KNX Database

SCN-SS1H.01 Sun sensor SCN-SS1H.01

MDT technologies GmbH · Order number SCN-SS1H.01 · Archive › Weather Sensors › Sun Sensor

Sun sensor, Facade control

Download .knxprod Sun sensor 1.0 · 94 KB

Product

ManufacturerMDT technologies GmbH
Product nameSCN-SS1H.01 Sun sensor
Order numberSCN-SS1H.01
HardwareSonnensensor
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationRegistered
Languagesde-DE, en-US
Catalog entryM-0083_H-78-1_HP-004E-10-C395_CI-SCN.2DSS1H.2E01-2
FingerprintC395
SHA-25653d88b5070cea3ef18c80b8e5ffcafad9e5464d6f689122aeaa0365bc23fbc12
First seen2026-11-25
Markets69 markets

Application program: Sun sensor 1.0

Application number$004E
Version1.0
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters156
Group objects82
Group objects (82)
NoNameFunctionSizeDPTFlags
0BrightnessMeasured value2 Bytes9.4 lux (Lux)CRT
1BrightnessThreshold value1 Bit1.1 switchCRT
2BrightnessBlock object for threshold val1 Bit1.3 enableCWT
3FacadeSend reference blind stop1 Bit1.3 enableCRT
4FacadeAutomatic 1 ON1 Bit1.1 switchCRT
4FacadeScene thershold1 ByteCRT
4FacadeSend position of blinds1 Byte5.1 percentage (0..100%)CRT
4FacadeSend shutter position1 Byte5.1 percentage (0..100%)CRT
4FacadeSend reference blind Up/Down1 Bit1.8 up/downCRT
5FacadeAutomatic 2 ON1 Bit1.1 switchCRT
5FacadeSend position of slats1 Byte5.1 percentage (0..100%)CRT
5FacadePosition of facade1 Byte5.1 percentage (0..100%)CRT
6FacadeBlock object for facade1 Bit1.3 enableCW
7BrightnessThreshold value 1 upper limit2 Bytes9.4 lux (Lux)CW
8BrightnessThreshold value 1 lower limit2 Bytes9.4 lux (Lux)CW
9FacadeTeach-In position1 Bit1.3 enableCW
10FacadeStatus of blinds for Teach-In1 Byte5.1 percentage (0..100%)CW
10FacadeStatus shutter for Teach-In1 Byte5.1 percentage (0..100%)CW
10FacadeStatus of blinds position1 Byte5.1 percentage (0..100%)CW
10FacadeStatus of shutter position1 Byte5.1 percentage (0..100%)CW
10FacadeStatus of reference blind1 Byte5.1 percentage (0..100%)CW
11FacadeStatus of slats for Teach-In1 Byte5.1 percentage (0..100%)CW
11FacadeStatus of slats position1 Byte5.1 percentage (0..100%)CW
12ModeStatus1 Bit1.1 switchCRT
13StatusOnly for internal functions1 Byte5.10 counter pulses (0..255)CRT
14Testing driveDrive to sun protaction1 BitCW
15Dummy1 Byte
16Dummy1 Byte
17Dummy1 Byte
18Dummy1 Byte
19Dummy1 Byte
20Dummy1 Byte
21Dummy1 Byte
22Dummy1 Byte
23Input 1Dimming on/off1 Bit1.1 switchCRT
23Input 1Shutter1 Bit1.8 up/downCRT
23Input 1Push-button short1 Bit1.1 switchCRT
23Input 1Push-button short1 Byte5.1 percentage (0..100%)CRT
23Input 1Push-button short1 ByteCRT
23Input 1Switch1 Bit1.1 switchCRT
23Input 1Send forced setting2 Bit2.1 switch controlCRT
23Input 1Send value1 Byte5.1 percentage (0..100%)CRT
23Inputs 1 / 2Switch ON/OFF1 Bit1.1 switchCRT
23Inputs 1 / 2Shutter Up/Down1 Bit1.8 up/downCRT
23Inputs 1 / 2Dimming on/off1 Bit1.1 switchCRT
24Input 1Dimming4 Bit3.7 dimming controlCRT
24Input 1Slats/Stop1 Bit1.1 switchCRT
24Input 1Value for toggle short1 Bit1.1 switchCWTU
24Input 1Value for toggle1 Bit1.1 switchCWTU
24Inputs 1 / 2Dimming4 Bit3.7 dimming controlCRT
24Inputs 1 / 2Slats/Stop1 Bit1.1 switchCRT
25Input 1Value for toggle1 Bit1.1 switchCWTU
25Input 1Value for change of direction1 Bit1.8 up/downCWTU
25Input 1Scene1 ByteCWT
25Input 1Push-button long1 Bit1.1 switchCRT
25Input 1Push-button long1 Byte5.1 percentage (0..100%)CRT
25Input 1Push-button long1 ByteCRT
26Input 1Value for toggle long1 BitCWT
27Input 1Block object1 Bit1.3 enableCWT
27Inputs 1 / 2Block object1 Bit1.3 enableCWT
28Input 2Dimming on/off1 Bit1.1 switchCRT
28Input 2Shutter1 Bit1.8 up/downCRT
28Input 2Push-button short1 Bit1.1 switchCRT
28Input 2Push-button short1 Byte5.1 percentage (0..100%)CRT
28Input 2Push-button short1 ByteCRT
28Input 2Switch1 Bit1.1 switchCRT
28Input 2Send forced setting2 Bit2.1 switch controlCRT
28Input 2Send value1 Byte5.1 percentage (0..100%)CRT
29Input 2Dimming4 Bit3.7 dimming controlCRT
29Input 2Slats/Stop1 Bit1.1 switchCRT
29Input 2Value for toggle short1 Bit1.1 switchCWTU
29Input 2Value for toggle1 Bit1.1 switchCWTU
30Input 2Value for toggle1 Bit1.1 switchCWTU
30Input 2Value for change of direction1 Bit1.8 up/downCWTU
30Input 2Scene1 ByteCWT
30Input 2Push-button long1 Bit1.1 switchCRT
30Input 2Push-button long1 Byte5.1 percentage (0..100%)CRT
30Input 2Push-button long1 ByteCRT
31Input 2Value for toggle long1 BitCWTU
32Input 1Block object1 Bit1.3 enableCWT
32Input 2Block object1 Bit1.3 enableCWT
33Dummy1 Byte
Parameters (69)
ParameterTypeDefault
Startup timelist1 s
Limitation of telegramslistno active
max. quantity in 10 secondsunsignedInt 0…25515
Cyclic send of "Operating"-Telegrammlistno send
Behavior after programminglistHold Teach-In/saved values
Entprellzeit [ms]list10 ms
Time for keystroke long [s]list0,4 s
Behaviour at Bus power uplistNo read value for toggle
DummylistNo
Send brightness value [Lux ]listat change
Send by change oflist10%
Time for cyclic sendinglist5 min
Threshold valuelistactive
Facade controllistactive
Threshold value upper limit at …[Lux] x 1000unsignedInt 1…9930
Minimum of period if limit exceededlist5 min
Threshold value lower limit at …[Lux] x 1000unsignedInt 1…9920
Minimum of period if limit fall belowlist5 min
Modifiable threshold valuelistonly via parameter
Send if limit exceededlistsend ON-telegramm
Send if lower deviationlistsend OFF-telegramm
Time for cyclic sendinglistno send
Block for thershold valuelistno use
DummyDptSideAutomatiklistno active
Reaction if threshold value exceededlistno reaction
Reaction if threshold value fall belowlistno reaction
Data type for moving objectlist1 Byte absolute position
Scene numberlist1
Reaction if threshold value fall belowlistSend scene
Drive position forlistBlinds
Absolute position for blindslist0%
Position 1listTeach-In will be not used
Only move iflistalways drive
Absolute position for shutterlist0%
Time for cyclic sendinglistnever
Block objectlistno use
Info servicelistnot active
Function inputs 1 / 2listInactive
Inputs 1 / 2listDimming
Switch function 1 / 2liston / off
FunktionlistShutter
Dimming function 1 / 2listBrighter/Darker
1 Byte value [0…255]unsignedInt 0…2550
Shutter function 1 / 2listUp, Down
1-B ShutterlistActive
1-B Shutterlistnot active
Operating funktionlistLong=move / short=stop/blinds
Blocking Objectlistnot active
FunctionlistInactive
SubfunctionlistSwitch rising edge
Value for risinge edgelistOn
Value for falling edgelistOff
Behaviour at Bus power uplistsend nothing
Send cyclic activlistOff
Time intervall for send cyclic [s]unsignedInt 1…30001
Value (1 Byte) / forced setting (2 Bit)list1 Byte value
Value for risinge edgeunsignedInt 0…2550
Send forced settinglistForced setting not activ
Block objectlistno active
SubfunctionlistSave
Scene Numberlist1
Block objectlistnot active
Value for keystroke short - Object 1listOn
Send valuelist1 Byte value [0…255]
Value for keystroke long - Object 2listNothing
Dimming stepslist100%
Repeat TelegramlistNo
Repetition timelist1.0 s
Value for keystroke short - Object 2listOn

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Sun sensor 1.0 latest$004EC3952026-11-2594 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH SCN-SS1H.01 Sun sensor (SCN-SS1H.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH

All MDT technologies GmbH products