Bit1.1 switchCW
20DIM 1Brightness Out1 Byte5.1 percentage (0..100%)CT
21DIM 1Brightness In1 Byte5.1 percentage (0..100%)CW
22DIM 2Switch Out1 Bit1.1 switchCT
23DIM 2Switch In1 Bit1.1 switchCW
24DIM 2Brightness Out1 Byte5.1 percentage (0..100%)CT
25DIM 2Brightness In1 Byte5.1 percentage (0..100%)CW
26DIM 3Switch Out1 Bit1.1 switchCT
27DIM 3Switch In1 Bit1.1 switchCW
28DIM 3Brightness Out1 Byte5.1 percentage (0..100%)CT
29DIM 3Brightness In1 Byte5.1 percentage (0..100%)CW
30DIM 4Switch Out1 Bit1.1 switchCT
31DIM 4Switch In1 Bit1.1 switchCW
32DIM 4Brightness Out1 Byte5.1 percentage (0..100%)CT
33DIM 4Brightness In1 Byte5.1 percentage (0..100%)CW
34CT 1Switch Out1 Bit1.1 switchCT
35CT 1Switch In1 Bit1.1 switchCW
36CT 1Brightness Out1 Byte5.1 percentage (0..100%)CT
37CT 1Brightness In1 Byte5.1 percentage (0..100%)CW
38CT 1Color Temperature Out2 Bytes7.600 absolute colour temperature (K)CT
39CT 1Color Temperature In2 Bytes7.600 absolute colour temperature (K)CW
40CT 2Switch Out1 Bit1.1 switchCT
41CT 2Switch In1 Bit1.1 switchCW
42CT 2Brightness Out1 Byte5.1 percentage (0..100%)CT
43CT 2Brightness In1 Byte5.1 percentage (0..100%)CW
44CT 2Color Temperature Out2 Bytes7.600 absolute colour temperature (K)CT
45CT 2Color Temperature In2 Bytes7.600 absolute colour temperature (K)CW
46CT 3Switch Out1 Bit1.1 switchCT
47CT 3Switch In1 Bit1.1 switchCW
48CT 3Brightness Out1 Byte5.1 percentage (0..100%)CT
49CT 3Brightness In1 Byte5.1 percentage (0..100%)CW
50CT 3Color Temperature Out2 Bytes7.600 absolute colour temperature (K)CT
51CT 3Color Temperature In2 Bytes7.600 absolute colour temperature (K)CW
52CT 4Switch Out1 Bit1.1 switchCT
53CT 4Switch In1 Bit1.1 switchCW
54CT 4Brightness Out1 Byte5.1 percentage (0..100%)CT
55CT 4Brightness In1 Byte5.1 percentage (0..100%)CW
56CT 4Color Temperature Out2 Bytes7.600 absolute colour temperature (K)CT
57CT 4Color Temperature In2 Bytes7.600 absolute colour temperature (K)CW
58Curtain 1Open/Close Out1 Bit1.9 open/closeCT
59Curtain 1Stop Out1 Bit1.17 triggerCT
60Curtain 2Open/Close Out1 Bit1.9 open/closeCT
61Curtain 2Stop Out1 Bit1.17 triggerCT
62Curtain 3Open/Close Out1 Bit1.9 open/closeCT
63Curtain 3Stop Out1 Bit1.17 triggerCT
64Curtain 4Open/Close Out1 Bit1.9 open/closeCT
65Curtain 4Stop Out1 Bit1.17 triggerCT
66Curtain with Blind 1OpenClose Out1 Bit1.9 open/closeCT
67Curtain with Blind 1Stop Out1 Bit1.17 triggerCT
68Curtain with Blind 1Slats Switch Out1 Bit1.1 switchCT
69Curtain with Blind 1Slats Stop Out1 Bit1.17 triggerCT
70Curtain with Blind 2OpenClose Out1 Bit1.9 open/closeCT
71Curtain with Blind 2Stop Out1 Bit1.17 triggerCT
72Curtain with Blind 2Slats Switch Out1 Bit1.1 switchCT
73Curtain with Blind 2Slats Stop Out1 Bit1.17 triggerCT
74Curtain with Blind 3OpenClose Out1 Bit1.9 open/closeCT
75Curtain with Blind 3Stop Out1 Bit1.17 triggerCT
76Curtain with Blind 3Slats Switch Out1 Bit1.1 switchCT
77Curtain with Blind 3Slats Stop Out1 Bit1.17 triggerCT
78Curtain with Blind 4OpenClose Out1 Bit1.9 open/closeCT
79Curtain with Blind 4Stop Out1 Bit1.17 triggerCT
80Curtain with Blind 4Slats Switch Out1 Bit1.1 switchCT
81Curtain with Blind 4Slats Stop Out1 Bit1.17 triggerCT
82Scene 1Scene Out1 Byte18.1 scene controlCT
83Scene 2Scene Out1 Byte18.1 scene controlCT
84Scene 3Scene Out1 Byte18.1 scene controlCT
85Scene 4Scene Out1 Byte18.1 scene controlCT
86Scene 5Scene Out1 Byte18.1 scene controlCT
87Scene 6Scene Out1 Byte18.1 scene controlCT
88AQTemp. In2 Bytes9.1 temperature (°C)CW
89AQHumi. In2 Bytes9.7 humidity (%)CW
90AQCO2 In2 Bytes9.8 parts/million (ppm)CW
91AQHCHO In2 Bytes9.8 parts/million (ppm)CW
92AQVOC In2 Bytes9.8 parts/million (ppm)CW
93AQPM1 In2 Bytes9.30 concentration (µg/m³)CW
94AQPM2.5 In2 Bytes9.30 concentration (µg/m³)CW
95AQPM10 In2 Bytes9.30 concentration (µg/m³)CW
96ACPower Out1 Bit1.1 switchCT
97ACPower In1 Bit1.1 switchCW
98ACMode Out1 Byte20.105 HVAC control modeCT
99ACMode In1 Byte20.105 HVAC control modeCW
100InternalTemperature Out2 Bytes9.1 temperature (°C)CT
101ClockDate Time In8 Bytes19.1 date timeCW
102ACFan Speed Out1 Byte5.1 percentage (0..100%)CT
103ACFan Speed In1 Byte5.1 percentage (0..100%)CW
104ACFan Auto Operation Out1 Bit1.3 enableCT
105ACFan Auto Operation In1 Bit1.3 enableCW
106ACSet Point Out2 Bytes9.1 temperature (°C)CT
107ACSet Point In2 Bytes9.1 temperature (°C)CW
108obj1091 ByteCT
109obj1101 ByteCW
110obj1111 ByteCT
111obj1121 ByteCW
112FloorHeatPower Out1 Bit1.1 switchCT
113FloorHeatPower In1 Bit1.1 switchCW
114FloorHeatSet Point Out2 Bytes9.1 temperature (°C)CT
115FloorHeatSet Point In2 Bytes9.1 temperature (°C)CW
116FloorHeatTemperature In2 Bytes9.1 temperature (°C)CW
117FloorHeatHeating control Out1 Bit1.1 switchCRT
118VENTPower Out1 Bit1.1 switchCT
119VENTPower In1 Bit1.1 switchCW
120ClockDate In3 Bytes11.1 dateCW
121ClockTime In3 Bytes10.1 time of dayCW
122VENTFan Speed Out1 Byte5.1 percentage (0..100%)CT
123VENTFan Speed In1 Byte5.1 percentage (0..100%)CW
124VENTFan Mannual Out1 Bit1.3 enableCT
125VENTFan Mannual In1 Bit1.3 enableCW
126obj1271 BitCW
127obj1281 BitCRT
128obj1291 ByteCW
129obj1301 BitCW
130obj1311 BitCW
131obj1321 BitCRT
132obj1331 ByteCW
133obj1341 BitCW
134obj1351 BitCW
135obj1361 BitCRT
136obj1371 ByteCW
137obj1381 BitCW
138obj1391 BitCW
139obj1401 BitCRT
140obj1411 ByteCW
141obj1421 BitCW
Parameters (89)
ParameterTypeDefault
UI Languagelist简体中文
Screen saver timelist30 seconds
SW AlistDisable
SW BlistDisable
SW ClistDisable
SW DlistDisable
SW ElistDisable
SW FlistDisable
SW GlistDisable
SW HlistDisable
SW IlistDisable
Descriptiontext
DIM AlistDisable
DIM BlistDisable
DIM ClistDisable
DIM DlistDisable
CT AlistDisable
CT BlistDisable
CT ClistDisable
CT DlistDisable
Curtain AlistDisable
Curtain BlistDisable
Curtain ClistDisable
Curtain DlistDisable
Curtain with Blind AlistDisable
Curtain with Blind BlistDisable
Curtain with Blind ClistDisable
Curtain with Blind DlistDisable
Scene AlistDisable
Scene BlistDisable
Scene ClistDisable
Scene DlistDisable
Scene ElistDisable
Scene FlistDisable
Item 1listTemperature
Item 2listHumidity
Item 3listCO2
Item 4listPM2.5
FunctionlistDisable
Templatelistdefault
Number of Fan Stepslist3
Automatic of FanlistDisable
State synclistSync UI only
Temperature reference fromlistInternal sensor
Hysteresis (*0.1℃)unsignedInt 0…10010
Normal statuslistOn for close, off for open
Control FunctionlistNormal
Timed On Duration(s)unsignedInt 0…6553560
Prewarning Off time(s):unsignedInt 0…2551
Manual Off EnablelistDisable
Shielding time for Manual Off(s)unsignedInt 0…25510
On Delay(10ms)unsignedInt 0…655350
Off Delay(10ms)unsignedInt 0…655350
Lock functionlistDisable
Behaviour at LockinglistOff
Behaviour at UnlockinglistOff
ScenelistDisable
Scene GlistDisable
Scene HlistDisable
ActionlistOff
Prewarning On time(s):unsignedInt 0…25510
Scene IconlistSelf define 自定义
Scene Icon IDunsignedInt 24…25524
Scene NounsignedInt 1…641
Favorite 1 TypelistDisable
No.unsignedInt 1…91
No.unsignedInt 1…41
Favorite 2 TypelistDisable
Favorite 3 TypelistDisable
Favorite 4 TypelistDisable
Favorite 5 TypelistDisable
Learn Function:listDisable
Learn FunctionlistDisable
Distance Sensor FunctionlistEnable
Send Out Local TemperaturelistDisable
Voice Control FunctionlistDisable
Fan Step 1 ValueunsignedInt 0…2551
Fan Step 2 ValueunsignedInt 0…2552
Fan Step 3 ValueunsignedInt 0…2553
Fan Step Low ValueunsignedInt 0…2551
Fan Step Mid ValueunsignedInt 0…2552
Fan Step High ValueunsignedInt 0…2553
Fan Step 1 ValueunsignedInt 0…2554
Fan Step 5 ValueunsignedInt 0…2555
Fan Speed Auto ValueunsignedInt 0…10
Sync Clock FormatlistDisable
Fan Step 2 ValueunsignedInt 0…2551
Fan Step 3 ValueunsignedInt 0…2552
Fan Step 4 ValueunsignedInt 0…2553

Version history

ApplicationApp noFingerprintFirst seenSizeFile
EP-KJ-D1/EP-KJ-D2 1.0 latest$E400DAE02026-11-25128 KBDownload

About this file

This is the official ETS product database for the NEXhome EP-KJ-D1/EP-KJ-D2 (EP-KJ-D1/EP-KJ-D2), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.