KNX Database

SCN-BWM60T.02 Motion Detector TS 60 CH with T-Sensor and 2 sensor keys SCN-BWM60T.02

MDT technologies GmbH · Order number SCN-BWM60T.02 · Motion / Presence Detector › Wal mounting

Download .knxprod Motion Detector TS 55 with T-Sensor and 2 sensor keys 4.4 · 178 KB

Product

ManufacturerMDT technologies GmbH
Product nameSCN-BWM60T.02 Motion Detector TS 60 CH with T-Sensor and 2 sensor keys
Order numberSCN-BWM60T.02
HardwareBewegungsmelder 60 CH mit Temp
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2021-06-15
Languagesde-DE, en-US, es-ES, fr-FR
Catalog entryM-0083_H-2.2E15-2_HP-006D-44-E3C8_CI-SCN.2DBWM60T.2E02-2
FingerprintE3C8
SHA-25657b5b9ce9e176a3263d3bc02727767175a950e29a0c0db5042748243dcd5a040
First seen2026-11-25
Markets69 markets

Application program: Motion Detector TS 55 with T-Sensor and 2 sensor keys 4.4

Application number$006D
Version4.4
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters604
Group objects229
Group objects (229)
NoNameFunctionSizeDPTFlags
0Light channel 1 - Output 1Dimming absolute1 Byte5.1 percentage (0..100%)CRT
0Light channel 1 - Output 1Switch1 Bit1.1 switchCRT
0Light channel 1 - Output 1Scene1 Byte17.1 scene numberCRT
0Light channel 1 - Output 1 (Day)Switch1 Bit1.1 switchCRT
1Light channel 1 - Output (Night)Switch1 Bit1.1 switchCRT
2Light channel 1 - Output 2 (Additional)Switch1 Bit1.1 switchCRT
3Light channel 1 - InputExternal push button short1 Bit1.1 switchCW
4Light channel 1 - InputExternal push button long1 Bit1.1 switchCW
5Light channel 1 - InputExternal motion (Slave)1 Bit1.1 switchCW
6Light channel 1 - InputStatus of actuator channel1 Bit1.1 switchCW
7Light channel 1 - InputLock motion detection1 Bit1.3 enableCW
8Light channel 1 - InputForced guidance2 Bit2.1 switch controlCW
8Light channel 1 - InputLock object1 Bit1.3 enableCW
9Light channel 1 - InputLock object ON1 Bit1.3 enableCW
10Light channel 1 - StatusAutomatic mode1 Bit1.11 stateCRT
10Light channel 1 - StatusLock/Manual mode1 Bit1.11 stateCRT
11Light channel 1 - InputSwitch dark1 Bit1.1 switchCW
12Light channel 1 - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CRW
13Light channel 1 - InputFollow-up time 10-65000s2 Bytes7.5 time (s)CRW
14dummy1 Bit
15Light channel 2 - Output 1Scene1 Byte17.1 scene numberCRT
15Light channel 2 - Output 1Switch1 Bit1.1 switchCRT
15Light channel 2 - Output 1Dimming absolute1 Byte5.1 percentage (0..100%)CRT
15Light channel 2 - Output 1 (Day)Switch1 Bit1.1 switchCRT
16Light channel 2 - Output (Night)Switch1 Bit1.1 switchCRT
17Light channel 2 - Output 2 (Additional)Switch1 Bit1.1 switchCRT
18Light channel 2 - InputExternal push button short1 Bit1.1 switchCW
19Light channel 2 - InputExternal push button long1 Bit1.1 switchCW
20Light channel 2 - InputExternal motion (Slave)1 Bit1.1 switchCW
21Light channel 2 - InputStatus of actuator channel1 Bit1.1 switchCW
22Light channel 2 - InputLock motion detection1 Bit1.3 enableCW
23Light channel 2 - InputForced guidance2 Bit2.1 switch controlCW
23Light channel 2 - InputLock object1 Bit1.3 enableCW
24Light channel 2 - InputLock object ON1 Bit1.3 enableCW
25Light channel 2 - StatusAutomatic mode1 Bit1.11 stateCRT
25Light channel 2 - StatusLock/Manual mode1 Bit1.11 stateCRT
26Light channel 2 - InputSwitch dark1 Bit1.1 switchCW
27Light channel 2 - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CRW
28Light channel 2 - InputFollow-up time 10-65000s2 Bytes7.5 time (s)CRW
29dummy1 Bit
30dummy1 Bit
31dummy1 Bit
32dummy1 Bit
33dummy1 Bit
34dummy1 Bit
35dummy1 Bit
36dummy1 Bit
37dummy1 Bit
38dummy1 Bit
39dummy1 Bit
40dummy1 Bit
41dummy1 Bit
42dummy1 Bit
43dummy1 Bit
44dummy1 Bit
45dummy1 Bit
46dummy1 Bit
47dummy1 Bit
48dummy1 Bit
49dummy1 Bit
50dummy1 Bit
51dummy2 Bit
52dummy1 Bit
53dummy1 Bit
54dummy1 Bit
55dummy1 Bit
56dummy1 Bit
57dummy1 Bit
58dummy1 Bit
59dummy1 Bit
60HVAC - OutputScene1 Byte17.1 scene numberCRT
60HVAC - OutputDimming absolute1 Byte5.1 percentage (0..100%)CRT
60HVAC - OutputSwitch1 Bit1.1 switchCRT
61dummy1 Bit
62dummy1 Bit
63HVAC - InputExternal push button short1 Bit1.1 switchCW
64HVAC - InputExternal push button long1 Bit1.1 switchCW
65HVAC - InputExternal motion1 Bit1.1 switchCW
66HVAC - InputStatus of actuator channel1 Bit1.1 switchCW
67HVAC - InputLock motion detection1 Bit1.3 enableCW
68HVAC - InputLock object1 Bit1.3 enableCW
68HVAC - InputForced guidance2 Bit2.1 switch controlCW
69HVAC - InputLock object ON1 Bit1.3 enableCW
70HVAC - StatusAutomatic mode1 Bit1.11 stateCRT
70HVAC - StatusLock/Manual mode1 Bit1.11 stateCRT
71HVAC - InputSwitch dark1 Bit1.1 switchCW
72HVAC - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CRW
73HVAC - InputFollow-up time 10-65000s2 Bytes7.5 time (s)CRW
74dummy1 Bit
75Alarm - OutputSwitch1 Bit1.1 switchCRT
75Alarm - Output (Day)Switch1 Bit1.1 switchCRT
76Alarm - Output (Night)Switch1 Bit1.1 switchCRT
77dummy1 Bit
78dummy1 Bit
79dummy1 Bit
80dummy1 Bit
81dummy1 Bit
82dummy1 Bit
83Alarm - InputLock1 Bit1.3 enableCW
83Alarm - InputEnable1 Bit1.3 enableCW
84dummy1 Bit
85dummy1 Bit
86dummy1 Bit
87dummy1 Bit
88dummy1 Bit
89dummy1 Bit
90Day/NightDay = 0 / Night = 11 Bit1.2 booleanCWTUI
90Day/NightDay = 1 / Night = 01 Bit1.2 booleanCWTUI
91LED greenSwitch1 Bit1.1 switchCW
92LED redFlashing1 Bit1.1 switchCW
93LED whiteSwitch1 Bit1.1 switchCW
94SceneInput1 Byte17.1 scene numberCW
95OperatingOutput1 Bit1.11 stateCRT
96dummy1 Bit
97BrightnessMeasured value2 Bytes9.4 lux (Lux)CRT
98BrightnessSet switch-on threshold for light channels2 Bytes9.4 lux (Lux)CRW
99Dummy1 Bit
100Dummy1 Bit
101Direction of movement 1Switch on movement from right to left1 Bit1.1 switchCRT
102Direction of movement 2Switch on movement from left to right1 Bit1.1 switchCRT
103dummy1 Bit
104dummy1 Bit
105dummy1 Bit
106dummy1 Bit
107dummy1 Bit
108dummy1 Bit
109dummy1 Bit
110Logic 1 {{1234}}Input C1 Bit1.2 booleanCWTU
111Logic 1 {{1234}}Input D1 Bit1.2 booleanCWTU
112Logic 1 {{1234}}Input E1 Bit1.2 booleanCWTU
113Logic 1 {{1234}}Input F1 Bit1.2 booleanCWTU
114Logic 1 {{1234}}Output 11 Byte17.1 scene numberCRT
114Logic 1 {{1234}}Output 11 Byte5.1 percentage (0..100%)CRT
114Logic 1 {{1234}}Output 11 Byte5.5 ratio (0..255)CRT
114Logic 1 {{1234}}Output 12 Bit2.1 switch controlCRT
114Logic 1 {{1234}}Output 11 Bit1.2 booleanCRT
115Logic 2 {{1269}}Input C1 Bit1.2 booleanCWTU
116Logic 2 {{1269}}Input D1 Bit1.2 booleanCWTU
117Logic 2 {{1269}}Input E1 Bit1.2 booleanCWTU
118Logic 2 {{1269}}Input F1 Bit1.2 booleanCWTU
119Logic 2 {{1269}}Output 21 Byte5.5 ratio (0..255)CRT
119Logic 2 {{1269}}Output 21 Byte5.1 percentage (0..100%)CRT
119Logic 2 {{1269}}Output 22 Bit2.1 switch controlCRT
119Logic 2 {{1269}}Output 21 Bit1.2 booleanCRT
119Logic 2 {{1269}}Output 21 Byte17.1 scene numberCRT
120Logic 3 {{1303}}Input C1 Bit1.2 booleanCWTU
121Logic 3 {{1303}}Input D1 Bit1.2 booleanCWTU
122Logic 3 {{1303}}Input E1 Bit1.2 booleanCWTU
123Logic 3 {{1303}}Input F1 Bit1.2 booleanCWTU
124Logic 3 {{1303}}Output 32 Bit2.1 switch controlCRT
124Logic 3 {{1303}}Output 31 Byte5.1 percentage (0..100%)CRT
124Logic 3 {{1303}}Output 31 Byte5.5 ratio (0..255)CRT
124Logic 3 {{1303}}Output 31 Byte17.1 scene numberCRT
124Logic 3 {{1303}}Output 31 Bit1.2 booleanCRT
125Logic 4 {{1338}}Input C1 Bit1.2 booleanCWTU
126Logic 4 {{1338}}Input D1 Bit1.2 booleanCWTU
127Logic 4 {{1338}}Input E1 Bit1.2 booleanCWTU
128Logic 4 {{1338}}Input F1 Bit1.2 booleanCWTU
129Logic 4 {{1338}}Output 41 Bit1.2 booleanCRT
129Logic 4 {{1338}}Output 41 Byte17.1 scene numberCRT
129Logic 4 {{1338}}Output 41 Byte5.5 ratio (0..255)CRT
129Logic 4 {{1338}}Output 41 Byte5.1 percentage (0..100%)CRT
129Logic 4 {{1338}}Output 42 Bit2.1 switch controlCRT
130TemperatureMeasured value2 Bytes9.1 temperature (°C)CRT
131Buttons left/rightSwitch On/Off1 Bit1.1 switchCRT
131Buttons left/rightDimming On/Off1 Bit1.1 switchCRT
131Buttons left/rightBlinds Up/Down1 Bit1.8 up/downCRT
131Button leftSwitch1 Bit1.1 switchCRT
131Button leftToggle1 Bit1.1 switchCRT
131Button leftSend value1 Byte5.10 counter pulses (0..255)CRT
131Button leftSend percent value1 Byte5.1 percentage (0..100%)CRT
131Button leftSend scene1 Byte17.1 scene numberCRT
131Button left shortSwitch1 Bit1.1 switchCRT
131Button left shortSend value1 Byte5.5 ratio (0..255)CRT
131Button left shortSend percent value1 Byte5.1 percentage (0..100%)CRT
131Button left shortSend scene1 Byte17.1 scene numberCRT
131Button leftDimming On/Off1 Bit1.1 switchCRT
131Button leftBlinds Up/Down1 Bit1.8 up/downCRT
131Button leftSend state1 Bit1.11 stateCRT
131Button leftForced guidance2 Bit2.1 switch controlCRT
132Buttons left/rightDimming relative4 Bit3.7 dimming controlCRT
132Buttons left/rightSlats adjustment / Stop1 Bit1.7 stepCRT
132Button leftStatus for toggle1 Bit1.1 switchCWTU
132Button left shortStatus for toggle1 Bit1.1 switchCWTU
132Button leftDimming relative4 Bit3.7 dimming controlCRT
132Button leftSlats adjustment / Stop1 Bit1.7 stepCRT
132Button left longSwitch1 Bit1.1 switchCRT
133Button left longSwitch1 Bit1.1 switchCRT
133Button left longSend value1 Byte5.5 ratio (0..255)CRT
133Button left longSend percent value1 Byte5.1 percentage (0..100%)CRT
133Button left longSend scene1 Byte17.1 scene numberCRT
133Button leftStatus for toggle1 Bit1.1 switchCWTU
133Button leftStatus for change of direction1 Bit1.8 up/downCWTU
134Button left longStatus for toggle1 Bit1.11 stateCWTU
135dummy1 Bit
136Button rightSwitch1 Bit1.1 switchCRT
136Button rightToggle1 Bit1.1 switchCRT
136Button rightSend value1 Byte5.5 ratio (0..255)CRT
136Button rightSend percent value1 Byte5.1 percentage (0..100%)CRT
136Button rightSend scene1 Byte17.1 scene numberCRT
136Button right shortSwitch1 Bit1.1 switchCRT
136Button right shortSend value1 Byte5.5 ratio (0..255)CRT
136Button right shortSend percent value1 Byte5.1 percentage (0..100%)CRT
136Button right shortSend scene1 Byte17.1 scene numberCRT
136Button rightDimming On/Off1 Bit1.1 switchCRT
136Button rightBlinds Up/Down1 Bit1.8 up/downCRT
136Button rightSend state1 Bit1.11 stateCRT
136Button rightForced guidance2 Bit2.1 switch controlCRT
137Button rightStatus for toggle1 Bit1.1 switchCWTU
137Button right shortStatus for toggle1 Bit1.1 switchCWTU
137Button rightDimming relative4 Bit3.7 dimming controlCRT
137Button rightSlats adjustment / Stop1 Bit1.7 stepCRT
138Button right longSwitch1 Bit1.1 switchCRT
138Button right longSend value1 Byte5.5 ratio (0..255)CRT
138Button right longSend percent value1 Byte5.1 percentage (0..100%)CRT
138Button right longSend scene1 Byte17.1 scene numberCRT
138Button rightStatus for toggle1 Bit1.1 switchCWTU
138Button rightStatus for change of direction1 Bit1.8 up/downCWTU
139Button right longStatus for toggle1 Bit1.11 stateCWTU
140dummy1 Bit
141dummy1 Bit
142dummy1 Bit
143dummy1 Bit
144dummy1 Bit
145dummy1 Bit
146dummy1 Bit
147dummy1 Bit
148dummy1 Bit
149dummy1 Bit
Parameters (213)
ParameterTypeDefault
Fallback of forced guidance/locklistnot active
Channel modelistfully automatic
Follow-up time "Day"list3 min
Switch-on threshold "Day"unsignedInt 5…1000100
Forced guidance or lock objectlistlock object
Action at lockinglistlock motion (lock current state)
Action at unlockinglistno changes
Object type for output - Lightlistswitch
Dimming value for "Day" when ONlist100%
Scene number for "Day" when ONlist1
Dimming value for "Day" when OFFlist0%
Scene number for "Day" when OFFlist2
Idle time after switch-offunsignedInt 0…601
Scene number for "Night" when ONlist3
Scene number for "Night" when OFFlist4
Output object 1 sends ON cyclicallylistnot active
Day/Night objectlistrequest after reset
Value for Day/NightlistDay = 1 / Night = 0
Send "Operating" cyclicallylistnot active
Output objects for Day/Nightlistone common object
Object type for output - HVAClistswitch
Trigger sensitivity "Night"list3 (low)
Dimming value for "Night" when OFFlist0%
Dimming value for "Night" when ONlist30%
Follow-up time for forced guidance/lock (Day)list3 min
Motion filter in standbylistnot active, no filtering
Presence sensitivitylist8 (high)
Trigger sensitivity "Day"list6
Toggle Day/Nightlistat next presence
Fallback time for forced guidance/lock (Day)list3 min
Switch-on threshold "Night"unsignedInt 5…100010
Light channel 1listactive
HVAC channellistnot active
Active sensorslist12
Brightnesslistbasic setting or object "Dark switch" is active
Reduction of follow-up timelistnot active
Maximum duration for short time presencelist20 s
Fallback for external push button long (Manual => Auto)listafter presence and follow-up time
Manual mode, follow-up time at ON (Day)list3 min
Manual mode, fallback time at ON (Day)list3 min
Follow-up time for short time presencelist60 s
Sensitivitylistbasic setting (General setting)
Length of monitoring time slotunsignedInt 0…3000030
Object value for "Day" when ONlistvalue 1
Object value for "Day" when OFFlistvalue 0
Object value for "Night" when ONlistvalue 1
Object value for "Night" when OFFlistvalue 0
Output object sends ON cyclicallylistnot active
External push button short reacts tolistON and OFF
Number of monitoring time slotslist3
Detection channel (Alarm) / Direction of movementlistnot active
Scene A numberlistnot active
Scene A Light channel 1listnot active
Scene A Light channel 2listnot active
Scene B numberlistnot active
Scene B Light channel 1listnot active
Scene B Light channel 2listnot active
Scene C numberlistnot active
Scene C Light channel 1listnot active
Scene C Light channel 2listnot active
Scene D numberlistnot active
Scene D Light channel 1listnot active
Scene D Light channel 2listnot active
Scene E numberlistnot active
Scene E Light channel 1listnot active
Scene E Light channel 2listnot active
Scene F numberlistnot active
Scene F Light channel 1listnot active
Scene F Light channel 2listnot active
Scene G numberlistnot active
Scene G Light channel 1listnot active
Scene G Light channel 2listnot active
Scene H numberlistnot active
Scene H Light channel 1listnot active
Scene H Light channel 2listnot active
Logic function 1listnot active
Request inputs after bus power returnlistnot active
FunctionlistAND
Description of functiontext
Sending conditionliston change of output
Output objectlistswitch
Outputlistnormal
Value for output value "False"unsignedInt 0…2550
Datapoint typelist1Byte DPT 5.005 Decimal factor (0...255)
Percent value for output value "False"list0%
Forced guidance for output value "False"list00 - no priority, Off
Forced guidance for output value "True"list00 - no priority, Off
Internal input Alistnot active
Object numberunsignedInt 0…1290
Internal input Blistnot active
External input Clistnot active
External input Dlistnot active
External input Elistnot active
External input Flistnot active
Preset logic input after reset with...listvalue 0
Logic function 2listnot active
Scene number for output value "False"list1
Logic function 3listnot active
Logic function 4listnot active
Trigger sensitivity "Day"list3 (low)
Trigger sensitivity "Night"list2
Presence sensitivitylist6
Length of monitoring time slotlist2s
Output object sends atlistON and OFF
Object sends cyclically every...listnot active
Behaviour after expiry of follow-up timelistswitch-off immediately
Switch-off delay for "Day"list30 s
Switch-off dimming value for "Day"list30%
Switch-off delay for "Night"list30 s
Switch-off dimming value for "Night"list20%
Sending conditionliston output change
Light channel 2listnot active
Motion filter in readinesslistnot active, no filtering
Scene number for output value "True"list1
Value for output value "True"unsignedInt 0…2550
Percent value for output value "True"list0%
Lock or enable objectlistlock object
Output 2 (Additional switch object)listnot active
Switch-on thresholdunsignedInt 5…1000100
External push button long reacts tolistON and OFF
If output “Day” is already ONlistswitch to manual mode
If Night light is activelistswitch to Day light
If output “Day” is already ONliststay in automatic mode
Send brightness on change oflist10%
Send measured value cyclicallylistnot active
Correction Lux valuelist0%
Temperature measurementlistnot active
Send measured value on change oflist0,2 K
Correction value for sensorsignedInt -80…500
LED greenlistactive on motion
LED red, object "LED red flashing"listnot active
LED white (Night light)listnot active
Brightness at "Night"list10%
Follow-up time for forced guidance/lock (Night)list3 min
Fallback time for forced guidance/lock (Night)list3 min
Manual mode, follow-up time at ON (Night)list3 min
Manual mode, fallback time at ON (Night)list3 min
Follow-up time "Night"list30 s
Status informationlistnot active
Manual mode, follow-up time at OFF (Day)list3 min
Manual mode, fallback time at OFF (Day)list3 min
Manual mode, follow-up time at OFF (Night)list3 min
Manual mode, fallback time at OFF (Night)list3 min
Trigger sensitivitylist6
Follow-up timelist3 min
Dimming value for ONlist100%
Dimming value for OFFlist0%
Switch-off delaylist30 s
Switch-off dimming valuelist30%
Scene number for ONlist1
Scene number for OFFlist2
Object value for ONlistvalue 1
Object value for OFFlistvalue 0
Trigger sensitivitylist3 (low)
Follow-up time for forced guidance/locklist3 min
Fallback time for forced guidance/locklist3 min
Manual mode, follow-up time at ONlist3 min
Manual mode, follow-up time at OFFlist3 min
Manual mode, fallback time at ONlist3 min
Manual mode, fallback time at OFFlist3 min
Output object 1 sendslistON and OFF
Output object 1 sendslistdimming value for ON and OFF
Output object 1 sendslistscene number for ON and OFF
Output object 1 sends value for ON cyclicallylistnot active
Output object 1 sends scene for ON cyclicallylistnot active
Additional texttext
Switch-off if exceedancelistnot active
Switch OFF when exceeding...unsignedInt 75…1000800
Interference / motion filterlistnot active, no filtering
Information about sensor assignmentunsignedInt 0…10
Position of sensorspicture
Direction of movementlistactive
Installation sitelistcorridor
Light channels influence the brightness measurementlistyes (several lights in the room)
Display "manual mode ON" with green LEDlistactive
Display "manual mode OFF" with red LEDlistactive
Display "lock/forced guidance ON" with green LEDlistactive
Display "lock/forced guidance OFF" with red LEDlistactive
Function Buttonslistnot active
Basic functionlistdimming
Button assignment (left/right)listON / OFF
Button assignment (left/right)listdarker/brighter
Button assignment (left/right)listUp / Down
Operation functionlistlong=move / short=stop/slats Open/Close
ValueunsignedInt 0…2550
Basic function: Left buttonlistswitch
Subfunctionlistswitch when button is pressed
ValuelistON
Valuelist100%
Scene numberlist1
Action for short keypresslistON
Scene Numberlist1
Action for long keypresslistnot active
Value for pressed buttonlistON
Value for released buttonlistON
Cyclic sendinglistnot active
Send cyclically every…unsignedInt 1…3000300
Send state after bus power returnlistactive
Basic function: Right buttonlistswitch
Display button operation with white LEDlistactive
Time for long keypresslist0,6 s
Selection for value for left button shortlistON
Selection for value for right button shortlistON
Idle time after external button short is OFFunsignedInt 1…305
Inernal functionlistswitch short/long
Forced guidance functionlistPriority, On
Lock function buttons left / rightlistON / OFF
Switch function buttons left/rightlistforced mode / automatic mode
Fallback of forced guidance/lock (General setting)listactive
Fallback of forced guidance/lock (General setting)listnot active
Objects for buttonslistnot active
If output is already ONlistswitch to manual mode
If output is already ONliststay in automatic mode

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Motion Detector TS 55 with T-Sensor and 2 sensor keys 4.4 latest$006DE3C82026-11-25178 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH SCN-BWM60T.02 Motion Detector TS 60 CH with T-Sensor and 2 sensor keys (SCN-BWM60T.02), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH

All MDT technologies GmbH products