Product

ManufacturerHoneywell Building Technologies
Product nameHoneywell MK Switch/Shutter/FCU 8CH 16A
Order numberKNX SW 0816
Hardware8 output Switch Actuator | Shutter Blinds
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)107
RegistrationCertified · 2022-09-06
Languagesde-DE, en, pt-PT, tr-TR
Catalog entryM-027D_H-KNXSW0816-18-O0111_HP-1330-12-2C00-O0111_CI-KNX.20SW.200816-1
Fingerprint2C00
SHA-256bc9ad83ae200cdd996e3ebd86f39d65c3f585ac888ae85d9056780201498b137
First seen2026-11-25
Markets24 markets

Application program: KNX Switch/Shutter/FCU 8CH 16A 1.2

Application number$1330
Version1.2
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters1938
Group objects253
Group objects (253)
NoNameFunctionSizeDPTFlags
0Lights 1On / Off1 Bit1.1 switchCW
0Shutter/Blinds 1-2Move Up / Down1 Bit1.8 up/downCW
0FCU H/C 1Heating/Cooling1 Bit1.100 heating/coolingCW
1Lights 1Start / Stop Timer1 Bit1.10 start/stopCW
1Shutter/Blinds 1-2Wind Alarm1 Bit1.2 booleanCW
1FCU H/C 1Heating Valve1 Bit1.1 switchCW
2Lights 1Priority On / Off2 Bit2.1 switch controlCW
2Shutter/Blinds 1-2Priority Close / Open2 Bit2.1 switch controlCW
3Lights 1Scene Control1 Byte18.1 scene controlCW
3Shutter/Blinds 1-2Scene Control1 Byte18.1 scene controlCW
4Lights 1Time Limited Toggle Switch1 Bit1.1 switchCW
4Shutter/Blinds 1-2Stop Up / Down1 Bit1.8 up/downCW
4Shutter/Blinds 1-2Slat Angle | Stop Up / Down1 Bit1.8 up/downCW
5Shutter/Blinds 1-2Shutter Position (%)1 Byte5.1 percentage (0..100%)CW
5Lights 1Logic - Authorize1 Bit1.2 booleanCW
5Lights 1Logic - AND1 Bit1.2 booleanCW
5Lights 1Logic - OR1 Bit1.2 booleanCW
5Lights 1Logic - XOR1 Bit1.2 booleanCW
5Lights 1Logic - Inv. Authorize1 Bit1.2 booleanCW
5Lights 1Logic - NAND1 Bit1.2 booleanCW
5Lights 1Logic - NOR1 Bit1.2 booleanCW
5Lights 1Logic - XNOR1 Bit1.2 booleanCW
5FCU H/C 1Valve On/Off1 Bit1.1 switchCW
6Shutter/Blinds 1-2Blinds Angle (º)1 Byte5.3 angle (degrees)CW
6Shutter/Blinds 1-2Blinds Position (%)1 Byte5.1 percentage (0..100%)CW
7Lights 1Jamming1 Bit1.2 booleanCW
7Shutter/Blinds 1-2Jamming1 Bit1.2 booleanCW
8Lights 1Reset Working Time counter1 Bit1.2 booleanCW
8Shutter/Blinds 1-2Rain Alarm1 Bit1.2 booleanCW
9Lights 1Timer delay (seconds)2 Bytes7.5 time (s)CW
9Lights 1Timer delay (seconds)2 Bytes9.10 time (s)CW
10Shutter/Blinds 1-2Shutter Position Indication1 Byte5.1 percentage (0..100%)CRTU
11Shutter/Blinds 1-2Blinds Position Indication1 Byte5.1 percentage (0..100%)CRTU
11Lights 1Working t. limit reached Ind.1 Bit1.2 booleanCRTU
11Shutter/Blinds 1-2Blinds Angle Indication1 Byte5.3 angle (degrees)CRTU
12Lights 1Working Time counter Ind.4 Bytes13.100 time lag (s)CRTU
12FCU H/C 1Heating Valve Indication1 Bit1.1 switchCRTU
13Lights 1Pre-warning Indication1 Bit1.2 booleanCRTU
13FCU H/C 1Heating/Cooling Indication1 Bit1.100 heating/coolingCRTU
14Lights 1Status Indication1 Bit1.1 switchCRTU
14Shutter/Blinds 1-2Up Status Indication1 Bit1.2 booleanCRTU
14FCU H/C 1Valve On/Off Indication1 Bit1.1 switchCRTU
15Lights 2On / Off1 Bit1.1 switchCW
15FCU FAN 1Fan Speed Step1 Bit1.1 switchCW
16Lights 2Start / Stop Timer1 Bit1.10 start/stopCW
16FCU FAN 1Fan Speed 11 Bit1.1 switchCW
17Lights 2Priority On / Off2 Bit2.1 switch controlCW
18Lights 2Scene Control1 Byte18.1 scene controlCW
19Lights 2Time Limited Toggle Switch1 Bit1.1 switchCW
20Lights 2Logic - Authorize1 Bit1.2 booleanCW
20Lights 2Logic - AND1 Bit1.2 booleanCW
20Lights 2Logic - OR1 Bit1.2 booleanCW
20Lights 2Logic - XOR1 Bit1.2 booleanCW
20Lights 2Logic - Inv. Authorize1 Bit1.2 booleanCW
20Lights 2Logic - NAND1 Bit1.2 booleanCW
20Lights 2Logic - NOR1 Bit1.2 booleanCW
20Lights 2Logic - XNOR1 Bit1.2 booleanCW
20FCU FAN 1Fan Speed Stage1 Byte5.100CW
21FCU FAN 1Fan Speed Percent1 Byte5.1 percentage (0..100%)CW
22Lights 2Jamming1 Bit1.2 booleanCW
23Lights 2Reset Working Time counter1 Bit1.2 booleanCW
24Lights 2Timer delay (seconds)2 Bytes7.5 time (s)CW
24Lights 2Timer delay (seconds)2 Bytes9.10 time (s)CW
25FCU FAN 1Fan Speed Stage Indication1 Byte5.100CRTU
26Lights 2Working t. limit reached Ind.1 Bit1.2 booleanCRTU
26FCU FAN 1Fan Speed Percent Indication1 Byte5.1 percentage (0..100%)CRTU
27Lights 2Working Time counter Ind.4 Bytes13.100 time lag (s)CRTU
28Lights 2Pre-warning Indication1 Bit1.2 booleanCRTU
28FCU FAN 1Fan Speed 1 Indication1 Bit1.1 switchCRTU
29Lights 2Status Indication1 Bit1.1 switchCRTU
29Shutter/Blinds 1-2Down Status Indication1 Bit1.2 booleanCRTU
30Lights 3On / Off1 Bit1.1 switchCW
30Shutter/Blinds 3-4Move Up / Down1 Bit1.8 up/downCW
31Lights 3Start / Stop Timer1 Bit1.10 start/stopCW
31Shutter/Blinds 3-4Wind Alarm1 Bit1.2 booleanCW
31FCU H/C 1Cooling Valve1 Bit1.1 switchCW
32Lights 3Priority On / Off2 Bit2.1 switch controlCW
32Shutter/Blinds 3-4Priority Close / Open2 Bit2.1 switch controlCW
33Lights 3Scene Control1 Byte18.1 scene controlCW
33Shutter/Blinds 3-4Scene Control1 Byte18.1 scene controlCW
34Lights 3Time Limited Toggle Switch1 Bit1.1 switchCW
34Shutter/Blinds 3-4Stop Up / Down1 Bit1.8 up/downCW
34Shutter/Blinds 3-4Slat Angle | Stop Up / Down1 Bit1.8 up/downCW
35Shutter/Blinds 3-4Shutter Position (%)1 Byte5.1 percentage (0..100%)CW
35Lights 3Logic - Authorize1 Bit1.2 booleanCW
35Lights 3Logic - AND1 Bit1.2 booleanCW
35Lights 3Logic - OR1 Bit1.2 booleanCW
35Lights 3Logic - XOR1 Bit1.2 booleanCW
35Lights 3Logic - Inv. Authorize1 Bit1.2 booleanCW
35Lights 3Logic - NAND1 Bit1.2 booleanCW
35Lights 3Logic - NOR1 Bit1.2 booleanCW
35Lights 3Logic - XNOR1 Bit1.2 booleanCW
36Shutter/Blinds 3-4Blinds Angle (º)1 Byte5.3 angle (degrees)CW
36Shutter/Blinds 3-4Blinds Position (%)1 Byte5.1 percentage (0..100%)CW
37Lights 3Jamming1 Bit1.2 booleanCW
37Shutter/Blinds 3-4Jamming1 Bit1.2 booleanCW
38Lights 3Reset Working Time counter1 Bit1.2 booleanCW
38Shutter/Blinds 3-4Rain Alarm1 Bit1.2 booleanCW
39Lights 3Timer delay (seconds)2 Bytes7.5 time (s)CW
39Lights 3Timer delay (seconds)2 Bytes9.10 time (s)CW
40Shutter/Blinds 3-4Shutter Position Indication1 Byte5.1 percentage (0..100%)CRTU
41Shutter/Blinds 3-4Blinds Position Indication1 Byte5.1 percentage (0..100%)CRTU
41Lights 3Working t. limit reached Ind.1 Bit1.2 booleanCRTU
41Shutter/Blinds 3-4Blinds Angle Indication1 Byte5.3 angle (degrees)CRTU
42Lights 3Working Time counter Ind.4 Bytes13.100 time lag (s)CRTU
42FCU H/C 1Cooling Valve Indication1 Bit1.1 switchCRTU
43Lights 3Pre-warning Indication1 Bit1.2 booleanCRTU
44Lights 3Status Indication1 Bit1.1 switchCRTU
44Shutter/Blinds 3-4Up Status Indication1 Bit1.2 booleanCRTU
45Lights 4On / Off1 Bit1.1 switchCW
46Lights 4Start / Stop Timer1 Bit1.10 start/stopCW
46FCU FAN 1Fan Speed 21 Bit1.1 switchCW
47Lights 4Priority On / Off2 Bit2.1 switch controlCW
48Lights 4Scene Control1 Byte18.1 scene controlCW
49Lights 4Time Limited Toggle Switch1 Bit1.1 switchCW
50Lights 4Logic - Authorize1 Bit1.2 booleanCW
50Lights 4Logic - AND1 Bit1.2 booleanCW
50Lights 4Logic - OR1 Bit1.2 booleanCW
50Lights 4Logic - XOR1 Bit1.2 booleanCW
50Lights 4Logic - Inv. Authorize1 Bit1.2 booleanCW
50Lights 4Logic - NAND1 Bit1.2 booleanCW
50Lights 4Logic - NOR1 Bit1.2 booleanCW
50Lights 4Logic - XNOR1 Bit1.2 booleanCW
52Lights 4Jamming1 Bit1.2 booleanCW
53Lights 4Reset Working Time counter1 Bit1.2 booleanCW
54Lights 4Timer delay (seconds)2 Bytes7.5 time (s)CW
54Lights 4Timer delay (seconds)2 Bytes9.10 time (s)CW
56Lights 4Working t. limit reached Ind.1 Bit1.2 booleanCRTU
57Lights 4Working Time counter Ind.4 Bytes13.100 time lag (s)CRTU
58Lights 4Pre-warning Indication1 Bit1.2 booleanCRTU
58FCU FAN 1Fan Speed 2 Indication1 Bit1.1 switchCRTU
59Lights 4Status Indication1 Bit1.1 switchCRTU
59Shutter/Blinds 3-4Down Status Indication1 Bit1.2 booleanCRTU
60Lights 5On / Off1 Bit1.1 switchCW
60Shutter/Blinds 5-6Move Up / Down1 Bit1.8 up/downCW
61Lights 5Start / Stop Timer1 Bit1.10 start/stopCW
61Shutter/Blinds 5-6Wind Alarm1 Bit1.2 booleanCW
62Lights 5Priority On / Off2 Bit2.1 switch controlCW
62Shutter/Blinds 5-6Priority Close / Open2 Bit2.1 switch controlCW
63Lights 5Scene Control1 Byte18.1 scene controlCW
63Shutter/Blinds 5-6Scene Control1 Byte18.1 scene controlCW
64Lights 5Time Limited Toggle Switch1 Bit1.1 switchCW
64Shutter/Blinds 5-6Stop Up / Down1 Bit1.8 up/downCW
64Shutter/Blinds 5-6Slat Angle | Stop Up / Down1 Bit1.8 up/downCW
65Shutter/Blinds 5-6Shutter Position (%)1 Byte5.1 percentage (0..100%)CW
65Lights 5Logic - Authorize1 Bit1.2 booleanCW
65Lights 5Logic - AND1 Bit1.2 booleanCW
65Lights 5Logic - OR1 Bit1.2 booleanCW
65Lights 5Logic - XOR1 Bit1.2 booleanCW
65Lights 5Logic - Inv. Authorize1 Bit1.2 booleanCW
65Lights 5Logic - NAND1 Bit1.2 booleanCW
65Lights 5Logic - NOR1 Bit1.2 booleanCW
65Lights 5Logic - XNOR1 Bit1.2 booleanCW
66Shutter/Blinds 5-6Blinds Angle (º)1 Byte5.3 angle (degrees)CW
66Shutter/Blinds 5-6Blinds Position (%)1 Byte5.1 percentage (0..100%)CW
67Lights 5Jamming1 Bit1.2 booleanCW
67Shutter/Blinds 5-6Jamming1 Bit1.2 booleanCW
68Lights 5Reset Working Time counter1 Bit1.2 booleanCW
68Shutter/Blinds 5-6Rain Alarm1 Bit1.2 booleanCW
69Lights 5Timer delay (seconds)2 Bytes7.5 time (s)CW
69Lights 5Timer delay (seconds)2 Bytes9.10 time (s)CW
70Shutter/Blinds 5-6Shutter Position Indication1 Byte5.1 percentage (0..100%)CRTU
71Shutter/Blinds 5-6Blinds Position Indication1 Byte5.1 percentage (0..100%)CRTU
71Lights 5Working t. limit reached Ind.1 Bit1.2 booleanCRTU
71Shutter/Blinds 5-6Blinds Angle Indication1 Byte5.3 angle (degrees)CRTU
72Lights 5Working Time counter Ind.4 Bytes13.100 time lag (s)CRTU
73Lights 5Pre-warning Indication1 Bit1.2 booleanCRTU
74Lights 5Status Indication1 Bit1.1 switchCRTU
74Shutter/Blinds 5-6Up Status Indication1 Bit1.2 booleanCRTU
75Lights 6On / Off1 Bit1.1 switchCW
76Lights 6Start / Stop Timer1 Bit1.10 start/stopCW
76FCU FAN 1Fan Speed 31 Bit1.1 switchCW
77Lights 6Priority On / Off2 Bit2.1 switch controlCW
78Lights 6Scene Control1 Byte18.1 scene controlCW
79Lights 6Time Limited Toggle Switch1 Bit1.1 switchCW
80Lights 6Logic - Authorize1 Bit1.2 booleanCW
80Lights 6Logic - AND1 Bit1.2 booleanCW
80Lights 6Logic - OR1 Bit1.2 booleanCW
80Lights 6Logic - XOR1 Bit1.2 booleanCW
80Lights 6Logic - Inv. Authorize1 Bit1.2 booleanCW
80Lights 6Logic - NAND1 Bit1.2 booleanCW
80Lights 6Logic - NOR1 Bit1.2 booleanCW
80Lights 6Logic - XNOR1 Bit1.2 booleanCW
82Lights 6Jamming1 Bit1.2 booleanCW
83Lights 6Reset Working Time counter1 Bit1.2 booleanCW
84Lights 6Timer delay (seconds)2 Bytes7.5 time (s)CW
84Lights 6Timer delay (seconds)2 Bytes9.10 time (s)CW
86Lights 6Working t. limit reached Ind.1 Bit1.2 booleanCRTU
87Lights 6Working Time counter Ind.4 Bytes13.100 time lag (s)CRTU
88Lights 6Pre-warning Indication1 Bit1.2 booleanCRTU
88FCU FAN 1Fan Speed 3 Indication1 Bit1.1 switchCRTU
89Lights 6Status Indication1 Bit1.1 switchCRTU
89Shutter/Blinds 5-6Down Status Indication1 Bit1.2 booleanCRTU
90Lights 7On / Off1 Bit1.1 switchCW
90Shutter/Blinds 7-8Move Up / Down1 Bit1.8 up/downCW
91Lights 7Start / Stop Timer1 Bit1.10 start/stopCW
91Shutter/Blinds 7-8Wind Alarm1 Bit1.2 booleanCW
92Lights 7Priority On / Off2 Bit2.1 switch controlCW
92Shutter/Blinds 7-8Priority Close / Open2 Bit2.1 switch controlCW
93Lights 7Scene Control1 Byte18.1 scene controlCW
93Shutter/Blinds 7-8Scene Control1 Byte18.1 scene controlCW
94Lights 7Time Limited Toggle Switch1 Bit1.1 switchCW
94Shutter/Blinds 7-8Stop Up / Down1 Bit1.8 up/downCW
94Shutter/Blinds 7-8Slat Angle | Stop Up / Down1 Bit1.8 up/downCW
95Shutter/Blinds 7-8Shutter Position (%)1 Byte5.1 percentage (0..100%)CW
95Lights 7Logic - Authorize1 Bit1.2 booleanCW
95Lights 7Logic - AND1 Bit1.2 booleanCW
95Lights 7Logic - OR1 Bit1.2 booleanCW
95Lights 7Logic - XOR1 Bit1.2 booleanCW
95Lights 7Logic - Inv. Authorize1 Bit1.2 booleanCW
95Lights 7Logic - NAND1 Bit1.2 booleanCW
95Lights 7Logic - NOR1 Bit1.2 booleanCW
95Lights 7Logic - XNOR1 Bit1.2 booleanCW
96Shutter/Blinds 7-8Blinds Angle (º)1 Byte5.3 angle (degrees)CW
96Shutter/Blinds 7-8Blinds Position (%)1 Byte5.1 percentage (0..100%)CW
97Lights 7Jamming1 Bit1.2 booleanCW
97Shutter/Blinds 7-8Jamming1 Bit1.2 booleanCW
98Lights 7Reset Working Time counter1 Bit1.2 booleanCW
98Shutter/Blinds 7-8Rain Alarm1 Bit1.2 booleanCW
99Lights 7Timer delay (seconds)2 Bytes7.5 time (s)CW
99Lights 7Timer delay (seconds)2 Bytes9.10 time (s)CW
100Shutter/Blinds 7-8Shutter Position Indication1 Byte5.1 percentage (0..100%)CRTU
101Shutter/Blinds 7-8Blinds Position Indication1 Byte5.1 percentage (0..100%)CRTU
101Lights 7Working t. limit reached Ind.1 Bit1.2 booleanCRTU
101Shutter/Blinds 7-8Blinds Angle Indication1 Byte5.3 angle (degrees)CRTU
102Lights 7Working Time counter Ind.4 Bytes13.100 time lag (s)CRTU
103Lights 7Pre-warning Indication1 Bit1.2 booleanCRTU
104Lights 7Status Indication1 Bit1.1 switchCRTU
104Shutter/Blinds 7-8Up Status Indication1 Bit1.2 booleanCRTU
105Lights 8On / Off1 Bit1.1 switchCW
106Lights 8Start / Stop Timer1 Bit1.10 start/stopCW
107Lights 8Priority On / Off2 Bit2.1 switch controlCW
108Lights 8Scene Control1 Byte18.1 scene controlCW
109Lights 8Time Limited Toggle Switch1 Bit1.1 switchCW
110Lights 8Logic - Authorize1 Bit1.2 booleanCW
110Lights 8Logic - AND1 Bit1.2 booleanCW
110Lights 8Logic - OR1 Bit1.2 booleanCW
110Lights 8Logic - XOR1 Bit1.2 booleanCW
110Lights 8Logic - Inv. Authorize1 Bit1.2 booleanCW
110Lights 8Logic - NAND1 Bit1.2 booleanCW
110Lights 8Logic - NOR1 Bit1.2 booleanCW
110Lights 8Logic - XNOR1 Bit1.2 booleanCW
112Lights 8Jamming1 Bit1.2 booleanCW
113Lights 8Reset Working Time counter1 Bit1.2 booleanCW
114Lights 8Timer delay (seconds)2 Bytes7.5 time (s)CW
114Lights 8Timer delay (seconds)2 Bytes9.10 time (s)CW
116Lights 8Working t. limit reached Ind.1 Bit1.2 booleanCRTU
117Lights 8Working Time counter Ind.4 Bytes13.100 time lag (s)CRTU
118Lights 8Pre-warning Indication1 Bit1.2 booleanCRTU
119Lights 8Status Indication1 Bit1.1 switchCRTU
119Shutter/Blinds 7-8Down Status Indication1 Bit1.2 booleanCRTU
240GeneralRestore Scenes1 Bit1.2 booleanCW
241GeneralMaintenance Mode1 Bit1.2 booleanCW
Parameters (134)
ParameterTypeDefault
For knowing when new values are writtenunsignedInt 0…255255
Durationlist5 min
Use Time Limited Manual mode?listNo
_PA_MAN_CONFS:usage=notusedunsignedInt 0…2550
_PA_MAN_CONFS:tl=nounsignedInt 0…150
Manual Mode usagelistUse
Send Status Ind. in Manual mode?listYes
Output 1 and 2 functionlistLighting
Output 3 and 4 functionlistLighting
Output 5 and 6 functionlistLighting
Output 7 and 8 functionlistLighting
Output 9 and 10 functionlistNot used
Output 11 and 12 functionlistNot used
Output 13 and 14 functionlistNot used
Output 15 and 16 functionlistNot used
Status after Manual Mode operationlistMaintain
Status after Priority operationlistMaintain
Status after jamminglistMaintain
Jamming usagelistNot used
Use Time Limited Jamming?listNo
Durationlist1 min
Output contact typelistOff = Relay Open; On = Relay Closed
Timer (default value)list10 s
Time Limited Toggle Switchlist10 s
Timer expiration pre-warninglist15 s
Allow timer reset?listNo
Consecutive presses multiply time (within 10s)?listNo
Timer operation modelistOn
Timer expiration Pre-Warning usagelistInvert output (during 1s)
Allow timer interruption with Stop?listNo
Pre-Warning message typelistOn
Output status for scene 1listNot involved
Output status for scene 2listNot involved
Output status for scene 3listNot involved
Output status for scene 4listNot involved
Output status for scene 8listNot involved
Output status for scene 7listNot involved
Output status for scene 6listNot involved
Output status for scene 5listNot involved
Output status for scene 12listNot involved
Output status for scene 11listNot involved
Output status for scene 10listNot involved
Output status for scene 9listNot involved
Output status for scene 16listNot involved
Output status for scene 15listNot involved
Output status for scene 14listNot involved
Output status for scene 13listNot involved
Output status for scene 20listNot involved
Output status for scene 19listNot involved
Output status for scene 18listNot involved
Output status for scene 17listNot involved
Output status for scene 24listNot involved
Output status for scene 23listNot involved
Output status for scene 22listNot involved
Output status for scene 21listNot involved
Output status for scene 28listNot involved
Output status for scene 27listNot involved
Output status for scene 26listNot involved
Output status for scene 25listNot involved
Output status for scene 32listNot involved
Output status for scene 31listNot involved
Output status for scene 30listNot involved
Output status for scene 29listNot involved
Scene learn allowed?listYes
Limit to send alert message (hours) (0 means don't measure)unsignedInt 0…5000001000
Output status to measurelistOn
Counter directionlistIncrement
_PA_CH2_TL:not_usedunsignedInt 0…2550
Status after system startlistMaintain
_PA_CH1_FUNC:lightsunsignedInt 0…2551
_PA_CH1_FUNC:lightsunsignedInt 0…2552
Control also blinds?listNo
_PA_CH1_FUNC:lightsunsignedInt 0…2554
Blinds step time ( x 10ms)unsignedInt 5…25520
Number of blinds stepsunsignedInt 1…25510
Time for complete up movement (s)unsignedInt 1…65535120
Time for complete down movement (s)unsignedInt 1…65535120
Delay for direction inversion (x 100ms)unsignedInt 5…2410
Status after system startlistLast stored position
_PA_TL:not_usedunsignedInt 0…2550
Blinds position control CO typelistPercentage [DPT_ID Scaling 5.001]
Shutter positionlist0.0% | 0x00
Blinds positionlist0.0% | 0x00
Position for Rain AlarmlistMaintain
Position for Wind AlarmlistMaintain
Use Rain Alarm?listNo
Use Wind Alarm?listNo
Alarm active iflistOn
Status after alarmlistMaintain
_PA_CH1_CH2_FUNC:lightsunsignedInt 0…2551
_PA_CH1_CH2_FUNC:lightsunsignedInt 0…2554
_PA_CH1_CH2_FUNC:lightsunsignedInt 0…2552
Use working duration counter?listNo
Use Timer?listNot used
"On/Off" Com.Obj. FunctionlistOn / Off
Logic input functionlistNot used
On Delay amountlist10 s
Off Delay amountlist10 s
_V_LogicConfslistYes
Delaylist10 s
Timer Delay change via Com. Obj.listNot used
PID_HW_TypeChecklist
_PA_CH1_FUNC:lightsunsignedInt 0…2550
_PA_CH1_CH2_FUNC:lightsunsignedInt 0…2550
Fan Coil Mode Usage:listNot used
Fan Coil System :list2 Pipes
_PA_GROUP_A_FUNC:FAN_COILunsignedInt 0…2555
_PA_GROUP_A_FUNC:FAN_COIL_4_PIPESunsignedInt 0…2556
Fan Coil FunctionlistHeating
Fan Coil FunctionlistHeating/Cooling
Valve Controller TypelistOn/Off (1 Bit)
Fan Operating ModelistChangeover Switch Control
Threshold Value from Off to Speed 1 (%1 - %100)list0
Threshold Value from Speed 1 to Speed 2 (1% - 100%)list0
Threshold Value from Speed 2 to Speed 3 (1% - 100%)list0
Hysteresis for Fan Speeds (0% - 25%)list0.0% | 0x00
Default ParameterunsignedInt 0…2557
Fan Speed Switching Delay (x100ms)unsignedInt 0…2551
Operating Mode Switching Delay (x100ms)unsignedInt 0…2551
Operating Mode After Manual Mode OperationlistMaintain
Operating Mode After System StartlistLast Stored Mode
Fan Speed After System StartlistLast Stored Speed
Fan Speed after Manual Mode OperationlistMaintain
2PPlistHeating
4PPlistHeating/Cooling
2PP_HEATINGlistHeating
FCU_FUNC_2PIPES_CH3unsignedInt 0…2555
FCU_FUNC_4PIPES_CH3unsignedInt 0…2556
FCU_FUNC_3LEVEL_FAN_CH4unsignedInt 0…2557
FCU_FUNC_3LEVEL_FAN_CH6unsignedInt 0…2557
Output 5 FunctionlistLighting
FCU H/C ChannelstextCH1 : HEATING VALVE, CH3 : COOLING VALVE
FCU FAN ChannelstextCH2: FAN LV1, CH4 : FAN LV2, CH6 : FAN LV3
FCU H/C ChannelstextCH1 : Valve Control

Version history

ApplicationApp noFingerprintFirst seenSizeFile
MSA08yy-CM_v1.3_fc04c31 1.3 latest$1330B3CC2026-11-25311 KBDownload
KNX Switch/Shutter/FCU 8CH 16A 1.2$13302C002026-11-25244 KBDownload

About this file

This is the official ETS product database for the Honeywell Building Technologies Honeywell MK Switch/Shutter/FCU 8CH 16A (KNX SW 0816), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Honeywell Building Technologies

All Honeywell Building Technologies products