KNX Database

switching actuator 4fold A4FX

Lime · Order number A4FX · binary output › netra series

Download .knxprod 4x switching, time, scene, announce, inh. 2025-21 2.1 · 93 KB

Product

ManufacturerLime
Product nameswitching actuator 4fold
Order numberA4FX
Product textnetra series switching actuator 4f
HardwareA4FX
MediumTwisted Pair
Bus current (mA)5
Rail mountedYes
Width (mm)72
RegistrationRegistered · 2017-08-04
Languagesen-US, de-DE
Catalog entryM-0198_H-2015-1-O00E1_HP-2025-21-1527-O00E1_CI-A4FX-1
Fingerprint1527
SHA-2562285212805a2ed88f2e5fb517498062c55e59869a27204c79244824fec957f51
First seen2026-11-25
MarketsGermany, Lebanon, United Arab Emirates

Application program: 4x switching, time, scene, announce, inh. 2025-21 2.1

Application number$2025
Version2.1
Mask versionMV-0021 (2.1)
KNX Data SecureNo
Parameters440
Group objects64
Group objects (64)
NoNameFunctionSizeDPTFlags
0input A, CH1 switchingchannel A, CH1 object 11 Bit1.1 switchCW
0input A1, CH1 ORchannel A, CH1 object 11 Bit1.1 switchCW
0input A1, CH1 EXORchannel A, CH1 object 11 Bit1.1 switchCW
0input A1, CH1 ANDchannel A, CH1 object 11 Bit1.1 switchCW
1input A2, CH1 ORchannel A, CH1 object 21 Bit1.1 switchCW
1input A2, CH1 EXORchannel A, CH1 object 21 Bit1.1 switchCW
1input A2, CH1 ANDchannel A, CH1 object 21 Bit1.1 switchCW
2output A, CH1 statuschannel A, CH1 object 31 Bit1.1 switchCT
2output A, CH1 status INVchannel A, CH1 object 31 Bit1.1 switchCT
3input A, CH1 sceneschannel A, CH1 object 41 Byte18.1 scene controlCW
4input A, CH1 announcechannel A, CH1 object 51 Bit1.1 switchCW
5input A, CH1 inhibitchannel A, CH1 object 61 Bit1.1 switchCW
6input A, CH1 reset hour meterchannel A, CH1 object 71 Bit1.15 resetCW
7output A, CH1 hour meter (h)channel A, CH1 object 82 Bytes7.7 time (h)CT
7output A, CH1 hour meter (s)channel A, CH1 object 84 Bytes13.100 time lag (s)CT
8output A, CH1 limit reachedchannel A, CH1 object 91 Bit1.2 booleanCT
9input B1, CH2 ORchannel B, CH2 object 11 Bit1.1 switchCW
9input B1, CH2 EXORchannel B, CH2 object 11 Bit1.1 switchCW
9input B1, CH2 ANDchannel B, CH2 object 11 Bit1.1 switchCW
9input B, CH2 switchingchannel B, CH2 object 11 Bit1.1 switchCW
10input B2, CH2 EXORchannel B, CH2 object 21 Bit1.1 switchCW
10input B2, CH2 ANDchannel B, CH2 object 21 Bit1.1 switchCW
10input B2, CH2 ORchannel B, CH2 object 21 Bit1.1 switchCW
11output B, CH2 statuschannel B, CH2 object 31 Bit1.1 switchCT
11output B, CH2 status INVchannel B, CH2 object 31 Bit1.1 switchCT
12input B, CH2 sceneschannel B, CH2 object 41 Byte18.1 scene controlCW
13input B, CH2 announcechannel B, CH2 object 51 Bit1.1 switchCW
14input B, CH2 inhibitchannel B, CH2 object 61 Bit1.1 switchCW
15input B, CH2 reset hour meterchannel B, CH2 object 71 Bit1.15 resetCW
16output B, CH2 hour meter (h)channel B, CH2 object 82 Bytes7.7 time (h)CT
16output B, CH2 hour meter (s)channel B, CH2 object 84 Bytes13.100 time lag (s)CT
17output B, CH2 limit reachedchannel B, CH2 object 91 Bit1.2 booleanCT
18input C1, CH3 ORchannel C, CH3 object 11 Bit1.1 switchCW
18input C1, CH3 EXORchannel C, CH3 object 11 Bit1.1 switchCW
18input C1, CH3 ANDchannel C, CH3 object 11 Bit1.1 switchCW
18input C, CH3 switchingchannel C, CH3 object 11 Bit1.1 switchCW
19input C2, CH3 ANDchannel C, CH3 object 21 Bit1.1 switchCW
19input C2, CH3 ORchannel C, CH3 object 21 Bit1.1 switchCW
19input C2, CH3 EXORchannel C, CH3 object 21 Bit1.1 switchCW
20output C, CH3 statuschannel C, CH3 object 31 Bit1.1 switchCT
20output C, CH3 status INVchannel C, CH3 object 31 Bit1.1 switchCT
21input C, CH3 sceneschannel C, CH3 object 41 Byte18.1 scene controlCW
22input C, CH3 announcechannel C, CH3 object 51 Bit1.1 switchCW
23input C, CH3 inhibitchannel C, CH3 object 61 Bit1.1 switchCW
24input C, CH3 reset hour meterchannel C, CH3 object 71 Bit1.15 resetCW
25output C, CH3 hour meter (h)channel C, CH3 object 82 Bytes7.7 time (h)CT
25output C, CH3 hour meter (s)channel C, CH3 object 84 Bytes13.100 time lag (s)CT
26output C, CH3 limit reachedchannel C, CH3 object 91 Bit1.2 booleanCT
27input D1, CH4 ORchannel D, CH4 object 11 Bit1.1 switchCW
27input D1, CH4 EXORchannel D, CH4 object 11 Bit1.1 switchCW
27input D1, CH4 ANDchannel D, CH4 object 11 Bit1.1 switchCW
27input D, CH4 switchingchannel D, CH4 object 11 Bit1.1 switchCW
28input D2, CH4 ANDchannel D, CH4 object 21 Bit1.1 switchCW
28input D2, CH4 ORchannel D, CH4 object 21 Bit1.1 switchCW
28input D2, CH4 EXORchannel D, CH4 object 21 Bit1.1 switchCW
29output D, CH4 statuschannel D, CH4 object 31 Bit1.1 switchCT
29output D, CH4 status INVchannel D, CH4 object 31 Bit1.1 switchCT
30input D, CH4 sceneschannel D, CH4 object 41 Byte18.1 scene controlCW
31input D, CH4 announcechannel D, CH4 object 51 Bit1.1 switchCW
32input D, CH4 inhibitchannel D, CH4 object 61 Bit1.1 switchCW
33input D, CH4 reset hour meterchannel D, CH4 object 71 Bit1.15 resetCW
34output D, CH4 hour meter (h)channel D, CH4 object 82 Bytes7.7 time (h)CT
34output D, CH4 hour meter (s)channel D, CH4 object 84 Bytes13.100 time lag (s)CT
35output D, CH4 limit reachedchannel D, CH4 object 91 Bit1.2 booleanCT
Parameters (75)
ParameterTypeDefault
usagelistenabled
at buspower recovery set switching object tolistdo not initialize
relay contact islistNO (norm. open)
at buspower failure contact islistno change
timing functionslistno
logic combinationlistno
statuslistno
sceneslistno
announce functionlistno
inhibit functionlistno
hour meterlistno
switch on delaylistno
delay time (1..255 sec)unsignedInt 1…2555
switch off delaylistno
staircase function / blinkinglistno
on time (1..255 sec)unsignedInt 1…2553
off time (1..255 sec)unsignedInt 1…2553
staircase on time (1..64800 sec)unsignedInt 1…64800180
retrigger staircase time (only, if on/off delay disabled)listyes
staircase prewarninglistno
prewarning off time (1..30 *100 ms)unsignedInt 1…305
prewarning on time (1..255 sec)unsignedInt 1…2553
number of prewarnings (1..7)unsignedInt 1…73
logic combinationlistnone
at buspower recovery set logic object tolist"1"
status is transmittedlistat value change
status send delay time (0..120 *100 ms)unsignedInt 0…1201
scene 1listno action
scene 2listno action
scene 3listno action
scene 4listno action
scene 5listno action
scene 6listno action
scene 7listno action
scene 8listno action
scene 9listno action
scene 10listno action
scene 11listno action
scene 12listno action
scene 13listno action
scene 14listno action
scene 15listno action
scene 16listno action
scene 17listno action
scene 18listno action
scene 19listno action
scene 20listno action
scene 21listno action
scene 22listno action
scene 23listno action
scene 24listno action
scene 25listno action
scene 26listno action
scene 27listno action
scene 28listno action
scene 29listno action
scene 30listno action
scene 31listno action
scene 32listno action
enable scene savinglistno
announce withlist"1"
at bus voltage recovery set announce object tolist"0"
action when announce startslistno action
on time (1..15 sec)unsignedInt 1…153
off time (1..15 sec)unsignedInt 1…153
action when announce endslistno action
inhibit withlist"1"
at bus voltage recovery set inhibit object tolist"0"
action when inhibit startslistno action
action when inhibit endslistno action
hour meter values are presented inlistDPT 7.007 hours (16bit unsigned int EIS10)
hour meter reading is transmittedlistcyclically
cycle timelist5 min
hour meter limit monitoringlistno
limit (1..65000 h)unsignedInt 1…655351000

Version history

ApplicationApp noFingerprintFirst seenSizeFile
4x switching, time, scene, announce, inh. 2025-21 2.1 latest$202515272026-11-2593 KBDownload

About this file

This is the official ETS product database for the Lime switching actuator 4fold (A4FX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Lime

All Lime products