AKH-0800.01 Heating actuator 8-fold, 4SU,24/230VAC AKH-0800.01
MDT technologies GmbH · Order number AKH-0800.01 · Archive › Actuators › Heating Actuator
Control valves, Control, 24/230VAC
Download .knxprod Heating actuator 8-fold 1.4 · 135 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | AKH-0800.01 Heating actuator 8-fold, 4SU,24/230VAC |
| Order number | AKH-0800.01 |
| Hardware | Heizungsaktor 8-fach |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Width (mm) | 71.3 |
| Registration | Certified · 2011-07-06 |
| Languages | de-DE, en-US |
| Catalog entry | M-0083_H-60-0_HP-003A-14-FEB2_CI-AKH.2D0800.2E01-2 |
| Fingerprint | FEB2 |
| SHA-256 | 6578563b98dcee0527bd7608ab3cfbf84c0f8006eafef5d6c952d959abb37c48 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Heating actuator 8-fold 1.4
| Application number | $003A |
|---|---|
| Version | 1.4 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0d |
| Parameters | 565 |
| Group objects | 228 |
Group objects (228)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Channel A | Control value | 1 Bit | 1.1 switch | CW |
| 0 | Channel A | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 0 | Channel A | Temperature value | 2 Bytes | 9.1 temperature (°C) | CW |
| 1 | Channel A | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 2 | Channel A | Block | 1 Bit | 1.3 enable | CW |
| 3 | Channel A | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 3 | Channel A | State control value | 1 Bit | 1.1 switch | CRT |
| 4 | Channel A | Message emergency mode | 1 Bit | CRT | |
| 5 | Channel A | Dew point alarm | 1 Bit | 1.3 enable | CW |
| 5 | Channel A | Forced position | 1 Bit | 1.3 enable | CW |
| 6 | Channel A | PWM cooling for 4 pipe system | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 7 | Channel A | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 8 | Channel A | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 9 | Channel A | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 10 | Channel A | Mode selection | 1 Byte | CW | |
| 10 | Channel A | Mode selection | 1 Byte | CRWT | |
| 11 | Channel A | DPT_HVAC Status | 1 Byte | CRT | |
| 12 | Channel A | DPT_RHCC Status | 2 Bytes | CRT | |
| 13 | Channel A | Mode comfort | 1 Bit | 1.1 switch | CW |
| 14 | Channel A | Mode night | 1 Bit | 1.1 switch | CW |
| 15 | Channel A | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 15 | Channel A | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 15 | Channel A | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 16 | Channel A | Frost alarm | 1 Bit | CRT | |
| 17 | Channel A | Heat alarm | 1 Bit | CRT | |
| 18 | Channel A | Setpoint value offset(1=+/0=-) | 1 Bit | CW | |
| 19 | Channel A | Dummy | 1 Bit | ||
| 20 | Channel B | Control value | 1 Bit | 1.1 switch | CW |
| 20 | Channel B | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 20 | Channel B | Temperature value | 2 Bytes | 9.1 temperature (°C) | CW |
| 21 | Channel B | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 22 | Channel B | Block | 1 Bit | 1.3 enable | CW |
| 23 | Channel B | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 23 | Channel B | State control value | 1 Bit | 1.1 switch | CRT |
| 24 | Channel B | Message emergency mode | 1 Bit | CRT | |
| 25 | Channel B | Dew point alarm | 1 Bit | 1.3 enable | CW |
| 25 | Channel B | Forced position | 1 Bit | 1.3 enable | CW |
| 26 | Channel B | PWM cooling for 4 pipe system | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | Channel B | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 28 | Channel B | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 29 | Channel B | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 30 | Channel B | Mode selection | 1 Byte | CW | |
| 30 | Channel B | Mode selection | 1 Byte | CRWT | |
| 31 | Channel B | DPT_HVAC Status | 1 Byte | CRT | |
| 32 | Channel B | DPT_RHCC Status | 2 Bytes | CRT | |
| 33 | Channel B | Mode comfort | 1 Bit | 1.1 switch | CW |
| 34 | Channel B | Mode night | 1 Bit | 1.1 switch | CW |
| 35 | Channel B | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 35 | Channel B | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 35 | Channel B | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 36 | Channel B | Frost alarm | 1 Bit | CRT | |
| 37 | Channel B | Heat alarm | 1 Bit | CRT | |
| 38 | Channel B | Setpoint value offset(1=+/0=-) | 1 Bit | CW | |
| 39 | Channel B | 1 Bit | |||
| 40 | Channel C | Control value | 1 Bit | 1.1 switch | CW |
| 40 | Channel C | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 40 | Channel C | Temperature value | 2 Bytes | 9.1 temperature (°C) | CW |
| 41 | Channel C | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 42 | Channel C | Block | 1 Bit | 1.3 enable | CW |
| 43 | Channel C | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 43 | Channel C | State control value | 1 Bit | 1.1 switch | CRT |
| 44 | Channel C | Message emergency mode | 1 Bit | CRT | |
| 45 | Channel C | Dew point alarm | 1 Bit | 1.3 enable | CW |
| 45 | Channel C | Forced position | 1 Bit | 1.3 enable | CW |
| 46 | Channel C | PWM cooling for 4 pipe system | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 47 | Channel C | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 48 | Channel C | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 49 | Channel C | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 50 | Channel C | Mode selection | 1 Byte | CW | |
| 50 | Channel C | Mode selection | 1 Byte | CRWT | |
| 51 | Channel C | DPT_HVAC Status | 1 Byte | CRT | |
| 52 | Channel C | DPT_RHCC Status | 2 Bytes | CRT | |
| 53 | Channel C | Mode comfort | 1 Bit | 1.1 switch | CW |
| 54 | Channel C | Mode night | 1 Bit | 1.1 switch | CW |
| 55 | Channel C | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 55 | Channel C | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 55 | Channel C | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 56 | Channel C | Frost alarm | 1 Bit | CRT | |
| 57 | Channel C | Heat alarm | 1 Bit | CRT | |
| 58 | Channel C | Setpoint value offset(1=+/0=-) | 1 Bit | CW | |
| 59 | Channel C | 1 Bit | |||
| 60 | Channel D | Control value | 1 Bit | 1.1 switch | CW |
| 60 | Channel D | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 60 | Channel D | Temperature value | 2 Bytes | 9.1 temperature (°C) | CW |
| 61 | Channel D | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 62 | Channel D | Block | 1 Bit | 1.3 enable | CW |
| 63 | Channel D | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 63 | Channel D | State control value | 1 Bit | 1.1 switch | CRT |
| 64 | Channel D | Message emergency mode | 1 Bit | CRT | |
| 65 | Channel D | Dew point alarm | 1 Bit | 1.3 enable | CW |
| 65 | Channel D | Forced position | 1 Bit | 1.3 enable | CW |
| 66 | Channel D | PWM cooling for 4 pipe system | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 67 | Channel D | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 68 | Channel D | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 69 | Channel D | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 70 | Channel D | Mode selection | 1 Byte | CW | |
| 70 | Channel D | Mode selection | 1 Byte | CRWT | |
| 71 | Channel D | DPT_HVAC Status | 1 Byte | CRT | |
| 72 | Channel D | DPT_RHCC Status | 2 Bytes | CRT | |
| 73 | Channel D | Mode comfort | 1 Bit | 1.1 switch | CW |
| 74 | Channel D | Mode night | 1 Bit | 1.1 switch | CW |
| 75 | Channel D | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 75 | Channel D | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 75 | Channel D | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 76 | Channel D | Frost alarm | 1 Bit | CRT | |
| 77 | Channel D | Heat alarm | 1 Bit | CRT | |
| 78 | Channel D | Setpoint value offset(1=+/0=-) | 1 Bit | CW | |
| 79 | Channel D | 1 Bit | |||
| 80 | Channel E | Control value | 1 Bit | 1.1 switch | CW |
| 80 | Channel E | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 80 | Channel E | Temperature value | 2 Bytes | 9.1 temperature (°C) | CW |
| 81 | Channel E | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 82 | Channel E | Block | 1 Bit | 1.3 enable | CW |
| 83 | Channel E | State control value | 1 Bit | 1.1 switch | CRT |
| 83 | Channel E | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel E | Message emergency mode | 1 Bit | CRT | |
| 85 | Channel E | Forced position | 1 Bit | 1.3 enable | CW |
| 85 | Channel E | Dew point alarm | 1 Bit | 1.3 enable | CW |
| 86 | Channel E | PWM cooling for 4 pipe system | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 87 | Channel E | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 88 | Channel E | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 89 | Channel E | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 90 | Channel E | Mode selection | 1 Byte | CW | |
| 90 | Channel E | Mode selection | 1 Byte | CRWT | |
| 91 | Channel E | DPT_HVAC Status | 1 Byte | CRT | |
| 92 | Channel E | DPT_RHCC Status | 2 Bytes | CRT | |
| 93 | Channel E | Mode comfort | 1 Bit | 1.1 switch | CW |
| 94 | Channel E | Mode night | 1 Bit | 1.1 switch | CW |
| 95 | Channel E | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 95 | Channel E | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 95 | Channel E | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 96 | Channel E | Frost alarm | 1 Bit | CRT | |
| 97 | Channel E | Heat alarm | 1 Bit | CRT | |
| 98 | Channel E | Setpoint value offset(1=+/0=-) | 1 Bit | CW | |
| 99 | Channel E | 1 Bit | |||
| 100 | Channel F | Control value | 1 Bit | 1.1 switch | CW |
| 100 | Channel F | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 100 | Channel F | Temperature value | 2 Bytes | 9.1 temperature (°C) | CW |
| 101 | Channel F | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 102 | Channel F | Block | 1 Bit | 1.3 enable | CW |
| 103 | Channel F | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 103 | Channel F | State control value | 1 Bit | 1.1 switch | CRT |
| 104 | Channel F | Message emergency mode | 1 Bit | CRT | |
| 105 | Channel F | Dew point alarm | 1 Bit | 1.3 enable | CW |
| 105 | Channel F | Forced position | 1 Bit | 1.3 enable | CW |
| 106 | Channel F | PWM cooling for 4 pipe system | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 107 | Channel F | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 108 | Channel F | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 109 | Channel F | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 110 | Channel F | Mode selection | 1 Byte | CW | |
| 110 | Channel F | Mode selection | 1 Byte | CRWT | |
| 111 | Channel F | DPT_HVAC Status | 1 Byte | CRT | |
| 112 | Channel F | DPT_RHCC Status | 2 Bytes | CRT | |
| 113 | Channel F | Mode comfort | 1 Bit | 1.1 switch | CW |
| 114 | Channel F | Mode night | 1 Bit | 1.1 switch | CW |
| 115 | Channel F | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 115 | Channel F | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 115 | Channel F | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 116 | Channel F | Frost alarm | 1 Bit | CRT | |
| 117 | Channel F | Heat alarm | 1 Bit | CRT | |
| 118 | Channel F | Setpoint value offset(1=+/0=-) | 1 Bit | CW | |
| 119 | Channel F | 1 Bit | |||
| 120 | Channel G | Control value | 1 Bit | 1.1 switch | CW |
| 120 | Channel G | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 120 | Channel G | Temperature value | 2 Bytes | 9.1 temperature (°C) | CW |
| 121 | Channel G | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 122 | Channel G | Block | 1 Bit | 1.3 enable | CW |
| 123 | Channel G | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 123 | Channel G | State control value | 1 Bit | 1.1 switch | CRT |
| 124 | Channel G | Message emergency mode | 1 Bit | CRT | |
| 125 | Channel G | Dew point alarm | 1 Bit | 1.3 enable | CW |
| 125 | Channel G | Forced position | 1 Bit | 1.3 enable | CW |
| 126 | Channel G | PWM cooling for 4 pipe system | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 127 | Channel G | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 128 | Channel G | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 129 | Channel G | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 130 | Channel G | Mode selection | 1 Byte | CW | |
| 130 | Channel G | Mode selection | 1 Byte | CRWT | |
| 131 | Channel G | DPT_HVAC Status | 1 Byte | CRT | |
| 132 | Channel G | DPT_RHCC Status | 2 Bytes | CRT | |
| 133 | Channel G | Mode comfort | 1 Bit | 1.1 switch | CW |
| 134 | Channel G | Mode night | 1 Bit | 1.1 switch | CW |
| 135 | Channel G | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 135 | Channel G | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 135 | Channel G | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 136 | Channel G | Frost alarm | 1 Bit | CRT | |
| 137 | Channel G | Heat alarm | 1 Bit | CRT | |
| 138 | Channel G | Setpoint value offset(1=+/0=-) | 1 Bit | CW | |
| 139 | Channel G | 1 Bit | |||
| 140 | Channel H | Control value | 1 Bit | 1.1 switch | CW |
| 140 | Channel H | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 140 | Channel H | Temperature value | 2 Bytes | 9.1 temperature (°C) | CW |
| 141 | Channel H | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 142 | Channel H | Block | 1 Bit | 1.3 enable | CW |
| 143 | Channel H | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 143 | Channel H | State control value | 1 Bit | 1.1 switch | CRT |
| 144 | Channel H | Message emergency mode | 1 Bit | CRT | |
| 145 | Channel H | Dew point alarm | 1 Bit | 1.3 enable | CW |
| 145 | Channel H | Forced position | 1 Bit | 1.3 enable | CW |
| 146 | Channel H | PWM cooling for 4 pipe system | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 147 | Channel H | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 148 | Channel H | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 149 | Channel H | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 150 | Channel H | Mode selection | 1 Byte | CW | |
| 150 | Channel H | Mode selection | 1 Byte | CRWT | |
| 151 | Channel H | DPT_HVAC Status | 1 Byte | CRT | |
| 152 | Channel H | DPT_RHCC Status | 2 Bytes | CRT | |
| 153 | Channel H | Mode comfort | 1 Bit | 1.1 switch | CW |
| 154 | Channel H | Mode night | 1 Bit | 1.1 switch | CW |
| 155 | Channel H | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 155 | Channel H | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 155 | Channel H | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 156 | Channel H | Frost alarm | 1 Bit | CRT | |
| 157 | Channel H | Heat alarm | 1 Bit | CRT | |
| 158 | Channel H | Setpoint value offset(1=+/0=-) | 1 Bit | CW | |
| 159 | Channel H | 1 Bit | |||
| 160 | Summer / Winter | Switchover | 1 Bit | 1.2 boolean | CW |
| 161 | Heating / Cooling | Switchover | 1 Bit | CW | |
| 162 | Heating / Cooling requirement | 0 if all valves closed, else 1 | 1 Bit | 1.2 boolean | CRT |
| 163 | Fault | At power failure/short circuit | 1 Bit | CRT | |
| 163 | Fault | At short circuit | 1 Bit | CRT | |
| 164 | Max. control value | Output | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 165 | Max. control value | Input | 1 Byte | 5.1 percentage (0..100%) | CW |
| 166 | Dummy | 1 Bit | |||
| 167 | Dummy | 1 Bit | |||
| 168 | Dummy | 1 Bit | |||
| 169 | Dummy | 1 Bit | |||
| 170 | Dummy | 1 Bit |
Parameters (78)
| Parameter | Type | Default |
|---|---|---|
| Startup delaytime | list | 0 s |
| Thermal driving | list | 230V |
| Object for requirement Heating/Cooling | list | inactive |
| Switching for cooling | list | inactive |
| Control values set to 0% at summer mode | list | No |
| Polarity for object "Summer/Winter" | list | Summer = 1 / Winter = 0 |
| Protection of forse fit (all 6 days for 5 min valve open/close) | list | inactive |
| Object max. control value | list | inactive |
| Request control value/temperature value after bus power reset | list | inactive |
| Behavior after bus power reset | list | No request values |
| Operating mode after reset | list | Comfort |
| This setting can be apply only for hardware starting from version 2.0 | text | <- TIP |
| Mode channel A | list | Chanel not active |
| Valve type | list | not energized closed |
| Block object | list | inactive |
| Regard channel in Heating / Cooling requirement and max. control value | list | Yes |
| Emergency mode | list | inactive |
| Emergency mode at failure of control value after | list | inactive |
| Control value for emergency mode winter | list | 50% |
| Control value for emergency mode summer | list | 0% |
| Forced position / dew point alarm | list | inactive |
| Control value for forced position winter | list | 50% |
| Control value for forced position summer | list | 20% |
| Send state control value | list | inactive |
| PWM cycletime (min) | list | 10 min |
| Minimum limit of control value at heating | list | 0% |
| Maximum limit of control value at heating | list | 100% |
| Minimum limit of control value at cooling | list | 0% |
| Maximum limit of control value at cooling | list | 100% |
| Flow temperature limit | list | inactive |
| Flow temperature limit at heating | list | inactive |
| Flow temperature limit at cooling | list | inactive |
| Heating / Cooling mode | list | Heating |
| Control value for emergency mode Summer/Cooling | list | 0% |
| Priority | list | Frost/Comfort/Night/Standby |
| Basic comfort setpoint (°C) | list | 21,0 °C |
| Standby reduction (K) | list | 2,0 K |
| Night reduction (K) | list | 3,0 K |
| Max setpoint offset (K) | list | 3,0 K |
| Setpoint value offset over | list | 2Byte-Object |
| Step width | list | 0,5 °C |
| Max setpoint offset vaild for | list | Comfort |
| Reset setpoint offset after change of mode | list | No |
| Send setpoint change | list | No |
| Send status on object 10 "Mode selection" | list | No |
| This setting can be apply only for hardware starting from version 2.2 | text | <- TIP |
| Heating system | list | Warm water heating (4K / 120 min) |
| Proportional range (K) | list | 3 K |
| Reset time (min) | list | 120 min |
| Heizsystem | list | Adjustment via control parameter |
| Message if value < | list | 8 °C |
| Message if value > | list | 35 °C |
| Standby increase (K) | list | 3,0 K |
| Night increase (K) | list | 2,0 K |
| Cooling system | list | Warm water heating (4K / 120 min) |
| Kühlsystem | list | Adjustment via control parameter |
| System | list | 2 Pipe system |
| Totzone zwischen Heizen und Kühlen (in K) | list | 0 K |
| Heating / Cooling system | list | Warm water heating (4K / 120 min) |
| Heiz-/Kühlsystem | list | Adjustment via control parameter |
| Mode channel B | list | Chanel not active |
| Emergency mode at failure of control value after | list | 45 min |
| Control value for forced position summer | list | 0% |
| Flow temperature limit at heating | list | 38 °C |
| Flow temperature limit at cooling | list | 18 °C |
| Send status on object 30 "Mode selection" | list | No |
| Mode channel C | list | Chanel not active |
| Send status on object 50 "Mode selection" | list | No |
| Mode channel D | list | Chanel not active |
| Send status on object 70 "Mode selection" | list | No |
| Mode channel E | list | Chanel not active |
| Send status on object 90 "Mode selection" | list | No |
| Mode channel F | list | Chanel not active |
| Send status on object 110 "Mode selection" | list | No |
| Mode channel G | list | Chanel not active |
| Send status on object 130 "Mode selection" | list | No |
| Mode channel H | list | Chanel not active |
| Send status on object 150 "Mode selection" | list | No |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Heating actuator 8-fold 1.4 latest | $003A | FEB2 | 2026-11-25 | 135 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH AKH-0800.01 Heating actuator 8-fold, 4SU,24/230VAC (AKH-0800.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- AKD-0224V.01 LED Controller 2 channel AKD-0224V.01
- AKD-0324V.01 RGB LED Controller AKD-0324V.01
- AKD-0410V.01 Dimming Control Unit 4-f, 4TE, 1-10V AKD-0410V.01
- AKD-0424R.01 RGBW LED Controller, MDRC AKD-0424R.01
- AKD-0424V.01 RGBW LED Controller AKD-0424V.01
- AKH-0400.01 Heating actuator 4-fold, 2SU,24/230VAC AKH-0400.01
- AKK-01UP.01 Switch Actuator 1-fold, UP, 16A AKK-01UP.01
- AKK-0216.01 Switch Actuator 2-fold, 2SU, 16A AKK-0216.01
- AKK-0216.02 Switch Actuator 2-fold, 2SU, 16A AKK-0216.02
- AKK-02UP.01 Switch Actuator 2-fold, UP, 6A AKK-02UP.01
- AKK-03UP.01 Switch Actuator 3fold, FanCoil AKK-03UP.01
- AKK-0406.01 Switch Actuator 4-fold, 2SU, 6A AKK-0406.01