Product
| Manufacturer | Module Electronic |
|---|---|
| Product name | PS-S.640.30.1 |
| Order number | PS-S.640.30.1 |
| Hardware | PS HW |
| Medium | Twisted Pair |
| Bus current (mA) | 640 |
| Rail mounted | Yes |
| Width (mm) | 35 |
| Device kind | PowerSupply, Choke |
| Registration | Certified · 2020-09-24 |
| Languages | de-DE, fr-FR, en-US, ru-RU |
| Catalog entry | M-01C6_H-01C609030101-1-O0072_HP-0931-10-9097-O0072_CI-PS.2DS.2E640.2E30.2E1-1 |
| Fingerprint | 9097 |
| SHA-256 | ea18c11fdb39ddf89375f4dbc4a04f2907eb37620c10172f5f7777a126f11a7f |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Power supply 1.0
| Application number | $0931 |
|---|---|
| Version | 1.0 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 284 |
| Group objects | 44 |
Group objects (44)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Output voltage | Send measured value | 4 Bytes | 14.27 electric potential (V) | CRT |
| 0 | Output voltage | Send measured value | 2 Bytes | 9.20 voltage (mV) | CRT |
| 1 | Output voltage threshold | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 2 | Output current | Send measured value | 2 Bytes | 7.12 current (mA) | CRT |
| 2 | Output current | Send measured value | 2 Bytes | 9.21 current (mA) | CRT |
| 2 | Output current | Send measured value | 4 Bytes | 14.19 electric current (A) | CRT |
| 3 | Output current threshold | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 4 | Output current maximum | Send measured value | 2 Bytes | 7.12 current (mA) | CRT |
| 4 | Output current maximum | Send measured value | 2 Bytes | 9.21 current (mA) | CRT |
| 4 | Output current maximum | Send measured value | 4 Bytes | 14.19 electric current (A) | CRT |
| 5 | Temperature | Send measured value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 6 | Temperature threshold | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 7 | Temperature maximum | Send measured value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 8 | Input voltage | Send measured value | 2 Bytes | 9.21 current (mA) | CRT |
| 8 | Input voltage | Send measured value | 4 Bytes | 14.19 electric current (A) | CRT |
| 9 | Input voltage threshold | Send alarm status | 1 Bit | 1.1 switch | CRT |
| 10 | Telegram traffic | Send measured value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 11 | Telegram traffic threshold | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 12 | Overload number | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 13 | Overload duration | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 14 | Short circuit number | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 15 | Load detached duration | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 16 | KNX bus reset | Initialize | 1 Bit | 1.1 switch | CWTU |
| 17 | KNX bus reset number | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 18 | Total operating time | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 19 | Operating time since startup | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 20 | Startup number | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 21 | Duration 1 | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 22 | Counter 1 | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 23 | Threshold 1 | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 24 | Duration 2 | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 25 | Counter 2 | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 26 | Threshold 2 | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 27 | Duration 3 | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 28 | Counter 3 | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 29 | Threshold 3 | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 30 | Duration 4 | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 31 | Counter 4 | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 32 | Threshold 4 | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 33 | Counter reset | Reset all | 1 Bit | 1.1 switch | CWT |
| 34 | Measured values | Send all | 1 Bit | 1.1 switch | CWT |
| 35 | Counter values | Send all | 1 Bit | 1.1 switch | CWT |
| 36 | Power supply is on | Send info value 1 | 1 Bit | 1.1 switch | CRT |
| 37 | Heartbeat | Send info value 1 | 1 Bit | 1.17 trigger | CRT |
Parameters (94)
| Parameter | Type | Default |
|---|---|---|
| ### | unsignedInt 0…255 | 0 |
| 8/24/2016 | text | 8/24/2016 |
| Heartbeat period [s] | unsignedInt 10…32000 | 60 |
| Induce a KNX bus reset | list | with 1 |
| Time traffic Led | unsignedInt 0…64000 | 10 |
| Delay time for "Power Supply is on" (obj. 36) | list | 1 min |
| Output voltage [V] | list | disable |
| Object type | list | 4-byte (DPT14) |
| Sending difference | list | 2 V |
| Cyclic sending | list | disabled |
| Threshold type | list | Threshold exceeded |
| Upper Value | unsignedInt 28…400 | 32 |
| Lower Value | unsignedInt 24…400 | 28 |
| Threshold alarm | list | disable |
| Behaviour on alarm activation | list | send value 1 |
| Behaviour on alarm deactivation | list | send value 0 |
| Output current [mA] | list | disable |
| Sending difference | list | disabled |
| Threshold | unsignedInt 0…800 | 640 |
| Hysteresis | unsignedInt 0…640 | 1 |
| Device temperature [°C] | list | disable |
| Object type | list | DPT9 |
| Sending difference | list | 2 °C |
| Threshold | unsignedInt 0…110 | 70 |
| Hysteresis | unsignedInt 0…40 | 1 |
| Tracking period [s] | unsignedInt 10…32000 | 1800 |
| Output current maximum [mA] | list | disable |
| Automatic sending | list | do not send |
| Threshold | unsignedInt 0…800 | 0 |
| Hysteresis | unsignedInt 0…640 | 0 |
| Device temperature maximum [°C] | list | disable |
| Threshold | unsignedInt 0…110 | 0 |
| Hysteresis | unsignedInt 0…40 | 0 |
| Input voltage | list | enable |
| Object type | list | 0 |
| Alarm settings | list | disable |
| Upper Value | unsignedInt 0…255 | 0 |
| Lower Value | unsignedInt 0…240 | 0 |
| Telegram traffic [%] | list | disable |
| Object type | list | DPT5 |
| Sending difference | unsignedInt 0…100 | 10 |
| Threshold | unsignedInt 0…100 | 80 |
| Hysteresis | unsignedInt 0…70 | 10 |
| Number of overloads | list | disable |
| Object type | list | DPT7 |
| Sending difference | unsignedInt 0…1000 | 0 |
| Threshold | unsignedInt 0…500 | 0 |
| Hysteresis | unsignedInt 0…500 | 0 |
| Duration of overloads [s] | list | disable |
| Object type | list | DPT13 |
| Sending difference | unsignedInt 0…32000 | 0 |
| Threshold | unsignedInt 0…26000000 | 0 |
| Hysteresis | unsignedInt 0…26000000 | 0 |
| Number of short circuits | list | disable |
| Sending difference | unsignedInt 0…500 | 0 |
| Duration of load detached [s] | list | disable |
| Sending difference | unsignedInt 0…32000 | 20 |
| Number of KNX bus resets | list | disable |
| Number of device startups | list | disable |
| Sending difference | unsignedInt 0…500 | 1 |
| Total operating time [s] | list | disable |
| Sending difference | unsignedInt 0…2600000 | 0 |
| Operating time since last device startup [s] | list | disable |
| shortCircuit_timeDetached | unsignedInt 0…64000 | 20 |
| shortCircuit_timeBeforeDetach | unsignedInt 0…64000 | 10 |
| shortCircuit_timeShortCircCheck | unsignedInt 0…64000 | 10 |
| PS | list | 640 |
| shortCircuit_shortCircuitCurrent | unsignedInt 0…26000000 | 1100 |
| Overload current | unsignedInt 0…128000 | 900 |
| nominal Current | unsignedInt 0…128000 | 640 |
| Value LED minimum Output voltage | unsignedInt 0…26000000 | 28000 |
| Value LED maximum Output voltage | unsignedInt 0…26000000 | 32000 |
| Value LED minimum Input voltage | unsignedInt 0…26000000 | 190000 |
| Value LED maximum Input voltage | unsignedInt 0…26000000 | 270000 |
| Maximum device temperature | unsignedInt 0…26000000 | 75 |
| Minimum Device Temperature | unsignedInt 0…1000 | 0 |
| Count Working Time | unsignedInt 0…64000 | 1 |
| Check Time | unsignedInt 0…64000 | 1 |
| Convert time | unsignedInt 0…64000 | 20 |
| Time send limit | unsignedInt 0…64000 | 1 |
| Reset Time | unsignedInt 0…64000 | 20 |
| Alarm 1 | list | disable |
| Measurement source | list | Output current |
| Threshold | unsignedInt 40…95 | 70 |
| Hysteresis | unsignedInt 5…100 | 5 |
| Threshold | unsignedInt 10…800 | 640 |
| Hysteresis | unsignedInt 5…500 | 5 |
| Threshold | unsignedInt 28…32 | 31 |
| Hysteresis | unsignedInt 1…32 | 5 |
| Alarmtype | list | Threshold exceeded |
| Alarm 2 | list | disable |
| Alarm 3 | list | disable |
| Alarm 4 | list | disable |
| xxx | list | Threshold exceeded |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Power supply 1.0 latest | $0931 | 9097 | 2026-11-25 | 91 KB | Download |
About this file
This is the official ETS product database for the Module Electronic PS-S.640.30.1 (PS-S.640.30.1), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.