KNX Database
FARADITE M360-X-KNX Motion Sensor 360 - KNX

Motion Sensor 360 - KNX M360-X-KNX

FARADITE · Order number M360-X-KNX · Motion Sensors

Download .knxprod SEN_01 0.1 · 181 KB

Product

ManufacturerFARADITE
Product nameMotion Sensor 360 - KNX
Order numberM360-X-KNX
HardwareH_SEN_01
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2023-01-16
Languagesen-US
Catalog entryM-0233_H-2-1_HP-0002-01-F1F8_CI-M360.2DX.2DKNX-1
FingerprintF1F8
SHA-256d48005ed149b66196e975f8c00abc04976944994906d2cce4d08725c5c7dcb0c
First seen2026-11-25
Markets59 markets

Application program: SEN_01 0.1

Application number$0002
Version0.1
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters180
Group objects55
Group objects (55)
NoNameFunctionSizeDPTFlags
1Brightness calibrationMeasured brightness value on lux metre input2 Bytes9.4 lux (Lux)CWU
1Function {{ModuleDefArg_ChannelNumber}}: {{0}} Dimming value output1 Byte5.1 percentage (0..100%)CT
2Brightness calibrationRoom correction factor input or output2 BytesDPT.9CRWT
2Function {{ModuleDefArg_ChannelNumber}}: {{0}}RGB red output1 Byte5.1 percentage (0..100%)CT
3BrightnessBrightness level output2 Bytes9.4 lux (Lux)CRT
3Function {{ModuleDefArg_ChannelNumber}}: {{0}}RGB green output1 Byte5.1 percentage (0..100%)CT
4Brightness trigger: {{0}}Brightness trigger 1 output1 Bit1.1 switchCT
4Function {{ModuleDefArg_ChannelNumber}}: {{0}}RGB blue output1 Byte5.1 percentage (0..100%)CT
5Brightness trigger: {{0}}Brightness trigger 2 output1 Bit1.1 switchCT
5Function {{ModuleDefArg_ChannelNumber}}: {{0}}RGB output3 Bytes232.600 RGB value 3x(0..255)CT
6External brightnessBrightness level input2 Bytes9.4 lux (Lux)CWU
6Function {{ModuleDefArg_ChannelNumber}}: {{0}}1 byte unsigned output1 ByteDPT.5CT
6Function {{ModuleDefArg_ChannelNumber}}: {{0}}1 byte signed output1 ByteDPT.6CT
6Function {{ModuleDefArg_ChannelNumber}}: {{0}}1 byte percentage output1 ByteDPT.5CT
6Function {{ModuleDefArg_ChannelNumber}}: {{0}}HVAC mode output1 Byte20.102 HVAC modeCT
7Day / Night ModeDay (0) / Night (1) mode output1 Bit1.24 day/nightCRT
7Function {{ModuleDefArg_ChannelNumber}}: {{0}}2 bytes unsigned output2 BytesDPT.7CT
7Function {{ModuleDefArg_ChannelNumber}}: {{0}}2 bytes signed output2 BytesDPT.8CT
7Function {{ModuleDefArg_ChannelNumber}}: {{0}}2 bytes float output2 BytesDPT.9CT
8Day / Night ModeDay (0) / Night (1) mode select input1 Bit1.24 day/nightCRWU
8Function {{ModuleDefArg_ChannelNumber}}: {{0}}Scene output1 Byte18.1 scene controlCT
9Day / Night ModeDay -> Night time input3 Bytes10.1 time of dayCRWU
9Function {{ModuleDefArg_ChannelNumber}}: {{0}}Switching output1 Bit1.1 switchCWTU
9Function {{ModuleDefArg_ChannelNumber}}: {{0}}Extractor fan output1 Bit1.1 switchCWTU
10Day / Night ModeNight -> Day time input3 Bytes10.1 time of dayCRWU
10Function {{ModuleDefArg_ChannelNumber}}: {{0}}CLC - Switching output1 Bit1.1 switchCWT
11Day / Night ModeCurrent time of day input3 Bytes10.1 time of dayCWU
11Function {{ModuleDefArg_ChannelNumber}}: {{0}}CLC - Brighter / darker output4 Bit3.7 dimming controlCWT
12MasterMotion input1 Bit1.1 switchCWU
12Function {{ModuleDefArg_ChannelNumber}}: {{0}}CLC - Dimming value output 1 Byte5.1 percentage (0..100%)CWT
13SlaveMotion output1 Bit1.1 switchCT
13Function {{ModuleDefArg_ChannelNumber}}: {{0}}CLC - Dimming feedback value input1 Byte5.1 percentage (0..100%)CWTU
14SlaveReset input1 Bit1.15 resetCWU
14Function {{ModuleDefArg_ChannelNumber}}: {{0}}Pushbutton blocking input1 Bit1.1 switchCWU
15MasterReset output1 Bit1.15 resetCT
15Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness threshold input2 Bytes9.4 lux (Lux)CRWU
15Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness threshold input (Day)2 Bytes9.4 lux (Lux)CRWU
16HeartbeatHeartbeat output1 Bit1.1 switchCT
16Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness threshold input (Night)2 Bytes9.4 lux (Lux)CRWU
17Test modeDetection area test mode input1 Bit1.1 switchCWU
17Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness threshold teach-in (Day)1 Bit1.1 switchCWTU
17Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness threshold teach-in1 Bit1.1 switchCWTU
18Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness threshold teach-in (Night)1 Bit1.1 switchCWTU
19Function {{ModuleDefArg_ChannelNumber}}: {{0}}Timeout input2 Bytes7.5 time (s)CRWU
19Function {{ModuleDefArg_ChannelNumber}}: {{0}}Timeout input (Day)2 Bytes7.5 time (s)CRWU
20Function {{ModuleDefArg_ChannelNumber}}: {{0}}Timeout input (Night)2 Bytes7.5 time (s)CRWU
21Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness setpoint input2 Bytes9.4 lux (Lux)CRWU
21Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness setpoint input (Day)2 Bytes9.4 lux (Lux)CRWU
22Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness setpoint input (Night)2 Bytes9.4 lux (Lux)CRWU
23Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness setpoint teach-in (Day)1 Bit1.1 switchCWTU
23Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness setpoint teach-in1 Bit1.1 switchCWTU
24Function {{ModuleDefArg_ChannelNumber}}: {{0}}Brightness setpoint teach-in (Night)1 Bit1.1 switchCWTU
25Function {{ModuleDefArg_ChannelNumber}}: {{0}}Standby dimming level input1 Byte5.1 percentage (0..100%)CRWU
25Function {{ModuleDefArg_ChannelNumber}}: {{0}}Standby dimming level input (Day)1 Byte5.1 percentage (0..100%)CRWU
26Function {{ModuleDefArg_ChannelNumber}}: {{0}}Standby dimming level input (Night)1 Byte5.1 percentage (0..100%)CRWU
Parameters (94)
ParameterTypeDefault
Number of functionsunsignedInt 1…42
Master & slave functionalitylistStandalone (no master / slave objects)
Detection LED feedbacklistDisable
Motion sensor sensitivitylistHighest sensitivity
Calibration objectslistDisable
Transmit update onlistCyclical
Cyclical transmission of brightnessunsignedInt 5…6553560
Transmission after change greater thanfloat 10…50020
Threshold trigger objectslistDisable
Trigger whenlistNever
Thresholdfloat 0…100000500
Hysteresisfloat 1…5020
Value sent on triggerlist1
Day/night modelistDisable
Day/night triggerlistDPT 1.1 (1 bit object)
Day -> Night time (PM)time1320
Night -> day time (AM)time360
Slave outputs locking timeunsignedInt 3…6553510
Startup delayunsignedInt 0…2550
Brightness sourcelistInternal brightness sensor
Heartbeat periodtime60
HeartbeatlistDisable
Test modelistDisable
ColourlistWhite
Nametext
Function typelistSwitching
On motionunsignedInt 1…641
Object typelist1 Bit
On motion (RGB)color#000000
On timeout (RGB)color#000000
On motion (0...255)unsignedInt 0…2550
On timeout (0...255)unsignedInt 0…2550
On motion (0...65535)unsignedInt 0…655350
On timeout (0...65535)unsignedInt 0…655350
On motion (0...100%)unsignedInt 0…1000
On timeout (0...100%)unsignedInt 0…1000
On motion (-128...127)signedInt -128…1270
On timeout (-128...127)signedInt -128…1270
On motion (-32768...32767)signedInt -32768…327670
On timeout (-32768...32767)signedInt -32768…327670
On motion (-671088.64...670760.96)float -671088.64…670760.961
On timeout (-671088.64...670760.96)float -671088.64…670760.961
Operating modelistPresence (Auto ON and Auto OFF)
Brightness threshold dependentlistEnable
Brightness threshold objectlistHide group objects
Brightness thresholdunsignedInt 0…65535500
Timeouttime600
Timeout objectlistHide group objects
On motionlistOn
On timeoutunsignedInt 1…642
On motionunsignedInt 0…100100
On timeoutunsignedInt 0…1000
On motion (HVAC)list1 - Comfort
On timeout (HVAC)list1 - Comfort
On motion send delaytime0
Function nametextDefault name
Exit periodtime20
Pushbutton ON - Blocking behaviourlistBlock
Long presence detectionlistDisable
Duration of continuous presence required for function activationunsignedInt 6…6553560
On motionlist1 - Comfort
On timeoutlist2 - Standby
Behaviour upon bus voltage return and programinglistNo reaction
PolaritylistDont invert
Pushbutton OFF - Blocking behaviourlistUnblock after an exit period
Timeout extensiontime1800
Cyclic sendinglistDisable
Cycle timetime60
Lower dimming output limitunsignedInt 1…4910
Upper dimming output limitunsignedInt 50…100100
Brightness setpointunsignedInt 0…65535500
HysteresisunsignedInt 0…6553510
Initial dimming levelunsignedInt 0…10070
Dimming control speedlistStandard
Switch off when there is enough brightnesslistNever turn OFF
Initialize control withlistDimming value telegram
Send stop telegram when LUX level is reached during initializationlistYes
Standby dimming levelunsignedInt 0…10010
Action on timeoutlistTurn lights off
On timeoutlistOff
Standby timeoutlistAlways ON
Duration with no motion to evaluate room as unoccupiedtime30
Response to 4 bit dimming telegramlistMaintain new LUX level
Alternative ON valueunsignedInt 1…641
Alternative OFF valueunsignedInt 1…642
Alternative ON valueunsignedInt 0…100100
Alternative OFF valueunsignedInt 0…1000
Pushbutton ON - Telegram behaviourlistSend ON telegram (Same as motion)
Disable (Auto ON) during the nightlistNo
Send telegram on day/night changelistEnable
Disable (Auto ON) during the daylistNo
Pushbutton OFF - Telegram behaviourlistSend OFF telegram (Same as timeout)
Pushbutton ON - BehaviourlistStart constant light control
Pushbutton OFF - BehaviourlistStop constant light control

Version history

ApplicationApp noFingerprintFirst seenSizeFile
SEN_01 0.1 latest$0002F1F82026-11-25181 KBDownload

About this file

This is the official ETS product database for the FARADITE Motion Sensor 360 - KNX (M360-X-KNX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from FARADITE

All FARADITE products