KNX Database
GIRA Giersiepen 2015 00 Dimming actuator, 4-gang Standard

Dimming actuator, 4-gang Standard 2015 00

GIRA Giersiepen · Order number 2015 00 · Illumination › Dimmer

Download .knxprod Dimming 303A21 2.1 · 1.1 MB

Product

ManufacturerGIRA Giersiepen
Product nameDimming actuator, 4-gang Standard
Order number2015 00
HardwareDimmaktor REG Standard
MediumTwisted Pair
Bus current (mA)6
Rail mountedYes
Width (mm)72
RegistrationCertified · 2020-10-27
Languagesde-DE, el-GR, en-US, es-ES, fr-FR, it-IT, nb-NO, ru-RU, sv-SE, nl-NL
Catalog entryM-0008_H-8.20.2F.2F.202015.2000-0-O000A_HP-303A-21-719E-O000A_CI-2015.2000-1
Fingerprint719E
SHA-25618753f6478c3f0cd05948f61296ab92c3c331623dc977285c5f6cab0e78189b0
First seen2026-11-25
Markets39 markets

Application program: Dimming 303A21 2.1

Application number$303A
Version2.1
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters1330
Group objects151
Group objects (151)
NoNameFunctionSizeDPTFlags
1Manual operation - InputDisabling1 Bit1.3 enableCWU
2Manual operation - OutputStatus1 Bit1.2 booleanCRTU
3Manual operation - Input/OutputTemporary status indication1 Bit1.17 triggerCWTU
5Central function 1 ({{0:...}}) - InputSwitching1 Bit1.1 switchCWU
6Central function 1 ({{0:...}}) - InputDimming4 Bit3.7 dimming controlCWU
7Central function 1 ({{0:...}}) - InputBrightness value1 Byte5.1 percentage (0..100%)CWU
8Central function 2 ({{0:...}}) - InputSwitching1 Bit1.1 switchCWU
9Central function 2 ({{0:...}}) - InputDimming4 Bit3.7 dimming controlCWU
10Central function 2 ({{0:...}}) - InputBrightness value1 Byte5.1 percentage (0..100%)CWU
11Central function 3 ({{0:...}}) - InputSwitching1 Bit1.1 switchCWU
12Central function 3 ({{0:...}}) - InputDimming4 Bit3.7 dimming controlCWU
13Central function 3 ({{0:...}}) - InputBrightness value1 Byte5.1 percentage (0..100%)CWU
14Central function 4 ({{0:...}}) - InputSwitching1 Bit1.1 switchCWU
15Central function 4 ({{0:...}}) - InputDimming4 Bit3.7 dimming controlCWU
16Central function 4 ({{0:...}}) - InputBrightness value1 Byte5.1 percentage (0..100%)CWU
17Central function 5 ({{0:...}}) - InputSwitching1 Bit1.1 switchCWU
18Central function 5 ({{0:...}}) - InputDimming4 Bit3.7 dimming controlCWU
19Central function 5 ({{0:...}}) - InputBrightness value1 Byte5.1 percentage (0..100%)CWU
20Central function 6 ({{0:...}}) - InputSwitching1 Bit1.1 switchCWU
21Central function 6 ({{0:...}}) - InputDimming4 Bit3.7 dimming controlCWU
22Central function 6 ({{0:...}}) - InputBrightness value1 Byte5.1 percentage (0..100%)CWU
23Dimming channels 1...4 - Collective feedback - OutputFeedback switching status4 Bytes27.1 bit-combined info on/offCRU
23Dimming channels 1...4 - Collective feedback - OutputFeedback switching status4 Bytes27.1 bit-combined info on/offCRTU
31Dimming channel 1 ({{0:...}}) - InputSwitching1 Bit1.1 switchCWU
32Dimming channel 1 ({{0:...}}) - OutputSwitching feedback1 Bit1.1 switchCRTU
32Dimming channel 1 ({{0:...}}) - OutputSwitching feedback1 Bit1.1 switchCRU
33Dimming channel 1 ({{0:...}}) - InputLogic operation1 Bit1.2 booleanCWU
34Dimming channel 1 ({{0:...}}) - InputDimming4 Bit3.7 dimming controlCWU
35Dimming channel 1 ({{0:...}}) - InputBrightness value1 Byte5.1 percentage (0..100%)CWU
36Dimming channel 1 ({{0:...}}) - OutputFeedback brightness value1 Byte5.1 percentage (0..100%)CRU
36Dimming channel 1 ({{0:...}}) - OutputFeedback brightness value1 Byte5.1 percentage (0..100%)CRTU
37Dimming channel 1 ({{0:...}}) - InputScene extension1 Byte18.1 scene controlCWU
38Dimming channel 1 ({{0:...}}) - InputExtended scene recall1 Bit1.1 switchCWU
39Dimming channel 1 ({{0:...}}) - InputDisabling1 Bit1.3 enableCWU
41Dimming channel 1 ({{0:...}}) - InputStaircase function start/stop1 Bit1.10 start/stopCWU
42Dimming channel 1 ({{0:...}}) - InputStaircase time factor1 Byte5.10 counter pulses (0..255)CWU
43Dimming channel 1 ({{0:...}}) - InputBurn-in function, start/stop1 Bit1.10 start/stopCW
44Dimming channel 1 ({{0:...}}) - OutputBurn-in function duration1 Byte5.10 counter pulses (0..255)CT
44Dimming channel 1 ({{0:...}}) - OutputBurn-in function duration1 Byte5.10 counter pulses (0..255)CR
45Dimming channel 1 ({{0:...}}) - InputBurn-in function pause1 Bit1.2 booleanCW
47Dimming channel 1 ({{0:...}}) - InputDisabling acknowledgment1 Bit1.16 acknowledgeCWU
48Dimming channel 1 ({{0:...}}) - OutputFeedback function state4 BytesCRTU
48Dimming channel 1 ({{0:...}}) - OutputFeedback function state4 BytesCRU
51Dimming channel 2 ({{0:...}}) - InputSwitching1 Bit1.1 switchCWU
52Dimming channel 2 ({{0:...}}) - OutputSwitching feedback1 Bit1.1 switchCRTU
52Dimming channel 2 ({{0:...}}) - OutputSwitching feedback1 Bit1.1 switchCRU
53Dimming channel 2 ({{0:...}}) - InputLogic operation1 Bit1.2 booleanCWU
54Dimming channel 2 ({{0:...}}) - InputDimming4 Bit3.7 dimming controlCWU
55Dimming channel 2 ({{0:...}}) - InputBrightness value1 Byte5.1 percentage (0..100%)CWU
56Dimming channel 2 ({{0:...}}) - OutputFeedback brightness value1 Byte5.1 percentage (0..100%)CRTU
56Dimming channel 2 ({{0:...}}) - OutputFeedback brightness value1 Byte5.1 percentage (0..100%)CRU
57Dimming channel 2 ({{0:...}}) - InputScene extension1 Byte18.1 scene controlCWU
58Dimming channel 2 ({{0:...}}) - InputExtended scene recall1 Bit1.1 switchCWU
59Dimming channel 2 ({{0:...}}) - InputDisabling1 Bit1.3 enableCWU
61Dimming channel 2 ({{0:...}}) - InputStaircase function start/stop1 Bit1.10 start/stopCWU
62Dimming channel 2 ({{0:...}}) - InputStaircase time factor1 Byte5.10 counter pulses (0..255)CWU
63Dimming channel 2 ({{0:...}}) - InputBurn-in function, start/stop1 Bit1.10 start/stopCW
64Dimming channel 2 ({{0:...}}) - OutputBurn-in function duration1 Byte5.10 counter pulses (0..255)CT
64Dimming channel 2 ({{0:...}}) - OutputBurn-in function duration1 Byte5.10 counter pulses (0..255)CR
65Dimming channel 2 ({{0:...}}) - InputBurn-in function pause1 Bit1.2 booleanCW
67Dimming channel 2 ({{0:...}}) - InputDisabling acknowledgment1 Bit1.16 acknowledgeCWU
68Dimming channel 2 ({{0:...}}) - OutputFeedback function state4 BytesCRTU
68Dimming channel 2 ({{0:...}}) - OutputFeedback function state4 BytesCRU
71Dimming channel 3 ({{0:...}}) - InputSwitching1 Bit1.1 switchCWU
72Dimming channel 3 ({{0:...}}) - OutputSwitching feedback1 Bit1.1 switchCRTU
72Dimming channel 3 ({{0:...}}) - OutputSwitching feedback1 Bit1.1 switchCRU
73Dimming channel 3 ({{0:...}}) - InputLogic operation1 Bit1.2 booleanCWU
74Dimming channel 3 ({{0:...}}) - InputDimming4 Bit3.7 dimming controlCWU
75Dimming channel 3 ({{0:...}}) - InputBrightness value1 Byte5.1 percentage (0..100%)CWU
76Dimming channel 3 ({{0:...}}) - OutputFeedback brightness value1 Byte5.1 percentage (0..100%)CRTU
76Dimming channel 3 ({{0:...}}) - OutputFeedback brightness value1 Byte5.1 percentage (0..100%)CRU
77Dimming channel 3 ({{0:...}}) - InputScene extension1 Byte18.1 scene controlCWU
78Dimming channel 3 ({{0:...}}) - InputExtended scene recall1 Bit1.1 switchCWU
79Dimming channel 3 ({{0:...}}) - InputDisabling1 Bit1.3 enableCWU
81Dimming channel 3 ({{0:...}}) - InputStaircase function start/stop1 Bit1.10 start/stopCWU
82Dimming channel 3 ({{0:...}}) - InputStaircase time factor1 Byte5.10 counter pulses (0..255)CWU
83Dimming channel 3 ({{0:...}}) - InputBurn-in function, start/stop1 Bit1.10 start/stopCW
84Dimming channel 3 ({{0:...}}) - OutputBurn-in function duration1 Byte5.10 counter pulses (0..255)CT
84Dimming channel 3 ({{0:...}}) - OutputBurn-in function duration1 Byte5.10 counter pulses (0..255)CR
85Dimming channel 3 ({{0:...}}) - InputBurn-in function pause1 Bit1.2 booleanCW
87Dimming channel 3 ({{0:...}}) - InputDisabling acknowledgment1 Bit1.16 acknowledgeCWU
88Dimming channel 3 ({{0:...}}) - OutputFeedback function state4 BytesCRTU
88Dimming channel 3 ({{0:...}}) - OutputFeedback function state4 BytesCRU
91Dimming channel 4 ({{0:...}}) - InputSwitching1 Bit1.1 switchCWU
92Dimming channel 4 ({{0:...}}) - OutputSwitching feedback1 Bit1.1 switchCRTU
92Dimming channel 4 ({{0:...}}) - OutputSwitching feedback1 Bit1.1 switchCRU
93Dimming channel 4 ({{0:...}}) - InputLogic operation1 Bit1.2 booleanCWU
94Dimming channel 4 ({{0:...}}) - InputDimming4 Bit3.7 dimming controlCWU
95Dimming channel 4 ({{0:...}}) - InputBrightness value1 Byte5.1 percentage (0..100%)CWU
96Dimming channel 4 ({{0:...}}) - OutputFeedback brightness value1 Byte5.1 percentage (0..100%)CRTU
96Dimming channel 4 ({{0:...}}) - OutputFeedback brightness value1 Byte5.1 percentage (0..100%)CRU
97Dimming channel 4 ({{0:...}}) - InputScene extension1 Byte18.1 scene controlCWU
98Dimming channel 4 ({{0:...}}) - InputExtended scene recall1 Bit1.1 switchCWU
99Dimming channel 4 ({{0:...}}) - InputDisabling1 Bit1.3 enableCWU
101Dimming channel 4 ({{0:...}}) - InputStaircase function start/stop1 Bit1.10 start/stopCWU
102Dimming channel 4 ({{0:...}}) - InputStaircase time factor1 Byte5.10 counter pulses (0..255)CWU
103Dimming channel 4 ({{0:...}}) - InputBurn-in function, start/stop1 Bit1.10 start/stopCW
104Dimming channel 4 ({{0:...}}) - OutputBurn-in function duration1 Byte5.10 counter pulses (0..255)CT
104Dimming channel 4 ({{0:...}}) - OutputBurn-in function duration1 Byte5.10 counter pulses (0..255)CR
105Dimming channel 4 ({{0:...}}) - InputBurn-in function pause1 Bit1.2 booleanCW
107Dimming channel 4 ({{0:...}}) - InputDisabling acknowledgment1 Bit1.16 acknowledgeCWU
108Dimming channel 4 ({{0:...}}) - OutputFeedback function state4 BytesCRTU
108Dimming channel 4 ({{0:...}}) - OutputFeedback function state4 BytesCRU
191Dimming channel 1 ({{0:...}}) - OutputFeedback load type (KNX compliant)1 Byte20.610 load type detectionCRTU
192Dimming channel 1 ({{0:...}}) - OutputFeedback load type (extended)1 ByteCRTU
193Dimming channel 1 ({{0:...}}) - OutputFeedback short-circuit1 Bit1.5 alarmCRTU
194Dimming channel 1 ({{0:...}}) - OutputFeedback overload / mains voltage failure1 Bit1.5 alarmCRTU
197Dimming channel 2 ({{0:...}}) - OutputFeedback load type (KNX compliant)1 Byte20.610 load type detectionCRTU
198Dimming channel 2 ({{0:...}}) - OutputFeedback load type (extended)1 ByteCRTU
199Dimming channel 2 ({{0:...}}) - OutputFeedback short-circuit1 Bit1.5 alarmCRTU
200Dimming channel 2 ({{0:...}}) - OutputFeedback overload / mains voltage failure1 Bit1.5 alarmCRTU
203Dimming channel 3 ({{0:...}}) - OutputFeedback load type (KNX compliant)1 Byte20.610 load type detectionCRTU
204Dimming channel 3 ({{0:...}}) - OutputFeedback load type (extended)1 ByteCRTU
205Dimming channel 3 ({{0:...}}) - OutputFeedback short-circuit1 Bit1.5 alarmCRTU
206Dimming channel 3 ({{0:...}}) - OutputFeedback overload / mains voltage failure1 Bit1.5 alarmCRTU
209Dimming channel 4 ({{0:...}}) - OutputFeedback load type (KNX compliant)1 Byte20.610 load type detectionCRTU
210Dimming channel 4 ({{0:...}}) - OutputFeedback load type (extended)1 ByteCRTU
211Dimming channel 4 ({{0:...}}) - OutputFeedback short-circuit1 Bit1.5 alarmCRTU
212Dimming channel 4 ({{0:...}}) - OutputFeedback overload / mains voltage failure1 Bit1.5 alarmCRTU
239Dimming channel 1 ({{0:...}}) - InputStarting value, operating hours counter 4 Bytes13.100 time lag (s)CWU
239Dimming channel 1 ({{0:...}}) - InputLimiting value, operating hours counter 4 Bytes13.100 time lag (s)CWU
240Dimming channel 1 ({{0:...}}) - InputLimiting value, operating hours counter 2 Bytes7.7 time (h)CWU
240Dimming channel 1 ({{0:...}}) - InputStarting value, operating hours counter 2 Bytes7.7 time (h)CWU
241Dimming channel 1 ({{0:...}}) - InputRestart op. hours counter1 Bit1.15 resetCWU
242Dimming channel 1 ({{0:...}}) - OutputValue operating hours counter4 Bytes13.100 time lag (s)CTU
243Dimming channel 1 ({{0:...}}) - OutputValue operating hours counter2 Bytes7.7 time (h)CTU
244Dimming channel 1 ({{0:...}}) - OutputOperating hours counter elapsed1 Bit1.2 booleanCTU
246Dimming channel 2 ({{0:...}}) - InputLimiting value, operating hours counter 4 Bytes13.100 time lag (s)CWU
246Dimming channel 2 ({{0:...}}) - InputStarting value, operating hours counter 4 Bytes13.100 time lag (s)CWU
247Dimming channel 2 ({{0:...}}) - InputLimiting value, operating hours counter 2 Bytes7.7 time (h)CWU
247Dimming channel 2 ({{0:...}}) - InputStarting value, operating hours counter 2 Bytes7.7 time (h)CWU
248Dimming channel 2 ({{0:...}}) - InputRestart op. hours counter1 Bit1.15 resetCWU
249Dimming channel 2 ({{0:...}}) - OutputValue operating hours counter4 Bytes13.100 time lag (s)CTU
250Dimming channel 2 ({{0:...}}) - OutputValue operating hours counter2 Bytes7.7 time (h)CTU
251Dimming channel 2 ({{0:...}}) - OutputOperating hours counter elapsed1 Bit1.2 booleanCTU
253Dimming channel 3 ({{0:...}}) - InputLimiting value, operating hours counter 4 Bytes13.100 time lag (s)CWU
253Dimming channel 3 ({{0:...}}) - InputStarting value, operating hours counter 4 Bytes13.100 time lag (s)CWU
254Dimming channel 3 ({{0:...}}) - InputLimiting value, operating hours counter 2 Bytes7.7 time (h)CWU
254Dimming channel 3 ({{0:...}}) - InputStarting value, operating hours counter 2 Bytes7.7 time (h)CWU
255Dimming channel 3 ({{0:...}}) - InputRestart op. hours counter1 Bit1.15 resetCWU
256Dimming channel 3 ({{0:...}}) - OutputValue operating hours counter4 Bytes13.100 time lag (s)CTU
257Dimming channel 3 ({{0:...}}) - OutputValue operating hours counter2 Bytes7.7 time (h)CTU
258Dimming channel 3 ({{0:...}}) - OutputOperating hours counter elapsed1 Bit1.2 booleanCTU
260Dimming channel 4 ({{0:...}}) - InputLimiting value, operating hours counter 4 Bytes13.100 time lag (s)CWU
260Dimming channel 4 ({{0:...}}) - InputStarting value, operating hours counter 4 Bytes13.100 time lag (s)CWU
261Dimming channel 4 ({{0:...}}) - InputLimiting value, operating hours counter 2 Bytes7.7 time (h)CWU
261Dimming channel 4 ({{0:...}}) - InputStarting value, operating hours counter 2 Bytes7.7 time (h)CWU
262Dimming channel 4 ({{0:...}}) - InputRestart op. hours counter1 Bit1.15 resetCWU
263Dimming channel 4 ({{0:...}}) - OutputValue operating hours counter4 Bytes13.100 time lag (s)CTU
264Dimming channel 4 ({{0:...}}) - OutputValue operating hours counter2 Bytes7.7 time (h)CTU
265Dimming channel 4 ({{0:...}}) - OutputOperating hours counter elapsed1 Bit1.2 booleanCTU
Parameters (188)
ParameterTypeDefault
Name of the dimming channeltext
After ETS programming operationlistno reaction
In case of bus voltage failurelistno reaction
Brightness valuelist100%
Minimum brightnesslist1%
Maximum brightnesslist100%
after bus voltage returnlistno reaction
FeedbackunsignedInt 0…11
Time delaysunsignedInt 0…10
Scene functionunsignedInt 0…10
switching statuslistfeedback is active signalling object
Updating of the object valuelistonly if the feedback value changes
Delay after bus voltage returnunsignedInt 0…10
Cyclical transmissionunsignedInt 0…10
Selection of time delaylistno time delay
Switch-on delay minutesunsignedInt 0…590
secondsunsignedInt 0…5910
Switch-on delay retriggerableunsignedInt 0…10
Switch-off delay minutesunsignedInt 0…590
Switch-off delay retriggerableunsignedInt 0…10
Staircase time hoursunsignedInt 0…230
minutesunsignedInt 0…593
secondsunsignedInt 0…590
Staircase time retriggerableunsignedInt 0…10
Reaction to OFF-telegramlistswitch off
Staircase function activatable via "Staircase time" objectunsignedInt 0…10
Maximum time extensionlist1-fold staircase time
Switch-on delayunsignedInt 0…10
Switch-on delay hoursunsignedInt 0…230
minutesunsignedInt 0…590
secondsunsignedInt 0…5930
At the end of the staircase timelistswitch off
Pre-warning time minutesunsignedInt 0…590
Reduced brightnesslist50%
Delay scene recallunsignedInt 0…10
Delay time minutesunsignedInt 0…590
Overwrite values stored in the device during the ETS programming operationunsignedInt 0…11
With overflowunsignedInt 0…10
Scene 1 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…641
Switching state in scene 1list10%
Storage function for scene 1unsignedInt 0…10
Type of counterlistup-counter
Limiting value presettinglistno
Limiting valueunsignedInt 1…6553565535
Start value presetlistno
Transmission behaviour of the counter valuelistcyclical
Count value interval (h)unsignedInt 1…655351
disabling functionunsignedInt 0…10
Polarity of the disabling objectlist0 = enabled, 1 = disabled
Beginning of the disabling functionlistswitch off
End of the disabling functionlisttracked brightness value
Type of logic operation functionlistOR
Object value after bus voltage returnlist0 (OFF)
Object value after ETS programming operationlist0 (OFF)
Scene 2 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…642
Storage function for scene 2unsignedInt 0…10
Scene 3 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…643
Storage function for scene 3unsignedInt 0…10
Scene 4 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…644
Storage function for scene 4unsignedInt 0…10
Scene 5 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…645
Storage function for scene 5unsignedInt 0…10
Scene 6 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…646
Storage function for scene 6unsignedInt 0…10
Scene 7 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…647
Storage function for scene 7unsignedInt 0…10
Scene 8 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…648
Storage function for scene 8unsignedInt 0…10
Scene 9 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…649
Storage function for scene 9unsignedInt 0…10
Scene 10 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…6410
Storage function for scene 10unsignedInt 0…10
Scene 11 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…6411
Storage function for scene 11unsignedInt 0…10
Scene 12 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…6412
Storage function for scene 12unsignedInt 0…10
Scene 13 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…6413
Storage function for scene 13unsignedInt 0…10
Scene 14 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…6414
Storage function for scene 14unsignedInt 0…10
Scene 15 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…6415
Storage function for scene 15unsignedInt 0…10
Scene 16 activatable by scene number (scene number "0" = scene deactivated)unsignedInt 0…6416
Storage function for scene 16unsignedInt 0…10
Visual feedback for storage functionunsignedInt 0…10
Flashing time for visual feedback secondsunsignedInt 1…105
Time for cyclic monitoring hoursunsignedInt 0…230
minutesunsignedInt 0…592
secondsunsignedInt 10…5910
Central function 1text
Central function 2text
Central function 3text
Central function 4text
Central function 5text
Central function 6text
Time for cyclical transmission hoursunsignedInt 0…230
Functionlistsecond counter (DPT 13.100)
Limiting valueunsignedInt 1…21474836472147483647
Counter value intervalunsignedInt 1…21474836473600
Time for cyclical transmission of operating hours hoursunsignedInt 0…230
minutesunsignedInt 0…5915
Delay after bus voltage return minutesunsignedInt 0…590
secondsunsignedInt 0…5917
Type of feedbacklistactive signalling object
Delay after bus voltage returnunsignedInt 0…10
Time for cyclical transmission hoursunsignedInt 0…230
Time for flashing the disabling functionslist1 s
Manual operationunsignedInt 0…11
Polarity of the disabling objectlist0 = enabled; 1 = disabled
Status object function and polaritylist0 = inactive; 1 = Manual operation active
End of permanent manual controllistno change
Bus control of individual outputs can be disabledunsignedInt 0…10
Number of logic functionsunsignedInt 1…81
Display length secondsunsignedInt 6…25510
Indicating status temporarilyunsignedInt 0…10
Number of scenesunsignedInt 1…1610
AssignmentunsignedInt 0…10
Function and polarity central objectslistSwitching (1 = ON / 0 = OFF) & dimming
Switching state in scene 1list30%
Switching state in scene 1list40%
Switching state in scene 1list50%
Switching state in scene 1list60%
Switching state in scene 1list70%
Switching state in scene 1list80%
Switching state in scene 1list90%
Switching state in scene 1list100%
Switching state in scene 1list20%
Burn-in duration hoursunsignedInt 1…10025
Start and stop via objectunsignedInt 0…11
Pause via objectunsignedInt 0…11
Feedback of current burn-in periodlistno feedback
Cycle time minutes (0 = no cyclical transmission)unsignedInt 1…2551
Brightness valuelistfeedback is active signalling object
Lower brightness limitlistas basic brightness
Basic brightnesslist Level 2
Switch-on brightnesslist100%
Load typelistuniversal (with automatic calibration procedure)
Operation with universal power booster (old)unsignedInt 0…10
Load typeunsignedInt 0…10
Number of dimming channelslist4 dimming channels (O1) + (O2) + (O3) + (O4)
On receipt of a brightness valuelistdimming to
With relative dimming up in the switched-off statelistSwitch ON channeL
secondsunsignedInt 0…24020
Characteristic curve value domainlistlinear function
Characteristic curve time domainlistlinear function
Area I Time between two dimming increments (ms)unsignedInt 1…25525
Brightness limit value Area I -> IIlist100%
Brightness limit value Area II -> IIIlist100%
Brightness limit value Area III -> IVlist100%
Brightness limit value Area IV -> Vlist100%
Brightness limit value Area I -> IIlist25%
Area II Time between two dimming increments (ms)unsignedInt 1…25520
Brightness limit value Area II -> IIIlist50%
Area III Time between two dimming increments (ms)unsignedInt 1…25515
Brightness limit value Area III -> IVlist75%
Area IV Time between two dimming increments (ms)unsignedInt 1…25510
Brightness limit value Area IV -> Vlist90%
Area V Time between two dimming increments (ms)unsignedInt 1…2555
Switching state in scene 2list20%
Switching state in scene 3list20%
Switching state in scene 4list40%
Switching state in scene 5list50%
Switching state in scene 6list60%
Switching state in scene 7list70%
Switching state in scene 8list80%
Switching state in scene 9list90%
Switching state in scene 10list100%
Switching state in scene 11list10%
Switching state in scene 12list20%
Switching state in scene 13list30%
Switching state in scene 14list40%
Switching state in scene 15list50%
Switching state in scene 16list60%
On scene requestlistDimming to brightness value via dimming increm. time
Dimming increment timeunsignedInt 0…2555
Fading timeunsignedInt 0…2402
Delay for feedbacksunsignedInt 0…10
Delay after central functions minutesunsignedInt 0…590
secondsunsignedInt 0…595
End of the disabling function after acknowledgementlisttracked brightness value
Control via objectunsignedInt 0…10
Staircase function / logic operation functionlistno selection
Channel parameterslisteach channel individual
Type of feedbackliststandard (KNX compliant)
Output 1 usedunsignedInt 0…11
Output 2 usedunsignedInt 0…11
Output 3 usedunsignedInt 0…11
Output 4 usedunsignedInt 0…11

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Dimming 303A22 2.2 latest$303A03FC2026-11-251.1 MBDownload
Dimming 303A21 2.1$303A719E2026-11-251.1 MBDownload

About this file

This is the official ETS product database for the GIRA Giersiepen Dimming actuator, 4-gang Standard (2015 00), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from GIRA Giersiepen

All GIRA Giersiepen products