KNX MultiVent Basic 54001
function Technology · Order number 54001 · Actuator › Ventilation
Download .knxprod KNX MultiVent Basic 1.0 · 71 KB
Product
| Manufacturer | function Technology |
|---|---|
| Product name | KNX MultiVent Basic |
| Order number | 54001 |
| Hardware | KNX MultiVent Basic |
| Medium | Twisted Pair |
| Bus current (mA) | 15 |
| Rail mounted | No |
| Registration | Registered |
| Languages | de-DE, en-US |
| Catalog entry | M-0088_H-2010.5F02.5F12-1_HP-1000-10-4561-O00C5_CI-54001-0 |
| Fingerprint | 4561 |
| SHA-256 | 4f6bfefe2d461167cd7ec6f467f61e9dbc545d2ea8d2700ca395a7e1ada23b98 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: KNX MultiVent Basic 1.0
| Application number | $1000 |
|---|---|
| Version | 1.0 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Parameters | 55 |
| Group objects | 34 |
Group objects (34)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Device: Self test status | 1 Bit | CRT | ||
| 1 | Valves: Fire operation | 1 Bit | CW | ||
| 2 | Valve 1: Value | 1 Byte | CW | ||
| 2 | Valve 1: Switch | 1 Bit | CW | ||
| 3 | Valve 1: Force open | 1 Bit | CW | ||
| 4 | Valve 1: Force close | 1 Bit | CW | ||
| 5 | Valve 1: Status | 1 Bit | CRT | ||
| 6 | Valve 1: Cycle counter | 4 Bytes | CRW | ||
| 7 | Valve 2: Value | 1 Byte | CW | ||
| 7 | Valve 2: Switch | 1 Bit | CW | ||
| 8 | Valve 2: Force open | 1 Bit | CW | ||
| 9 | Valve 2: Force close | 1 Bit | CW | ||
| 10 | Valve 2: Status | 1 Bit | CRT | ||
| 11 | Valve 2: Cycle counter | 4 Bytes | CRW | ||
| 12 | Relay: Continuous heating/cooling | 1 Byte | CW | ||
| 12 | Relay: Switch heating/cooling | 1 Bit | CW | ||
| 12 | Relay: Switch | 1 Bit | CW | ||
| 13 | Relay: Force operation | 1 Bit | CW | ||
| 14 | Relay: Disable staircase function | 1 Bit | CW | ||
| 14 | Relay: Disable delay function | 1 Bit | CW | ||
| 15 | Relay: Change duration | 2 Bytes | CRW | ||
| 16 | Relay: Logic OR | 1 Bit | CW | ||
| 16 | Relay: Logic AND | 1 Bit | CW | ||
| 17 | Relay: Status switch | 1 Bit | CRT | ||
| 18 | Relay 2: Switch | 1 Bit | CW | ||
| 18 | Relay 2: Continuous heating/cooling | 1 Byte | CW | ||
| 18 | Relay 2: Switch heating/cooling | 1 Bit | CW | ||
| 19 | Relay 2: Force operation | 1 Bit | CW | ||
| 20 | Relay 2: Disable staircase function | 1 Bit | CW | ||
| 20 | Relay 2: Disable delay function | 1 Bit | CW | ||
| 21 | Relay 2: Change duration | 2 Bytes | CRW | ||
| 22 | Relay 2: Logic OR | 1 Bit | CW | ||
| 22 | Relay 2: Logic AND | 1 Bit | CW | ||
| 23 | Relay 2: Status switch | 1 Bit | CRT |
Parameters (22)
| Parameter | Type | Default |
|---|---|---|
| Cyclic sending status of device (Hour, 0 = Disable) | unsignedInt 0…24 | 0 |
| Valve configuration | list | 1-valve blade |
| Fire operation | list | Valves open |
| Relay count | list | No Relay |
| Valve control | list | Switch |
| Open valve on value higher than (%) | unsignedInt 1…100 | 50 |
| Close valve on value lower than (%) | unsignedInt 1…100 | 10 |
| Forced priority | list | Forced close |
| Function | list | Switching actuator |
| Addition function | list | Disable |
| Relay type | list | Normally open (relay inverted) |
| Valve actuator type | list | Normally open (relay inverted) |
| Type of telegram for control | list | Switch (1bit) |
| Factor (0 = Disable) | unsignedInt 0…255 | 0 |
| PWM cycle time (min) | unsignedInt 5…255 | 30 |
| Time | list | 1 min |
| Automatic valve purge | list | Disable |
| Days between automatic valve purge (days) | unsignedInt 5…30 | 5 |
| Duration of staircase function (min) | unsignedInt 1…255 | 20 |
| Possibility to switch off the relay from bus | list | Disable |
| Logic | list | Disable |
| Forced operation | list | Relay on |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| KNX MultiVent Basic 1.0 latest | $1000 | 4561 | 2026-11-25 | 71 KB | Download |
About this file
This is the official ETS product database for the function Technology KNX MultiVent Basic (54001), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.