KNX ON-OFF DIN CONTROLLER 8 outputs 16A 002681
LEGRAND Appareillage électrique · Order number 002681 · Lighting › Gateway
KNX ON-OFF DIN CONTROLLER 8 outputs 16A
Download .knxprod KNX ON-OFF DIN CONTROLLER 8 outputs 16A 1.0 · 128 KB
Product
| Manufacturer | LEGRAND Appareillage électrique |
|---|---|
| Product name | KNX ON-OFF DIN CONTROLLER 8 outputs 16A |
| Order number | 002681 |
| Hardware | KNX ON-OFF DIN CONTROLLER 8 outputs 16A |
| Medium | Twisted Pair |
| Bus current (mA) | 12 |
| Rail mounted | Yes |
| Registration | Certified · 2014-07-31 |
| Languages | en-US |
| Catalog entry | M-000B_H-10AA02-2-O0085_HP-0A79-10-9C75-O0085_CI-002681-1 |
| Fingerprint | 9C75 |
| SHA-256 | 58f6c19d5aa991f69029585b5efd0638100f8fa6afaca108c15c879fe0926c42 |
| First seen | 2026-11-25 |
| Markets | China, France, India, Italy, United Kingdom |
Application program: KNX ON-OFF DIN CONTROLLER 8 outputs 16A 1.0
| Application number | $0A79 |
|---|---|
| Version | 1.0 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Parameters | 901 |
| Group objects | 203 |
Group objects (203)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | General | In operation | 1 Bit | CRT | |
| 1 | General | safety priority 1 | 1 Bit | CWU | |
| 2 | General | safety priority 2 | 1 Bit | CWU | |
| 3 | Output A | reply the switch status, A | 1 Bit | CR | |
| 3 | Output A | send the switch status, A | 1 Bit | CT | |
| 3 | Output A | Reply status of contact , A | 1 Bit | CR | |
| 4 | Output A | Switch, A | 1 Bit | CW | |
| 4 | Output A | on-off of regulating , A | 1 Bit | CW | |
| 5 | Output A | Switch out with delay, A | 1 Bit | CW | |
| 5 | Output A | Switch out with flashing, A | 1 Bit | CW | |
| 5 | Output A | Output of staircase lighting,A | 1 Bit | CW | |
| 5 | Output A | Status (continuous),1 bit , A | 1 Bit | CR | |
| 6 | Output A | Switch time function, A | 1 Bit | CW | |
| 7 | Output A | Warning of staircase , A | 1 Bit | CT | |
| 7 | Output A | report fault, regulating , A | 1 Bit | CRT | |
| 8 | Output A | Duration of staircase , A | 2 Bytes | CRW | |
| 9 | Output A | Call preset 1/2 , A | 1 Bit | CW | |
| 10 | Output A | Store preset 1/2, A | 1 Bit | CW | |
| 10 | Output A | Trigger switch regularly , A | 1 Bit | CW | |
| 11 | Output A | Input 1 of logic , A | 1 Bit | CW | |
| 12 | Output A | Input 2 of logic , A | 1 Bit | CW | |
| 13 | Output A | Scene handle, A | 1 Byte | CW | |
| 13 | Output A | Status (continuous),1 byte, A | 1 Byte | CR | |
| 14 | Output A | Change threshold 1, A | 1 Byte | CW | |
| 14 | Output A | continuous of regulating , A | 1 Byte | CW | |
| 15 | Output A | Threshold input , A | 1 Byte | CW | |
| 16 | Output A | Forced output , A | 1 Bit | CW | |
| 16 | Output A | forced operation,regulating, A | 1 Bit | CW | |
| 17 | Output B | reply the switch status, B | 1 Bit | CR | |
| 17 | Output B | send the switch status, B | 1 Bit | CT | |
| 17 | Output B | Reply status of contact , B | 1 Bit | CR | |
| 18 | Output B | Switch, B | 1 Bit | CW | |
| 18 | Output B | on-off of regulating , B | 1 Bit | CW | |
| 19 | Output B | Switch out with delay, B | 1 Bit | CW | |
| 19 | Output B | Output of staircase lighting,B | 1 Bit | CW | |
| 19 | Output B | Switch out with flashing, B | 1 Bit | CW | |
| 19 | Output B | Status (continuous),1 bit, B | 1 Bit | CR | |
| 20 | Output B | Switch time function, B | 1 Bit | CW | |
| 21 | Output B | Warning of staircase , B | 1 Bit | CT | |
| 21 | Output B | report fault, regulating , B | 1 Bit | CRT | |
| 22 | Output B | Duration of staircase , B | 2 Bytes | CRW | |
| 23 | Output B | Call preset 1/2 , B | 1 Bit | CW | |
| 24 | Output B | Store preset 1/2, B | 1 Bit | CW | |
| 24 | Output B | Trigger switch regularly , B | 1 Bit | CW | |
| 25 | Output B | Input 1 of logic , B | 1 Bit | CW | |
| 26 | Output B | Input 2 of logic , B | 1 Bit | CW | |
| 27 | Output B | Scene handle, B | 1 Byte | CW | |
| 27 | Output B | Status (continuous),1 byte, B | 1 Byte | CR | |
| 28 | Output B | Change threshold 1, B | 1 Byte | CW | |
| 28 | Output B | continuous of regulating , B | 1 Byte | CW | |
| 29 | Output B | Threshold input , B | 1 Byte | CW | |
| 30 | Output B | Forced output , B | 1 Bit | CW | |
| 30 | Output B | forced operation,regulating, B | 1 Bit | CW | |
| 31 | Output C | reply the switch status, C | 1 Bit | CR | |
| 31 | Output C | send the switch status, C | 1 Bit | CT | |
| 31 | Output C | Reply status of contact , C | 1 Bit | CR | |
| 32 | Output C | Switch, C | 1 Bit | CW | |
| 32 | Output C | on-off of regulating , C | 1 Bit | CW | |
| 33 | Output C | Switch out with delay, C | 1 Bit | CW | |
| 33 | Output C | Output of staircase lighting,C | 1 Bit | CW | |
| 33 | Output C | Switch out with flashing, C | 1 Bit | CW | |
| 33 | Output C | Status (continuous),1 bit , C | 1 Bit | CR | |
| 34 | Output C | Switch time function, C | 1 Bit | CW | |
| 35 | Output C | Warning of staircase , C | 1 Bit | CT | |
| 35 | Output C | report fault, regulating , C | 1 Bit | CRT | |
| 36 | Output C | Duration of staircase , C | 2 Bytes | CRW | |
| 37 | Output C | Call preset 1/2 , C | 1 Bit | CW | |
| 38 | Output C | Store preset 1/2, C | 1 Bit | CW | |
| 38 | Output C | Trigger switch regularly , C | 1 Bit | CW | |
| 39 | Output C | Input 1 of logic , C | 1 Bit | CW | |
| 40 | Output C | Input 2 of logic , C | 1 Bit | CW | |
| 41 | Output C | Scene handle, C | 1 Byte | CW | |
| 41 | Output C | Status (continuous),1 byte, C | 1 Byte | CR | |
| 42 | Output C | Change threshold 1, C | 1 Byte | CW | |
| 42 | Output C | continuous of regulating , C | 1 Byte | CW | |
| 43 | Output C | Threshold input , C | 1 Byte | CW | |
| 44 | Output C | Forced output , C | 1 Bit | CW | |
| 44 | Output C | forced operation,regulating, C | 1 Bit | CW | |
| 45 | Output D | reply the switch status, D | 1 Bit | CR | |
| 45 | Output D | send the switch status, D | 1 Bit | CT | |
| 45 | Output D | Reply status of contact , D | 1 Bit | CR | |
| 46 | Output D | Switch, D | 1 Bit | CW | |
| 46 | Output D | on-off of regulating , D | 1 Bit | CW | |
| 47 | Output D | Switch out with delay, D | 1 Bit | CW | |
| 47 | Output D | Output of staircase lighting,D | 1 Bit | CW | |
| 47 | Output D | Switch out with flashing, D | 1 Bit | CW | |
| 47 | Output D | Status (continuous),1 bit , D | 1 Bit | CR | |
| 48 | Output D | Switch time function, D | 1 Bit | CW | |
| 49 | Output D | Warning of staircase , D | 1 Bit | CT | |
| 49 | Output D | report fault, regulating , D | 1 Bit | CRT | |
| 50 | Output D | Duration of staircase , D | 2 Bytes | CRW | |
| 51 | Output D | Call preset 1/2 , D | 1 Bit | CW | |
| 52 | Output D | Store preset 1/2, D | 1 Bit | CW | |
| 52 | Output D | Trigger switch regularly , D | 1 Bit | CW | |
| 53 | Output D | Input 1 of logic , D | 1 Bit | CW | |
| 54 | Output D | Input 2 of logic , D | 1 Bit | CW | |
| 55 | Output D | Scene handle, D | 1 Byte | CW | |
| 55 | Output D | Status (continuous),1 byte, D | 1 Byte | CR | |
| 56 | Output D | Change threshold 1, D | 1 Byte | CW | |
| 56 | Output D | continuous of regulating , D | 1 Byte | CW | |
| 57 | Output D | Threshold input , D | 1 Byte | CW | |
| 58 | Output D | Forced output , D | 1 Bit | CW | |
| 58 | Output D | forced operation,regulating, D | 1 Bit | CW | |
| 59 | Output E | reply the switch status, E | 1 Bit | CR | |
| 59 | Output E | send the switch status, E | 1 Bit | CT | |
| 59 | Output E | Reply status of contact , E | 1 Bit | CR | |
| 60 | Output E | Switch, E | 1 Bit | CW | |
| 60 | Output E | on-off of regulating , E | 1 Bit | CW | |
| 61 | Output E | Switch out with delay, E | 1 Bit | CW | |
| 61 | Output E | Output of staircase lighting,E | 1 Bit | CW | |
| 61 | Output E | Switch out with flashing, E | 1 Bit | CW | |
| 61 | Output E | Status (continuous),1 bit , E | 1 Bit | CR | |
| 62 | Output E | Switch time function, E | 1 Bit | CW | |
| 63 | Output E | Warning of staircase , E | 1 Bit | CT | |
| 63 | Output E | report fault, regulating , E | 1 Bit | CRT | |
| 64 | Output E | Duration of staircase , D | 2 Bytes | CRW | |
| 65 | Output E | Call preset 1/2 , E | 1 Bit | CW | |
| 66 | Output E | Store preset 1/2, E | 1 Bit | CW | |
| 66 | Output E | Trigger switch regularly , E | 1 Bit | CW | |
| 67 | Output E | Input 1 of logic , E | 1 Bit | CW | |
| 68 | Output E | Input 2 of logic , E | 1 Bit | CW | |
| 69 | Output E | Scene handle, E | 1 Byte | CW | |
| 69 | Output E | Status (continuous),1 byte, E | 1 Byte | CR | |
| 70 | Output E | Change threshold 1, E | 1 Byte | CW | |
| 70 | Output E | continuous of regulating , E | 1 Byte | CW | |
| 71 | Output E | Threshold input , E | 1 Byte | CW | |
| 72 | Output E | Forced output , E | 1 Bit | CW | |
| 72 | Output E | forced operation,regulating, E | 1 Bit | CW | |
| 73 | Output F | reply the switch status, F | 1 Bit | CR | |
| 73 | Output F | send the switch status, F | 1 Bit | CT | |
| 73 | Output F | Reply status of contact , F | 1 Bit | CR | |
| 74 | Output F | Switch, F | 1 Bit | CW | |
| 74 | Output F | on-off of regulating , F | 1 Bit | CW | |
| 75 | Output F | Switch out with delay, F | 1 Bit | CW | |
| 75 | Output F | Output of staircase lighting,F | 1 Bit | CW | |
| 75 | Output F | Switch out with flashing, F | 1 Bit | CW | |
| 75 | Output F | Status (continuous),1 bit , F | 1 Bit | CR | |
| 76 | Output F | Switch time function, F | 1 Bit | CW | |
| 77 | Output F | Warning of staircase , F | 1 Bit | CT | |
| 77 | Output F | report fault, regulating , F | 1 Bit | CRT | |
| 78 | Output F | Duration of staircase , F | 2 Bytes | CRW | |
| 79 | Output F | Call preset 1/2 , F | 1 Bit | CW | |
| 80 | Output F | Store preset 1/2, F | 1 Bit | CW | |
| 80 | Output F | Trigger switch regularly , F | 1 Bit | CW | |
| 81 | Output F | Input 1 of logic , F | 1 Bit | CW | |
| 82 | Output F | Input 2 of logic , F | 1 Bit | CW | |
| 83 | Output F | Scene handle, F | 1 Byte | CW | |
| 83 | Output F | Status (continuous),1 byte, F | 1 Byte | CR | |
| 84 | Output F | Change threshold 1, F | 1 Byte | CW | |
| 84 | Output F | continuous of regulating , F | 1 Byte | CW | |
| 85 | Output F | Threshold input , F | 1 Byte | CW | |
| 86 | Output F | Forced output , F | 1 Bit | CW | |
| 86 | Output F | forced operation,regulating, F | 1 Bit | CW | |
| 87 | Output G | reply the switch status, G | 1 Bit | CR | |
| 87 | Output G | send the switch status, G | 1 Bit | CT | |
| 87 | Output G | Reply status of contact , G | 1 Bit | CR | |
| 88 | Output G | Switch, G | 1 Bit | CW | |
| 88 | Output G | on-off of regulating , G | 1 Bit | CW | |
| 89 | Output G | Switch out with delay, G | 1 Bit | CW | |
| 89 | Output G | Output of staircase lighting,G | 1 Bit | CW | |
| 89 | Output G | Switch out with flashing, G | 1 Bit | CW | |
| 89 | Output G | Status (continuous),1 bit , G | 1 Bit | CR | |
| 90 | Output G | Switch time function, G | 1 Bit | CW | |
| 91 | Output G | Warning of staircase , G | 1 Bit | CT | |
| 91 | Output G | report fault, regulating , G | 1 Bit | CRT | |
| 92 | Output G | Duration of staircase , G | 2 Bytes | CRW | |
| 93 | Output G | Call preset 1/2 , G | 1 Bit | CW | |
| 94 | Output G | Store preset 1/2, G | 1 Bit | CW | |
| 94 | Output G | Trigger switch regularly , G | 1 Bit | CW | |
| 95 | Output G | Input 1 of logic , G | 1 Bit | CW | |
| 96 | Output G | Input 2 of logic , G | 1 Bit | CW | |
| 97 | Output G | Scene handle, G | 1 Byte | CW | |
| 97 | Output G | Status (continuous),1 byte, G | 1 Byte | CR | |
| 98 | Output G | Change threshold 1, G | 1 Byte | CW | |
| 98 | Output G | continuous of regulating , G | 1 Byte | CW | |
| 99 | Output G | Threshold input , G | 1 Byte | CW | |
| 100 | Output G | Forced output , G | 1 Bit | CW | |
| 100 | Output G | forced operation,regulating, G | 1 Bit | CW | |
| 101 | Output H | reply the switch status, H | 1 Bit | CR | |
| 101 | Output H | send the switch status, H | 1 Bit | CT | |
| 101 | Output H | Reply status of contact , H | 1 Bit | CR | |
| 102 | Output H | Switch, H | 1 Bit | CW | |
| 102 | Output H | on-off of regulating , H | 1 Bit | CW | |
| 103 | Output H | Switch out with delay, H | 1 Bit | CW | |
| 103 | Output H | Output of staircase lighting,H | 1 Bit | CW | |
| 103 | Output H | Switch out with flashing, H | 1 Bit | CW | |
| 103 | Output H | Status (continuous),1 bit , H | 1 Bit | CR | |
| 104 | Output H | Switch time function, H | 1 Bit | CW | |
| 105 | Output H | Warning of staircase , H | 1 Bit | CT | |
| 105 | Output H | report fault, regulating , H | 1 Bit | CRT | |
| 106 | Output H | Duration of staircase , H | 2 Bytes | CRW | |
| 107 | Output H | Call preset 1/2 , H | 1 Bit | CW | |
| 108 | Output H | Store preset 1/2, H | 1 Bit | CW | |
| 108 | Output H | Trigger switch regularly , H | 1 Bit | CW | |
| 109 | Output H | Input 1 of logic , H | 1 Bit | CW | |
| 110 | Output H | Input 2 of logic , H | 1 Bit | CW | |
| 111 | Output H | Scene handle, H | 1 Byte | CW | |
| 111 | Output H | Status (continuous),1 byte, H | 1 Byte | CR | |
| 112 | Output H | Change threshold 1, H | 1 Byte | CW | |
| 112 | Output H | continuous of regulating , H | 1 Byte | CW | |
| 113 | Output H | Threshold input , H | 1 Byte | CW | |
| 114 | Output H | Forced output , H | 1 Bit | CW | |
| 114 | Output H | forced operation,regulating, H | 1 Bit | CW |
Parameters (112)
| Parameter | Type | Default |
|---|---|---|
| Operation delay after recovery of bus voltage(1...250s) | unsignedInt 1…250 | 1 |
| Sending cycle of "In operation" telegram (1......240s , 0=inactive) | unsignedInt 0…240 | 0 |
| Enable safety priority function | list | disable |
| ---set safety priority 1: | list | inactive |
| Control period of safety priority 1 (1......240 s, 0=inactive) | unsignedInt 0…240 | 0 |
| ---set safety priority 2: | list | inactive |
| Control period of safety priority 2 (1......240 s, 0=inactive) | unsignedInt 0…240 | 0 |
| ¡¡¡¡=====N o t e===== Normal, object value map switch on/off | list | "1"=switch on; "0"=switch off |
| Channel A work mode is | list | Switch actuator |
| If bus voltage recovery,contact is | list | unchange |
| If bus voltage fail,contact is | list | unchange |
| Object value of "telegram switch" after bus voltage recovery | list | not write |
| Set the reply mode of switch status for channel A | list | no reply |
| Object value of switch status : | list | 0=contact open ; 1=contact close |
| Contact position if tele. value is "1" ("0" is opposite of "1" if changed) | list | close |
| Special functions of switch actuator mode for channel A is | list | inactive |
| Function of "time" for switch is | list | disable |
| Function of "preset" for switch is | list | disable |
| Function of "logic" for switch is | list | disable |
| Function of "scene" for switch is | list | disable |
| Function of "threshold" for switch is | list | disable |
| Function of "safety" for switch is | list | disable |
| Function of "forced" for switch is | list | disable |
| The mode of time function | list | delay switch |
| Delay for switch on : --(0...240 minutes) | unsignedInt 0…240 | 0 |
| --(0...59 seconds) | unsignedInt 0…59 | 0 |
| Delay for switch off : --(0...240 minutes) | unsignedInt 0…240 | 0 |
| Number of ON-impulses (1...255 , 0=no limited) | unsignedInt 0…255 | 0 |
| Contact position after flashing | list | unchange |
| The mode of control for flashing | list | Start with "1" , Stop with "0" |
| Duration of staircase lighting --(0...1000 minutes) | unsignedInt 0…1000 | 2 |
| The mode of control for staircase lighting is | list | Start with "0/1" , can not be stop |
| During the lighting time, if receive the "Start" telegram, | list | restart duration of staircase lighting |
| Warning mode for ending of staircase lighting | list | nothing |
| --The warning time for end of staircase lighting(0...59 s) | unsignedInt 0…59 | 0 |
| Modify the duration via object (0...60059 seconds) | list | disable |
| Action for preset 1(object value=0) | list | None |
| Action for preset 2(object value=1) | list | OFF |
| Setting for preset via telegram is | list | disable |
| The input 0 (switch object) for logic is | list | disable |
| The input 1 of logic is | list | disable |
| Function type between input0 and input1 | list | AND |
| Result is inverted | list | NO |
| Value of input 1 after bus voltage recovery : | list | "0" |
| The input 2 of logic is | list | disable |
| Function type between input2 and input0/1 | list | AND |
| Value of input 2 after bus voltage recovery : | list | "0" |
| 1> channel is assigned to (1...64 scene NO.,0= no allocation) | unsignedInt 0…64 | 0 |
| --Standard output value is | list | OFF |
| 2> channel is assigned to (1...64 scene NO.,0= no allocation) | unsignedInt 0…64 | 0 |
| 3> channel is assigned to (1...64 scene NO.,0= no allocation) | unsignedInt 0…64 | 0 |
| 4> channel is assigned to (1...64 scene NO.,0= no allocation) | unsignedInt 0…64 | 0 |
| 5> channel is assigned to (1...64 scene NO.,0= no allocation) | unsignedInt 0…64 | 0 |
| Threshold 1 value | unsignedInt 0…255 | 80 |
| Threshold 2 value | unsignedInt 0…255 | 200 |
| Change threshold 1via object : | list | disable |
| Threshold behaviour | list | without hysteresis |
| --If falling below lower threshold, contact position | list | unchange |
| --If exceeding upper threshold, contact position | list | unchange |
| --If lower < object value < upper contact position | list | unchange |
| Setting of safety | list | on parameter-window "General" |
| Contact position if safety priority 1 | list | unchange |
| Contact position if safety priority 2 | list | unchange |
| Contact position if forced operation | list | unchange |
| If bus voltage fail ,contact is | list | unchange |
| If bus voltage recovery, the duty cycle of dynamic regulate | list | 0%(OFF) |
| PWM cycle time for continuous control (1...240 minutes) | unsignedInt 0…240 | 3 |
| PWM cycle time for continuous control (0...59 seconds | unsignedInt 0…59 | 0 |
| Control telegram is received as | list | 1 bit ( on-off control ) |
| Reply the status of channel for continuous control | list | nothing |
| Reply the status of contact state | list | nothing |
| Special functions of dynamic regulating actuator mode for channel A is | list | inactive |
| Function for monitoring is | list | disable |
| Function of forced operation is | list | disable |
| Function of regular switch is | list | disable |
| Function of safety operation is | list | disable |
| Cyclic monitoring --in minutes (0...240 minutes) | unsignedInt 0…240 | 60 |
| --in seconds (0...59 seconds) | unsignedInt 0…59 | 0 |
| The duty cycle of dynamic regulating during fault | list | unchange |
| sending object "report fault" is | list | disable |
| The duty cycle of dynamic regulating during forced operation | list | unchange |
| Time of switch regular in minutes (0..255) | unsignedInt 0…255 | 10 |
| Automatic switch regularly | list | disable |
| The duty cycle of dynamic regulating during safety 1 operation | list | unchange |
| The duty cycle of dynamic regulating during safety 2 operation | list | unchange |
| Channel B work mode is | list | Switch actuator |
| Set the reply mode of switch status for channel B | list | no reply |
| Special functions of switch actuator mode for channel B is | list | inactive |
| Special functions of dynamic regulating actuator mode for channel B is | list | inactive |
| Channel C work mode is | list | Switch actuator |
| Set the reply mode of switch status for channel C | list | no reply |
| Special functions of switch actuator mode for channel C is | list | inactive |
| Special functions of dynamic regulating actuator mode for channel C is | list | inactive |
| Channel D work mode is | list | Switch actuator |
| Set the reply mode of switch status for channel D | list | no reply |
| Special functions of switch actuator mode for channel D is | list | inactive |
| Special functions of dynamic regulating actuator mode for channel D is | list | inactive |
| Channel E work mode is | list | Switch actuator |
| Set the reply mode of switch status for channel E | list | no reply |
| Special functions of switch actuator mode for channel E is | list | inactive |
| Special functions of dynamic regulating actuator mode for channel E is | list | inactive |
| Channel F work mode is | list | Switch actuator |
| Set the reply mode of switch status for channel F | list | no reply |
| Special functions of switch actuator mode for channel F is | list | inactive |
| Special functions of dynamic regulating actuator mode for channel F is | list | inactive |
| Channel G work mode is | list | Switch actuator |
| Set the reply mode of switch status for channel G | list | no reply |
| Special functions of switch actuator mode for channel G is | list | inactive |
| Special functions of dynamic regulating actuator mode for channel G is | list | inactive |
| Channel H work mode is | list | Switch actuator |
| Special functions of switch actuator mode for channel H is | list | inactive |
| Special functions of dynamic regulating actuator mode for channel H is | list | inactive |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| KNX ON-OFF DIN CONTROLLER 8 outputs 16A 1.0 latest | $0A79 | 9C75 | 2026-11-25 | 128 KB | Download |
About this file
This is the official ETS product database for the LEGRAND Appareillage électrique KNX ON-OFF DIN CONTROLLER 8 outputs 16A (002681), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from LEGRAND Appareillage électrique
- LG-002668 Dimmer 0000002668
- DALI GATEWAY 002635
- LG-002665 DALI-Gateway 8-Sensor Slot, Emergency Light 002665
- KNX ON-OFF DIN CONTROLLER 4 outputs 16A 002680
- KNX ON-OFF DIN CONTROLLER 12 outputs 16A 002682
- KNX DIN universal dimmer 2 outputs, 500W/CH 002686
- KNX DIN universal dimmer 4 outputs, 400W/CH 002687
- LG-002699 DALI-Gateway Individual Control/2.0 002699
- KNX 0-10V Fan coil Actuator 002890
- FCU actuators 0-10V 049041
- Room Thermostat 0 490 31 0 490 31
- IP-Router 002638