Interra ITR830-0014 ITR830-0014 Toshiba VRF AC-KNX Gateway

ITR830-0014 Toshiba VRF AC-KNX Gateway ITR830-0014

Interra · Order number ITR830-0014 · Gateway

Download .knxprod ITR830-0014 Toshiba VRF AC-KNX Gateway 1.0 · 141 KB

Product

ManufacturerInterra
Product nameITR830-0014 Toshiba VRF AC-KNX Gateway
Order numberITR830-0014
Product textToshiba VRF AC KNX Gateway
HardwareITR830-0014 Toshiba VRF AC-KNX Gateway
MediumTwisted Pair
Bus current (mA)5
Rail mountedNo
RegistrationCertified · 2024-02-20
Languagesen-US
Catalog entryM-0107_H-ITR830.2D0014-1_HP-034C-10-3835_CI-ITR830.2D0014-1
Fingerprint3835
SHA-256ac876ac73fd01dc8bb4f2a6b8ea30a377ff569aa6306655f8b0c5e6b9b4bb898
First seen2026-11-25
Markets59 markets

Application program: ITR830-0014 Toshiba VRF AC-KNX Gateway 1.0

Application number$034C
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters317
Group objects177
Group objects (177)
NoNameFunctionSizeDPTFlags
1Alive beaconAlive beacon1 Bit1.2 booleanCT
2Logic 1 - Input 1Logic Input1 Bit1.2 booleanCRW
3Logic 1 - Input 2Logic Input1 Bit1.2 booleanCRW
4Logic 1 - Input 3Logic Input1 Bit1.2 booleanCRW
5Logic 1 - Input 4Logic Input1 Bit1.2 booleanCRW
6Logic 1 - OutputLogic Output1 Bit1.2 booleanCRT
7Logic 2 - Input 1Logic Input1 Bit1.2 booleanCRW
8Logic 2 - Input 2Logic Input1 Bit1.2 booleanCRW
9Logic 2 - Input 3Logic Input1 Bit1.2 booleanCRW
10Logic 2 - Input 4Logic Input1 Bit1.2 booleanCRW
11Logic 2 - OutputLogic Output1 Bit1.2 booleanCRT
12Logic 3 - Input 1Logic Input1 Bit1.2 booleanCRW
13Logic 3 - Input 2Logic Input1 Bit1.2 booleanCRW
14Logic 3 - Input 3Logic Input1 Bit1.2 booleanCRW
15Logic 3 - Input 4Logic Input1 Bit1.2 booleanCRW
16Logic 3 - OutputLogic Output1 Bit1.2 booleanCRT
17Logic 4 - Input 1Logic Input1 Bit1.2 booleanCRW
18Logic 4 - Input 2Logic Input1 Bit1.2 booleanCRW
19Logic 4 - Input 3Logic Input1 Bit1.2 booleanCRW
20Logic 4 - Input 4Logic Input1 Bit1.2 booleanCRW
21Logic 4 - OutputLogic Output1 Bit1.2 booleanCRT
22Converter 1 - Input (1 Bit)Converter Input1 Bit1.6 binary valueCRW
23Converter 1 - Input (2 Bits)Converter Input2 Bit2.6 binary value controlCRW
24Converter 1 - Input (1 Byte)Converter Input1 Byte5.10 counter pulses (0..255)CRW
25Converter 1 - Input (2 Bytes)Converter Input2 Bytes7.1 pulsesCRW
26Converter 1 - Output (1 Bit)Converter Output1 Bit1.6 binary valueCRWT
27Converter 1 - Output (2 Bits)Converter Output2 Bit2.6 binary value controlCRWT
28Converter 1 - Output (1 Byte)Converter Output1 Byte5.10 counter pulses (0..255)CRWT
29Converter 1 - Output (2 Bytes)Converter Output2 Bytes7.1 pulsesCRWT
30Converter 2 - Input (1 Bit)Converter Input1 Bit1.6 binary valueCRW
31Converter 2 - Input (2 Bits)Converter Input2 Bit2.6 binary value controlCRW
32Converter 2 - Input (1 Byte)Converter Input1 Byte5.10 counter pulses (0..255)CRW
33Converter 2 - Input (2 Bytes)Converter Input2 Bytes7.1 pulsesCRW
34Converter 2 - Output (1 Bit)Converter Output1 Bit1.6 binary valueCRWT
35Converter 2 - Output (2 Bits)Converter Output2 Bit2.6 binary value controlCRWT
36Converter 2 - Output (1 Byte)Converter Output1 Byte5.10 counter pulses (0..255)CRWT
37Converter 2 - Output (2 Bytes)Converter Output2 Bytes7.1 pulsesCRWT
38Converter 3 - Input (1 Bit)Converter Input1 Bit1.6 binary valueCRW
39Converter 3 - Input (2 Bits)Converter Input2 Bit2.6 binary value controlCRW
40Converter 3 - Input (1 Byte)Converter Input1 Byte5.10 counter pulses (0..255)CRW
41Converter 3 - Input (2 Bytes)Converter Input2 Bytes7.1 pulsesCRW
42Converter 3 - Output (1 Bit)Converter Output1 Bit1.6 binary valueCRWT
43Converter 3 - Output (2 Bits)Converter Output2 Bit2.6 binary value controlCRWT
44Converter 3 - Output (1 Byte)Converter Output1 Byte5.10 counter pulses (0..255)CRWT
45Converter 3 - Output (2 Bytes)Converter Output2 Bytes7.1 pulsesCRWT
46Converter 4 - Input (1 Bit)Converter Input1 Bit1.6 binary valueCRW
47Converter 4 - Input (2 Bits)Converter Input2 Bit2.6 binary value controlCRW
48Converter 4 - Input (1 Byte)Converter Input1 Byte5.10 counter pulses (0..255)CRW
49Converter 4 - Input (2 Bytes)Converter Input2 Bytes7.1 pulsesCRW
50Converter 4 - Output (1 Bit)Converter Output1 Bit1.6 binary valueCRWT
51Converter 4 - Output (2 Bits)Converter Output2 Bit2.6 binary value controlCRWT
52Converter 4 - Output (1 Byte)Converter Output1 Byte5.10 counter pulses (0..255)CRWT
53Converter 4 - Output (2 Bytes)Converter Output2 Bytes7.1 pulsesCRWT
54Converter 5 - Input (1 Bit)Converter Input1 Bit1.6 binary valueCRW
55Converter 5 - Input (2 Bits)Converter Input2 Bit2.6 binary value controlCRW
56Converter 5 - Input (1 Byte)Converter Input1 Byte5.10 counter pulses (0..255)CRW
57Converter 5 - Input (2 Bytes)Converter Input2 Bytes7.1 pulsesCRW
58Converter 5 - Output (1 Bit)Converter Output1 Bit1.6 binary valueCRWT
59Converter 5 - Output (2 Bits)Converter Output2 Bit2.6 binary value controlCRWT
60Converter 5 - Output (1 Byte)Converter Output1 Byte5.10 counter pulses (0..255)CRWT
61Converter 5 - Output (2 Bytes)Converter Output2 Bytes7.1 pulsesCRWT
62Converter 6 - Input (1 Bit)Converter Input1 Bit1.6 binary valueCRW
63Converter 6 - Input (2 Bits)Converter Input2 Bit2.6 binary value controlCRW
64Converter 6 - Input (1 Byte)Converter Input1 Byte5.10 counter pulses (0..255)CRW
65Converter 6 - Input (2 Bytes)Converter Input2 Bytes7.1 pulsesCRW
66Converter 6 - Output (1 Bit)Converter Output1 Bit1.6 binary valueCRWT
67Converter 6 - Output (2 Bits)Converter Output2 Bit2.6 binary value controlCRWT
68Converter 6 - Output (1 Byte)Converter Output1 Byte5.10 counter pulses (0..255)CRWT
69Converter 6 - Output (2 Bytes)Converter Output2 Bytes7.1 pulsesCRWT
70Converter 7 - Input (1 Bit)Converter Input1 Bit1.6 binary valueCRW
71Converter 7 - Input (2 Bits)Converter Input2 Bit2.6 binary value controlCRW
72Converter 7 - Input (1 Byte)Converter Input1 Byte5.10 counter pulses (0..255)CRW
73Converter 7 - Input (2 Bytes)Converter Input2 Bytes7.1 pulsesCRW
74Converter 7 - Output (1 Bit)Converter Output1 Bit1.6 binary valueCRWT
75Converter 7 - Output (2 Bits)Converter Output2 Bit2.6 binary value controlCRWT
76Converter 7 - Output (1 Byte)Converter Output1 Byte5.10 counter pulses (0..255)CRWT
77Converter 7 - Output (2 Bytes)Converter Output2 Bytes7.1 pulsesCRWT
78Converter 8 - Input (1 Bit)Converter Input1 Bit1.6 binary valueCRW
79Converter 8 - Input (2 Bits)Converter Input2 Bit2.6 binary value controlCRW
80Converter 8 - Input (1 Byte)Converter Input1 Byte5.10 counter pulses (0..255)CRW
81Converter 8 - Input (2 Bytes)Converter Input2 Bytes7.1 pulsesCRW
82Converter 8 - Output (1 Bit)Converter Output1 Bit1.6 binary valueCRWT
83Converter 8 - Output (2 Bits)Converter Output2 Bit2.6 binary value controlCRWT
84Converter 8 - Output (1 Byte)Converter Output1 Byte5.10 counter pulses (0..255)CRWT
85Converter 8 - Output (2 Bytes)Converter Output2 Bytes7.1 pulsesCRWT
86On Off0-Off ;1-On1 Bit1.1 switchCW
87OnOff_Feedback0-Off;1-On1 Bit1.1 switchCRT
88Operating Mode0-Auto;1-Heat;3-Cool;9-Fan;14-Dry1 Byte20.105 HVAC control modeCW
89Operating_Mode_Feedback0-Auto;1-Heat;3-Cool;9-Fan;14-Dry1 Byte20.105 HVAC control modeCRT
90Mode Cool/Heat0-Cool;1-Heat1 Bit1.100 cooling/heatingCW
90Mode Heat/Cool0-Heat;1-Cool1 Bit1.100 cooling/heatingCW
91Mode Cool/Heat Feedback0-Cool;1-Heat1 Bit1.100 cooling/heatingCRT
91Mode Heat/Cool Feedback0-Heat;1-Cool1 Bit1.100 cooling/heatingCRT
92Mode Heating Percentage0%-Off;1%-100%-On+Heat1 Byte5.1 percentage (0..100%)CW
93Mode Cooling Percentage0%-Off;1%-100%-On+Cool1 Byte5.1 percentage (0..100%)CW
94Mode Auto1-Set AUTO mode1 Bit1.2 booleanCW
95Mode Auto Feedback1-AUTO mode1 Bit1.2 booleanCRT
96Mode Heat1-Set HEAT mode1 Bit1.2 booleanCW
97Mode Heat Feedback1-HEAT mode1 Bit1.2 booleanCRT
98Mode Cool1-Set COOL mode1 Bit1.2 booleanCW
99Mode Cool Feedback1-COOL mode1 Bit1.2 booleanCRT
100Mode Fan1-Set FAN mode1 Bit1.2 booleanCW
101Mode Fan Feedback1-FAN mode1 Bit1.2 booleanCRT
102Mode Dry1-Set DRY mode1 Bit1.2 booleanCW
103Mode Dry Feedback1-DRY mode1 Bit1.2 booleanCRT
104Mode +/-0-Decrease;1-Increase1 Bit1.7 stepCW
104Mode +/-0-Up;1-Down1 Bit1.8 up/downCW
105Operating Mode Text FeedbackText Feedback14 Bytes16.1 Character String (ISO 8859-1)CRT
106Fan Speed ScalingThreshold Defined in Parameter1 Byte5.1 percentage (0..100%)CW
106Fan Speed Enumerated0-Auto;1-Speed1;...5-Speed5;1 Byte5.100 fan stage (0..255)CW
107Fan Speed Scaling Feedback% Percentage value 1 Byte5.1 percentage (0..100%)CRT
107Fan Speed Enumerated Feedback0-Auto;1-Speed1;...5-Speed5;1 Byte5.100 fan stage (0..255)CRT
108Fan Speed 1 Control1-Set Fan Speed 11 Bit1.2 booleanCW
109Fan Speed 1 Feedback1-Fan Speed 11 Bit1.2 booleanCRT
110Fan Speed 2 Control1-Set Fan Speed 21 Bit1.2 booleanCW
111Fan Speed 2 Feedback1-Fan Speed 21 Bit1.2 booleanCRT
112Fan Speed 3 Control1-Set Fan Speed 31 Bit1.2 booleanCW
113Fan Speed 3 Feedback1-Fan Speed 31 Bit1.2 booleanCRT
114Fan Speed 4 Control1-Set Fan Speed 41 Bit1.2 booleanCW
115Fan Speed 4 Feedback1-Fan Speed 41 Bit1.2 booleanCRT
116Fan Speed 5 Control1-Set Fan Speed 51 Bit1.2 booleanCW
117Fan Speed 5 Feedback1-Fan Speed 51 Bit1.2 booleanCRT
118Fan Speed Auto Control1-Set Fan Speed Auto1 Bit1.2 booleanCW
119Fan Speed Auto Feedback1-Fan Speed Auto1 Bit1.2 booleanCRT
120Fan Speed +/-0-Decrease;1-Increase1 Bit1.7 stepCW
120Fan Speed +/-0-Up;1-Down1 Bit1.8 up/downCW
121Fan Speed Text FeedbackFan Speed Text14 Bytes16.1 Character String (ISO 8859-1)CRT
122Setpoint Temperature Control°C2 Bytes9.1 temperature (°C)CW
123Setpoint Temperature Feedback°C2 Bytes9.1 temperature (°C)CRT
124Setpoint Temperature +/-0-Decrease;1-Increase1 Bit1.7 stepCW
124Setpoint Temperature +/-0-Up;1-Down1 Bit1.8 up/downCW
125Ambient Temperature°C2 Bytes9.1 temperature (°C)CW
126Ambient Temperature Feedback°C2 Bytes9.1 temperature (°C)CRT
127Air Deflector Broadcast Value0-Swing;1-Pos1;...5-Pos51 ByteCW
128Air Deflector +/-0-Decrease;1-Increase1 Bit1.7 stepCW
128Air Deflector +/-0-Up;1-Down1 Bit1.8 up/downCW
129Air Deflector Feedback0-Swing;1-Pos1;...5-Pos51 ByteCRT
130Window Contact Status0-Opened;1-Closed1 Bit1.9 open/closeCRWT
130Window Contact Status0-Closed;1-Opened1 Bit1.19 window/doorCRWT
131Window Contact Off DelayValues are accepted according to the data type of 20.0131 Byte20.13 time delayCW
132Standby 1 Function0-Stop;1-Start1 Bit1.10 start/stopCW
132Standby 1 Function0-Not occupied;1-Occupied1 Bit1.18 occupancyCW
133Standby 1 Feedback0-Stop;1-Start1 Bit1.10 start/stopCRT
133Standby 1 Feedback0-Not occupied;1-Occupied1 Bit1.18 occupancyCRT
134Standby 1 DelayValues are accepted according to the data type of 20.0131 Byte20.13 time delayCW
135Standby 1 Setpoint Shifting°C2 Bytes9.1 temperature (°C)CW
136Standby 2 Function0-Not occupied;1-Occupied1 Bit1.18 occupancyCW
136Standby 2 Function0-Stop;1-Start1 Bit1.10 start/stopCW
137Standby 2 Feedback0-Not occupied;1-Occupied1 Bit1.18 occupancyCRT
137Standby 2 Feedback0-Stop;1-Start1 Bit1.10 start/stopCRT
138Standby 2 DelayValues are accepted according to the data type of 20.0131 Byte20.13 time delayCW
139Standby 2 Setpoint Shifting°C2 Bytes9.1 temperature (°C)CW
140Timer State0-Start;1-Stop1 Bit1.10 start/stopCW
140Timer State0-Stop;1-Start1 Bit1.10 start/stopCW
141Timer State Feedback0-Stop;1-Start1 Bit1.10 start/stopCRT
141Timer State Feedback0-Start;1-Stop1 Bit1.10 start/stopCRT
142Timer DurationValues are accepted according to the data type of 20.0131 Byte20.13 time delayCW
143Scene0-63 (Execute 1-64); 128-191 (Storage 1-64)1 Byte18.1 scene controlCRWTU
144Scene 1 Run0-Nothing;1-Run Scene1 Bit1.2 booleanCWT
145Scene 1 Storage0-Nothing;1-Storage Scene1 Bit1.2 booleanCWT
146Scene 2 Run0-Nothing;1-Run Scene1 Bit1.2 booleanCWT
147Scene 2 Storage0-Nothing;1-Storage Scene1 Bit1.2 booleanCWT
148Scene 3 Run0-Nothing;1-Run Scene1 Bit1.2 booleanCWT
149Scene 3 Storage0-Nothing;1-Storage Scene1 Bit1.2 booleanCWT
150Scene 4 Run0-Nothing;1-Run Scene1 Bit1.2 booleanCWT
151Scene 4 Storage0-Nothing;1-Storage Scene1 Bit1.2 booleanCWT
152Scene 5 Run0-Nothing;1-Run Scene1 Bit1.2 booleanCWT
153Scene 5 Storage0-Nothing;1-Storage Scene1 Bit1.2 booleanCWT
154Current Scene Feedback1-64:Current Scene1 Byte17.1 scene numberCRT
155Device Control Locking0-Disable;1-Enable1 Bit1.3 enableCW
155Device Control Locking0-Enable;1-Disable1 Bit1.3 enableCW
156Error Alarm Feedback0-No Alarm;1-Alarm1 Bit1.5 alarmCRT
157Error Code FeedbackError Code Information2 BytesCRT
158Error Code Text FeedbackError Text Information14 Bytes16.1 Character String (ISO 8859-1)CRT
159Working Hour Counter FeedbackWorking Hours Counter Feedback4 Bytes13.100 time lag (s)CRT
160Working Hour Alert Feedback0-No Alarm;1-Alarm1 Bit1.5 alarmCRT
161Reset Hours Counter0-No Action;1-Reset1 Bit1.15 resetCW
Parameters (125)
ParameterTypeDefault
Alive beacon statelistDisable
Alive beacon output logic statelistvalue '1'
Alive beacon intervaltime5
Behavior after bus voltage failurelistNo Reaction
Scene selectionlistScene 1
AC feedbacks time delay at startuptime10
Number of logic gateslistNo Logic Gate
TypelistAND
Send status onlistInput Triggered
Number of inputslist1 Input
Output behaviorlistNormal
Switch on delaytime0
Switch off delaytime0
Send feedback periodicallytime1
Switch on delaytime10
Switch off delaytime10
Number of ConverterslistNo Converter
Input typelist1 Bit
Logical OperatorslistDisable
Priority to "Operating mode Heat/Cool"listDisable
Text feedback for mode HEAT ->textHEAT
Text feedback for mode COOL ->textCOOL
Text feedback for mode FAN ->textFAN
Text feedback for mode DRY ->textDRY
Include AUTO fan mode in the sequencelistNo
Loop the sequencelistNo
Fan speed 1 lower limit (%)unsignedInt 0…2550
Fan speed 2 lower limit (%)unsignedInt 0…25516
Fan speed 3 lower limit (%)unsignedInt 0…25532
Fan speed 4 lower limit (%)unsignedInt 0…25548
Fan speed 5 lower limit (%)unsignedInt 0…25564
Text feedback for mode Fan Speed 1->textFAN SPEED 1
Text feedback for mode Fan Speed 2->textFAN SPEED 2
Text feedback for mode Fan Speed 3->textFAN SPEED 3
Text feedback for mode Fan Speed 4->textFAN SPEED 4
Text feedback for mode Fan Speed 5->textFAN SPEED 5
Include 'SWING' mode in the sequencelistNo
Feedback sending periodtime30
Setpoint temperature limit controllistDisable
Setpoint temperature lower limitunsignedInt 18…2518
Setpoint temperature higher limitunsignedInt 20…2929
NumberunsignedInt 1…641
Ac On/OfflistAC Off
Ac modelistFan
Ac fan speedlistAuto
Ac setpoint temperature (°C)unsignedInt 18…2920
Delaytime5
Setpoint for alerttime1
Switch-off time delaytime1
Reject AC On/Off actions if window is openlistDisable
Behavior after window is closed.listNo Reaction
Standby function delaytime1
Setpoint temperature shifting (°C)unsignedInt 0…50
Reject modifications during standbylistDisable
Behavior after standby functionlistNo Reaction
Setpoint temperature shifting statelistDisable
Timer durationtime60
Timer retriggablelistNo
Input valueunsignedInt 0…2550
Input valueunsignedInt 0…655350
Standby function scenelistScene 1
After window is closed scenelistScene 1
Input valueunsignedInt 0…10
Input valueunsignedInt 0…30
Lower limitunsignedInt 0…25525
Lower limitunsignedInt 0…6553525
Output valueunsignedInt 0…10
Output valueunsignedInt 0…30
Output valueunsignedInt 0…2550
Output valueunsignedInt 0…655350
Upper limitunsignedInt 0…25575
Upper limitunsignedInt 0…6553575
Output typelist1 Byte
Output typelist1 Bit
Cyclic send statelistDisable
Cyclic Send StatelistDisable
Ambient temperature referencelistAC indoor sensor temp
Calculation valueunsignedInt 0…2550
Calculation valueunsignedInt 0…655350
AC feedbacks send statelistDisable
AC feedback periodicallyunsignedInt 0…2550
Text feedback for mode Fan Auto->textFAN AUTO
Error Code (1 Bit)listDisable
Error Code (2 Bytes)listDisable
Error code (14 Chars)listDisable
Operating mode HVAC objectlistDisable
Feedback operating mode objects (1 Byte)listDisable
Operating mode Heat/Cool objectlistDisable
Operating mode percentage value objectslistDisable
Operating mode individual objectslistDisable
Feedback operating mode individual (1 Bit)listDisable
Operating mode +/- objectlistDisable
Feedback operating mode objects (14 Chars)listDisable
Fan level control & feedback objects (1 Byte)listDisable
Fan level control individual objectslistDisable
Feedback fan speed level individual (1 Bit)listDisable
Fan level control +/- objectlistDisable
Feedback fan speed text object (14 chars)listDisable
Setpoint temperature feedback send statelistDisable
Setpoint temperature +/- objectlistDisable
Enable ambient temperaturelistNo
Ambient temperature feedback send statelistPeriodically
Ambient temperature referencelistKNX bus
Air deflector controllistDisable
Air deflector control +/- objectlistDisable
Air deflector feedbacklistDisable
Device control lockinglistDisable
SCENE 1listDisable
Activation objectlistDisable
Storage functionlistDisable
SCENE 2listDisable
SCENE 3listDisable
SCENE 4listDisable
SCENE 5listDisable
Working hours counterlistDisable
Enable window contactlistDisable
Switch-off time delay statelistDisable
Enable standby functionlistDisable
Standby function delay statelistDisable
Behavior during standby functionlistSetpoint Temp Shift
Enable timer functionlistStop
PolaritylistNormal
Timer duration statelistVia parameter
Gateway's communication role on communication portlistMaster
Text feedback for mode AUTO ->textAUTO

Version history

ApplicationApp noFingerprintFirst seenSizeFile
ITR830-0014 Toshiba VRF AC-KNX Gateway 1.0 latest$034C38352026-11-25141 KBDownload

About this file

This is the official ETS product database for the Interra ITR830-0014 Toshiba VRF AC-KNX Gateway (ITR830-0014), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Interra