KNX IP-Router V4 (additional functions) 2167 00
GIRA Giersiepen · Order number 2167 00 · Communication › Router Applications
KNX/IP Router
Download .knxprod Router Applications V3.5 3.5 · 89 KB
Product
| Manufacturer | GIRA Giersiepen |
|---|---|
| Product name | KNX IP-Router V4 (additional functions) |
| Order number | 2167 00 |
| Product text | KNX/IP Router |
| Hardware | Router Applications |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Registration | Certified · 2015-08-31 |
| Languages | de-DE, el-GR, en-US, es-ES, fr-FR, it-IT, nb-NO, ru-RU, sv-SE, nl-NL |
| Catalog entry | M-0008_H-9013-2_HP-901A-35-853F_CI-2167.2000.20.20-1 |
| Fingerprint | 853F |
| SHA-256 | 6d78e92c776e9d12da84fd7bd91d0d9ba592bf29ca5e6f6d9373014d14c49850 |
| First seen | 2026-11-25 |
| Markets | 39 markets |
Application program: Router Applications V3.5 3.5
| Application number | $901A |
|---|---|
| Version | 3.5 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 14 |
| Group objects | 14 |
Group objects (14)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Time | Send | 3 Bytes | 10.1 time of day | CT |
| 2 | Date | Send | 3 Bytes | 11.1 date | CT |
| 3 | Trigger send date/time | Receive | 1 Bit | 1.17 trigger | CW |
| 4 | Time | Receive | 3 Bytes | 10.1 time of day | CW |
| 5 | Date | Receive | 3 Bytes | 11.1 date | CW |
| 6 | Activate data logger | Receive | 1 Bit | 1.1 switch | CRW |
| 7 | Data logger state | Send | 1 Bit | 1.2 boolean | CRT |
| 8 | SD card buffer state | Send | 1 Bit | 1.2 boolean | CR |
| 9 | SD card buffer value | Send | 1 Byte | 5.1 percentage (0..100%) | CR |
| 10 | NTP request status | Send | 1 Bit | 1.2 boolean | CRT |
| 11 | Bus voltage breakdown | Send | 1 Bit | 1.2 boolean | CT |
| 12 | SD card value | Send | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 13 | SD card error | Send | 1 Bit | 1.2 boolean | CRT |
| 14 | SD error code | Send | 1 Byte | CR |
Parameters (14)
| Parameter | Type | Default |
|---|---|---|
| Time function | list | None |
| Send time | list | Every minute |
| Send date | list | Every minute |
| Data logger | list | No |
| Data logging format | list | ETS4 |
| Datalogger type | list | static buffer |
| Datalogger status type | list | value (0-255) |
| visibilityLoggerStatus | list | No |
| Time zone | list | (UTC+01:00) Europe/Berlin |
| Daylight saving time | list | None |
| Use NTP server | list | No |
| NTP server address | text | |
| NTP interval (min) | unsignedInt 1…65535 | 60 |
| Use reliable communication? | list | No |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| KNX IP-Router V4 (additional functions) 4.0 latest | $901A | EEA7 | 2026-11-25 | 119 KB | Download |
| KNX IP-Router V4 4.0 | $901B | DAE0 | 2026-11-25 | 102 KB | Download |
| Router Applications V3.5 3.5 | $901A | 853F | 2026-11-25 | 89 KB | Download |
| KNX/IP Router V3.5 3.5 | $901B | 509B | 2026-11-25 | 70 KB | Download |
| KNX/IP Router V3.0 901B30 3.0 | $901B | 0006 | 2026-11-25 | 76 KB | Download |
| Router Applications V3.0 901A10 1.0 | $901A | 2430 | 2026-11-25 | 91 KB | Download |
| Data Logger/Timer 901310 1.0 | $9013 | C03E | 2026-11-25 | 85 KB | Download |
| Data Logger/Timer V2.0 901510 0.1 | $9015 | 14D6 | 2026-11-25 | 88 KB | Download |
| KNX/IP Router V2.0 901610 0.1 | $9016 | AA07 | 2026-11-25 | 71 KB | Download |
About this file
This is the official ETS product database for the GIRA Giersiepen KNX IP-Router V4 (additional functions) (2167 00), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from GIRA Giersiepen
- USB data interface FM 1070 00
- USB data interface DRA 1080 00
- data interface DRA 1153 00
- USB data interface 2014 00
- USB data interface insert 2024 00
- Gira F1 KNX Bridge TP 2049 00
- KNX/IP Interface 2168 00
- data interface FT1.2 504 xx
- data interface FM 558 xx
- radio-instabus converter 868 00
- TeleCoppler 893 00.
- Dummy Secure Dummy