KNX Database

AKK-02UP.04S KNX Switch Actuator 2-fold, flush mounted, 10A, Secure AKK-02UP.04S

MDT technologies GmbH · Order number AKK-02UP.04S · Actuators › Switch Actuator, compact version

Compact version, 230VAC, 10A, 14µF

Download .knxprod Switch, Staircase light, Switch pulse 1.0 · 178 KB

Product

ManufacturerMDT technologies GmbH
Product nameAKK-02UP.04S KNX Switch Actuator 2-fold, flush mounted, 10A, Secure
Order numberAKK-02UP.04S
Product textAKK-02UP.04S KNX Switch Actuator 2-fold, flush mounted, 10A, Secure
HardwareAKK Schaltaktoren Secure
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationRegistered · 2026-11-24
Languagesde-DE, en-US, es-ES, fr-FR, it-IT
Catalog entryM-0083_H-412-1_HP-0402-10-A3D4_CI-AKK.2D02UP.2E04S-1
FingerprintA3D4
SHA-256113d974efcc0ac61794d581d197b2e78e96b1e2637ffa66fe4233f5538660166
First seen2026-11-26
Markets69 markets

Application program: Switch, Staircase light, Switch pulse 1.0

Application number$0402
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters299
Group objects37
Group objects (37)
NoNameFunctionSizeDPTFlags
0Channel {{ChNo}}: {{0}}Switch ON/OFF1 Bit1.1 switchCW
1Central functionIn operation1 Bit1.11 stateCRT
1Channel {{ChNo}}: {{0}}Additional object: Switch On/Off1 Bit1.1 switchCW
1Channel {{ChNo}}: {{0}}Additional object: Switch pulse1 Bit1.1 switchCW
2Central functionLock manual operation1 Bit1.3 enableCW
2Channel {{ChNo}}: {{0}}Staircase light1 Bit1.1 switchCW
2Channel {{ChNo}}: {{0}}Switch pulse1 Bit1.1 switchCW
3Central functionStatus: Lock manual operation1 Bit1.3 enableCRT
3Channel {{ChNo}}: {{0}}Status: Emergency mode1 Bit1.11 stateCRT
4Central function, Group 1Switch ON/OFF1 Bit1.1 switchCW
4Channel {{ChNo}}: {{0}}Status: Staircase light time2 Bytes7.5 time (s)CRT
4Channel {{ChNo}}: {{0}}Status: Staircase light time2 Bytes7.5 time (s)CRWTU
5Central function, Group 2Switch ON/OFF1 Bit1.1 switchCW
5Channel {{ChNo}}: {{0}}Prewarning1 Bit1.1 switchCT
6Central function, Group 3Switch ON/OFF1 Bit1.1 switchCW
6Channel {{ChNo}}: {{0}}Lock1 Bit1.3 enableCW
7Central function, Group 4Switch ON/OFF1 Bit1.1 switchCW
7Channel {{ChNo}}: {{0}}Status: Lock1 Bit1.3 enableCRT
8Central function, Group 5Switch ON/OFF1 Bit1.1 switchCW
9Central function, Group 6Switch ON/OFF1 Bit1.1 switchCW
9Channel {{ChNo}}: {{0}}Scene1 Byte17.1 scene numberCW
9Channel {{ChNo}}: {{0}}Scene1 Byte18.1 scene controlCW
10Central function, Group 1Status: ON/OFF1 Bit1.1 switchCRT
10Channel {{ChNo}}: {{0}}Status: ON/OFF1 Bit1.1 switchCRT
10Channel {{ChNo}}: {{0}}Status1 Bit1.11 stateCRT
11Central function, Group 2Status: ON/OFF1 Bit1.1 switchCRT
11Channel {{ChNo}}: {{0}}Inverted status1 Bit1.1 switchCRT
12Central function, Group 3Status: ON/OFF1 Bit1.1 switchCRT
12Channel {{ChNo}}: {{0}}Logic 11 Bit1.2 booleanCW
13Central function, Group 4Status: ON/OFF1 Bit1.1 switchCRT
13Channel {{ChNo}}: {{0}}Logic 21 Bit1.2 booleanCW
14Central function, Group 5Status: ON/OFF1 Bit1.1 switchCRT
14Channel {{ChNo}}: {{0}}Threshold switch2 Bytes9.1 temperature (°C)CW
15Central function, Group 6Status: ON/OFF1 Bit1.1 switchCRT
16Central functionCombined Info: ON/OFF 1 (Channels A-P)4 Bytes27.1 bit-combined info on/offCRT
17Central functionCombined Info: ON/OFF 2 (Channels Q-X)4 Bytes27.1 bit-combined info on/offCRT
18Channel {{ChNo}}: {{0}}Control value1 Byte5.1 percentage (0..100%)CW
Parameters (119)
ParameterTypeDefault
Startup timetime2
Channel Alistswitch
Eco mode, switch LED's off afterlistnot active
Manual operationlistactive
Channel Blistswitch
Channel Clistswitch
Channel Dlistswitch
Channel Elistswitch
Channel Flistswitch
Channel Glistswitch
Channel Hlistswitch
Channel Ilistswitch
Channel Jlistswitch
Channel Klistswitch
Channel Llistswitch
Channel Mlistswitch
Channel Nlistswitch
Channel Olistswitch
Channel Plistswitch
Channel Qlistswitch
Channel Rlistswitch
Channel Slistswitch
Channel Tlistswitch
Channel Ulistswitch
Channel Vlistswitch
Channel Wlistswitch
Channel Xlistswitch
Send "In operation" cyclicallylistnot active
Cycle timetime2
Status objectlistnot active
Behaviour after programminglistload parameter
Switch-on delayunsignedInt 0…50000
Device selectionlistPlease select a device!
Send status on changelistactive
Cycle timetime1
Send status cyclicallylistnot active
Restore lock and force objectslistnot active
Channel / Object descriptiontext
Additional texttext
Modelistnormally open
Switch-on delayunsignedInt 0…300000
Switch-off delayunsignedInt 0…300000
Central function, Group 1unsignedInt 0…10
Send statusliston change
Send status cyclically (0 = not active)unsignedInt 0…300000
Additional inverted statuslistnot active
Behaviour on lockinglistno change
Behaviour on unlockinglistno change
Behaviour on bus power returnlistno change
Behaviour on bus power failurelistno change
Logic functionlistnot active
Sceneslistnot active
Prewarning timeunsignedInt 0…300000
Inverte Lock objectlistnot active
Manual switching offlistactive
Extend time staircase lightlistrestart time
Delay time for status after bus power uplist1 s
Logic operationlistOR
Logic functionlistwith switch object and one logic object
Invert inputslistnot active
Invert outputlistnot active
Set objects to value after bus power returnlistnot active
Value for switch objectlistnot active
Value for logic object 1listnot active
Value for logic object 2listnot active
Learn scenelistnot active
Scene Alistnot active
Scene numberlist1
Scene behaviourlistON
Scene Blistnot active
Scene numberlist2
Scene Clistnot active
Scene numberlist3
Scene Dlistnot active
Scene numberlist4
Scene Elistnot active
Scene numberlist5
Scene Flistnot active
Scene numberlist6
Scene Glistnot active
Scene numberlist7
Scene Hlistnot active
Scene numberlist8
Additional objectlistnot active
Central function, Group 2unsignedInt 0…10
Central function, Group 3unsignedInt 0…10
Central function, Group 4unsignedInt 0…10
Central function, Group 5unsignedInt 0…10
Central function, Group 6unsignedInt 0…10
Switch off channel earlylistnot active
Fallback time for lock (0 = not active)unsignedInt 0…6000
Additional switch objectlistnot active
Staircase light timeunsignedInt 1…300001
Prewarninglistnot active
Prewarning durationunsignedInt 0…300001
Manual switch-offlistactive
Extend staircase light timelistrestart time
Factor for object "Staircase light with time"list1 s
Behaviour on unlockinglistOFF
Behaviour on bus power returnliststate before bus power failure
Off delayunsignedInt 0…300000
Status: Staircase light timelistnot active
Priority / Forced controllistnot active
Pulse timelist500 ms
Repeat pulse signal oncelistnot active
Time to the next pulselist0.5 s
Manual switch-offlistnot active
PWM cycleunsignedInt 0…25510
Emergency mode: Monitoring timelistnot active
Control value for emergency modelist50 %
Behaviour on lockinglistOFF
Threshold switchlistnot active
Minimum temperaturefloat -100…20020
Maximum temperaturefloat -100…20025
Control value when falling below the minimum temperaturelist20 %
Control value for overtemperature protectionlist0 %
Monitoring timeunsignedInt 0…25530
Minimum control valuelist0 %
Maximum control valuelist100 %

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Switch, Staircase light, Switch pulse 1.0 latest$0402A3D42026-11-26178 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH AKK-02UP.04S KNX Switch Actuator 2-fold, flush mounted, 10A, Secure (AKK-02UP.04S), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.