PowerSupply 960 00001152
Enertex Bayern GmbH · Order number 00001152 · System devices
Download .knxprod PowerSupply 960 0.1 · 66 KB
Product
| Manufacturer | Enertex Bayern GmbH |
|---|---|
| Product name | PowerSupply 960 |
| Order number | 00001152 |
| Product text | Enertex KNX PowerSupply 960 |
| Hardware | Enertex KNX PowerSupply 960 |
| Medium | Twisted Pair |
| Bus current (mA) | 960 |
| Rail mounted | Yes |
| Width (mm) | 105 |
| Device kind | PowerSupply |
| Registration | Certified · 2015-04-14 |
| Languages | de-DE, en-US |
| Catalog entry | M-00A6_H-00000003-1_HP-0003-01-C5D3_CI-00001152-1 |
| Fingerprint | C5D3 |
| SHA-256 | f5ce4fc8c284923bdbfa68cf7aab7608e325324eddb82e547e3a6fe67418de6b |
| First seen | 2026-11-25 |
| Markets | Germany |
Application program: PowerSupply 960 0.1
| Application number | $0003 |
|---|---|
| Version | 0.1 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0d |
| Parameters | 30 |
| Group objects | 34 |
Group objects (34)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | General | Time | 3 Bytes | 10.1 time of day | CWTU |
| 1 | General | Date | 3 Bytes | 11.1 date | CWTU |
| 2 | General | Request time | 1 Bit | DPT.1 | CT |
| 3 | General | Request date | 1 Bit | DPT.1 | CT |
| 4 | General | Turn-on time | 3 Bytes | 10.1 time of day | CRT |
| 5 | General | Turn-on date | 3 Bytes | 11.1 date | CRT |
| 6 | General | Operating hours life time | 2 Bytes | DPT.7 | CRT |
| 7 | General | Analysis reset | 1 Bit | DPT.1 | CW |
| 8 | General | Operating seconds life time | 4 Bytes | DPT.13 | CRT |
| 16 | Measurement | Request measurement values | 1 Bit | DPT.1 | CW |
| 17 | Measurement | Voltage | 2 Bytes | 9.20 voltage (mV) | CRT |
| 18 | Measurement | Current | 2 Bytes | 9.21 current (mA) | CRT |
| 19 | Measurement | Power | 4 Bytes | 14.56 power (W) | CRT |
| 20 | Measurement | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 21 | Measurement | Voltage – Set a limited value | 2 Bytes | 9.20 voltage (mV) | CRWT |
| 22 | Measurement | Volt. – Exceed./falling below | 1 Bit | DPT.1 | CT |
| 23 | Measurement | Current – Set a limited value | 2 Bytes | 9.21 current (mA) | CRWT |
| 24 | Measurement | Curr. – Exceed./falling below | 1 Bit | DPT.1 | CT |
| 25 | Measurement | Temp. – Set a limited value | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 26 | Measurement | Temp. – Exceed./falling below | 1 Bit | DPT.1 | CT |
| 35 | Extreme value | Voltage – Minimum | 2 Bytes | 9.20 voltage (mV) | CRT |
| 36 | Extreme value | Voltage – Maximum | 2 Bytes | 9.20 voltage (mV) | CRT |
| 37 | Extreme value | Current – Minimum | 2 Bytes | 9.21 current (mA) | CRT |
| 38 | Extreme value | Current – Maximum | 2 Bytes | 9.21 current (mA) | CRT |
| 39 | Extreme value | Power – Minimum | 4 Bytes | 14.56 power (W) | CRT |
| 40 | Extreme value | Power – Maximum | 4 Bytes | 14.56 power (W) | CRT |
| 41 | Extreme value | Temperature – Minimum | 2 Bytes | 9.1 temperature (°C) | CRT |
| 42 | Extreme value | Temperature – Maximum | 2 Bytes | 9.1 temperature (°C) | CRT |
| 75 | Energy | Delivered energy lifetime | 4 Bytes | DPT.13 | CRT |
| 76 | Energy | Delivered energy since turn-on | 4 Bytes | DPT.13 | CRT |
| 77 | Energy | Delivered en. since An. Reset | 4 Bytes | DPT.13 | CRT |
| 78 | Energy | Received energy lifetime | 4 Bytes | DPT.13 | CRT |
| 79 | Energy | Received energy since turn-on | 4 Bytes | DPT.13 | CRT |
| 80 | Energy | Received en. since An. Reset | 4 Bytes | DPT.13 | CRT |
Parameters (26)
| Parameter | Type | Default |
|---|---|---|
| Cyclic analysis reset | list | Never |
| Request time after bus voltage return | list | Yes |
| Value of com. Object „request time“ | unsignedInt 0…1 | 0 |
| Request date after bus voltage return | list | Yes |
| Value of com. Object „request date“ | unsignedInt 0…1 | 0 |
| Release com. Object „Req. Meas. Values“ | list | Yes |
| Value of com. Object „Req. Measurement“ | list | 0 |
| Release cyclic measurement output | list | Yes |
| Period cyclical output (s) | unsignedInt 0…172800 | 60 |
| Sending via changing a value in % | list | Yes |
| Sending via changing a value in % | unsignedInt 0…100 | 3 |
| Release output when exc./falling below lim. Val. | list | Yes |
| Telegram when exceeding/falling below limited value (voltage) | list | Yes |
| Limited value (mV) | unsignedInt 0…35000 | 28000 |
| Hysteresis (mV) | unsignedInt 0…2000 | 100 |
| Telegram when exceeding/falling below limited value (current) | list | Yes |
| Limited value (mA) | unsignedInt 0…2000 | 960 |
| Hysteresis (mA) | unsignedInt 0…255 | 20 |
| Telegram when exceeding/falling below limited value (temp.) | list | Yes |
| Limited value (°C) | unsignedInt 0…100 | 60 |
| Hysteresis (°C) | unsignedInt 0…20 | 2 |
| Release the output of extreme values | list | Yes |
| Output extreme values cyclic (s) | unsignedInt 0…172800 | 60 |
| Output when changing | list | Yes |
| Release the output of energy values | list | Yes |
| Output energy values cyclic (s) | unsignedInt 0…172800 | 60 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| PowerSupply 960 0.1 latest | $0003 | C5D3 | 2026-11-25 | 66 KB | Download |
About this file
This is the official ETS product database for the Enertex Bayern GmbH PowerSupply 960 (00001152), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Enertex Bayern GmbH
- PowerSupply 960² 00001152-2
- SynOhr MultiSense KNX 00001144
- KNXnet/IP Router 00001147
- SmartMeter 85A/85A RT/630A 00001149
- KNXnet/IP Interface 00001150
- ProxyTouch 00001155
- MeTa 00001157
- 4Kanal LED Dimmsequenzer 5A DK/REG 00001160
- PowerSupply 960³ 1152-3
- IP Secure Router 1164
- IP system devices - Additional function 1164 - 1168
- IP Secure Interface 1168