KNX Database

AKH-0400.01 Heating actuator 4-fold, 2SU,24/230VAC AKH-0400.01

MDT technologies GmbH · Order number AKH-0400.01 · Archive › Actuators › Heating Actuator

Control valves, Control, 24/230VAC

Download .knxprod Heating actuator 4-fold 1.4 · 105 KB

Product

ManufacturerMDT technologies GmbH
Product nameAKH-0400.01 Heating actuator 4-fold, 2SU,24/230VAC
Order numberAKH-0400.01
HardwareHeizungsaktor 4-fach
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)36.3
RegistrationCertified · 2011-07-06
Languagesde-DE, en-US
Catalog entryM-0083_H-61-0_HP-003B-14-52E9_CI-AKH.2D0400.2E01-2
Fingerprint52E9
SHA-2569d3818b1a1a6e9a7611b70fc4260de1731b9dbb6154aca874d485fd6c3934623
First seen2026-11-25
Markets69 markets

Application program: Heating actuator 4-fold 1.4

Application number$003B
Version1.4
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters289
Group objects120
Group objects (120)
NoNameFunctionSizeDPTFlags
0Channel AControl value1 Bit1.1 switchCW
0Channel AControl value1 Byte5.1 percentage (0..100%)CW
0Channel ATemperature value2 Bytes9.1 temperature (°C)CW
1Channel AFlow temperature2 Bytes9.1 temperature (°C)CW
2Channel ABlock1 Bit1.3 enableCW
3Channel AState control value1 Byte5.1 percentage (0..100%)CRT
3Channel AState control value1 Bit1.1 switchCRT
4Channel AMessage emergency mode1 BitCRT
5Channel ADew point alarm1 Bit1.3 enableCW
5Channel AForced position1 Bit1.3 enableCW
6Channel APWM cooling for 4 pipe system1 Byte5.1 percentage (0..100%)CRT
7Channel ASetpoint comfort2 Bytes9.1 temperature (°C)CW
8Channel ASetpoint value offset2 Bytes9.2 temperature difference (K)CW
9Channel AActual setpoint2 Bytes9.1 temperature (°C)CRT
10Channel AMode selection1 ByteCRWT
10Channel AMode selection1 ByteCW
11Channel ADPT_HVAC Status1 ByteCRT
12Channel ADPT_RHCC Status 2 BytesCRT
13Channel AMode comfort1 Bit1.1 switchCW
14Channel AMode night1 Bit1.1 switchCW
15Channel AMode heat protection1 Bit1.1 switchCW
15Channel AMode frost/heat protection1 Bit1.1 switchCW
15Channel AMode frost protection1 Bit1.1 switchCW
16Channel AFrost alarm1 BitCRT
17Channel AHeat alarm1 BitCRT
18Channel ASetpoint value offset(1=+/0=-)1 BitCW
19Channel ADummy1 Bit
20Channel BControl value1 Bit1.1 switchCW
20Channel BControl value1 Byte5.1 percentage (0..100%)CW
20Channel BTemperature value2 Bytes9.1 temperature (°C)CW
21Channel BFlow temperature2 Bytes9.1 temperature (°C)CW
22Channel BBlock1 Bit1.3 enableCW
23Channel BState control value1 Byte5.1 percentage (0..100%)CRT
23Channel BState control value1 Bit1.1 switchCRT
24Channel BMessage emergency mode1 BitCRT
25Channel BDew point alarm1 Bit1.3 enableCW
25Channel BForced position1 Bit1.3 enableCW
26Channel BPWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
27Channel BSetpoint comfort2 Bytes9.1 temperature (°C)CW
28Channel BSetpoint value offset2 Bytes9.2 temperature difference (K)CW
29Channel BAcutal setpoint2 Bytes9.1 temperature (°C)CRT
30Channel BMode selection1 ByteCW
30Channel BMode selection1 ByteCRWT
31Channel BDPT_HVAC Status1 ByteCRT
32Channel BDPT_RHCC Status 2 BytesCRT
33Channel BMode comfort1 Bit1.1 switchCW
34Channel BMode night1 Bit1.1 switchCW
35Channel BMode heat protection1 Bit1.1 switchCW
35Channel BMode frost/heat protection1 Bit1.1 switchCW
35Channel BMode frost protection1 Bit1.1 switchCW
36Channel BFrost alarm1 BitCRT
37Channel BHeat alarm1 BitCRT
38Channel BSetpoint value offset(1=+/0=-)1 BitCW
39Channel B1 Bit
40Channel CControl value1 Bit1.1 switchCW
40Channel CControl value1 Byte5.1 percentage (0..100%)CW
40Channel CTemperature value2 Bytes9.1 temperature (°C)CW
41Channel CFlow temperature2 Bytes9.1 temperature (°C)CW
42Channel CBlock1 Bit1.3 enableCW
43Channel CState control value1 Byte5.1 percentage (0..100%)CRT
43Channel CState control value1 Bit1.1 switchCRT
44Channel CMessage emergency mode1 BitCRT
45Channel CDew point alarm1 Bit1.3 enableCW
45Channel CForced position1 Bit1.3 enableCW
46Channel CPWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
47Channel CSetpoint comfort2 Bytes9.1 temperature (°C)CW
48Channel CSetpoint value offset2 Bytes9.2 temperature difference (K)CW
49Channel CAcutal setpoint2 Bytes9.1 temperature (°C)CRT
50Channel CMode selection1 ByteCW
50Channel CMode selection1 ByteCRWT
51Channel CDPT_HVAC Status1 ByteCRT
52Channel CDPT_RHCC Status 2 BytesCRT
53Channel CMode comfort1 Bit1.1 switchCW
54Channel CMode night1 Bit1.1 switchCW
55Channel CMode heat protection1 Bit1.1 switchCW
55Channel CMode frost/heat protection1 Bit1.1 switchCW
55Channel CMode frost protection1 Bit1.1 switchCW
56Channel CFrost alarm1 BitCRT
57Channel CHeat alarm1 BitCRT
58Channel CSetpoint value offset(1=+/0=-)1 BitCW
59Channel C1 Bit
60Channel DControl value1 Bit1.1 switchCW
60Channel DControl value1 Byte5.1 percentage (0..100%)CW
60Channel DTemperature value2 Bytes9.1 temperature (°C)CW
61Channel DFlow temperature2 Bytes9.1 temperature (°C)CW
62Channel DBlock1 Bit1.3 enableCW
63Channel DState control value1 Byte5.1 percentage (0..100%)CRT
63Channel DState control value1 Bit1.1 switchCRT
64Channel DMessage emergency mode1 BitCRT
65Channel DDew point alarm1 Bit1.3 enableCW
65Channel DForced position1 Bit1.3 enableCW
66Channel DPWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
67Channel DSetpoint comfort2 Bytes9.1 temperature (°C)CW
68Channel DSetpoint value offset2 Bytes9.2 temperature difference (K)CW
69Channel DAcutal setpoint2 Bytes9.1 temperature (°C)CRT
70Channel DMode selection1 ByteCRWT
70Channel DMode selection1 ByteCW
71Channel DDPT_HVAC Status1 ByteCRT
72Channel DDPT_RHCC Status 2 BytesCRT
73Channel DMode comfort1 Bit1.1 switchCW
74Channel DMode night1 Bit1.1 switchCW
75Channel DMode heat protection1 Bit1.1 switchCW
75Channel DMode frost/heat protection1 Bit1.1 switchCW
75Channel DMode frost protection1 Bit1.1 switchCW
76Channel DFrost alarm1 BitCRT
77Channel DHeat alarm1 BitCRT
78Channel DSetpoint value offset(1=+/0=-)1 BitCW
79Channel D1 Bit
80Summer / WinterSwitchover1 Bit1.2 booleanCW
81Heating / CoolingSwitchover1 BitCW
82Heating / Cooling requirement0 if all valves closed, else 11 Bit1.2 booleanCRT
83FaultAt short circuit1 BitCRT
83FaultAt power failure/short circuit1 BitCRT
84Max. control valueOutput1 Byte5.1 percentage (0..100%)CRT
85Max. control valueInput1 Byte5.1 percentage (0..100%)CW
86Dummy1 Bit
87Dummy1 Bit
88Dummy1 Bit
89Dummy1 Bit
90Dummy1 Bit
Parameters (69)
ParameterTypeDefault
Startup delaytimelist0 s
Thermal drivinglist230V
Object for requirement Heating/Coolinglistnot active
Switching for coolinglistnot active
Control values set to 0% at summer modelistNo
Polarity for object "Summer/Winter"listSummer = 1 / Winter = 0
Protection of forse fit (all 6 days for 5 min valve open/close)listnot active
Object max. control valuelistnot active
Request control value/temperature value after bus power resetlistinactive
Behavior after bus power resetlistNo request values
Operating mode after resetlistComfort
This setting can be apply only for hardware starting from version 2.0text<- TIP
Mode channel AlistChanel not active
Valve typelistnot energized closed
Block objectlistinactive
Regard channel in Heating / Cooling requirement and max. control valuelistYes
Emergency modelistinactive
Emergency mode at failure of control value afterlistnot active
Control value for emergency mode winterlist50%
Control value for emergency mode summerlist0%
Forced position / dew point alarmlistnot active
Control value for forced position winterlist50%
Control value for forced position summerlist0%
Send state control valuelistnot active
PWM cycletime (min)list10 min
Minimum limit of control value at heatinglist0%
Maximum limit of control value at heatinglist100%
Minimum limit of control value at coolinglist0%
Maximum limit of control value at coolinglist100%
Flow temperature limitlistinactive
Flow temperature limit at heatinglistinactive
Flow temperature limit at coolinglistinactive
Heating / Cooling modelistHeating
Control value for emergency mode Summer/Coolinglist0%
PrioritylistFrost/Comfort/Night/Standby
Basic comfort setpoint (°C)list21,0 °C
Standby reduction (K)list2,0 K
Night reduction (K)list3,0 K
Max setpoint offset (K)list3,0 K
Setpoint value offset overlist2Byte-Object
Step widthlist0,5 °C
Max setpoint offset vaild forlistComfort
Reset setpoint offset after change of modelistNo
Send setpoint changelistNo
Send status on object 10 "Mode selection"listNo
This setting can be apply only for hardware starting from version 2.2text<- TIP
Heating systemlistWarm water heating (4K / 120 min)
Proportional range (K)list3 K
Reset time (min)list120 min
HeizsystemlistAdjustment via control parameter
Message if value <list8 °C
Message if value >list35 °C
Standby increase (K)list3,0 K
Night increase (K)list2,0 K
Cooling systemlistWarm water heating (4K / 120 min)
KühlsystemlistAdjustment via control parameter
Systemlist2 Pipe system
Totzone zwischen Heizen und Kühlen (in K)list0 K
Heating / Cooling systemlistWarm water heating (4K / 120 min)
Heiz-/KühlsystemlistAdjustment via control parameter
Mode channel BlistChanel not active
Emergency mode at failure of control value afterlist45 min
Flow temperature limit at heatinglist38 °C
Flow temperature limit at coolinglist18 °C
Send status on object 30 "Mode selection"listNo
Mode channel ClistChanel not active
Send status on object 50 "Mode selection"listNo
Mode channel DlistChanel not active
Send status on object 70 "Mode selection"listNo

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Heating actuator 4-fold 1.4 latest$003B52E92026-11-25105 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH AKH-0400.01 Heating actuator 4-fold, 2SU,24/230VAC (AKH-0400.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.