KNX Database

PSE-B552T0x.02S KNX Motion Detector 2,2 m TS 55, Secure PSE-B552T0x.02S

MDT technologies GmbH · Order number PSE-B552T0x.02S · Motion / Presence Detector › Wal mounting

Download .knxprod Motion Detector 2,2 m TS 55, Secure 1.0 · 212 KB

Product

ManufacturerMDT technologies GmbH
Product namePSE-B552T0x.02S KNX Motion Detector 2,2 m TS 55, Secure
Order numberPSE-B552T0x.02S
HardwareBewegungsmelder 2,2m TS 55 Secure
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationRegistered · 2025-10-31
Languagesde-DE, en-US, es-ES, fr-FR, it-IT
Catalog entryM-0083_H-409-1_HP-047A-10-6CE0_CI-PSE.2DB552T0x.2E02S-1
Fingerprint6CE0
SHA-256281c616312b2bd19719bf4381f005acc6eeb928c128c9d1e37698e4bed726fd5
First seen2026-11-25
Markets69 markets

Application program: Motion Detector 2,2 m TS 55, Secure 1.0

Application number$047A
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters532
Group objects108
Group objects (108)
NoNameFunctionSizeDPTFlags
1Light channel 1 - Output 1Switch1 Bit1.1 switchCRT
1Light channel 1 - Output 1 (Day)Switch1 Bit1.1 switchCRT
1Light channel 1 - Output 1Dimming absolute1 Byte5.1 percentage (0..100%)CRT
1Light channel 1 - Output 1Scene1 Byte17.1 scene numberCRT
2Light channel 1 - Output (Night)Switch1 Bit1.1 switchCRT
3Light channel 1 - Output 2 (Additional)Switch1 Bit1.1 switchCRT
4Light channel 1 - InputExternal button short1 Bit1.1 switchCW
5Light channel 1 - InputExternal button long1 Bit1.1 switchCW
6Light channel 1 - InputExternal motion (Slave)1 Bit1.1 switchCW
7Light channel 1 - InputStatus of actuator channel1 Bit1.1 switchCW
8Light channel 1 - InputLock motion detection1 Bit1.3 enableCW
9Light channel 1 - InputForced guidance2 Bit2.1 switch controlCW
9Light channel 1 - InputLock object1 Bit1.3 enableCW
10Light channel 1 - InputLock object ON1 Bit1.3 enableCW
11Light channel 1 - StatusAutomatic mode1 Bit1.11 stateCRT
11Light channel 1 - StatusLock/Manual mode1 Bit1.11 stateCRT
12Light channel 1 - InputSwitch dark1 Bit1.1 switchCW
13Light channel 1 - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CRW
14Light channel 1 - InputFollow-up time 10 - 65000 s2 Bytes7.5 time (s)CRW
16Light channel 2 - Output 1Switch1 Bit1.1 switchCRT
16Light channel 2 - Output 1 (Day)Switch1 Bit1.1 switchCRT
16Light channel 2 - Output 1Dimming absolute1 Byte5.1 percentage (0..100%)CRT
16Light channel 2 - Output 1Scene1 Byte17.1 scene numberCRT
17Light channel 2 - Output (Night)Switch1 Bit1.1 switchCRT
18Light channel 2 - Output 2 (Additional)Switch1 Bit1.1 switchCRT
19Light channel 2 - InputExternal button short1 Bit1.1 switchCW
20Light channel 2 - InputExternal button long1 Bit1.1 switchCW
21Light channel 2 - InputExternal motion (Slave)1 Bit1.1 switchCW
22Light channel 2 - InputStatus of actuator channel1 Bit1.1 switchCW
23Light channel 2 - InputLock motion detection1 Bit1.3 enableCW
24Light channel 2 - InputForced guidance2 Bit2.1 switch controlCW
24Light channel 2 - InputLock object1 Bit1.3 enableCW
25Light channel 2 - InputLock object ON1 Bit1.3 enableCW
26Light channel 2 - StatusAutomatic mode1 Bit1.11 stateCRT
26Light channel 2 - StatusLock/Manual mode1 Bit1.11 stateCRT
27Light channel 2 - InputSwitch dark1 Bit1.1 switchCW
28Light channel 2 - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CRW
29Light channel 2 - InputFollow-up time 10 - 65000 s2 Bytes7.5 time (s)CRW
61HVAC - OutputSwitch1 Bit1.1 switchCRT
61HVAC - OutputDimming absolute1 Byte5.1 percentage (0..100%)CRT
61HVAC - OutputScene1 Byte17.1 scene numberCRT
64HVAC - InputExternal button short1 Bit1.1 switchCW
65HVAC - InputExternal button long1 Bit1.1 switchCW
66HVAC - InputExternal motion1 Bit1.1 switchCW
67HVAC - InputStatus of actuator channel1 Bit1.1 switchCW
68HVAC - InputLock motion detection1 Bit1.3 enableCW
69HVAC - InputForced guidance2 Bit2.1 switch controlCW
69HVAC - InputLock object1 Bit1.3 enableCW
70HVAC - InputLock object ON1 Bit1.3 enableCW
71HVAC - StatusAutomatic mode1 Bit1.11 stateCRT
71HVAC - StatusLock/Manual mode1 Bit1.11 stateCRT
72HVAC - InputSwitch dark1 Bit1.1 switchCW
73HVAC - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CRW
74HVAC - InputFollow-up time 10 - 65000 s2 Bytes7.5 time (s)CRW
76Alarm - OutputSwitch1 Bit1.1 switchCRT
76Alarm - Output (Day)Switch1 Bit1.1 switchCRT
77Alarm - Output (Night)Switch1 Bit1.1 switchCRT
84Alarm - InputLock1 Bit1.3 enableCW
84Alarm - InputRelease1 Bit1.3 enableCW
91Day/NightDay = 1 / Night = 01 Bit1.2 booleanCWTUI
91Day/NightDay = 0 / Night = 11 Bit1.2 booleanCWTUI
92LED greenSwitch1 Bit1.1 switchCW
93LED redFlashing1 Bit1.1 switchCW
94LED whiteSwitch1 Bit1.1 switchCW
95SceneInput1 Byte17.1 scene numberCW
96In operationOutput1 Bit1.11 stateCRT
98BrightnessSend measured value2 Bytes9.4 lux (Lux)CRT
99BrightnessSet switch-on threshold for light channels2 Bytes9.4 lux (Lux)CRW
102Direction of movement 1Switch when moving from right to left1 Bit1.1 switchCRT
103Direction of movement 2Switch when moving from left to right1 Bit1.1 switchCRT
111Logic 1 {{0}}Input C1 Bit1.2 booleanCWTU
112Logic 1 {{0}}Input D1 Bit1.2 booleanCWTU
113Logic 1 {{0}}Input E1 Bit1.2 booleanCWTU
114Logic 1 {{0}}Input F1 Bit1.2 booleanCWTU
115Logic 1 {{0}}Output 11 Bit1.2 booleanCRT
115Logic 1 {{0}}Output 11 Byte17.1 scene numberCRT
115Logic 1 {{0}}Output 11 Byte5.5 ratio (0..255)CRT
115Logic 1 {{0}}Output 11 Byte5.1 percentage (0..100%)CRT
115Logic 1 {{0}}Output 12 Bit2.1 switch controlCRT
116Logic 2 {{0}}Input C1 Bit1.2 booleanCWTU
117Logic 2 {{0}}Input D1 Bit1.2 booleanCWTU
118Logic 2 {{0}}Input E1 Bit1.2 booleanCWTU
119Logic 2 {{0}}Input F1 Bit1.2 booleanCWTU
120Logic 2 {{0}}Output 21 Bit1.2 booleanCRT
120Logic 2 {{0}}Output 21 Byte17.1 scene numberCRT
120Logic 2 {{0}}Output 21 Byte5.5 ratio (0..255)CRT
120Logic 2 {{0}}Output 21 Byte5.1 percentage (0..100%)CRT
120Logic 2 {{0}}Output 22 Bit2.1 switch controlCRT
121Logic 3 {{0}}Input C1 Bit1.2 booleanCWTU
122Logic 3 {{0}}Input D1 Bit1.2 booleanCWTU
123Logic 3 {{0}}Input E1 Bit1.2 booleanCWTU
124Logic 3 {{0}}Input F1 Bit1.2 booleanCWTU
125Logic 3 {{0}}Output 31 Bit1.2 booleanCRT
125Logic 3 {{0}}Output 31 Byte17.1 scene numberCRT
125Logic 3 {{0}}Output 31 Byte5.5 ratio (0..255)CRT
125Logic 3 {{0}}Output 31 Byte5.1 percentage (0..100%)CRT
125Logic 3 {{0}}Output 32 Bit2.1 switch controlCRT
126Logic 4 {{0}}Input C1 Bit1.2 booleanCWTU
127Logic 4 {{0}}Input D1 Bit1.2 booleanCWTU
128Logic 4 {{0}}Input E1 Bit1.2 booleanCWTU
129Logic 4 {{0}}Input F1 Bit1.2 booleanCWTU
130Logic 4 {{0}}Output 41 Bit1.2 booleanCRT
130Logic 4 {{0}}Output 41 Byte17.1 scene numberCRT
130Logic 4 {{0}}Output 41 Byte5.5 ratio (0..255)CRT
130Logic 4 {{0}}Output 41 Byte5.1 percentage (0..100%)CRT
130Logic 4 {{0}}Output 42 Bit2.1 switch controlCRT
131TemperatureSend measured value2 Bytes9.1 temperature (°C)CRT
150dummy1 Bit
Parameters (184)
ParameterTypeDefault
Send "In operation" cyclicallylistnot active
Day/Night objectlistrequest after reset
Value for Day/NightlistDay = 1 / Night = 0
Toggle Day/Nightlistat next presence
Trigger sensitivitylist6
Trigger sensitivity "Day"list6
Trigger sensitivity "Night"list3 (low)
Presence sensitivitylist8 (high)
Switch-on thresholdunsignedInt 5…1000100
Switch-on threshold "Day"unsignedInt 5…1000100
Switch-on threshold "Night"unsignedInt 5…100010
Switch off when exceedinglistnot active
Switch OFF when exceeding...unsignedInt 75…1000800
Fallback of forced guidance/locklistnot active
Follow-up time for forced guidance/locklist3 min
Follow-up time for forced guidance/lock "Day"list3 min
Follow-up time for forced guidance/lock "Night"list3 min
Fallback time for forced guidance/locklist3 min
Fallback time for forced guidance/lock "Day"list3 min
Fallback time for forced guidance/lock "Night"list3 min
Fallback for external button long (Manual => Auto)listafter presence and follow-up time
Manual mode, follow-up time when ONlist3 min
Manual mode, follow-up time when OFFlist3 min
Manual mode, follow-up time at ON "Day"list3 min
Manual mode, follow-up time for OFF "Day"list3 min
Manual mode, follow-up time for ON "Night"list3 min
Manual mode, follow-up time for OFF "Night"list3 min
Manual mode, fallback time at ONlist3 min
Manual mode, fallback time at OFFlist3 min
Manual mode, fallback time for ON "Day"list3 min
Manual mode, fallback time for OFF "Day"list3 min
Manual mode, fallback time for ON "Night"list3 min
Manual mode, fallback time for OFF "Night"list3 min
Light channel 1listactive
Active sensorslist1 2
Information about sensor assignmentunsignedInt 0…10
Position of sensorspicture
Sensitivitylistbasic settings (General settings)
Brightnesslistbasic setting or object "Switch Dark" is active
Channel operating modelistfully automatic
Motion filter in standbylistnot active, no filtering
Reduction of follow-up timelistnot active
Maximum duration for short time presencelist20 s
Follow-up time for short time presencelist60 s
Follow-up timelist3 min
Follow-up time "Day"list3 min
Follow-up time "Night"list30 s
Forced guidance or lock objectlistlock object
Action on lockinglistlock motion (lock current state)
Action at unlockinglistno changes
Fallback of forced guidance/lock (General setting)listactive
Object type for output - Lightlistswitch
Output objects for Day/Nightlistone common object
Dimming value for ONlist100 %
Dimming value for OFFlist0 %
Dimming value for "Day" when ONlist100 %
Dimming value for "Day" when OFFlist0 %
Dimming value for "Night" when ONlist30 %
Dimming value for "Night" when OFFlist0 %
Orientation light for leavinglistswitch-off immediately
Switch-off delaylist30 s
Switch-off dimming valuelist30 %
Switch-off delay for "Day"list30 s
Switch-off dimming value for "Day"list30 %
Switch-off delay for "Night"list30 s
Switch-off dimming value for "Night"list20 %
Scene number for ONlist1
Scene number for OFFlist2
Scene number for "Day" when ONlist1
Scene number for "Day" when OFFlist2
Scene number for "Night" when ONlist3
Scene number for "Night" when OFFlist4
Output object 1 sendslistON and OFF
Output object 1 sends ON cyclicallylistnot active
Output object 1 sendslistdimming value for ON and OFF
Output object 1 sends value for ON cyclicallylistnot active
Output object 1 sendslistscene number for ON and OFF
Output object 1 sends scene for ON cyclicallylistnot active
Output 2 (Additional switch object)listnot active
External button short reacts tolistON and OFF
Idle time after external button short is OFFunsignedInt 1…305
External button long reacts tolistON and OFF
Idle time after switch-offunsignedInt 0…601
If Night light is activelistswitch to Day light
If output "Day" is already ONlistswitch to manual mode
If output is already ONlistswitch to manual mode
Status informationlistnot active
Light channel 2listnot active
Motion filter in readinesslistnot active, no filtering
HVAC channellistnot active
Number of monitoring time slotslist3
Length of monitoring time slotunsignedInt 0…3000030
Object type for output - HVAClistswitch
Object value for ONlistvalue "1"
Object value for OFFlistvalue "0"
Object value for "Day" when ONlistvalue "1"
Object value for "Day" when OFFlistvalue "0"
Object value for "Night" when ONlistvalue "1"
Object value for "Night" when OFFlistvalue "0"
Output object sends ON cyclicallylistnot active
If output is already ONlistremains in automatic mode
Alarm/Message channel / Direction of movementlistnot active
Trigger sensitivitylist3 (low)
Trigger sensitivity "Day"list3 (low)
Trigger sensitivity "Night"list2
Presence sensitivitylist6
Interference / motion filterlistnot active, no filtering
Length of monitoring time slotlist2 s
Lock or release objectlistlock object
Fallback of forced guidance/lock (General setting)listnot active
Output object sends atlistON and OFF
Object sends cyclically every...listnot active
Direction of movementlistactive
Installation sitelistcorridor
LED greenlistactive on motion
LED red, object "LED red flashing"listnot active
LED whitelistnot active
Brightness at "Night"list10 %
Function of buttonslistnot active
Display button operation with white LEDlistactive
Display "manual mode ON" with green LEDlistactive
Display "manual mode OFF" with red LEDlistactive
Display "lock/forced guidance ON" with green LEDlistactive
Display "lock/forced guidance OFF" with red LEDlistactive
Scene A numberlistnot active
Scene A Light channel 1listnot active
Scene A Light channel 2listnot active
Scene B numberlistnot active
Scene B Light channel 1listnot active
Scene B Light channel 2listnot active
Scene C numberlistnot active
Scene C Light channel 1listnot active
Scene C Light channel 2listnot active
Scene D numberlistnot active
Scene D Light channel 1listnot active
Scene D Light channel 2listnot active
Scene E numberlistnot active
Scene E Light channel 1listnot active
Scene E Light channel 2listnot active
Scene F numberlistnot active
Scene F Light channel 1listnot active
Scene F Light channel 2listnot active
Scene G numberlistnot active
Scene G Light channel 1listnot active
Scene G Light channel 2listnot active
Scene H numberlistnot active
Scene H Light channel 1listnot active
Scene H Light channel 2listnot active
Light channels influence the brightness measurementlistyes (several lights in the room)
Correction valuelist0 %
Send brightness on change oflist10 %
Send measured value cyclicallylistnot active
Room reflection factorlist0.4 medium
Temperature measurementlistnot active
Send measured value on change oflist0.2 K
Correction value for sensorsignedInt -80…500
Logic function 1listnot active
Description of functiontext
Additional texttext
FunctionlistAND
Output objectlistswitch
Sending conditionliston change of output
Outputlistnormal
Scene number for output value "False"list1
Scene number for output value "True"list1
Datapoint typelist1 Byte DPT 5.005 Decimal factor (0...255)
Value for output value "False"unsignedInt 0…2550
Value for output value "True"unsignedInt 0…2550
Percent value for output value "False"list0 %
Percent value for output value "True"list0 %
Forced guidance for output value "False"list00 - no priority, Off
Forced guidance for output value "True"list00 - no priority, Off
Internal input Alistnot active
Object numberunsignedInt 0…1290
Internal input Blistnot active
External input Clistnot active
Preset logic input after reset with...listvalue "0"
External input Dlistnot active
External input Elistnot active
External input Flistnot active
Logic function 2listnot active
Logic function 3listnot active
Logic function 4listnot active
Request inputs after bus power returnlistnot active

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Motion Detector, Secure 1.1 latest$047AB6E02026-11-25647 KBDownload
Motion Detector 2,2 m TS 55, Secure 1.0$047A6CE02026-11-25212 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH PSE-B552T0x.02S KNX Motion Detector 2,2 m TS 55, Secure (PSE-B552T0x.02S), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH

All MDT technologies GmbH products