| 0 | Switch{{Module_Index}}-Output | Switch output | 1 Bit | 1.1 switch | CWU |
| 0 | Curtain{{Module_Index}}-Move up/down | Curtain move up/down | 1 Bit | 1.8 up/down | CWU |
| 0 | {{Name}}{{Module_Index}}-Actual temperature | Actual temperature 1 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 0 | Dry Contact{{Module_Index}}-Input Active | Dry Contact input activate | 1 Bit | 1.3 enable | CWU |
| 0 | D1-Comb Obj{{Module_Index}}(Switch) | Dry Contact Output for Switch | 1 Bit | 1.1 switch | CRT |
| 0 | D1-Comb Obj{{Module_Index}}(Shutter) | Dry Contact Output for Shutter | 1 Bit | 1.8 up/down | CRT |
| 0 | D1-Comb Obj{{Module_Index}}(Scene) | Dry Contact Output for Scene | 1 Byte | 18.1 scene control | CRT |
| 0 | D1-Comb Obj{{Module_Index}}(Sequence) | Dry Contact Output for Sequence | 1 Bit | 1.10 start/stop | CRT |
| 0 | D1-Comb Obj{{Module_Index}}(Percent) | Dry Contact Output for Percent | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 0 | D2-Comb Obj{{Module_Index}}(Switch) | Dry Contact Output for Switch | 1 Bit | 1.1 switch | CRT |
| 0 | D2-Comb Obj{{Module_Index}}(Shutter) | Dry Contact Output for Shutter | 1 Bit | 1.8 up/down | CRT |
| 0 | D2-Comb Obj{{Module_Index}}(Scene) | Dry Contact Output for Scene | 1 Byte | 18.1 scene control | CRT |
| 0 | D2-Comb Obj{{Module_Index}}(Sequence) | Dry Contact Output for Sequence | 1 Bit | 1.10 start/stop | CRT |
| 0 | D2-Comb Obj{{Module_Index}}(Percent) | Dry Contact Output for Percent | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 1 | General | Heartbeat telegram | 1 Bit | 1.2 boolean | CT |
| 1 | Switch{{Module_Index}}-Response | Switch response | 1 Bit | 1.1 switch | CRT |
| 1 | Curtain1-Stop moving | Curtain Stop moving | 1 Bit | 1.10 start/stop | CWU |
| 1 | Curtain1-Adjust louvre/Stop moving | Curtain Adjust louvre/Stop moving | 1 Bit | 1.8 up/down | CWU |
| 1 | Curtain2-Stop moving | Curtain Stop moving | 1 Bit | 1.10 start/stop | CWU |
| 1 | Curtain2-Adjust louvre/Stop moving | Curtain Adjust louvre/Stop moving | 1 Bit | 1.8 up/down | CWU |
| 1 | Curtain3-Stop moving | Curtain Stop moving | 1 Bit | 1.10 start/stop | CWU |
| 1 | Curtain3-Adjust louvre/Stop moving | Curtain Adjust louvre/Stop moving | 1 Bit | 1.8 up/down | CWU |
| 1 | Curtain4-Stop moving | Curtain Stop moving | 1 Bit | 1.10 start/stop | CWU |
| 1 | Curtain4-Adjust louvre/Stop moving | Curtain Adjust louvre/Stop moving | 1 Bit | 1.8 up/down | CWU |
| 1 | Curtain5-Stop moving | Curtain Stop moving | 1 Bit | 1.10 start/stop | CWU |
| 1 | Curtain5-Adjust louvre/Stop moving | Curtain Adjust louvre/Stop moving | 1 Bit | 1.8 up/down | CWU |
| 1 | Curtain6-Stop moving | Curtain Stop moving | 1 Bit | 1.10 start/stop | CWU |
| 1 | Curtain6-Adjust louvre/Stop moving | Curtain Adjust louvre/Stop moving | 1 Bit | 1.8 up/down | CWU |
| 1 | Curtain7-Stop moving | Curtain Stop moving | 1 Bit | 1.10 start/stop | CWU |
| 1 | Curtain7-Adjust louvre/Stop moving | Curtain Adjust louvre/Stop moving | 1 Bit | 1.8 up/down | CWU |
| 1 | Curtain8-Stop moving | Curtain Stop moving | 1 Bit | 1.10 start/stop | CWU |
| 1 | Curtain8-Adjust louvre/Stop moving | Curtain Adjust louvre/Stop moving | 1 Bit | 1.8 up/down | CWU |
| 1 | {{Name}}{{Module_Index}}-Actual temperature | Actual temperature 2 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 1 | Dry Contact{{Module_Index}}-Report Status | Dry Contact Report Input Status | 1 Bit | 1.9 open/close | CRT |
| 2 | Switch{{Module_Index}}-Flashing | Switch flashing | 1 Bit | 1.1 switch | CWU |
| 2 | Curtain{{Module_Index}}-Percent of position(0%..100%) | Curtain Percent of position | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 2 | {{Name}}{{Module_Index}}-Actual temperature | Actual temp. 1 error signal | 1 Bit | 1.5 alarm | CRT |
| 2 | Dry Contact1-Switch | Dry Contact Output for Switch | 1 Bit | 1.1 switch | CRT |
| 2 | Dry Contact1-Switch(Short) | Dry Contact Output for Switch(Short) | 1 Bit | 1.1 switch | CRT |
| 2 | Dry Contact1-Dimming | Dry Contact Output for Dimming | 4 Bit | 3.7 dimming control | CRT |
| 2 | Dry Contact1-Scene | Dry Contact Output for Scene | 1 Byte | 18.1 scene control | CRT |
| 2 | Dry Contact1-Sequence | Dry Contact Output for Sequence | 1 Bit | 1.10 start/stop | CRT |
| 2 | Dry Contact1-Sequence(Short) | Dry Contact Output for Sequence(Short) | 1 Bit | 1.10 start/stop | CRT |
| 2 | Dry Contact1-Percent | Dry Contact Output for Percent | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 2 | Dry Contact1-Percent(Short) | Dry Contact Output for Percent(Short) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 2 | Dry Contact1-Curtain Moving(Open) | Dry Contact Output for Curtain Moving(Open) | 1 Bit | 1.8 up/down | CRT |
| 2 | Dry Contact1-Curtain Stepping(Open) | Dry Contact Output for Curtain Stepping(Open) | 1 Bit | 1.7 step | CRT |
| 2 | Dry Contact1-Curtain Moving(Short) | Dry Contact Output for Curtain Moving(Short) | 1 Bit | 1.8 up/down | CRT |
| 2 | Dry Contact1-Curtain Stepping(Short) | Dry Contact Output for Curtain Stepping(Short) | 1 Bit | 1.7 step | CRT |
| 2 | Dry Contact2-Switch | Dry Contact Output for Switch | 1 Bit | 1.1 switch | CRT |
| 2 | Dry Contact2-Switch(Short) | Dry Contact Output for Switch(Short) | 1 Bit | 1.1 switch | CRT |
| 2 | Dry Contact2-Dimming | Dry Contact Output for Dimming | 4 Bit | 3.7 dimming control | CRT |
| 2 | Dry Contact2-Scene | Dry Contact Output for Scene | 1 Byte | 18.1 scene control | CRT |
| 2 | Dry Contact2-Sequence | Dry Contact Output for Sequence | 1 Bit | 1.10 start/stop | CRT |
| 2 | Dry Contact2-Sequence(Short) | Dry Contact Output for Sequence(Short) | 1 Bit | 1.10 start/stop | CRT |
| 2 | Dry Contact2-Percent | Dry Contact Output for Percent | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 2 | Dry Contact2-Percent(Short) | Dry Contact Output for Percent(Short) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 2 | Dry Contact2-Curtain Moving(Open) | Dry Contact Output for Curtain Moving(Open) | 1 Bit | 1.8 up/down | CRT |
| 2 | Dry Contact2-Curtain Stepping(Open) | Dry Contact Output for Curtain Stepping(Open) | 1 Bit | 1.7 step | CRT |
| 2 | Dry Contact2-Curtain Moving(Short) | Dry Contact Output for Curtain Moving(Short) | 1 Bit | 1.8 up/down | CRT |
| 2 | Dry Contact2-Curtain Stepping(Short) | Dry Contact Output for Curtain Stepping(Short) | 1 Bit | 1.7 step | CRT |
| 3 | Switch{{Module_Index}}-Scene(8bit) | Switchl scene | 1 Byte | 18.1 scene control | CWU |
| 3 | Curtain{{Module_Index}}-Percent of louvre(0%..100%) | Curtain Percent of louvre | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 3 | {{Name}}{{Module_Index}}-Actual temperature | Actual temp. 2 error signal | 1 Bit | 1.5 alarm | CRT |
| 3 | Dry Contact1-Switch(Long) | Dry Contact Output for Switch(Long) | 1 Bit | 1.1 switch | CRT |
| 3 | Dry Contact1-Dimming | Dry Contact Output for Dimming | 4 Bit | 3.7 dimming control | CRT |
| 3 | Dry Contact1-Sequence(Long) | Dry Contact Output for Sequence(Long) | 1 Bit | 1.10 start/stop | CRT |
| 3 | Dry Contact1-Percent(Long) | Dry Contact Output for Percent(Long) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 3 | Dry Contact1-Curtain Moving(Close) | Dry Contact Output for Curtain Moving(Close) | 1 Bit | 1.8 up/down | CRT |
| 3 | Dry Contact1-Curtain Stepping(Close) | Dry Contact Output for Curtain Stepping(Close) | 1 Bit | 1.7 step | CRT |
| 3 | Dry Contact1-Curtain Moving(Long) | Dry Contact Output for Curtain Moving(Long) | 1 Bit | 1.8 up/down | CRT |
| 3 | Dry Contact1-Curtain Stepping(Long) | Dry Contact Output for Curtain Stepping(Long) | 1 Bit | 1.7 step | CRT |
| 3 | Dry Contact2-Switch(Long) | Dry Contact Output for Switch(Long) | 1 Bit | 1.1 switch | CRT |
| 3 | Dry Contact2-Dimming | Dry Contact Output for Dimming | 4 Bit | 3.7 dimming control | CRT |
| 3 | Dry Contact2-Sequence(Long) | Dry Contact Output for Sequence(Long) | 1 Bit | 1.10 start/stop | CRT |
| 3 | Dry Contact2-Percent(Long) | Dry Contact Output for Percent(Long) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 3 | Dry Contact2-Curtain Moving(Close) | Dry Contact Output for Curtain Moving(Close) | 1 Bit | 1.8 up/down | CRT |
| 3 | Dry Contact2-Curtain Stepping(Close) | Dry Contact Output for Curtain Stepping(Close) | 1 Bit | 1.7 step | CRT |
| 3 | Dry Contact2-Curtain Moving(Long) | Dry Contact Output for Curtain Moving(Long) | 1 Bit | 1.8 up/down | CRT |
| 3 | Dry Contact2-Curtain Stepping(Long) | Dry Contact Output for Curtain Stepping(Long) | 1 Bit | 1.7 step | CRT |
| 4 | Switch{{Module_Index}}-Threshold Input | Switch threshold input | 1 Byte | 5.10 counter pulses (0..255) | CWU |
| 4 | Switch{{Module_Index}}-Threshold Input | Switch threshold input | 2 Bytes | 7.1 pulses | CWU |
| 4 | Curtain{{Module_Index}}-Status of position(0%..100%) | Curtain Status of position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 4 | {{Name}}{{Module_Index}}-Actual temperature | Frost/heat alarm error signal | 1 Bit | 1.5 alarm | CRT |
| 5 | Switch{{Module_Index}}-Threshold value1 | Switchl threshold change value1 | 1 Byte | 5.10 counter pulses (0..255) | CWU |
| 5 | Switch{{Module_Index}}-Threshold value1 | Switchl threshold change value1 | 2 Bytes | 7.1 pulses | CWU |
| 5 | Curtain{{Module_Index}}-Status of louvre(0%..100%) | Curtain Status of louvre | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 5 | {{Name}}{{Module_Index}}-Setpoint | Base setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 6 | Switch{{Module_Index}}-Threshold value2 | Switch threshold change value2 | 1 Byte | 5.10 counter pulses (0..255) | CWU |
| 6 | Switch{{Module_Index}}-Threshold value2 | Switch threshold change value2 | 2 Bytes | 7.1 pulses | CWU |
| 6 | Curtain{{Module_Index}}-Status of up/down | Curtain Status of up/down | 1 Bit | 1.8 up/down | CRT |
| 6 | {{Name}}{{Module_Index}}-Setpoint | Base setpoint temp. step | 1 Bit | 1.7 step | CWU |
| 7 | Switch{{Module_Index}}-Logic1 | Switchl logic input1 | 1 Bit | 1.2 boolean | CWU |
| 7 | Curtain{{Module_Index}}-Status of stop | Curtain Status of stop | 1 Bit | 1.10 start/stop | CRT |
| 7 | {{Name}}{{Module_Index}}-Control value A | Heating/Cooling value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 7 | {{Name}}{{Module_Index}}-Control value A | Heating value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 8 | Slave clock | Network datetime | 8 Bytes | 19.1 date time | CRWTU |
| 8 | Switch{{Module_Index}}-Logic2 | Switchl logic input2 | 1 Bit | 1.2 boolean | CWU |
| 8 | Curtain{{Module_Index}}-Status of upper pos | Curtain Status of upper pos | 1 Bit | 1.2 boolean | CRT |
| 8 | {{Name}}{{Module_Index}}-Control value B | Cooling value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 8 | {{Name}}{{Module_Index}}-Control value B | Heating/Cooling value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 9 | Slave clock | Network date | 3 Bytes | 11.1 date | CRWTU |
| 9 | Switch{{Module_Index}}-Pulse start/stop | Switch pulse start/stop | 1 Bit | 1.10 start/stop | CWU |
| 9 | Curtain{{Module_Index}}-Status of lower pos | Curtain Status of lower pos | 1 Bit | 1.2 boolean | CRT |
| 9 | HVAC1-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | {{Name}}{{Module_Index}}-Control Switch heat/cool | 1'-heat valve,'0'-cool valve | 1 Bit | 1.1 switch | CWTU |
| 9 | {{Name}}{{Module_Index}}-Control Switch heat/cool | 0'-heat valve,'1'-cool valve" | 1 Bit | 1.1 switch | CWTU |
| 9 | HVAC1-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | HVAC2-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | HVAC2-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | HVAC3-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | HVAC3-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | HVAC4-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | HVAC4-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | HVAC5-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | HVAC5-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating1-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating1-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating2-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating2-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating3-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating3-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating4-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating4-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating5-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating5-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating6-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating6-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating7-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating7-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating8-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Floor Heating8-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Fan1-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Fan1-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Fan2-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Fan2-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Fan3-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Fan3-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Fan4-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Fan4-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Fan5-Control Switch A/B | 0'-A,'1'-B | 1 Bit | 1.1 switch | CWTU |
| 9 | Fan5-Control Switch A/B | 1'-A,'0'-B | 1 Bit | 1.1 switch | CWTU |
| 10 | Slave clock | Network time of day | 3 Bytes | 10.1 time of day | CRWTU |
| 10 | Switch{{Module_Index}}-Pulse number | Switch pulse number | 2 Bytes | 7.1 pulses | CWU |
| 10 | Curtain{{Module_Index}}-Set preset1/2 | Curtain set preset1/2 | 1 Bit | 1.22 scene | CWU |
| 10 | {{Name}}{{Module_Index}}-Control value err | Control value error signal | 1 Bit | 1.5 alarm | CRT |
| 11 | Switch group control1 | Switch group control1 | 1 Bit | 1.1 switch | CWU |
| 11 | Switch{{Module_Index}}-Pulse on time | Switchl pulse on time | 2 Bytes | 7.5 time (s) | CWU |
| 11 | Curtain{{Module_Index}}-Set preset3/4 | Curtain set preset3/4 | 1 Bit | 1.22 scene | CWU |
| 11 | {{Name}}{{Module_Index}}-System | System ON/OFF(1-ON,0-OFF) | 1 Bit | 1.1 switch | CWU |
| 12 | Switch group control2 | Switch group control2 | 1 Bit | 1.1 switch | CWU |
| 12 | Switch{{Module_Index}}-Pulse off time | Switchl pulse off time | 2 Bytes | 7.5 time (s) | CWU |
| 12 | Curtain{{Module_Index}}-Move to preset1/2 | Curtain move to preset1/2 | 1 Bit | 1.22 scene | CWU |
| 12 | {{Name}}{{Module_Index}}-System | Status system ON/OFF | 1 Bit | 1.1 switch | CRT |
| 13 | Switch group control3 | Switch group control3 | 1 Bit | 1.1 switch | CWU |
| 13 | Switch{{Module_Index}}-Stairlight | Switch stairlight | 1 Bit | 1.1 switch | CWU |
| 13 | Curtain{{Module_Index}}-Move to preset3/4 | Curtain move to preset3/4 | 1 Bit | 1.22 scene | CWU |
| 13 | {{Name}}{{Module_Index}}-Valve Heating | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | HVAC1-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | HVAC2-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | HVAC3-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | HVAC4-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | HVAC5-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Floor Heating1-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Floor Heating2-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Floor Heating3-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Floor Heating4-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Floor Heating5-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Floor Heating6-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Floor Heating7-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Floor Heating8-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Fan1-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Fan2-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Fan3-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Fan4-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 13 | Fan5-Valve Heating/Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 14 | Curtain group control1 | Curtain group control1 | 1 Bit | 1.8 up/down | CWU |
| 14 | Switch{{Module_Index}}-Stairlight off time | Switchl stairlight off time | 2 Bytes | 7.5 time (s) | CWU |
| 14 | Curtain{{Module_Index}}-Scene(8bit) | Curtain scene | 1 Byte | 18.1 scene control | CWU |
| 14 | {{Name}}{{Module_Index}}-Valve Heating | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | HVAC1-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | HVAC2-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | HVAC3-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | HVAC4-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | HVAC5-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Floor Heating1-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Floor Heating2-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Floor Heating3-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Floor Heating4-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Floor Heating5-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Floor Heating6-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Floor Heating7-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Floor Heating8-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Fan1-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Fan2-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Fan3-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Fan4-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 14 | Fan5-Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 15 | Curtain group control2 | Curtain group control2 | 1 Bit | 1.8 up/down | CWU |
| 15 | Switch{{Module_Index}}-Stairlight alarm | Switch stairlight alarm | 1 Bit | 1.5 alarm | CRT |
| 15 | Curtain{{Module_Index}}-Auto Enable | Curtain enable auto sun function | 1 Bit | 1.3 enable | CRWU |
| 15 | {{Name}}{{Module_Index}}-Valve Heating | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | HVAC1-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | HVAC2-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | HVAC3-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | HVAC4-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | HVAC5-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Floor Heating1-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Floor Heating2-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Floor Heating3-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Floor Heating4-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Floor Heating5-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Floor Heating6-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Floor Heating7-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Floor Heating8-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Fan1-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Fan2-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Fan3-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Fan4-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 15 | Fan5-Valve Heating/Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 16 | Curtain group control3 | Curtain group control3 | 1 Bit | 1.8 up/down | CWU |
| 16 | Switch{{Module_Index}}-Force Operation(1bit) | Switch Force Operation | 1 Bit | 1.3 enable | CRWU |
| 16 | Curtain{{Module_Index}}-Auto "Sun=0/1" | Curtain auto function of Sun=0/1 | 1 Bit | 1.2 boolean | CRWU |
| 16 | {{Name}}{{Module_Index}}-Valve Heating | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | HVAC1-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | HVAC2-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | HVAC3-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | HVAC4-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | HVAC5-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Floor Heating1-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Floor Heating2-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Floor Heating3-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Floor Heating4-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Floor Heating5-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Floor Heating6-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Floor Heating7-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Floor Heating8-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Fan1-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Fan2-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Fan3-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Fan4-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 16 | Fan5-Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 17 | Switch{{Module_Index}}-Force Operation(2bit) | Switch Force Operation | 2 Bit | 2.1 switch control | CRWU |
| 17 | Curtain{{Module_Index}}-Position for Auto(%) | Curtain position for auto function(%) | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 17 | {{Name}}{{Module_Index}}-Valve Cooling | Status value | 1 Bit | 1.1 switch | CRT |
| 18 | Switch{{Module_Index}}-Time out | Alarm | 1 Bit | 1.5 alarm | CRT |
| 18 | Curtain{{Module_Index}}-Louvre for Auto(%) | Curtain louvre for auto function(%) | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 18 | {{Name}}{{Module_Index}}-Valve Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 19 | Switch{{Module_Index}}-Time out | Alarm threshold set | 2 Bytes | 7.7 time (h) | CWTU |
| 19 | Curtain{{Module_Index}}-Heating for Auto | Curtain heating for auto function | 1 Bit | 1.2 boolean | CRWU |
| 19 | {{Name}}{{Module_Index}}-Valve Cooling | Valve open/close | 1 Bit | 1.9 open/close | CWU |
| 20 | Switch{{Module_Index}}-Time out | Operation sending | 1 Bit | 1.1 switch | CRT |
| 20 | Curtain{{Module_Index}}-Cooling for Auto | Curtain cooling for auto function | 1 Bit | 1.2 boolean | CRWU |
| 20 | {{Name}}{{Module_Index}}-Valve Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 21 | Switch{{Module_Index}}-Time out | Operation threshold set | 2 Bytes | 7.7 time (h) | CWTU |
| 21 | Curtain{{Module_Index}}-Auto Energy Enable | Curtain enable auto energy function | 1 Bit | 1.3 enable | CRWU |
| 21 | {{Name}}{{Module_Index}}-Fan | Fan speed automatic | 1 Bit | 1.3 enable | CWU |
| 22 | Switch{{Module_Index}}-Time out | Report ON time(hours) | 2 Bytes | 7.7 time (h) | CRTU |
| 22 | Curtain{{Module_Index}}-Status of Auto Sun Enable | Curtain Status of Auto Sun enable | 1 Bit | 1.3 enable | CRT |
| 22 | {{Name}}{{Module_Index}}-Fan | Fan speed with 0-255 value | 1 Byte | 5.100 fan stage (0..255) | CWU |
| 22 | {{Name}}{{Module_Index}}-Fan | Fan speed with % value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 23 | Switch{{Module_Index}}-Time out | Request ON time | 1 Bit | 1.17 trigger | CWTU |
| 23 | Curtain{{Module_Index}}-Status of Auto Energy Enable | Curtain Status of Auto Energy enable | 1 Bit | 1.3 enable | CRT |
| 23 | {{Name}}{{Module_Index}}-Fan | Fan speed 1 | 1 Bit | 1.1 switch | CWU |
| 24 | Switch{{Module_Index}}-Time out | Write ON time(hours) | 2 Bytes | 7.7 time (h) | CWTU |
| 24 | Curtain{{Module_Index}}-Safety Enable | Curtain enable safety function | 1 Bit | 1.3 enable | CWU |
| 24 | {{Name}}{{Module_Index}}-Fan | Fan speed 2 | 1 Bit | 1.1 switch | CWU |
| 25 | Switch{{Module_Index}}-Counter | Alarm | 1 Bit | 1.5 alarm | CRT |
| 25 | Curtain{{Module_Index}}-Status of Safety Enable | Curtain Status of Safety Enable | 1 Bit | 1.3 enable | CRT |
| 25 | {{Name}}{{Module_Index}}-Fan | Fan speed 3 | 1 Bit | 1.1 switch | CWU |
| 26 | Switch{{Module_Index}}-Counter | Alarm threshold set | 4 Bytes | 12.1 counter pulses (unsigned) | CWTU |
| 26 | Curtain{{Module_Index}}-Alarm of weak wind for safety | Curtain Alarm of weak wind for safety | 1 Bit | 1.5 alarm | CWU |
| 26 | {{Name}}{{Module_Index}}-Fan | Status fan speed 1 | 1 Bit | 1.1 switch | CRT |
| 27 | Switch{{Module_Index}}-Counter | Operation sending | 1 Bit | 1.1 switch | CRT |
| 27 | Curtain{{Module_Index}}-Alarm of slight wind for safety | Curtain Alarm of slight wind for safety | 1 Bit | 1.5 alarm | CWU |
| 27 | {{Name}}{{Module_Index}}-Fan | Status fan speed 2 | 1 Bit | 1.1 switch | CRT |
| 28 | Switch{{Module_Index}}-Counter | Operation threshold set | 4 Bytes | 12.1 counter pulses (unsigned) | CWTU |
| 28 | Curtain{{Module_Index}}-Alarm of strong wind for safety | Curtain Alarm of strong wind for safety | 1 Bit | 1.5 alarm | CWU |
| 28 | {{Name}}{{Module_Index}}-Fan | Status fan speed 3 | 1 Bit | 1.1 switch | CRT |
| 29 | Switch{{Module_Index}}-Counter | Report ON count(4 bytes) | 4 Bytes | 12.1 counter pulses (unsigned) | CRTU |
| 29 | Curtain{{Module_Index}}-Report Alarm of Wind Action | Curtain Report Alarm of Wind Action | 1 Bit | 1.11 state | CRT |
| 29 | {{Name}}{{Module_Index}}-Fan | Status fan speed with % value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 29 | {{Name}}{{Module_Index}}-Fan | Status fan speed with 0-255 value | 1 Byte | 5.100 fan stage (0..255) | CRT |
| 30 | Switch{{Module_Index}}-Counter | Request ON count | 1 Bit | 1.17 trigger | CWTU |
| 30 | Curtain{{Module_Index}}-Alarm of rain for safety | Curtain Alarm of rain for safety | 1 Bit | 1.5 alarm | CWU |
| 30 | {{Name}}{{Module_Index}}-Fan | Status fan On/Off | 1 Bit | 1.1 switch | CRT |
| 31 | Switch{{Module_Index}}-Counter | Write counter(4bytes) | 4 Bytes | 12.1 counter pulses (unsigned) | CWTU |
| 31 | Curtain{{Module_Index}}-Report Alarm of Rain Action | Curtain Report Alarm of Rain Action | 1 Bit | 1.11 state | CRT |
| 31 | {{Name}}{{Module_Index}}-Fan | Status fan speed automatic | 1 Bit | 1.3 enable | CRT |
| 32 | Curtain{{Module_Index}}-Alarm of frost for safety | Curtain Alarm of frost for safety | 1 Bit | 1.5 alarm | CWU |
| 32 | {{Name}}{{Module_Index}}-Fan | Limitation 1 | 1 Bit | 1.3 enable | CRWTU |
| 33 | Curtain{{Module_Index}}-Report Alarm of Frost Action | Curtain Report Alarm of Frost Action | 1 Bit | 1.11 state | CRT |
| 33 | {{Name}}{{Module_Index}}-Fan | Limitation 2 | 1 Bit | 1.3 enable | CRWTU |
| 34 | Curtain{{Module_Index}}-Force Operation1(2bit) | Curtain Force Operation1 | 2 Bit | 2.8 direction control 1 | CWU |
| 34 | {{Name}}{{Module_Index}}-Fan | Limitation 3 | 1 Bit | 1.3 enable | CRWTU |
| 35 | Curtain{{Module_Index}}-Force Operation2(1bit) | Curtain Force Operation2 | 1 Bit | 1.1 switch | CWU |
| 35 | {{Name}}{{Module_Index}}-Fan | Limitation 4 | 1 Bit | 1.3 enable | CRWTU |
| 36 | Curtain{{Module_Index}}-Force Operation3(1bit) | Curtain Force Operation3 | 1 Bit | 1.1 switch | CWU |
| 36 | {{Name}}{{Module_Index}}-Control mode | HVAC control mode (byte) | 1 Byte | 20.105 HVAC control mode | CWU |
| 37 | Curtain{{Module_Index}}-Report Action of Force | Curtain Report Action of Force | 1 Bit | 1.11 state | CRT |
| 37 | {{Name}}{{Module_Index}}-Control mode | Automatic heating/cooling mode | 1 Bit | 1.3 enable | CWU |
| 38 | Curtain{{Module_Index}}-Status of Force Enable | Curtain Status of Force enable | 1 Bit | 1.3 enable | CRT |
| 38 | {{Name}}{{Module_Index}}-Control mode | Heating mode | 1 Bit | 1.3 enable | CWU |
| 39 | {{Name}}{{Module_Index}}-Control mode | Cooling mode | 1 Bit | 1.3 enable | CWU |
| 40 | {{Name}}{{Module_Index}}-Control mode | Off mode | 1 Bit | 1.3 enable | CWU |
| 41 | {{Name}}{{Module_Index}}-Control mode | Fan only mode | 1 Bit | 1.3 enable | CWU |
| 42 | {{Name}}{{Module_Index}}-Operation mode | HVAC operation mode (byte) | 1 Byte | 20.102 HVAC mode | CWU |
| 43 | {{Name}}{{Module_Index}}-Operation mode | Comfort mode | 1 Bit | 1.1 switch | CWU |
| 44 | {{Name}}{{Module_Index}}-Operation mode | Standby mode | 1 Bit | 1.1 switch | CWU |
| 45 | {{Name}}{{Module_Index}}-Operation mode | Economy mode | 1 Bit | 1.1 switch | CWU |
| 46 | {{Name}}{{Module_Index}}-Operation mode | Building protection mode | 1 Bit | 1.1 switch | CWU |
| 47 | {{Name}}{{Module_Index}}-Energy saving function | Trigger | 1 Bit | 1.17 trigger | CWU |
| 48 | {{Name}}{{Module_Index}}-Energy saving function | Change delay time | 2 Bytes | 8.6 time lag (min) | CWU |
| 49 | {{Name}}{{Module_Index}}-Energy saving function | Change saving mode | 1 Byte | 20.102 HVAC mode | CWU |
| 50 | {{Name}}{{Module_Index}}-Control mode | Status of control mode(byte) | 1 Byte | 20.105 HVAC control mode | CRT |
| 51 | {{Name}}{{Module_Index}}-Control mode | Status of automatic mode | 1 Bit | 1.3 enable | CRT |
| 52 | {{Name}}{{Module_Index}}-Control mode | Status of heating mode | 1 Bit | 1.3 enable | CRT |
| 53 | {{Name}}{{Module_Index}}-Control mode | Status of cooling mode | 1 Bit | 1.3 enable | CRT |
| 54 | {{Name}}{{Module_Index}}-Control mode | Status of off mode | 1 Bit | 1.3 enable | CRT |
| 55 | {{Name}}{{Module_Index}}-Control mode | Status of fan only mode | 1 Bit | 1.3 enable | CRT |
| 56 | {{Name}}{{Module_Index}}-Operation mode | Status of operation mode(byte) | 1 Byte | 20.102 HVAC mode | CRT |
| 57 | {{Name}}{{Module_Index}}-Operation mode | Status of comfort mode | 1 Bit | 1.1 switch | CRT |
| 58 | {{Name}}{{Module_Index}}-Operation mode | Status of standby mode | 1 Bit | 1.1 switch | CRT |
| 59 | {{Name}}{{Module_Index}}-Operation mode | Status of economy mode | 1 Bit | 1.1 switch | CRT |
| 60 | {{Name}}{{Module_Index}}-Operation mode | Status of building protection | 1 Bit | 1.1 switch | CRT |
| 61 | {{Name}}{{Module_Index}}-Setpoint | Status of base setpoint temp. | 2 Bytes | 9.1 temperature (°C) | CRT |
| 62 | {{Name}}{{Module_Index}}-Valve | Pipe pressure protection | 1 Bit | 1.1 switch | CRT |
| 63 | {{Name}}{{Module_Index}}-Valve | Alarm of overtemp protection | 1 Bit | 1.5 alarm | CRT |
| 64 | {{Name}}{{Module_Index}}-Valve | Alarm of antifreeze protection | 1 Bit | 1.5 alarm | CRT |
| 65 | {{Name}}{{Module_Index}}-Setpoint | Normal-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 66 | {{Name}}{{Module_Index}}-Setpoint | Day-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 67 | {{Name}}{{Module_Index}}-Setpoint | Night-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 68 | {{Name}}{{Module_Index}}-Setpoint | Away-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 69 | {{Name}}{{Module_Index}}-Preset 1 | Preset 1 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 70 | {{Name}}{{Module_Index}}-Preset 1 | Time of day for preset 1 | 3 Bytes | 10.1 time of day | CRWTU |
| 71 | {{Name}}{{Module_Index}}-Preset 1 | Start/Stop heating for preset1 | 1 Bit | 1.10 start/stop | CRWTU |
| 72 | {{Name}}{{Module_Index}}-Preset 2 | Preset 2 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 73 | {{Name}}{{Module_Index}}-Preset 2 | Time of day for preset 2 | 3 Bytes | 10.1 time of day | CRWTU |
| 74 | {{Name}}{{Module_Index}}-Preset 2 | Start/Stop heating for preset2 | 1 Bit | 1.10 start/stop | CRWTU |
| 75 | {{Name}}{{Module_Index}}-Preset 3 | Preset 3 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 76 | {{Name}}{{Module_Index}}-Preset 3 | Time of day for preset 3 | 3 Bytes | 10.1 time of day | CRWTU |
| 77 | {{Name}}{{Module_Index}}-Preset 3 | Start/Stop heating for preset3 | 1 Bit | 1.10 start/stop | CRWTU |
| 78 | {{Name}}{{Module_Index}}-System | Working(1-ON,0-OFF) | 1 Bit | 1.1 switch | CRWTU |
| 79 | {{Name}}{{Module_Index}}-Mode | ON CMD for Normal-mode | 1 Bit | 1.1 switch | CRWTU |
| 80 | {{Name}}{{Module_Index}}-Mode | ON CMD for Day-mode | 1 Bit | 1.1 switch | CRWTU |
| 81 | {{Name}}{{Module_Index}}-Mode | ON CMD for Night-mode | 1 Bit | 1.1 switch | CRWTU |
| 82 | {{Name}}{{Module_Index}}-Mode | ON CMD for Away-mode | 1 Bit | 1.1 switch | CRWTU |
| 83 | {{Name}}{{Module_Index}}-Mode | ON CMD for Timer-mode | 1 Bit | 1.1 switch | CRWTU |
| 84 | {{Name}}{{Module_Index}}-Valve | Status value | 1 Bit | 1.1 switch | CRT |
| 85 | {{Name}}{{Module_Index}}-Valve | Trigger valve purge | 1 Bit | 1.17 trigger | CWU |
| 86 | {{Name}}{{Module_Index}}-Valve | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 87 | {{Name}}{{Module_Index}}-Setpoint | Status of base setpoint temp. | 2 Bytes | 9.1 temperature (°C) | CRT |
| 88 | {{Name}}{{Module_Index}}-Control value A | Control value A | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 89 | {{Name}}{{Module_Index}}-Control value A | Control value error signal | 1 Bit | 1.5 alarm | CRT |
| 90 | {{Name}}{{Module_Index}}-System | Status of working(1-ON,0-OFF) | 1 Bit | 1.1 switch | CRT |
| 91 | {{Name}}{{Module_Index}}-Mode | Status of Normal-mode | 1 Bit | 1.1 switch | CRT |
| 92 | {{Name}}{{Module_Index}}-Mode | Status of Day-mode | 1 Bit | 1.1 switch | CRT |
| 93 | {{Name}}{{Module_Index}}-Mode | Status of Night-mode | 1 Bit | 1.1 switch | CRT |
| 94 | {{Name}}{{Module_Index}}-Mode | Status of Away-mode | 1 Bit | 1.1 switch | CRT |
| 95 | {{Name}}{{Module_Index}}-Mode | Status of Timer-mode | 1 Bit | 1.1 switch | CRT |