MWC1-KT.10 MWC1KT10D2309
HDL · Order number MWC1KT10D2309 · Motor
Curtain Motor - KNX
Download .knxprod Curtain Motor(V1.0) 1.0 · 132 KB
Product
| Manufacturer | HDL |
|---|---|
| Product name | MWC1-KT.10 |
| Order number | MWC1KT10D2309 |
| Hardware | MWC1-KT.10 |
| Medium | Twisted Pair |
| Bus current (mA) | 8 |
| Rail mounted | No |
| Registration | Certified · 2024-05-06 |
| Languages | en-US, zh-CN |
| Catalog entry | M-0073_H-MWC1KT10D2309-10_HP-2300-10-CABA_CI-MWC1KT10D2309-1 |
| Fingerprint | CABA |
| SHA-256 | a8e041a41574155859e83cd2bb4edc7930022d960ac093f2abd5c58edac1e667 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Curtain Motor(V1.0) 1.0
| Application number | $2300 |
|---|---|
| Version | 1.0 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0f |
| Parameters | 187 |
| Group objects | 56 |
Group objects (56)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | System function | 1-open(100%),0-close(0%) | 1 Bit | 1.19 window/door | CWU |
| 1 | System function | 0-open(100%),1-close(0%) | 1 Bit | 1.19 window/door | CWU |
| 2 | System function | Stop ('0'/'1'-stop) | 1 Bit | 1.7 step | CWU |
| 3 | System function | Percentage set | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 4 | Heartbeat telegram | Send "0" periodically | 1 Bit | 1.3 enable | CT |
| 4 | Heartbeat telegram | Send "1" periodically | 1 Bit | 1.3 enable | CT |
| 4 | Heartbeat telegram | Send "1/0" alternately | 1 Bit | 1.3 enable | CT |
| 5 | X | X | 1 Bit | 1.1 switch | CWT |
| 6 | Limitation point set | '1'-set open limitation | 1 Bit | 1.11 state | CWU |
| 7 | Limitation point set | '1'-set close limitation | 1 Bit | 1.11 state | CWU |
| 8 | Reset limitation point | '1'-reset limitation | 1 Bit | 1.11 state | CWU |
| 9 | Short drag function | '1'-Enable,'0'-disable | 1 Bit | 1.3 enable | CWU |
| 10 | Open/close state report | Depends on control settings | 1 Bit | 1.19 window/door | CRT |
| 11 | Stop state report | '1'-stop | 1 Bit | 1.7 step | CRT |
| 11 | Stop state report | '0'-stop | 1 Bit | 1.7 step | CRT |
| 12 | Percentage state report | Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 13 | Set preset position | '0'-preset 1,'1'-preset 2 | 1 Bit | 1.22 scene | CWU |
| 14 | Set preset position | '0'-preset 3,'1'-preset 4 | 1 Bit | 1.22 scene | CWU |
| 15 | Move to preset position | '0'-preset 1,'1'-preset 2 | 1 Bit | 1.22 scene | CWU |
| 16 | Move to preset position | '0'-preset 3,'1'-preset 4 | 1 Bit | 1.22 scene | CWU |
| 17 | Preset report | Report '1' after operation | 1 Bit | 1.11 state | CRT |
| 17 | Preset report | Report '0' after operation | 1 Bit | 1.11 state | CRT |
| 18 | Enable/Disable safety mode | '1'-Enable,'0'-Disable | 1 Bit | 1.3 enable | CWTU |
| 19 | Report of safety mode | '1'-Enabled,'0'-Disabled | 1 Bit | 1.3 enable | CRT |
| 20 | Alarm of weak wind | '0'-No alarm,'1'-Alarm | 1 Bit | 1.5 alarm | CWTU |
| 20 | Alarm of weak wind | '1'-No alarm,'0'-Alarm | 1 Bit | 1.5 alarm | CWTU |
| 21 | Alarm of slight wind | '0'-No alarm,'1'-Alarm | 1 Bit | 1.5 alarm | CWTU |
| 21 | Alarm of slight wind | '1'-No alarm,'0'-Alarm | 1 Bit | 1.5 alarm | CWTU |
| 22 | Alarm of strong wind | '0'-No alarm,'1'-Alarm | 1 Bit | 1.5 alarm | CWTU |
| 22 | Alarm of strong wind | '1'-No alarm,'0'-Alarm | 1 Bit | 1.5 alarm | CWTU |
| 23 | Report after wind alarm reaction | Report '1' after operation | 1 Bit | 1.11 state | CRT |
| 23 | Report after wind alarm reaction | Report '0' after operation | 1 Bit | 1.11 state | CRT |
| 24 | Rain alarm | '0'-No alarm,'1'-Alarm | 1 Bit | 1.5 alarm | CWTU |
| 24 | Rain alarm | '1'-No alarm,'0'-Alarm | 1 Bit | 1.5 alarm | CWTU |
| 25 | Report after rain alarm reaction | Report '1' after operation | 1 Bit | 1.11 state | CRT |
| 25 | Report after rain alarm reaction | Report '0' after operation | 1 Bit | 1.11 state | CRT |
| 26 | Frost alarm | '0'-No alarm,'1'-Alarm | 1 Bit | 1.5 alarm | CWTU |
| 26 | Frost alarm | '1'-No alarm,'0'-Alarm | 1 Bit | 1.5 alarm | CWTU |
| 27 | Report after frost alarm reaction | Report '1' after operation | 1 Bit | 1.11 state | CRT |
| 27 | Report after frost alarm reaction | Report '0' after operation | 1 Bit | 1.11 state | CRT |
| 28 | Enable/Disable auto1 | '1'-Enable,'0'-Disable | 1 Bit | 1.3 enable | CWTU |
| 29 | Report of auto1 | '1'-Enabled,'0'-Disabled | 1 Bit | 1.3 enable | CRT |
| 30 | Auto1 | Sun-"0"/"1" | 1 Bit | 1.1 switch | CWTU |
| 31 | Enable/Disable auto2 | '1'-Enable,'0'-Disable | 1 Bit | 1.3 enable | CWU |
| 32 | Report of auto2 | '1'-Enabled,'0'-Disabled | 1 Bit | 1.3 enable | CRT |
| 33 | Auto2 presence check | '1'-presence,'0'-absence | 1 Bit | 1.2 boolean | CWTU |
| 34 | Auto2 | Heating-"0"/"1" | 1 Bit | 1.2 boolean | CWTU |
| 35 | Auto2 | Cooling-"0"/"1" | 1 Bit | 1.2 boolean | CWTU |
| 36 | Scene control | Call/Save scene number | 1 Byte | 18.1 scene control | CWU |
| 37 | Scene report | Report '1' after operation | 1 Bit | 1.11 state | CRT |
| 37 | Scene report | Report '0' after operation | 1 Bit | 1.11 state | CRT |
| 38 | Forced control | Forced operation 1(2 bit) | 2 Bit | 2.8 direction control 1 | CWTU |
| 39 | Forced control | Forced operation 2(1 bit) | 1 Bit | 1.1 switch | CWTU |
| 40 | Forced control | Forced operation 3(1 bit) | 1 Bit | 1.1 switch | CWTU |
| 41 | Forced operation report | Report '1' after operation | 1 Bit | 1.11 state | CRT |
| 41 | Forced operation report | Report '0' after operation | 1 Bit | 1.11 state | CRT |
Parameters (106)
| Parameter | Type | Default |
|---|---|---|
| Operation delay after recovered(1..255s) | unsignedInt 1…255 | 1 |
| Heartbeat telegram | list | Disable |
| Period of heartbeat transmission(1..65535s) | unsignedInt 1…65535 | 1 |
| Detection form of bus voltage | list | Disable |
| The hightest normal voltage(value*0.1V) | unsignedInt 0…60 | 32 |
| The lowest normal voltage(value*0.1V) | unsignedInt 0…60 | 20 |
| Way of detection report | list | Report after changed |
| Detection report period(1..255s) | unsignedInt 1…255 | 1 |
| Set/Reset limitation point via bus | list | Disable |
| Moving automatically after short drag | list | Enable |
| Enable/Disable short drag function via bus | list | Disable |
| Running direction | list | Forward |
| Report state after finished running | list | Enable |
| Report stop state after stopped | list | Report '1' |
| Report percentage state after finished change percentage | list | Enable |
| Automatically measure travel after downloading the database | list | Enable |
| Control setting | list | '1'-open(100%),'0'-close(0%) |
| Motor operation type after voltage recover | list | No action |
| Preset position | list | Disable |
| Safety control | list | Disable |
| Auto1 for sun | list | Disable |
| Auto2 for cooling and heating | list | Disable |
| Scene control | list | Disable |
| Forced control | list | Disable |
| Preset position 1 | list | 0%(close) |
| Preset position 2 | list | 25% |
| Preset position 3 | list | 50% |
| Preset position 4 | list | 100%(open) |
| Set preset position(1 bit) | list | Disable |
| Move to preset position(1 bit) | list | Disable |
| Preset report | list | Disable |
| Enable/Disable safety mode via bus | list | Disable |
| Report after safety mode enabled/disabled | list | Disable |
| Enable wind alarm | list | Enable |
| Alarm of weak wind | list | '1'-No alarm,'0'-Alarm |
| Reaction on weak wind alarm | list | Preset position 3 |
| Position for weak wind alarm | list | 90% |
| Alarm of slight wind | list | '1'-No alarm,'0'-Alarm |
| Reaction on slight wind alarm | list | Preset position 2 |
| Position for slight wind alarm | list | 75% |
| Alarm of strong wind | list | '1'-No alarm,'0'-Alarm |
| Reaction on strong wind alarm | list | Preset position 1 |
| Position for strong wind alarm | list | 0%(close) |
| Reaction on reset wind alarm | list | Preset position 4 |
| Position for reset wind alarm | list | 100%(open) |
| Report after wind alarm reaction | list | Disable |
| Enable rain alarm | list | Enable |
| Rain alarm | list | '1'-No alarm,'0'-Alarm |
| Reaction on rain alarm | list | Preset position 1 |
| Position for rain alarm | list | 0%(close) |
| Reaction on reset rain alarm | list | Preset position 4 |
| Position for reset rain alarm | list | 100%(open) |
| Report after rain alarm reaction | list | Disable |
| Enable frost alarm | list | Enable |
| Frost alarm | list | '1'-No alarm,'0'-Alarm |
| Reaction on frost alarm | list | Preset position 1 |
| Position for frost alarm | list | 0%(close) |
| Reaction on reset frost alarm | list | Preset position 4 |
| Position for reset frost alarm | list | 100%(open) |
| Report after frost alarm reaction | list | Disable |
| Priority for alarms | list | Frost>Rain>Wind |
| Safety mode after voltage recover | list | Invalid |
| Read alarm status after voltage recover | list | Disable |
| Delay for reading alarm status(2..255S) | unsignedInt 2…255 | 2 |
| If status have no update then repeatedly read(1 time/s) | list | 2 times |
| Enable/Disable auto1 via bus | list | Disable |
| Report after auto1 enabled | list | Disable |
| Delay for sun='0' (0..3600s) | unsignedInt 0…3600 | 0 |
| Delay for sun='1' (0..3600s) | unsignedInt 0…3600 | 0 |
| Reaction on sun='0' | list | No reaction |
| Position for sun='0' | list | 100%(open) |
| Reaction on sun='1' | list | No reaction |
| Position for sun='1' | list | 100%(open) |
| Auto1 mode after voltage recover | list | Invalid |
| Read auto1 status after voltage recover | list | Disable |
| Delay for reading auto1 status(2..255S) | unsignedInt 2…255 | 2 |
| Enable/Disable auto2 via bus | list | Disable |
| Report after auto2 enabled | list | Disable |
| Auto switch for presence check('1'-presence,'0'-absence) | list | '0'-auto1,'1'-auto2 |
| Delay for switch to auto1(0..3600s) | unsignedInt 0…3600 | 0 |
| Delay for switch to auto2(0..3600s) | unsignedInt 0…3600 | 0 |
| Reaction when heating='1' and sun='0' | list | No reaction |
| Position when heating='1' and sun='0' | list | 100%(open) |
| Reaction when heating='1' and sun='1' | list | No reaction |
| Position when heating='1' and sun='1' | list | 50% |
| Reaction when cooling='1' and sun='0' | list | No reaction |
| Position when cooling='1' and sun='0' | list | 0%(close) |
| Reaction when cooling='1' and sun='1' | list | No reaction |
| Position when cooling='1' and sun='1' | list | 50% |
| Output is assigned to(scene 1..64) | list | Invalid |
| Reaction on output position | list | No reaction |
| Output position | list | 100%(open) |
| Output delay | list | Disable |
| Delay(0..255 Min) | unsignedInt 0…255 | 0 |
| Delay(0..59 Sec) | unsignedInt 0…59 | 0 |
| Scene report | list | Disable |
| Forced operation 1(2 bit) | list | Enable |
| Forced operation 2(1 bit) | list | Enable |
| Reaction on forced output position | list | Preset position 3 |
| Output position | list | 0%(close) |
| Forced operation 3(1 bit) | list | Enable |
| Reaction after exit from forced operation | list | Last position |
| Forced operation after voltage recover | list | Invalid |
| Read forced operation status after voltage recover | list | Disable |
| Delay for reading forced operation status(2..255S) | unsignedInt 2…255 | 2 |
| Forced operation report | list | Disable |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Curtain Motor(V1.0) 1.0 latest | $2300 | CABA | 2026-11-25 | 132 KB | Download |
About this file
This is the official ETS product database for the HDL MWC1-KT.10 (MWC1KT10D2309), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from HDL
- M/AG40B.1 M/AG40B 1811 W006
- M/S410.1 M/S410 1811 W006
- M/CBVRV.GW.1 M/CBVRVGW1905
- M/DA6.10.1 M/DA 1110 D005
- MDL64-KT.53 M/DALI 1410 2603
- M/DALI.1 M/DALI 1410 DL001
- MDL64-KT.53 M/DALI 1410 DL002
- M/DLP04.1-A2 M/DLP 1209 P001
- M/DM02.1 M/DM02C1902
- M/DM02.1 M/DM02C2604
- M/DM04.1 M/DM04C1902
- M/DM04.1 M/DM04C2604