KNX Database
GVS AMMAF-03/06.1 Multifunctional Actuator,3-Fold,6A,Flush Mounted

Multifunctional Actuator,3-Fold,6A,Flush Mounted AMMAF-03/06.1

GVS · Order number AMMAF-03/06.1 · Input/Output › I/O Multifunction

Download .knxprod Multifunctional Actuator,3-Fold,6A,Flush Mounted/1.0 1.0 · 235 KB

Product

ManufacturerGVS
Product nameMultifunctional Actuator,3-Fold,6A,Flush Mounted
Order numberAMMAF-03/06.1
HardwareAMMAF-03/06.1
MediumTwisted Pair
Bus current (mA)7
Rail mountedNo
RegistrationCertified · 2021-08-17
Languagesde-DE, en-US
Catalog entryM-0085_H-AM20KA-1_HP-0055-10-BDEC_CI-AMMAF.2D03.2F06.2E1-1
FingerprintBDEC
SHA-256856358c995be02d0532468c076723219390ed69ebe1ea92b0bd8d279f8f05844
First seen2026-11-25
Markets69 markets

Application program: Multifunctional Actuator,3-Fold,6A,Flush Mounted/1.0 1.0

Application number$0055
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters1164
Group objects512
Group objects (512)
NoNameFunctionSizeDPTFlags
1GeneralIn operation1 Bit1.1 switchCT
2Output 1 SwitchSwitch1 Bit1.1 switchCW
2Output CurtainMove UP/DOWN1 Bit1.8 up/downCW
2Output 1 SwitchOn-off control value1 Bit1.1 switchCW
3Output 1 SwitchSwitch status1 Bit1.1 switchCRT
3Output CurtainSlat adj/stop1 Bit1.7 stepCW
3Output CurtainStop1 Bit1.7 stepCW
3Output 1 SwitchStatus of contact1 Bit1.1 switchCRT
4Output 1 SwitchEnable time function1 Bit1.3 enableCW
4Output CurtainReference movement1 Bit1.8 up/downCW
4Output 1 SwitchStatus of continuous, 1bit1 Bit1.1 switchCRT
5Output 1 SwitchDelay function1 Bit1.1 switchCW
5Output 1 SwitchStaircase function1 Bit1.1 switchCW
5Output 1 SwitchFlashing function1 Bit1.1 switchCW
5Output CurtainMove to position 0..100%1 Byte5.1 percentage (0..100%)CW
5Output 1 SwitchControl value(Continuous)1 Byte5.1 percentage (0..100%)CW
6Output 1 SwitchOperation hours counter4 Bytes13.100 time lag (s)CRWTU
6Output 1 SwitchOperation hours counter2 Bytes7.7 time (h)CRWTU
6Output CurtainSlat position 0..100%1 Byte5.1 percentage (0..100%)CW
6Output 1 SwitchStatus of continuous, 1byte1 Byte5.1 percentage (0..100%)CRT
7Output 1 SwitchScene1 Byte18.1 scene controlCW
7Output CurtainScene1 Byte18.1 scene controlCW
7Output 1 SwitchReport fault1 Bit1.5 alarmCRT
8Output 1 SwitchForced output1 Bit1.3 enableCW
8Output 1 SwitchForced output2 Bit2.1 switch controlCW
8Output CurtainPosition status 0..100%1 Byte5.1 percentage (0..100%)CRT
9Output 1 SwitchLogic 11 Bit1.2 booleanCW
9Output CurtainSlat status 0..100%1 Byte5.1 percentage (0..100%)CRT
10Output 1 SwitchLogic 21 Bit1.2 booleanCW
10Output CurtainSun operation1 Bit1.1 switchCW
11Output 2 SwitchSwitch1 Bit1.1 switchCW
11Output 2 SwitchOn-off control value1 Bit1.1 switchCW
11Output CurtainEnable auto.control1 Bit1.3 enableCW
12Output 2 SwitchSwitch status1 Bit1.1 switchCRT
12Output 2 SwitchStatus of contact1 Bit1.1 switchCRT
12Output CurtainSun: blind position 0..100%1 Byte5.1 percentage (0..100%)CW
12Output CurtainSun: shutter position 0..100%1 Byte5.1 percentage (0..100%)CW
13Output 2 SwitchEnable time function1 Bit1.3 enableCW
13Output CurtainSun:slat adj. 0...100%1 Byte5.1 percentage (0..100%)CW
13Output 2 SwitchStatus of continuous, 1bit1 Bit1.1 switchCRT
14Output 2 SwitchControl value(Continuous)1 Byte5.1 percentage (0..100%)CW
14Output 2 SwitchDelay function1 Bit1.1 switchCW
14Output 2 SwitchFlashing function1 Bit1.1 switchCW
14Output 2 SwitchStaircase function1 Bit1.1 switchCW
14Output CurtainSafety operation 11 Bit1.5 alarmCW
15Output 2 SwitchOperation hours counter2 Bytes7.7 time (h)CRWTU
15Output 2 SwitchOperation hours counter4 Bytes13.100 time lag (s)CRWTU
15Output CurtainSafety operation 21 Bit1.5 alarmCW
15Output 2 SwitchStatus of continuous, 1byte1 Byte5.1 percentage (0..100%)CRT
16Output 2 SwitchReport fault1 Bit1.5 alarmCRT
16Output 2 SwitchScene1 Byte18.1 scene controlCW
16Output CurtainStatus of operation1 ByteCRT
17Output 2 SwitchForced output1 Bit1.3 enableCW
17Output 2 SwitchForced output2 Bit2.1 switch controlCW
18Output 2 SwitchLogic 11 Bit1.2 booleanCW
19Output 2 SwitchLogic 21 Bit1.2 booleanCW
20Output 3 SwitchSwitch1 Bit1.1 switchCW
20Output 3 SwitchOn-off control value1 Bit1.1 switchCW
21Output 3 SwitchSwitch status1 Bit1.1 switchCRT
21Output 3 SwitchStatus of contact1 Bit1.1 switchCRT
22Output 3 SwitchEnable time function1 Bit1.3 enableCW
22Output 3 SwitchStatus of continuous, 1bit1 Bit1.1 switchCRT
23Output 3 SwitchDelay function1 Bit1.1 switchCW
23Output 3 SwitchFlashing function1 Bit1.1 switchCW
23Output 3 SwitchStaircase function1 Bit1.1 switchCW
23Output 3 SwitchControl value(Continuous)1 Byte5.1 percentage (0..100%)CW
24Output 3 SwitchOperation hours counter2 Bytes7.7 time (h)CRWTU
24Output 3 SwitchOperation hours counter4 Bytes13.100 time lag (s)CRWTU
24Output 3 SwitchStatus of continuous, 1byte1 Byte5.1 percentage (0..100%)CRT
25Output 3 SwitchScene1 Byte18.1 scene controlCW
25Output 3 SwitchReport fault1 Bit1.5 alarmCRT
26Output 3 SwitchForced output1 Bit1.3 enableCW
26Output 3 SwitchForced output2 Bit2.1 switch controlCW
27Output 3 SwitchLogic 11 Bit1.2 booleanCW
28Output 3 SwitchLogic 21 Bit1.2 booleanCW
29Output FanFan speed1 Byte5.1 percentage (0..100%)CW
29Output FanFan speed1 Bit1.1 switchCW
30Output FanFan speed 11 Bit1.1 switchCW
31Output FanFan speed 21 Bit1.1 switchCW
32Output FanFan speed 31 Bit1.1 switchCW
33Output FanStatus Fan ON/OFF1 Bit1.1 switchCRT
34Output FanStatus Fan speed1 Byte5.1 percentage (0..100%)CRT
35Output FanStatus Fan speed 11 Bit1.1 switchCRT
36Output FanStatus Fan speed 21 Bit1.1 switchCRT
37Output FanStatus Fan speed 31 Bit1.1 switchCRT
38Output FanAutomatic function1 Bit1.3 enableCW
39Output FanStatus Automatic1 Bit1.3 enableCRT
40Output FanForced operation1 Bit1.3 enableCW
41Output FanControl value 11 Byte5.1 percentage (0..100%)CW
41Output FanControl value1 Byte5.1 percentage (0..100%)CW
42Output FanControl value 21 Byte5.1 percentage (0..100%)CW
43Output FanSwitching control value 1/21 Bit1.1 switchCW
44Output FanControl value fault1 Bit1.5 alarmCRT
45Output ValveHeat/Cool mode status1 Bit1.100 cooling/heatingCRT
46Output ValveControl value fault1 Bit1.5 alarmCRT
47Output ValveDisable,Heat1 Bit1.3 enableCW
47Output ValveDisable,Heat/Cool1 Bit1.3 enableCW
48Output ValveControl value, Heat1 Bit1.1 switchCW
48Output ValveControl value, Heat1 Byte5.1 percentage (0..100%)CW
48Output ValveControl value, Heat/Cool1 Bit1.1 switchCW
48Output ValveControl value, Heat/Cool1 Byte5.1 percentage (0..100%)CW
49Output ValveValve status, Heat1 Bit1.1 switchCRT
49Output ValveValve status, Heat1 Byte5.1 percentage (0..100%)CRT
49Output ValveValve status, Heat/Cool1 Bit1.1 switchCRT
49Output ValveValve status, Heat/Cool1 Byte5.1 percentage (0..100%)CRT
50Output ValveTrigger valve purge, Heat1 Bit1.3 enableCW
50Output ValveTrigger valve purge, Heat/Cool1 Bit1.3 enableCW
51Output ValveValve purge status, Heat1 Bit1.3 enableCRT
51Output ValveValve purge status, Heat/Cool1 Bit1.3 enableCRT
52Output ValveDisable,Cool1 Bit1.3 enableCW
53Output ValveControl value, Cool1 Bit1.1 switchCW
53Output ValveControl value, Cool1 Byte5.1 percentage (0..100%)CW
54Output ValveValve status, Cool1 Bit1.1 switchCRT
54Output ValveValve status, Cool1 Byte5.1 percentage (0..100%)CRT
55Output ValveTrigger valve purge, Cool1 Bit1.3 enableCW
56Output ValveValve purge status, Cool1 Bit1.3 enableCRT
57Input 1Switch1 Bit1.1 switchCWTU
57Input 1Press, Switch1 Bit1.1 switchCWTU
57Input 1Short, Switch1 Bit1.1 switchCWTU
57Input 1Up/Down, Blind1 Bit1.8 up/downCWT
57Input 1Press, 1bit value1 Bit1.1 switchCT
57Input 1Press, 2bit value2 Bit2.1 switch controlCT
57Input 1Press, 4bit value4 Bit3.7 dimming controlCT
57Input 1Press, 1byte value1 Byte5.10 counter pulses (0..255)CT
57Input 1Press, 2byte value2 Bytes7.1 pulsesCT
57Input 1Short, 1bit value1 Bit1.1 switchCT
57Input 1Short, 2bit value2 Bit2.1 switch controlCT
57Input 1Short, 4bit value4 Bit3.7 dimming controlCT
57Input 1Short, 1byte value1 Byte5.10 counter pulses (0..255)CT
57Input 1Short, 2byte value2 Bytes7.1 pulsesCT
57Input 1Scene1 Byte18.1 scene controlCT
57Input 1Press, Scene1 Byte18.1 scene controlCT
57Input 1Short, Scene1 Byte18.1 scene controlCT
57Input 1Register value1 Byte5.10 counter pulses (0..255)CWT
57Input 1Object1-On/Off1 Bit1.1 switchCWT
57Input 1Object1-Up/Down1 Bit1.8 up/downCWT
57Input 1Object1-SceneControl1 Byte18.1 scene controlCT
57Input 1Object1-Percentage1 Byte5.1 percentage (0..100%)CT
57Input 1Object1-Unsigned value1 Byte5.10 counter pulses (0..255)CT
57Input 1Press, Delay mode1 Bit1.1 switchCT
57Input 1Press, Delay mode4 Bit3.7 dimming controlCT
57Input 1Press, Delay mode1 Byte5.10 counter pulses (0..255)CT
57Input 1Short, Delay mode1 Bit1.1 switchCT
57Input 1Short, Delay mode4 Bit3.7 dimming controlCT
57Input 1Short, Delay mode1 Byte5.10 counter pulses (0..255)CT
58Input 1Release, Switch1 Bit1.1 switchCWTU
58Input 1Long, Switch1 Bit1.1 switchCWTU
58Input 1Long, Dimming4 Bit3.7 dimming controlCWT
58Input 1Stop/Adjust, Blind1 Bit1.7 stepCWT
58Input 1Release, 1bit value1 Bit1.1 switchCT
58Input 1Release, 2bit value2 Bit2.1 switch controlCT
58Input 1Release, 4bit value4 Bit3.7 dimming controlCT
58Input 1Release, 1byte value1 Byte5.10 counter pulses (0..255)CT
58Input 1Release, 2byte value2 Bytes7.1 pulsesCT
58Input 1Long, 1bit value1 Bit1.1 switchCT
58Input 1Long, 2bit value2 Bit2.1 switch controlCT
58Input 1Long, 4bit value4 Bit3.7 dimming controlCT
58Input 1Long, 1byte value1 Byte5.10 counter pulses (0..255)CT
58Input 1Long, 2byte value2 Bytes7.1 pulsesCT
58Input 1Release, Scene1 Byte18.1 scene controlCT
58Input 1Long, Scene1 Byte18.1 scene controlCT
58Input 1Object2-On/Off1 Bit1.1 switchCWT
58Input 1Object2-Up/Down1 Bit1.8 up/downCWT
58Input 1Object2-SceneControl1 Byte18.1 scene controlCT
58Input 1Object2-Percentage1 Byte5.1 percentage (0..100%)CT
58Input 1Object2-Unsigned value1 Byte5.10 counter pulses (0..255)CT
58Input 1Long, Delay mode1 Bit1.1 switchCT
58Input 1Long, Delay mode4 Bit3.7 dimming controlCT
58Input 1Long, Delay mode1 Byte5.10 counter pulses (0..255)CT
59Input 1Object3-On/Off1 Bit1.1 switchCWT
59Input 1Object3-Up/Down1 Bit1.8 up/downCWT
59Input 1Object3-SceneControl1 Byte18.1 scene controlCT
59Input 1Object3-Percentage1 Byte5.1 percentage (0..100%)CT
59Input 1Object3-Unsigned value1 Byte5.10 counter pulses (0..255)CT
60Input 1Object4-On/Off1 Bit1.1 switchCWT
60Input 1Object4-Up/Down1 Bit1.8 up/downCWT
60Input 1Object4-SceneControl1 Byte18.1 scene controlCT
60Input 1Object4-Percentage1 Byte5.1 percentage (0..100%)CT
60Input 1Object4-Unsigned value1 Byte5.10 counter pulses (0..255)CT
61Input 1Disable1 Bit1.3 enableCW
62Input 2Switch1 Bit1.1 switchCWTU
62Input 2Press, Switch1 Bit1.1 switchCWTU
62Input 2Short, Switch1 Bit1.1 switchCWTU
62Input 2Up/Down, Blind1 Bit1.8 up/downCWT
62Input 2Press, 1bit value1 Bit1.1 switchCT
62Input 2Press, 2bit value2 Bit2.1 switch controlCT
62Input 2Press, 4bit value4 Bit3.7 dimming controlCT
62Input 2Press, 1byte value1 Byte5.10 counter pulses (0..255)CT
62Input 2Press, 2byte value2 Bytes7.1 pulsesCT
62Input 2Short, 1bit value1 Bit1.1 switchCT
62Input 2Short, 2bit value2 Bit2.1 switch controlCT
62Input 2Short, 4bit value4 Bit3.7 dimming controlCT
62Input 2Short, 1byte value1 Byte5.10 counter pulses (0..255)CT
62Input 2Short, 2byte value2 Bytes7.1 pulsesCT
62Input 2Scene1 Byte18.1 scene controlCT
62Input 2Press, Scene1 Byte18.1 scene controlCT
62Input 2Short, Scene1 Byte18.1 scene controlCT
62Input 2Register value1 Byte5.10 counter pulses (0..255)CWT
62Input 2Object1-On/Off1 Bit1.1 switchCWT
62Input 2Object1-Up/Down1 Bit1.8 up/downCWT
62Input 2Object1-SceneControl1 Byte18.1 scene controlCT
62Input 2Object1-Percentage1 Byte5.1 percentage (0..100%)CT
62Input 2Object1-Unsigned value1 Byte5.10 counter pulses (0..255)CT
62Input 2Press, Delay mode1 Bit1.1 switchCT
62Input 2Press, Delay mode4 Bit3.7 dimming controlCT
62Input 2Press, Delay mode1 Byte5.10 counter pulses (0..255)CT
62Input 2Short, Delay mode1 Bit1.1 switchCT
62Input 2Short, Delay mode4 Bit3.7 dimming controlCT
62Input 2Short, Delay mode1 Byte5.10 counter pulses (0..255)CT
63Input 2Release, Switch1 Bit1.1 switchCWTU
63Input 2Long, Switch1 Bit1.1 switchCWTU
63Input 2Long, Dimming4 Bit3.7 dimming controlCWT
63Input 2Stop/Adjust, Blind1 Bit1.7 stepCWT
63Input 2Release, 1bit value1 Bit1.1 switchCT
63Input 2Release, 2bit value2 Bit2.1 switch controlCT
63Input 2Release, 4bit value4 Bit3.7 dimming controlCT
63Input 2Release, 1byte value1 Byte5.10 counter pulses (0..255)CT
63Input 2Release, 2byte value2 Bytes7.1 pulsesCT
63Input 2Long, 1bit value1 Bit1.1 switchCT
63Input 2Long, 2bit value2 Bit2.1 switch controlCT
63Input 2Long, 4bit value4 Bit3.7 dimming controlCT
63Input 2Long, 1byte value1 Byte5.10 counter pulses (0..255)CT
63Input 2Long, 2byte value2 Bytes7.1 pulsesCT
63Input 2Release, Scene1 Byte18.1 scene controlCT
63Input 2Long, Scene1 Byte18.1 scene controlCT
63Input 2Object2-On/Off1 Bit1.1 switchCWT
63Input 2Object2-Up/Down1 Bit1.8 up/downCWT
63Input 2Object2-SceneControl1 Byte18.1 scene controlCT
63Input 2Object2-Percentage1 Byte5.1 percentage (0..100%)CT
63Input 2Object2-Unsigned value1 Byte5.10 counter pulses (0..255)CT
63Input 2Long, Delay mode1 Bit1.1 switchCT
63Input 2Long, Delay mode4 Bit3.7 dimming controlCT
63Input 2Long, Delay mode1 Byte5.10 counter pulses (0..255)CT
64Input 2Object3-On/Off1 Bit1.1 switchCWT
64Input 2Object3-Up/Down1 Bit1.8 up/downCWT
64Input 2Object3-SceneControl1 Byte18.1 scene controlCT
64Input 2Object3-Percentage1 Byte5.1 percentage (0..100%)CT
64Input 2Object3-Unsigned value1 Byte5.10 counter pulses (0..255)CT
65Input 2Object4-On/Off1 Bit1.1 switchCWT
65Input 2Object4-Up/Down1 Bit1.8 up/downCWT
65Input 2Object4-SceneControl1 Byte18.1 scene controlCT
65Input 2Object4-Percentage1 Byte5.1 percentage (0..100%)CT
65Input 2Object4-Unsigned value1 Byte5.10 counter pulses (0..255)CT
66Input 2Disable1 Bit1.3 enableCW
67Input 3Switch1 Bit1.1 switchCWTU
67Input 3Press, Switch1 Bit1.1 switchCWTU
67Input 3Short, Switch1 Bit1.1 switchCWTU
67Input 3Up/Down, Blind1 Bit1.8 up/downCWT
67Input 3Press, 1bit value1 Bit1.1 switchCT
67Input 3Press, 2bit value2 Bit2.1 switch controlCT
67Input 3Press, 4bit value4 Bit3.7 dimming controlCT
67Input 3Press, 1byte value1 Byte5.10 counter pulses (0..255)CT
67Input 3Press, 2byte value2 Bytes7.1 pulsesCT
67Input 3Short, 1bit value1 Bit1.1 switchCT
67Input 3Short, 2bit value2 Bit2.1 switch controlCT
67Input 3Short, 4bit value4 Bit3.7 dimming controlCT
67Input 3Short, 1byte value1 Byte5.10 counter pulses (0..255)CT
67Input 3Short, 2byte value2 Bytes7.1 pulsesCT
67Input 3Scene1 Byte18.1 scene controlCT
67Input 3Press, Scene1 Byte18.1 scene controlCT
67Input 3Short, Scene1 Byte18.1 scene controlCT
67Input 3Register value1 Byte5.10 counter pulses (0..255)CWT
67Input 3Object1-On/Off1 Bit1.1 switchCWT
67Input 3Object1-Up/Down1 Bit1.8 up/downCWT
67Input 3Object1-SceneControl1 Byte18.1 scene controlCT
67Input 3Object1-Percentage1 Byte5.1 percentage (0..100%)CT
67Input 3Object1-Unsigned value1 Byte5.10 counter pulses (0..255)CT
67Input 3Press, Delay mode1 Bit1.1 switchCT
67Input 3Press, Delay mode4 Bit3.7 dimming controlCT
67Input 3Press, Delay mode1 Byte5.10 counter pulses (0..255)CT
67Input 3Short, Delay mode1 Bit1.1 switchCT
67Input 3Short, Delay mode4 Bit3.7 dimming controlCT
67Input 3Short, Delay mode1 Byte5.10 counter pulses (0..255)CT
68Input 3Release, Switch1 Bit1.1 switchCWTU
68Input 3Long, Switch1 Bit1.1 switchCWTU
68Input 3Long, Dimming4 Bit3.7 dimming controlCWT
68Input 3Stop/Adjust, Blind1 Bit1.7 stepCWT
68Input 3Release, 1bit value1 Bit1.1 switchCT
68Input 3Release, 2bit value2 Bit2.1 switch controlCT
68Input 3Release, 4bit value4 Bit3.7 dimming controlCT
68Input 3Release, 1byte value1 Byte5.10 counter pulses (0..255)CT
68Input 3Release, 2byte value2 Bytes7.1 pulsesCT
68Input 3Long, 1bit value1 Bit1.1 switchCT
68Input 3Long, 2bit value2 Bit2.1 switch controlCT
68Input 3Long, 4bit value4 Bit3.7 dimming controlCT
68Input 3Long, 1byte value1 Byte5.10 counter pulses (0..255)CT
68Input 3Long, 2byte value2 Bytes7.1 pulsesCT
68Input 3Release, Scene1 Byte18.1 scene controlCT
68Input 3Long, Scene1 Byte18.1 scene controlCT
68Input 3Object2-On/Off1 Bit1.1 switchCWT
68Input 3Object2-Up/Down1 Bit1.8 up/downCWT
68Input 3Object2-SceneControl1 Byte18.1 scene controlCT
68Input 3Object2-Percentage1 Byte5.1 percentage (0..100%)CT
68Input 3Object2-Unsigned value1 Byte5.10 counter pulses (0..255)CT
68Input 3Long, Delay mode1 Bit1.1 switchCT
68Input 3Long, Delay mode4 Bit3.7 dimming controlCT
68Input 3Long, Delay mode1 Byte5.10 counter pulses (0..255)CT
69Input 3Object3-On/Off1 Bit1.1 switchCWT
69Input 3Object3-Up/Down1 Bit1.8 up/downCWT
69Input 3Object3-SceneControl1 Byte18.1 scene controlCT
69Input 3Object3-Percentage1 Byte5.1 percentage (0..100%)CT
69Input 3Object3-Unsigned value1 Byte5.10 counter pulses (0..255)CT
70Input 3Object4-On/Off1 Bit1.1 switchCWT
70Input 3Object4-Up/Down1 Bit1.8 up/downCWT
70Input 3Object4-SceneControl1 Byte18.1 scene controlCT
70Input 3Object4-Percentage1 Byte5.1 percentage (0..100%)CT
70Input 3Object4-Unsigned value1 Byte5.10 counter pulses (0..255)CT
71Input 3Disable1 Bit1.3 enableCW
72Input 4Switch1 Bit1.1 switchCWTU
72Input 4Press, Switch1 Bit1.1 switchCWTU
72Input 4Short, Switch1 Bit1.1 switchCWTU
72Input 4Up/Down, Blind1 Bit1.8 up/downCWT
72Input 4Press, 1bit value1 Bit1.1 switchCT
72Input 4Press, 2bit value2 Bit2.1 switch controlCT
72Input 4Press, 4bit value4 Bit3.7 dimming controlCT
72Input 4Press, 1byte value1 Byte5.10 counter pulses (0..255)CT
72Input 4Press, 2byte value2 Bytes7.1 pulsesCT
72Input 4Short, 1bit value1 Bit1.1 switchCT
72Input 4Short, 2bit value2 Bit2.1 switch controlCT
72Input 4Short, 4bit value4 Bit3.7 dimming controlCT
72Input 4Short, 1byte value1 Byte5.10 counter pulses (0..255)CT
72Input 4Short, 2byte value2 Bytes7.1 pulsesCT
72Input 4Scene1 Byte18.1 scene controlCT
72Input 4Press, Scene1 Byte18.1 scene controlCT
72Input 4Short, Scene1 Byte18.1 scene controlCT
72Input 4Register value1 Byte5.10 counter pulses (0..255)CWT
72Input 4Object1-On/Off1 Bit1.1 switchCWT
72Input 4Object1-Up/Down1 Bit1.8 up/downCWT
72Input 4Object1-SceneControl1 Byte18.1 scene controlCT
72Input 4Object1-Percentage1 Byte5.1 percentage (0..100%)CT
72Input 4Object1-Unsigned value1 Byte5.10 counter pulses (0..255)CT
72Input 4Press, Delay mode1 Bit1.1 switchCT
72Input 4Press, Delay mode4 Bit3.7 dimming controlCT
72Input 4Press, Delay mode1 Byte5.10 counter pulses (0..255)CT
72Input 4Short, Delay mode1 Bit1.1 switchCT
72Input 4Short, Delay mode4 Bit3.7 dimming controlCT
72Input 4Short, Delay mode1 Byte5.10 counter pulses (0..255)CT
73Input 4Release, Switch1 Bit1.1 switchCWTU
73Input 4Long, Switch1 Bit1.1 switchCWTU
73Input 4Long, Dimming4 Bit3.7 dimming controlCWT
73Input 4Stop/Adjust, Blind1 Bit1.7 stepCWT
73Input 4Release, 1bit value1 Bit1.1 switchCT
73Input 4Release, 2bit value2 Bit2.1 switch controlCT
73Input 4Release, 4bit value4 Bit3.7 dimming controlCT
73Input 4Release, 1byte value1 Byte5.10 counter pulses (0..255)CT
73Input 4Release, 2byte value2 Bytes7.1 pulsesCT
73Input 4Long, 1bit value1 Bit1.1 switchCT
73Input 4Long, 2bit value2 Bit2.1 switch controlCT
73Input 4Long, 4bit value4 Bit3.7 dimming controlCT
73Input 4Long, 1byte value1 Byte5.10 counter pulses (0..255)CT
73Input 4Long, 2byte value2 Bytes7.1 pulsesCT
73Input 4Release, Scene1 Byte18.1 scene controlCT
73Input 4Long, Scene1 Byte18.1 scene controlCT
73Input 4Object2-On/Off1 Bit1.1 switchCWT
73Input 4Object2-Up/Down1 Bit1.8 up/downCWT
73Input 4Object2-SceneControl1 Byte18.1 scene controlCT
73Input 4Object2-Percentage1 Byte5.1 percentage (0..100%)CT
73Input 4Object2-Unsigned value1 Byte5.10 counter pulses (0..255)CT
73Input 4Long, Delay mode1 Bit1.1 switchCT
73Input 4Long, Delay mode4 Bit3.7 dimming controlCT
73Input 4Long, Delay mode1 Byte5.10 counter pulses (0..255)CT
74Input 4Object3-On/Off1 Bit1.1 switchCWT
74Input 4Object3-Up/Down1 Bit1.8 up/downCWT
74Input 4Object3-SceneControl1 Byte18.1 scene controlCT
74Input 4Object3-Percentage1 Byte5.1 percentage (0..100%)CT
74Input 4Object3-Unsigned value1 Byte5.10 counter pulses (0..255)CT
75Input 4Object4-On/Off1 Bit1.1 switchCWT
75Input 4Object4-Up/Down1 Bit1.8 up/downCWT
75Input 4Object4-SceneControl1 Byte18.1 scene controlCT
75Input 4Object4-Percentage1 Byte5.1 percentage (0..100%)CT
75Input 4Object4-Unsigned value1 Byte5.10 counter pulses (0..255)CT
76Input 4Disable1 Bit1.3 enableCW
77Input 5Switch1 Bit1.1 switchCWTU
77Input 5Press, Switch1 Bit1.1 switchCWTU
77Input 5Short, Switch1 Bit1.1 switchCWTU
77Input 5Up/Down, Blind1 Bit1.8 up/downCWT
77Input 5Press, 1bit value1 Bit1.1 switchCT
77Input 5Press, 2bit value2 Bit2.1 switch controlCT
77Input 5Press, 4bit value4 Bit3.7 dimming controlCT
77Input 5Press, 1byte value1 Byte5.10 counter pulses (0..255)CT
77Input 5Press, 2byte value2 Bytes7.1 pulsesCT
77Input 5Short, 1bit value1 Bit1.1 switchCT
77Input 5Short, 2bit value2 Bit2.1 switch controlCT
77Input 5Short, 4bit value4 Bit3.7 dimming controlCT
77Input 5Short, 1byte value1 Byte5.10 counter pulses (0..255)CT
77Input 5Short, 2byte value2 Bytes7.1 pulsesCT
77Input 5Scene1 Byte18.1 scene controlCT
77Input 5Press, Scene1 Byte18.1 scene controlCT
77Input 5Short, Scene1 Byte18.1 scene controlCT
77Input 5Register value1 Byte5.10 counter pulses (0..255)CWT
77Input 5Object1-On/Off1 Bit1.1 switchCWT
77Input 5Object1-Up/Down1 Bit1.8 up/downCWT
77Input 5Object1-SceneControl1 Byte18.1 scene controlCT
77Input 5Object1-Percentage1 Byte5.1 percentage (0..100%)CT
77Input 5Object1-Unsigned value1 Byte5.10 counter pulses (0..255)CT
77Input 5Press, Delay mode1 Bit1.1 switchCT
77Input 5Press, Delay mode4 Bit3.7 dimming controlCT
77Input 5Press, Delay mode1 Byte5.10 counter pulses (0..255)CT
77Input 5Short, Delay mode1 Bit1.1 switchCT
77Input 5Short, Delay mode4 Bit3.7 dimming controlCT
77Input 5Short, Delay mode1 Byte5.10 counter pulses (0..255)CT
78Input 5Release, Switch1 Bit1.1 switchCWTU
78Input 5Long, Switch1 Bit1.1 switchCWTU
78Input 5Long, Dimming4 Bit3.7 dimming controlCWT
78Input 5Stop/Adjust, Blind1 Bit1.7 stepCWT
78Input 5Release, 1bit value1 Bit1.1 switchCT
78Input 5Release, 2bit value2 Bit2.1 switch controlCT
78Input 5Release, 4bit value4 Bit3.7 dimming controlCT
78Input 5Release, 1byte value1 Byte5.10 counter pulses (0..255)CT
78Input 5Release, 2byte value2 Bytes7.1 pulsesCT
78Input 5Long, 1bit value1 Bit1.1 switchCT
78Input 5Long, 2bit value2 Bit2.1 switch controlCT
78Input 5Long, 4bit value4 Bit3.7 dimming controlCT
78Input 5Long, 1byte value1 Byte5.10 counter pulses (0..255)CT
78Input 5Long, 2byte value2 Bytes7.1 pulsesCT
78Input 5Release, Scene1 Byte18.1 scene controlCT
78Input 5Long, Scene1 Byte18.1 scene controlCT
78Input 5Object2-On/Off1 Bit1.1 switchCWT
78Input 5Object2-Up/Down1 Bit1.8 up/downCWT
78Input 5Object2-SceneControl1 Byte18.1 scene controlCT
78Input 5Object2-Percentage1 Byte5.1 percentage (0..100%)CT
78Input 5Object2-Unsigned value1 Byte5.10 counter pulses (0..255)CT
78Input 5Long, Delay mode1 Bit1.1 switchCT
78Input 5Long, Delay mode4 Bit3.7 dimming controlCT
78Input 5Long, Delay mode1 Byte5.10 counter pulses (0..255)CT
79Input 5Object3-On/Off1 Bit1.1 switchCWT
79Input 5Object3-Up/Down1 Bit1.8 up/downCWT
79Input 5Object3-SceneControl1 Byte18.1 scene controlCT
79Input 5Object3-Percentage1 Byte5.1 percentage (0..100%)CT
79Input 5Object3-Unsigned value1 Byte5.10 counter pulses (0..255)CT
80Input 5Object4-On/Off1 Bit1.1 switchCWT
80Input 5Object4-Up/Down1 Bit1.8 up/downCWT
80Input 5Object4-SceneControl1 Byte18.1 scene controlCT
80Input 5Object4-Percentage1 Byte5.1 percentage (0..100%)CT
80Input 5Object4-Unsigned value1 Byte5.10 counter pulses (0..255)CT
81Input 5Disable1 Bit1.3 enableCW
82Input 6Switch1 Bit1.1 switchCWTU
82Input 6Press, Switch1 Bit1.1 switchCWTU
82Input 6Short, Switch1 Bit1.1 switchCWTU
82Input 6Up/Down, Blind1 Bit1.8 up/downCWT
82Input 6Press, 1bit value1 Bit1.1 switchCT
82Input 6Press, 2bit value2 Bit2.1 switch controlCT
82Input 6Press, 4bit value4 Bit3.7 dimming controlCT
82Input 6Press, 1byte value1 Byte5.10 counter pulses (0..255)CT
82Input 6Press, 2byte value2 Bytes7.1 pulsesCT
82Input 6Short, 1bit value1 Bit1.1 switchCT
82Input 6Short, 2bit value2 Bit2.1 switch controlCT
82Input 6Short, 4bit value4 Bit3.7 dimming controlCT
82Input 6Short, 1byte value1 Byte5.10 counter pulses (0..255)CT
82Input 6Short, 2byte value2 Bytes7.1 pulsesCT
82Input 6Scene1 Byte18.1 scene controlCT
82Input 6Press, Scene1 Byte18.1 scene controlCT
82Input 6Short, Scene1 Byte18.1 scene controlCT
82Input 6Register value1 Byte5.10 counter pulses (0..255)CWT
82Input 6Object1-On/Off1 Bit1.1 switchCWT
82Input 6Object1-Up/Down1 Bit1.8 up/downCWT
82Input 6Object1-SceneControl1 Byte18.1 scene controlCT
82Input 6Object1-Percentage1 Byte5.1 percentage (0..100%)CT
82Input 6Object1-Unsigned value1 Byte5.10 counter pulses (0..255)CT
82Input 6Press, Delay mode1 Bit1.1 switchCT
82Input 6Press, Delay mode4 Bit3.7 dimming controlCT
82Input 6Press, Delay mode1 Byte5.10 counter pulses (0..255)CT
82Input 6Short, Delay mode1 Bit1.1 switchCT
82Input 6Short, Delay mode4 Bit3.7 dimming controlCT
82Input 6Short, Delay mode1 Byte5.10 counter pulses (0..255)CT
83Input 6Release, Switch1 Bit1.1 switchCWTU
83Input 6Long, Switch1 Bit1.1 switchCWTU
83Input 6Long, Dimming4 Bit3.7 dimming controlCWT
83Input 6Stop/Adjust, Blind1 Bit1.7 stepCWT
83Input 6Release, 1bit value1 Bit1.1 switchCT
83Input 6Release, 2bit value2 Bit2.1 switch controlCT
83Input 6Release, 4bit value4 Bit3.7 dimming controlCT
83Input 6Release, 1byte value1 Byte5.10 counter pulses (0..255)CT
83Input 6Release, 2byte value2 Bytes7.1 pulsesCT
83Input 6Long, 1bit value1 Bit1.1 switchCT
83Input 6Long, 2bit value2 Bit2.1 switch controlCT
83Input 6Long, 4bit value4 Bit3.7 dimming controlCT
83Input 6Long, 1byte value1 Byte5.10 counter pulses (0..255)CT
83Input 6Long, 2byte value2 Bytes7.1 pulsesCT
83Input 6Release, Scene1 Byte18.1 scene controlCT
83Input 6Long, Scene1 Byte18.1 scene controlCT
83Input 6Object2-On/Off1 Bit1.1 switchCWT
83Input 6Object2-Up/Down1 Bit1.8 up/downCWT
83Input 6Object2-SceneControl1 Byte18.1 scene controlCT
83Input 6Object2-Percentage1 Byte5.1 percentage (0..100%)CT
83Input 6Object2-Unsigned value1 Byte5.10 counter pulses (0..255)CT
83Input 6Long, Delay mode1 Bit1.1 switchCT
83Input 6Long, Delay mode4 Bit3.7 dimming controlCT
83Input 6Long, Delay mode1 Byte5.10 counter pulses (0..255)CT
84Input 6Object3-On/Off1 Bit1.1 switchCWT
84Input 6Object3-Up/Down1 Bit1.8 up/downCWT
84Input 6Object3-SceneControl1 Byte18.1 scene controlCT
84Input 6Object3-Percentage1 Byte5.1 percentage (0..100%)CT
84Input 6Object3-Unsigned value1 Byte5.10 counter pulses (0..255)CT
85Input 6Object4-On/Off1 Bit1.1 switchCWT
85Input 6Object4-Up/Down1 Bit1.8 up/downCWT
85Input 6Object4-SceneControl1 Byte18.1 scene controlCT
85Input 6Object4-Percentage1 Byte5.1 percentage (0..100%)CT
85Input 6Object4-Unsigned value1 Byte5.10 counter pulses (0..255)CT
86Input 6Disable1 Bit1.3 enableCW
87LED 1Status1 Byte5.10 counter pulses (0..255)CWTU
87LED 1Status1 Bit1.1 switchCWTU
88LED 2Status1 Byte5.10 counter pulses (0..255)CWTU
88LED 2Status1 Bit1.1 switchCWTU
89LED 3Status1 Byte5.10 counter pulses (0..255)CWTU
89LED 3Status1 Bit1.1 switchCWTU
90LED 4Status1 Byte5.10 counter pulses (0..255)CWTU
90LED 4Status1 Bit1.1 switchCWTU
91LED 5Status1 Byte5.10 counter pulses (0..255)CWTU
91LED 5Status1 Bit1.1 switchCWTU
92LED 6Status1 Byte5.10 counter pulses (0..255)CWTU
92LED 6Status1 Bit1.1 switchCWTU
Parameters (292)
ParameterTypeDefault
Operation delay after power on [5..250]unsignedInt 5…2505
Limit number of send telegramlistNo
Periodlist100ms
Max.number tele.within a period [1..255]unsignedInt 1…255100
Sending cycle of "In operation" telegram [1..240,0=inactive]unsignedInt 0…2400
Function of Channel 1listDisable
Function of Channel 2listDisable
Function of Channel 3listDisable
Function of Channel 4listDisable
Function of Channel 5listDisable
Function of Channel 6listDisable
Output LED voltagelist5V(Max. 1mA)
The connect type for the LEDlistCommon Anode
LED object need send read request after power onlistYes
Initial status indicationlistNo
Debounce timelist50
Outputs config aslist3 switch outputs
Output 1 SwitchlistDisable
Output 2 SwitchlistDisable
Output 3 SwitchlistDisable
Fan output is fixed forlist1level:1; 2level:1&2; 3level: 1&2&3
If Fan speed set to 1 level, Output 2&3 as switch outputlist<<--Attention
If Fan speed set to 2 level, Output 3 as switch outputlist<<--Attention
Work mode of the channel islistSwitch actuator
If bus recovery, contact islistUnchange
If bus failure, contact islistUnchange
After downloading,contact islistOpen
Set the reply mode of switch statuslistRespond after change
Object value of switch statuslist1=contact close;0=contact open
Contact position if tele.value is "1" ("0" is opposite of "1" if changed)listClose
Special function of channellistDisable
Valve typelistNormal (de-energised closed)
If bus recovery, valve positionlist0%[Closed]
PWM cycle time for continuous [60..65535]unsignedInt 60…65535120
Control telegram is received aslist1bit (on-off control or PWM)
Reply the status for continuous controllistNo reply
Reply the status for contactlistYes, 1=contact close; 0=contact open
Function for monitoring islistEnable
Cyclic monitoring of thermostat [0..65535]unsignedInt 0…65535120
Valve position during faultlistUnchange
Send object "Report fault" islistEnable
Function of forced operation islistDisable
Valve position during forced operationlistUnchange
Function of "Time"listDisable
Function of "Logic"listDisable
Function of "Scene"listDisable
Function of "Forced"listDisable
Force operation typelist1Bit
Contact position if forced operationlistUnchange
Function of "Operation hours counter"listDisable
Object datatype of "Operation hours counter"list4 byte Value in s(DPT13.100)
Cyclically send counter value in [0..100] ("0" = not send,only for reading)unsignedInt 0…1000
Type of time functionlistDelay
Delay for switch on: --[0..240]unsignedInt 0…2400
--[0..59]unsignedInt 0…590
Delay for switch off: --[0..240]unsignedInt 0…2400
Number of ON-implused (1..255,0=no limited)unsignedInt 0…2550
Contact position after flashinglistUnchange
Control mode of flashinglistStart with "1",Stop with"0"
Duration of staircase lighting: --[0..1000]unsignedInt 0…10001
Control mode of staircase lightinglistStart with "1",Stop with"0"
During the lighting time,if receive the "start" telegramlistRestart duration of staircase lighting
Enable input 0listDisable
Input 0 reverselistNo
The input 1 of logiclistDisable
Logic function typelistAND
Input 1 reverselistNo
Result reverselistNo
Value of input1 after bus recoverylist0
The input 2 of logiclistDisable
Input 2 reverselistNo
Value of input2 after bus recoverylist0
Overwrite scene stored values during downloadlistEnable
1> channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
Standard output value islistOpen
2> channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
3> channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
4> channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
5> channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
6> channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
7> channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
8> channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
Function for monitoring islistDisable
Overwrite scene stored values during downloadlistDisable
Config channel function aslistVenetian Blind
Motor typelistAC-motor
Drive pulse time [1..50]unsignedInt 1…501
If bus recovery, position islistUnchange
If bus failure, position islistUnchange
After reference movement,Position islistDisable
Position of slat after arriving on lower end positionlist100
When blind is under end position, up/down object function islistDisable
Set response mode for positionlistRespond after change
Total travel time [20..50000]unsignedInt 20…50000600
Delay time from switch-on to moving [0..200]unsignedInt 0…2000
Duration of Slat adjustment [10...250]unsignedInt 10…25020
Total travel time of Slat 0..100% in [10..250]unsignedInt 10…250100
Pause on change in direction [5...255]unsignedInt 5…25510
Additional travel time in upward direction [0..255]unsignedInt 0…2550
Function automaticlistInactive
Object value of "Enable auto. control" after bus voltage recoverylist"0"(Disable auto. control)
Automatically enable for auto.controllistNo
Enable auto. control after [10..6000]unsignedInt 10…600010
Position if sun = 1 (sun is shining)listDown
Delay time on sun = 1 [0...65535]unsignedInt 0…6553510
Position if sun = 0 (sun not shining)listDown
Delay time on sun = 0 [0...65535]unsignedInt 0…6553510
Function scenelistInactive
1> Channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
Blind position: [0..100] (0=top,100=bottom)unsignedInt 0…1000
Slat position: [0..100] (0=open,100=close)unsignedInt 0…1000
2> Channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
3> Channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
4> Channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
5> Channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
6> Channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
7> Channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
8> Channel is assigned to [1..64,0=no assignment]unsignedInt 0…640
Safety functionlistInactive
Safety operation 1listInactive
Safety operation trigger value (Cancel safety is opposite of selection)list0
Position on safety operation 1listUnchange
Cyclic monitoring time in [0..65535, 0= no monitoring]unsignedInt 0…65535120
Safety operation 2listInactive
Position on safety operation 2listUnchange
Position with canceling of the safety operationlistUnchange
Delay time from switch-off to Stop [0..200]unsignedInt 0…2000
Shutter position: [0..100] (0=top,100=bottom)unsignedInt 0…1000
Modify the duration via object [0..60059]listDisable
HVAC control modelistHeating and Cooling
HVAC Systemlist4 pipes system
Number of control valuelist2 control value
Monitoring control valuelistEnable
Monitoring period of control value [10..65535]unsignedInt 10…6553560
Reply mode of Obj."Control value fault"listRespond after change
Control value after fault occurs [0..100]unsignedInt 0…1000
Valve control modelist2 state-ON/OFF
Valve typelistNormal(de-energised closed)
If bus recovery, valve positionlistUnchange
If bus failure, valve positionlistUnchange
Reply mode for valve statuslistRespond after change
PWM cycle time [10..6000]unsignedInt 10…6000120
Observe reversing timelist400ms
Valve control time 0%->100% [50..6000]unsignedInt 50…6000100
Automatic adjust valve positionlistNo
Number of valve control up to adjust [1..65535]unsignedInt 1…65535200
Correct Valve characteristic curvelistNo
Min. controller value for closed valve [0..100]unsignedInt 0…1000
Max. controller value for fully opened valve [0..100]unsignedInt 0…100100
Lower valve position for opening [0..100]unsignedInt 0…1000
Upper valve position for opening [0..100]unsignedInt 0…100100
Object type of valve statuslist1Byte
Object value with valve position >0list1
Valve purge functionlistDisable
Duration of valve purge time [1..255]unsignedInt 1…25510
Automatic valve purgelistDisable
Purge Cycle in weeks[1..12]unsignedInt 1…121
Reply mode for valve purge status(1bit)listRespond after change
"Disable Cooling" object functionlistDisable
Trigger object valuelist0=Disable/1=Enable
"Disable Heating/Cooling" object functionlistDisable
"Disable Heating" object functionlistDisable
Fan typelistOne level
When bus failure,Fan speed islistUnchange
When bus recovery, fan speed islistUnchange
After downloading,fan speed islistOFF
Forced operation functionlistDisable
Forced operation on object valuelist1=Force/0=Cancel
Behaviour on Forced operationlistUnchange
Auto. operation functionlistDisable
Time mode for function ONlistSwitch Delay
Delay time [1..65535]unsignedInt 1…6553510
Minimum time [1..65535]unsignedInt 1…6553510
Time mode for function OFFlistSwitch Delay
Fan speeds on 2 limitlistNo
Fan operation modelistChangeover switch
Delay between fan speed switch [50..5000]unsignedInt 50…5000500
Object value for Fan speed 1unsignedInt 1…10033
Object value for Fan speed 2unsignedInt 1…10067
Object value for Fan speed 3unsignedInt 1…100100
Limitation on forced operationlistUnchange
Obj. "Switch speed x " 1bit functionlistDisable
Delay time for function OFF [0..65535]unsignedInt 0…655350
Starting characteristic of fanlistEnable
Switch on over fan speedlist1
Minimum time in switch [1..65535]unsignedInt 1…6553510
Auto.operation on object valuelist1=Auto/0=Cancel
State of Auto.operation after startuplistDisable
Automatically enable auto.operationlistNo
Enable auto.operation after in [10..6000]unsignedInt 10…6000100
Threshold value 0FF<->ON[1..100]unsignedInt 1…10030
Hysteresis threshold value in +/-[0..50]unsignedInt 0…5010
Number of control valuelist1
Select bylistControl value with switching object
Monitoring period of control value [10..65535]unsignedInt 10…65535120
Reply mode of Obj. "Status Fan ON/OFF"(1bit)listRespond after change
Reply mode of Obj. "Status Automatic"(1bit)listRespond after change
Object value of "switch" after bus recoverylist0
Threshold value OFF<->speed 1 [1..100]unsignedInt 1…10030
Threshold value speed 1<->speed 2 [1..100]unsignedInt 1…10060
Threshold value speed 2<->speed 3 [1..100]unsignedInt 1…10080
Minimum time in fan speed [0..65535]unsignedInt 0…6553510
Reply mode of Obj. "Status Fan speed x"(1bit)listRespond after change
Reply mode of Obj. "Status Fan speed"(1byte)listRespond after change
Status value for Fan speed 1unsignedInt 1…10033
Status value for Fan speed 2unsignedInt 1…10067
Status value for Fan speed 3unsignedInt 1…100100
Function of channellistSwitch
Distinction between short and long operationlistNo
Long operation after [3..25]unsignedInt 3…255
Connected contact typelistNormally open
Reaction on short operationlistTOGGLE
Reaction on long operationlistNo reaction
Reaction on press the contactlistTOGGLE
Reaction on release the contactlistNo reaction
Send object value after bus recovery(valid if reaction is not toggle)listNo
Number of objectslist1
Reaction on long operationlistBrighter/Darker
Dimming modelistStart-Stop dimming
Step sizelist12.5
Interval of tele. cyclic send [0..25] (0=send once)unsignedInt 0…250
Reaction on short operationlistUp/Down
Reaction on long operationlistStop(Adjust Up/Down)
Reaction on short operationlistNo reaction
Output value [0..1]unsignedInt 0…10
Output value [0..3]unsignedInt 0…30
Output value [0..15]unsignedInt 0…158
Output value [0..255]unsignedInt 0…255127
Output value [0..65535]unsignedInt 0…655351000
Reaction on press the contactlistNo reaction
8 bit scene numberlistScene NO.1
Shift typelistShift by step value
Value begin withunsignedInt 0…2400
Value end with(must be larger than value begin with)unsignedInt 1…25510
Step sizeunsignedInt 0…2402
Shift numberlist1
Value 1unsignedInt 0…2550
Value 2unsignedInt 0…2551
Value 3unsignedInt 0…2552
Value 4unsignedInt 0…2553
Value 5unsignedInt 0…2554
Value 6unsignedInt 0…2555
Value 7unsignedInt 0…2556
Value 8unsignedInt 0…2557
Value 9unsignedInt 0…2558
Value 10unsignedInt 0…2559
DirectionlistFrom lowest to highest
Reset functionlistEnable by long operation
Reaction on press the contactlistSend shift value
Reaction on release the contactlistNo reaction
Object type for object1list1Bit_On/Off
Function of press the contactlistTOGGLE
Function of press the contactlistUp/Down
Function of press the contactlistSend Value
Value 1 (Scene NO.)listScene NO.1
Value 1 (Percentage)unsignedInt 0…10030
Value 1 (Unsigned value)unsignedInt 0…255127
Function of short operationlistTOGGLE
Function of short operationlistUp/Down
Function of short operationlistSend Value
Function of long operationlistTOGGLE
Function of long operationlistUp/Down
Function of long operationlistSend Value
Value 2 (Scene NO.)listScene NO.2
Value 2 (Percentage)unsignedInt 0…100100
Value 2 (Unsigned value)unsignedInt 0…255255
Object type for object2list1Bit_On/Off
Object type for object3list1Bit_On/Off
Object type for object4list1Bit_On/Off
Object type for press the contactlist1Bit_On/Off
Send modelistNo action when press,delay then send value1
Delay time [0..6500]unsignedInt 0…650010
Value 1list0
Value 1unsignedInt 0…151
Value 1unsignedInt 0…255127
Value 2list1
Value 2unsignedInt 0…150
Value 2unsignedInt 0…255255
Object type for short operationlist1Bit_On/Off
Object type for long operationlist1Bit_On/Off
Disable functionlistDisable
Trigger value of disable objectlistDisable=0/Enable=1
Status LED indicationlistControl by external object
External object datatypelist1Bit
When object value="0", LED islistOFF
When object value="1", LED islistOn
Threshold value isunsignedInt 1…25550
If object value<threshold value, LED islistOFF
If object value=threshold value, LED islistOn
If object value>threshold value, LED islistOFF
Brightness of LEDlistLevel 3
Drive typelistThree-wire

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Multifunctional Actuator,3-Fold,6A,Flush Mounted/1.0 1.0 latest$0055BDEC2026-11-25235 KBDownload

About this file

This is the official ETS product database for the GVS Multifunctional Actuator,3-Fold,6A,Flush Mounted (AMMAF-03/06.1), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from GVS

All GVS products