AMS-0416.01 Switch Actuator with current measur.4f AMS-0416.01
MDT technologies GmbH · Order number AMS-0416.01 · Archive › Actuators › Switch Actuators witch current measurement
Standard version 230VAC, 16A, 100µF C-Load
Download .knxprod Switching, Staircase, Meter current 4f 1.2 · 105 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | AMS-0416.01 Switch Actuator with current measur.4f |
| Order number | AMS-0416.01 |
| Hardware | Schaltaktor mit Strommessung 4-fach, 8TE, 230V,16A |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Width (mm) | 71.3 |
| Registration | Certified · 2011-11-08 |
| Languages | de-DE, en-US, es-ES |
| Catalog entry | M-0083_H-8-1_HP-0018-12-E8AC_CI-AMS.2D0416.2E01-2 |
| Fingerprint | E8AC |
| SHA-256 | d22a991e8c3928e6af3f5a9ce9831a593fd5f7c74bdb6ad05ef42335a1c93726 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Schalten, Treppenlicht, Strom messen 4f 1.2
| Application number | $0018 |
|---|---|
| Version | 1.2 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0d |
| Parameters | 427 |
| Group objects | 105 |
Group objects (105)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Kanal A | Schalten EIN/AUS | 1 Bit | 1.1 switch | CW |
| 1 | Kanal A | Treppenlicht | 1 Bit | 1.1 switch | CW |
| 2 | Kanal A | Sperren | 1 Bit | 1.3 enable | CW |
| 3 | Kanal A | Zwangsführung | 2 Bit | 2.1 switch control | CW |
| 4 | Kanal A | Szene | 1 Byte | CW | |
| 5 | Kanal A | Status | 1 Bit | CRT | |
| 6 | Kanal A | Logik 1 | 1 Bit | 1.2 boolean | CW |
| 7 | Kanal A | Logik 2 | 1 Bit | 1.2 boolean | CW |
| 8 | Kanal A | Rückmeldung Betriebsstunden | 2 Bytes | CRT | |
| 8 | Kanal A | Zeit bis zum nächsten Service | 2 Bytes | CRT | |
| 9 | Kanal A | Rücksetzen Betriebsstunden | 1 Bit | 1.1 switch | CW |
| 9 | Kanal A | Rücksetzen Service | 1 Bit | 1.1 switch | CW |
| 10 | Kanal A | Service erforderlich | 1 Bit | CRT | |
| 11 | Kanal A | Stromwert | 2 Bytes | CRT | |
| 11 | Kanal A | Stromwert | 2 Bytes | 9.21 current (mA) | CRT |
| 11 | Kanal A | Stromwert | 4 Bytes | 14.19 electric current (A) | CRT |
| 12 | Kanal A | Lastüberschreitung | 1 Bit | 1.1 switch | CRT |
| 13 | Kanal A | Lastunterschreitung | 1 Bit | 1.1 switch | CRT |
| 14 | Kanal A | Fehlerstrom | 1 Bit | CRT | |
| 14 | Kanal A | Lastausfall | 1 Bit | CRT | |
| 14 | Kanal A | Fehlerstrom/Lastausfall | 1 Bit | CRT | |
| 15 | CO_dummyA0 | 1 Bit | CRT | ||
| 16 | CO_dummyA1 | 1 Bit | CRT | ||
| 17 | CO_dummyA2 | 1 Bit | CRT | ||
| 18 | Kanal B | Schalten EIN/AUS | 1 Bit | 1.1 switch | CW |
| 19 | Kanal B | Treppenlicht | 1 Bit | 1.1 switch | CW |
| 20 | Kanal B | Sperren | 1 Bit | 1.3 enable | CW |
| 21 | Kanal B | Zwangsführung | 2 Bit | 2.1 switch control | CW |
| 22 | Kanal B | Szene | 1 Byte | CW | |
| 23 | Kanal B | Status | 1 Bit | CRT | |
| 24 | Kanal B | Logik 1 | 1 Bit | 1.2 boolean | CW |
| 25 | Kanal B | Logik 2 | 1 Bit | 1.2 boolean | CW |
| 26 | Kanal B | Rückmeldung Betriebsstunden | 2 Bytes | CRT | |
| 26 | Kanal B | Zeit bis zum nächsten Service | 2 Bytes | CRT | |
| 27 | Kanal B | Rücksetzen Betriebsstunden | 1 Bit | 1.1 switch | CW |
| 27 | Kanal B | Rücksetzen Service | 1 Bit | 1.1 switch | CW |
| 28 | Kanal B | Service erforderlich | 1 Bit | CRT | |
| 29 | Kanal B | Stromwert | 2 Bytes | CRT | |
| 29 | Kanal B | Stromwert | 2 Bytes | 9.21 current (mA) | CRT |
| 29 | Kanal B | Stromwert | 4 Bytes | 14.19 electric current (A) | CRT |
| 30 | Kanal B | Lastüberschreitung | 1 Bit | 1.1 switch | CRT |
| 31 | Kanal B | Lastunterschreitung | 1 Bit | 1.1 switch | CRT |
| 32 | Kanal B | Fehlerstrom | 1 Bit | CRT | |
| 32 | Kanal B | Lastausfall | 1 Bit | CRT | |
| 32 | Kanal B | Fehlerstrom/Lastausfall | 1 Bit | CRT | |
| 33 | CO_dummyB0 | 1 Bit | CRT | ||
| 34 | CO_dummyB1 | 1 Bit | CRT | ||
| 35 | CO_dummyB2 | 1 Bit | CRT | ||
| 36 | Kanal C | Schalten EIN/AUS | 1 Bit | 1.1 switch | CW |
| 37 | Kanal C | Treppenlicht | 1 Bit | 1.1 switch | CW |
| 38 | Kanal C | Sperren | 1 Bit | 1.3 enable | CW |
| 39 | Kanal C | Zwangsführung | 2 Bit | 2.1 switch control | CW |
| 40 | Kanal C | Szene | 1 Byte | CW | |
| 41 | Kanal C | Status | 1 Bit | CRT | |
| 42 | Kanal C | Logik 1 | 1 Bit | 1.2 boolean | CW |
| 43 | Kanal C | Logik 2 | 1 Bit | 1.2 boolean | CW |
| 44 | Kanal C | Rückmeldung Betriebsstunden | 2 Bytes | CRT | |
| 44 | Kanal C | Zeit bis zum nächsten Service | 2 Bytes | CRT | |
| 45 | Kanal C | Rücksetzen Betriebsstunden | 1 Bit | 1.1 switch | CW |
| 45 | Kanal C | Rücksetzen Service | 1 Bit | 1.1 switch | CW |
| 46 | Kanal C | Service erforderlich | 1 Bit | CRT | |
| 47 | Kanal C | Stromwert | 2 Bytes | CRT | |
| 47 | Kanal C | Stromwert | 2 Bytes | 9.21 current (mA) | CRT |
| 47 | Kanal C | Stromwert | 4 Bytes | 14.19 electric current (A) | CRT |
| 48 | Kanal C | Lastüberschreitung | 1 Bit | 1.1 switch | CRT |
| 49 | Kanal C | Lastunterschreitung | 1 Bit | 1.1 switch | CRT |
| 50 | Kanal C | Fehlerstrom | 1 Bit | CRT | |
| 50 | Kanal C | Lastausfall | 1 Bit | CRT | |
| 50 | Kanal C | Fehlerstrom/Lastausfall | 1 Bit | CRT | |
| 51 | CO_dummyC0 | 1 Bit | CRT | ||
| 52 | CO_dummyC1 | 1 Bit | CRT | ||
| 53 | CO_dummyC2 | 1 Bit | CRT | ||
| 54 | Kanal D | Schalten EIN/AUS | 1 Bit | 1.1 switch | CW |
| 55 | Kanal D | Treppenlicht | 1 Bit | 1.1 switch | CW |
| 56 | Kanal D | Sperren | 1 Bit | 1.3 enable | CW |
| 57 | Kanal D | Zwangsführung | 2 Bit | 2.1 switch control | CW |
| 58 | Kanal D | Szene | 1 Byte | CW | |
| 59 | Kanal D | Status | 1 Bit | CRT | |
| 60 | Kanal D | Logik 1 | 1 Bit | 1.2 boolean | CW |
| 61 | Kanal D | Logik 2 | 1 Bit | 1.2 boolean | CW |
| 62 | Kanal D | Rückmeldung Betriebsstunden | 2 Bytes | CRT | |
| 62 | Kanal D | Zeit bis zum nächsten Service | 2 Bytes | CRT | |
| 63 | Kanal D | Rücksetzen Betriebsstunden | 1 Bit | 1.1 switch | CW |
| 63 | Kanal D | Rücksetzen Service | 1 Bit | 1.1 switch | CW |
| 64 | Kanal D | Service erforderlich | 1 Bit | CRT | |
| 65 | Kanal D | Stromwert | 2 Bytes | CRT | |
| 65 | Kanal D | Stromwert | 2 Bytes | 9.21 current (mA) | CRT |
| 65 | Kanal D | Stromwert | 4 Bytes | 14.19 electric current (A) | CRT |
| 66 | Kanal D | Lastüberschreitung | 1 Bit | 1.1 switch | CRT |
| 67 | Kanal D | Lastunterschreitung | 1 Bit | 1.1 switch | CRT |
| 68 | Kanal D | Fehlerstrom | 1 Bit | CRT | |
| 68 | Kanal D | Lastausfall | 1 Bit | CRT | |
| 68 | Kanal D | Fehlerstrom/Lastausfall | 1 Bit | CRT | |
| 69 | CO_dummyD0 | 1 Bit | CRT | ||
| 70 | CO_dummyD1 | 1 Bit | CRT | ||
| 71 | CO_dummyD2 | 1 Bit | CRT | ||
| 72 | CO_dummy3 | 1 Bit | CRT | ||
| 73 | CO_dummy4 | 1 Bit | CRT | ||
| 74 | CO_dummy5 | 1 Bit | CRT | ||
| 75 | CO_dummy6 | 1 Bit | CRT | ||
| 76 | Zentralfunktion | Summenstromwert | 2 Bytes | 9.21 current (mA) | CRT |
| 76 | Zentralfunktion | Summenstromwert | 4 Bytes | 14.19 electric current (A) | CRT |
| 76 | Zentralfunktion | Summenstromwert | 2 Bytes | CRT | |
| 77 | Zentralfunktion | Summenlastüberschreitung | 1 Bit | 1.1 switch | CRT |
| 78 | Zentralfunktion | Schalten | 1 Bit | 1.1 switch | CW |
Parameters (82)
| Parameter | Type | Default |
|---|---|---|
| Disabled objects | unsignedInt 0…255 | 1 |
| Geräteanlaufzeit | list | 1 s |
| Summenstrom | list | nicht aktiv |
| Auswahl des Objektes für Strommessung | list | Gleitkommawert in mA (DPT 9.021) |
| Faktor=1 | list | EIN |
| Faktor für Umrechnung in theoretische Leistung kW: Stromwert x Faktor | unsignedInt 100…250 | 230 |
| Stromwert bei Änderung senden | list | nicht aktiv |
| Zyklisches Senden | list | nicht aktiv |
| Überwachung Lastüberschreitung | list | nicht aktiv |
| Lastüberwachung inaktiv | list | AUS |
| Faktor für Lastüberwachung [A] | unsignedInt 1…200 | 1 |
| Faktor für Lastüberwachung | list | 1:00 AM |
| Hysterese [%] | unsignedInt 10…100 | 10 |
| Verhalten bei Überschreiten | list | kein Telegramm senden |
| Verhalten bei nicht Überschreiten | list | kein Telegramm senden |
| Überschreiten zyklisch senden | list | nicht aktiv |
| Kanal A | list | nicht aktiv |
| Zentrale Schaltfunktion | list | nicht aktiv |
| Kanal B | list | nicht aktiv |
| Kanal C | list | nicht aktiv |
| Kanal D | list | nicht aktiv |
| delay on SOO or ADV | list | SOO |
| Treppenlichtzeit in [s] | unsignedInt 0…30000 | 0 |
| Vorwarnzeit in [s] | unsignedInt 0…30000 | 0 |
| Manuelles Ausschalten | list | nicht aktiv |
| Warndauer in [s] | unsignedInt 0…30000 | 1 |
| Verlängern bei Treppenlicht | list | Disable |
| Betrieb als | list | Schließer |
| Einschaltverzögerung [s] | unsignedInt 0…30000 | 0 |
| Ausschaltverzögerung [s] | unsignedInt 0…30000 | 0 |
| Zyklisches senden dess aktuellen Istwertes | unsignedInt 0…30000 | 0 |
| Zyklisches senden des aktuellen Istwertes | unsignedInt 0…30000 | 0 |
| Szene speichern | list | gesperrt |
| State at the beginning of the lock state | list | AUS |
| Szene A | list | AUS |
| State at the end of the lock state | list | AUS |
| Verhalten bei Sperren | list | keine Änderung |
| Verhalten bei Entsperren | list | keine Änderung |
| invertieren des Lock Objektes | list | nicht invertiert |
| Value of the device after bus power down | list | AUS |
| Value of the device after bus power up | list | AUS |
| Verhalten bei Busspannungswiederkehr | list | keine Änderung |
| Verhalten bei Busspannungsausfall | list | keine Änderung |
| Betriebsstundenzähler | list | nicht aktiv |
| Strommessung | list | nicht aktiv |
| Bus Power Up Message Delay | list | 1 s |
| Logikfunktionen | list | nicht aktiv |
| active Logic Inputs | list | nicht aktiv |
| Logische Operation | list | ODER |
| mode | list | switching |
| Szene | list | nicht aktiv |
| Art des Betriebsstundenzählers | list | Betriebsstundenzähler |
| Zählen wenn | list | Relais EIN |
| Melden der Betriebsstunden alle ... [h] | unsignedInt 0…10000 | 0 |
| Melden der Servicestunden alle ... [h] | unsignedInt 0…10000 | 0 |
| Servicemeldung in Abständen von ... x10h | unsignedInt 0…250 | 0 |
| Auswahl des Objekts für die Strommessung | list | Ganzer Wert in mA (DPT 7.012) |
| Kanal bei Summenstrom berücksichtigen | list | nicht aktiv |
| Faktor für Lastüberwachung x100mA | unsignedInt 1…200 | 1 |
| Überwachung Lastunterschreitung | list | nicht aktiv |
| Verhalten bei Unterschreiten | list | kein Telegramm senden |
| Verhalten bei nicht Unterschreiten | list | kein Telegramm senden |
| Unterschreiten zyklisch senden | list | nicht aktiv |
| Fehlermeldung | list | nicht aktiv |
| Schaltschwelle | list | 20 mA |
| Szene Nummer A | list | 1 |
| Szene B | list | AUS |
| Szene Nummer B | list | 2 |
| Szene C | list | AUS |
| Szene Nummer C | list | 3 |
| Szene D | list | AUS |
| Szene Nummer D | list | 4 |
| Szene E | list | AUS |
| Szene Nummer E | list | 5 |
| Szene F | list | AUS |
| Szene Nummer F | list | 6 |
| Szene G | list | AUS |
| Szene Nummer G | list | 7 |
| Szene H | list | AUS |
| Szene Nummer H | list | 8 |
| Vorwarnung | list | nicht aktiv |
| Verlängern bei Treppenlicht | list | nicht aktiv |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Switching, Staircase, Meter current 4f 1.6 latest | $0018 | 18AC | 2026-11-25 | 112 KB | Download |
| Switching, Staircase, Meter current 4f 1.2 | $0018 | E8AC | 2026-11-25 | 105 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH AMS-0416.01 Switch Actuator with current measur.4f (AMS-0416.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- AKD-0224V.01 LED Controller 2 channel AKD-0224V.01
- AKD-0324V.01 RGB LED Controller AKD-0324V.01
- AKD-0410V.01 Dimming Control Unit 4-f, 4TE, 1-10V AKD-0410V.01
- AKD-0424R.01 RGBW LED Controller, MDRC AKD-0424R.01
- AKD-0424V.01 RGBW LED Controller AKD-0424V.01
- AKH-0400.01 Heating actuator 4-fold, 2SU,24/230VAC AKH-0400.01
- AKH-0800.01 Heating actuator 8-fold, 4SU,24/230VAC AKH-0800.01
- AKK-01UP.01 Switch Actuator 1-fold, UP, 16A AKK-01UP.01
- AKK-0216.01 Switch Actuator 2-fold, 2SU, 16A AKK-0216.01
- AKK-0216.02 Switch Actuator 2-fold, 2SU, 16A AKK-0216.02
- AKK-02UP.01 Switch Actuator 2-fold, UP, 6A AKK-02UP.01
- AKK-03UP.01 Switch Actuator 3fold, FanCoil AKK-03UP.01