Product

ManufacturerLEGRAND Appareillage électrique
Product nameKNX ON-OFF DIN CONTROLLER 8 outputs 16A
Order number002681
HardwareKNX ON-OFF DIN CONTROLLER 8 outputs 16A
MediumTwisted Pair
Bus current (mA)12
Rail mountedYes
RegistrationCertified · 2014-07-31
Languagesen-US
Catalog entryM-000B_H-10AA02-2-O0085_HP-0A79-10-9C75-O0085_CI-002681-1
Fingerprint9C75
SHA-25658f6c19d5aa991f69029585b5efd0638100f8fa6afaca108c15c879fe0926c42
First seen2026-11-25
MarketsChina, France, India, Italy, United Kingdom

Application program: KNX ON-OFF DIN CONTROLLER 8 outputs 16A 1.0

Application number$0A79
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Parameters901
Group objects203
Group objects (203)
NoNameFunctionSizeDPTFlags
0GeneralIn operation1 BitCRT
1Generalsafety priority 11 BitCWU
2Generalsafety priority 21 BitCWU
3Output Areply the switch status, A1 BitCR
3Output Asend the switch status, A1 BitCT
3Output AReply status of contact , A1 BitCR
4Output ASwitch, A1 BitCW
4Output Aon-off of regulating , A1 BitCW
5Output ASwitch out with delay, A1 BitCW
5Output ASwitch out with flashing, A1 BitCW
5Output AOutput of staircase lighting,A1 BitCW
5Output AStatus (continuous),1 bit , A1 BitCR
6Output ASwitch time function, A1 BitCW
7Output AWarning of staircase , A1 BitCT
7Output Areport fault, regulating , A1 BitCRT
8Output ADuration of staircase , A2 BytesCRW
9Output ACall preset 1/2 , A1 BitCW
10Output AStore preset 1/2, A1 BitCW
10Output ATrigger switch regularly , A1 BitCW
11Output AInput 1 of logic , A1 BitCW
12Output AInput 2 of logic , A1 BitCW
13Output AScene handle, A1 ByteCW
13Output AStatus (continuous),1 byte, A1 ByteCR
14Output AChange threshold 1, A1 ByteCW
14Output Acontinuous of regulating , A1 ByteCW
15Output AThreshold input , A1 ByteCW
16Output AForced output , A1 BitCW
16Output Aforced operation,regulating, A1 BitCW
17Output Breply the switch status, B1 BitCR
17Output Bsend the switch status, B1 BitCT
17Output BReply status of contact , B1 BitCR
18Output BSwitch, B1 BitCW
18Output Bon-off of regulating , B1 BitCW
19Output BSwitch out with delay, B1 BitCW
19Output BOutput of staircase lighting,B1 BitCW
19Output BSwitch out with flashing, B1 BitCW
19Output BStatus (continuous),1 bit, B1 BitCR
20Output BSwitch time function, B1 BitCW
21Output BWarning of staircase , B1 BitCT
21Output Breport fault, regulating , B1 BitCRT
22Output BDuration of staircase , B2 BytesCRW
23Output BCall preset 1/2 , B1 BitCW
24Output BStore preset 1/2, B1 BitCW
24Output BTrigger switch regularly , B1 BitCW
25Output BInput 1 of logic , B1 BitCW
26Output BInput 2 of logic , B1 BitCW
27Output BScene handle, B1 ByteCW
27Output BStatus (continuous),1 byte, B1 ByteCR
28Output BChange threshold 1, B1 ByteCW
28Output Bcontinuous of regulating , B1 ByteCW
29Output BThreshold input , B1 ByteCW
30Output BForced output , B1 BitCW
30Output Bforced operation,regulating, B1 BitCW
31Output Creply the switch status, C1 BitCR
31Output Csend the switch status, C1 BitCT
31Output CReply status of contact , C1 BitCR
32Output CSwitch, C1 BitCW
32Output Con-off of regulating , C1 BitCW
33Output CSwitch out with delay, C1 BitCW
33Output COutput of staircase lighting,C1 BitCW
33Output CSwitch out with flashing, C1 BitCW
33Output CStatus (continuous),1 bit , C1 BitCR
34Output CSwitch time function, C1 BitCW
35Output CWarning of staircase , C1 BitCT
35Output Creport fault, regulating , C1 BitCRT
36Output CDuration of staircase , C2 BytesCRW
37Output CCall preset 1/2 , C1 BitCW
38Output CStore preset 1/2, C1 BitCW
38Output CTrigger switch regularly , C1 BitCW
39Output CInput 1 of logic , C1 BitCW
40Output CInput 2 of logic , C1 BitCW
41Output CScene handle, C1 ByteCW
41Output CStatus (continuous),1 byte, C1 ByteCR
42Output CChange threshold 1, C1 ByteCW
42Output Ccontinuous of regulating , C1 ByteCW
43Output CThreshold input , C1 ByteCW
44Output CForced output , C1 BitCW
44Output Cforced operation,regulating, C1 BitCW
45Output Dreply the switch status, D1 BitCR
45Output Dsend the switch status, D1 BitCT
45Output DReply status of contact , D1 BitCR
46Output DSwitch, D1 BitCW
46Output Don-off of regulating , D1 BitCW
47Output DSwitch out with delay, D1 BitCW
47Output DOutput of staircase lighting,D1 BitCW
47Output DSwitch out with flashing, D1 BitCW
47Output DStatus (continuous),1 bit , D1 BitCR
48Output DSwitch time function, D1 BitCW
49Output DWarning of staircase , D1 BitCT
49Output Dreport fault, regulating , D1 BitCRT
50Output DDuration of staircase , D2 BytesCRW
51Output DCall preset 1/2 , D1 BitCW
52Output DStore preset 1/2, D1 BitCW
52Output DTrigger switch regularly , D1 BitCW
53Output DInput 1 of logic , D1 BitCW
54Output DInput 2 of logic , D1 BitCW
55Output DScene handle, D1 ByteCW
55Output DStatus (continuous),1 byte, D1 ByteCR
56Output DChange threshold 1, D1 ByteCW
56Output Dcontinuous of regulating , D1 ByteCW
57Output DThreshold input , D1 ByteCW
58Output DForced output , D1 BitCW
58Output Dforced operation,regulating, D1 BitCW
59Output Ereply the switch status, E1 BitCR
59Output Esend the switch status, E1 BitCT
59Output EReply status of contact , E1 BitCR
60Output ESwitch, E1 BitCW
60Output Eon-off of regulating , E1 BitCW
61Output ESwitch out with delay, E1 BitCW
61Output EOutput of staircase lighting,E1 BitCW
61Output ESwitch out with flashing, E1 BitCW
61Output EStatus (continuous),1 bit , E1 BitCR
62Output ESwitch time function, E1 BitCW
63Output EWarning of staircase , E1 BitCT
63Output Ereport fault, regulating , E1 BitCRT
64Output EDuration of staircase , D2 BytesCRW
65Output ECall preset 1/2 , E1 BitCW
66Output EStore preset 1/2, E1 BitCW
66Output ETrigger switch regularly , E1 BitCW
67Output EInput 1 of logic , E1 BitCW
68Output EInput 2 of logic , E1 BitCW
69Output EScene handle, E1 ByteCW
69Output EStatus (continuous),1 byte, E1 ByteCR
70Output EChange threshold 1, E1 ByteCW
70Output Econtinuous of regulating , E1 ByteCW
71Output EThreshold input , E1 ByteCW
72Output EForced output , E1 BitCW
72Output Eforced operation,regulating, E1 BitCW
73Output Freply the switch status, F1 BitCR
73Output Fsend the switch status, F1 BitCT
73Output FReply status of contact , F1 BitCR
74Output FSwitch, F1 BitCW
74Output Fon-off of regulating , F1 BitCW
75Output FSwitch out with delay, F1 BitCW
75Output FOutput of staircase lighting,F1 BitCW
75Output FSwitch out with flashing, F1 BitCW
75Output FStatus (continuous),1 bit , F1 BitCR
76Output FSwitch time function, F1 BitCW
77Output FWarning of staircase , F1 BitCT
77Output Freport fault, regulating , F1 BitCRT
78Output FDuration of staircase , F2 BytesCRW
79Output FCall preset 1/2 , F1 BitCW
80Output FStore preset 1/2, F1 BitCW
80Output FTrigger switch regularly , F1 BitCW
81Output FInput 1 of logic , F1 BitCW
82Output FInput 2 of logic , F1 BitCW
83Output FScene handle, F1 ByteCW
83Output FStatus (continuous),1 byte, F1 ByteCR
84Output FChange threshold 1, F1 ByteCW
84Output Fcontinuous of regulating , F1 ByteCW
85Output FThreshold input , F1 ByteCW
86Output FForced output , F1 BitCW
86Output Fforced operation,regulating, F1 BitCW
87Output Greply the switch status, G1 BitCR
87Output Gsend the switch status, G1 BitCT
87Output GReply status of contact , G1 BitCR
88Output GSwitch, G1 BitCW
88Output Gon-off of regulating , G1 BitCW
89Output GSwitch out with delay, G1 BitCW
89Output GOutput of staircase lighting,G1 BitCW
89Output GSwitch out with flashing, G1 BitCW
89Output GStatus (continuous),1 bit , G1 BitCR
90Output GSwitch time function, G1 BitCW
91Output GWarning of staircase , G1 BitCT
91Output Greport fault, regulating , G1 BitCRT
92Output GDuration of staircase , G2 BytesCRW
93Output GCall preset 1/2 , G1 BitCW
94Output GStore preset 1/2, G1 BitCW
94Output GTrigger switch regularly , G1 BitCW
95Output GInput 1 of logic , G1 BitCW
96Output GInput 2 of logic , G1 BitCW
97Output GScene handle, G1 ByteCW
97Output GStatus (continuous),1 byte, G1 ByteCR
98Output GChange threshold 1, G1 ByteCW
98Output Gcontinuous of regulating , G1 ByteCW
99Output GThreshold input , G1 ByteCW
100Output GForced output , G1 BitCW
100Output Gforced operation,regulating, G1 BitCW
101Output Hreply the switch status, H1 BitCR
101Output Hsend the switch status, H1 BitCT
101Output HReply status of contact , H1 BitCR
102Output HSwitch, H1 BitCW
102Output Hon-off of regulating , H1 BitCW
103Output HSwitch out with delay, H1 BitCW
103Output HOutput of staircase lighting,H1 BitCW
103Output HSwitch out with flashing, H1 BitCW
103Output HStatus (continuous),1 bit , H1 BitCR
104Output HSwitch time function, H1 BitCW
105Output HWarning of staircase , H1 BitCT
105Output Hreport fault, regulating , H1 BitCRT
106Output HDuration of staircase , H2 BytesCRW
107Output HCall preset 1/2 , H1 BitCW
108Output HStore preset 1/2, H1 BitCW
108Output HTrigger switch regularly , H1 BitCW
109Output HInput 1 of logic , H1 BitCW
110Output HInput 2 of logic , H1 BitCW
111Output HScene handle, H1 ByteCW
111Output HStatus (continuous),1 byte, H1 ByteCR
112Output HChange threshold 1, H1 ByteCW
112Output Hcontinuous of regulating , H1 ByteCW
113Output HThreshold input , H1 ByteCW
114Output HForced output , H1 BitCW
114Output Hforced operation,regulating, H1 BitCW
Parameters (112)
ParameterTypeDefault
Operation delay after recovery of bus voltage(1...250s)unsignedInt 1…2501
Sending cycle of "In operation" telegram (1......240s , 0=inactive)unsignedInt 0…2400
Enable safety priority functionlistdisable
---set safety priority 1:listinactive
Control period of safety priority 1 (1......240 s, 0=inactive)unsignedInt 0…2400
---set safety priority 2:listinactive
Control period of safety priority 2 (1......240 s, 0=inactive)unsignedInt 0…2400
¡¡¡¡=====N o t e===== Normal, object value map switch on/offlist"1"=switch on; "0"=switch off
Channel A work mode islistSwitch actuator
If bus voltage recovery,contact islistunchange
If bus voltage fail,contact islistunchange
Object value of "telegram switch" after bus voltage recoverylistnot write
Set the reply mode of switch status for channel Alistno reply
Object value of switch status :list0=contact open ; 1=contact close
Contact position if tele. value is "1" ("0" is opposite of "1" if changed)listclose
Special functions of switch actuator mode for channel A islistinactive
Function of "time" for switch islistdisable
Function of "preset" for switch islistdisable
Function of "logic" for switch islistdisable
Function of "scene" for switch islistdisable
Function of "threshold" for switch islistdisable
Function of "safety" for switch islistdisable
Function of "forced" for switch islistdisable
The mode of time functionlistdelay switch
Delay for switch on : --(0...240 minutes)unsignedInt 0…2400
--(0...59 seconds)unsignedInt 0…590
Delay for switch off : --(0...240 minutes)unsignedInt 0…2400
Number of ON-impulses (1...255 , 0=no limited)unsignedInt 0…2550
Contact position after flashinglistunchange
The mode of control for flashinglistStart with "1" , Stop with "0"
Duration of staircase lighting --(0...1000 minutes)unsignedInt 0…10002
The mode of control for staircase lighting islistStart with "0/1" , can not be stop
During the lighting time, if receive the "Start" telegram,listrestart duration of staircase lighting
Warning mode for ending of staircase lightinglistnothing
--The warning time for end of staircase lighting(0...59 s)unsignedInt 0…590
Modify the duration via object (0...60059 seconds)listdisable
Action for preset 1(object value=0)listNone
Action for preset 2(object value=1)listOFF
Setting for preset via telegram islistdisable
The input 0 (switch object) for logic islistdisable
The input 1 of logic islistdisable
Function type between input0 and input1listAND
Result is invertedlistNO
Value of input 1 after bus voltage recovery :list"0"
The input 2 of logic islistdisable
Function type between input2 and input0/1listAND
Value of input 2 after bus voltage recovery :list"0"
1> channel is assigned to (1...64 scene NO.,0= no allocation)unsignedInt 0…640
--Standard output value islistOFF
2> channel is assigned to (1...64 scene NO.,0= no allocation)unsignedInt 0…640
3> channel is assigned to (1...64 scene NO.,0= no allocation)unsignedInt 0…640
4> channel is assigned to (1...64 scene NO.,0= no allocation)unsignedInt 0…640
5> channel is assigned to (1...64 scene NO.,0= no allocation)unsignedInt 0…640
Threshold 1 valueunsignedInt 0…25580
Threshold 2 valueunsignedInt 0…255200
Change threshold 1via object :listdisable
Threshold behaviourlistwithout hysteresis
--If falling below lower threshold, contact positionlistunchange
--If exceeding upper threshold, contact positionlistunchange
--If lower < object value < upper contact positionlistunchange
Setting of safetyliston parameter-window "General"
Contact position if safety priority 1listunchange
Contact position if safety priority 2listunchange
Contact position if forced operationlistunchange
If bus voltage fail ,contact islistunchange
If bus voltage recovery, the duty cycle of dynamic regulatelist0%(OFF)
PWM cycle time for continuous control (1...240 minutes)unsignedInt 0…2403
PWM cycle time for continuous control (0...59 secondsunsignedInt 0…590
Control telegram is received aslist1 bit ( on-off control )
Reply the status of channel for continuous controllistnothing
Reply the status of contact statelistnothing
Special functions of dynamic regulating actuator mode for channel A islistinactive
Function for monitoring islistdisable
Function of forced operation islistdisable
Function of regular switch islistdisable
Function of safety operation islistdisable
Cyclic monitoring --in minutes (0...240 minutes)unsignedInt 0…24060
--in seconds (0...59 seconds)unsignedInt 0…590
The duty cycle of dynamic regulating during faultlistunchange
sending object "report fault" islistdisable
The duty cycle of dynamic regulating during forced operationlistunchange
Time of switch regular in minutes (0..255)unsignedInt 0…25510
Automatic switch regularlylistdisable
The duty cycle of dynamic regulating during safety 1 operationlistunchange
The duty cycle of dynamic regulating during safety 2 operationlistunchange
Channel B work mode islistSwitch actuator
Set the reply mode of switch status for channel Blistno reply
Special functions of switch actuator mode for channel B islistinactive
Special functions of dynamic regulating actuator mode for channel B islistinactive
Channel C work mode islistSwitch actuator
Set the reply mode of switch status for channel Clistno reply
Special functions of switch actuator mode for channel C islistinactive
Special functions of dynamic regulating actuator mode for channel C islistinactive
Channel D work mode islistSwitch actuator
Set the reply mode of switch status for channel Dlistno reply
Special functions of switch actuator mode for channel D islistinactive
Special functions of dynamic regulating actuator mode for channel D islistinactive
Channel E work mode islistSwitch actuator
Set the reply mode of switch status for channel Elistno reply
Special functions of switch actuator mode for channel E islistinactive
Special functions of dynamic regulating actuator mode for channel E islistinactive
Channel F work mode islistSwitch actuator
Set the reply mode of switch status for channel Flistno reply
Special functions of switch actuator mode for channel F islistinactive
Special functions of dynamic regulating actuator mode for channel F islistinactive
Channel G work mode islistSwitch actuator
Set the reply mode of switch status for channel Glistno reply
Special functions of switch actuator mode for channel G islistinactive
Special functions of dynamic regulating actuator mode for channel G islistinactive
Channel H work mode islistSwitch actuator
Special functions of switch actuator mode for channel H islistinactive
Special functions of dynamic regulating actuator mode for channel H islistinactive

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX ON-OFF DIN CONTROLLER 8 outputs 16A 1.0 latest$0A799C752026-11-25128 KBDownload

About this file

This is the official ETS product database for the LEGRAND Appareillage électrique KNX ON-OFF DIN CONTROLLER 8 outputs 16A (002681), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from LEGRAND Appareillage électrique

All LEGRAND Appareillage électrique products