KNX Database
Enertex Bayern GmbH 00001149 SmartMeter 85A/85A RT/630A

SmartMeter 85A/85A RT/630A 00001149

Enertex Bayern GmbH · Order number 00001149 · Energy measurement

Download .knxprod SmartMeter 85A/85A RT/630A 0.0 · 101 KB

Product

ManufacturerEnertex Bayern GmbH
Product nameSmartMeter 85A/85A RT/630A
Order number00001149
Product textEnertex KNX SmartMeter 85A/85A RT/630A
HardwareKNXSmartmeter
MediumTwisted Pair
Bus current (mA)18
Rail mountedNo
RegistrationRegistered · 2016-03-07
Languagesde-DE, en-US
Catalog entryM-00A6_H-00000005-1_HP-0005-00-043A_CI-00001149-1
Fingerprint043A
SHA-2564dab3875c6a799a34fb9e2fc3677991847afecc4b32a4066d2d14a1f6862cb44
First seen2026-11-25
Markets59 markets

Application program: SmartMeter 85A/85A RT/630A 0.0

Application number$0005
Version0.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters331
Group objects163
Group objects (163)
NoNameFunctionSizeDPTFlags
0GeneralPower-save mode1 Bit1.3 enableCRWT
1GeneralTime3 Bytes10.1 time of dayCWU
2GeneralRequest time1 BitDPT.1CT
3GeneralIn operation1 BitDPT.1CT
4MeasurementRequest measurements1 BitDPT.1CW
5MeasurementRequest power values1 BitDPT.1CW
6MeasurementFrequency4 Bytes14.33 frequency (Hz)CRT
7Measurement Ch1Voltage (rms)2 Bytes9.20 voltage (mV)CRT
8Measurement Ch1Current (rms)2 Bytes9.21 current (mA)CRT
9Measurement Ch1Active power4 Bytes14.56 power (W)CRT
10Measurement Ch1External active power limit2 BytesDPT.8CRWT
11Measurement Ch1Active power limit message1 BitDPT.1CT
12Measurement Ch1Voltage limit message1 BitDPT.1CT
13Measurement Ch1Voltage failure message1 BitDPT.1CT
14Measurement Ch1Voltage peak message1 BitDPT.1CT
15Measurement Ch1Current limit message1 BitDPT.1CT
16Measurement Ch1Current peak message1 BitDPT.1CT
17Measurement Ch1THD-U limit message1 BitDPT.1CT
18Measurement Ch1THD-I limit message1 BitDPT.1CT
19Measurement Ch1Apparent power4 Bytes14.56 power (W)CRT
20Measurement Ch1Reactive power4 Bytes14.56 power (W)CRT
21Measurement Ch1Power factor4 Bytes14.57 power factor (cos Φ)CRT
22Measurement Ch1THD-U2 BytesDPT.8CRT
23Measurement Ch1THD-I2 BytesDPT.8CRT
24Measurement Ch1Spectrum U14 BytesCRT
25Measurement Ch1Spectrum I14 BytesCRT
26Measurement Ch2Voltage (rms)2 Bytes9.20 voltage (mV)CRT
27Measurement Ch2Current (rms)2 Bytes9.21 current (mA)CRT
28Measurement Ch2Active power4 Bytes14.56 power (W)CRT
29Measurement Ch2External active power limit2 BytesDPT.8CRWT
30Measurement Ch2Active power limit message1 BitDPT.1CT
31Measurement Ch2Voltage limit message1 BitDPT.1CT
32Measurement Ch2Voltage failure message1 BitDPT.1CT
33Measurement Ch2Voltage peak message1 BitDPT.1CT
34Measurement Ch2Current limit message1 BitDPT.1CT
35Measurement Ch2Current peak message1 BitDPT.1CT
36Measurement Ch2THD-U limit message1 BitDPT.1CT
37Measurement Ch2THD-I limit message1 BitDPT.1CT
38Measurement Ch2Apparent power4 Bytes14.56 power (W)CRT
39Measurement Ch2Reactive power4 Bytes14.56 power (W)CRT
40Measurement Ch2Power factor4 Bytes14.57 power factor (cos Φ)CRT
41Measurement Ch2THD-U2 BytesDPT.8CRT
42Measurement Ch2THD-I2 BytesDPT.8CRT
43Measurement Ch2Spectrum U14 BytesCRT
44Measurement Ch2Spectrum I14 BytesCRT
45Measurement Ch3Voltage (rms)2 Bytes9.20 voltage (mV)CRT
46Measurement Ch3Current (rms)2 Bytes9.21 current (mA)CRT
47Measurement Ch3Active power4 Bytes14.56 power (W)CRT
48Measurement Ch3External active power limit2 BytesDPT.8CRWT
49Measurement Ch3Active power limit message1 BitDPT.1CT
50Measurement Ch3Voltage limit message1 BitDPT.1CT
51Measurement Ch3Voltage failure message1 BitDPT.1CT
52Measurement Ch3Voltage peak message1 BitDPT.1CT
53Measurement Ch3Current limit message1 BitDPT.1CT
54Measurement Ch3Current peak message1 BitDPT.1CT
55Measurement Ch3THD-U limit message1 BitDPT.1CT
56Measurement Ch3THD-I limit message1 BitDPT.1CT
57Measurement Ch3Apparent power4 Bytes14.56 power (W)CRT
58Measurement Ch3Reactive power4 Bytes14.56 power (W)CRT
59Measurement Ch3Power factor4 Bytes14.57 power factor (cos Φ)CRT
60Measurement Ch3THD-U2 BytesDPT.8CRT
61Measurement Ch3THD-I2 BytesDPT.8CRT
62Measurement Ch3Spectrum U14 BytesCRT
63Measurement Ch3Spectrum I14 BytesCRT
64Measurement three-phaseActive power4 Bytes14.56 power (W)CRT
65Measurement three-phaseExternal active power limit2 BytesDPT.8CRWT
66Measurement three-phaseActive power limit message1 BitDPT.1CT
67Measurement three-phaseReactive power4 Bytes14.56 power (W)CRT
68Measurement three-phaseExternal reactive power- LV2 BytesDPT.8CRWT
69Measurement three-phaseReactive power limit message1 BitDPT.1CT
70Measurement three-phaseApparent power4 Bytes14.56 power (W)CRT
71Measurement three-phaseUnbalanced load2 BytesDPT.8CRT
72Measurement three-phaseUnbalanced load limit message1 BitDPT.1CT
73Measurement three-phaseZero current2 Bytes9.21 current (mA)CRT
74Measurement three-phaseZero current limit message1 BitDPT.1CT
75Energy counter Ch1Active energy counter (bal.)4 BytesDPT.13CRT
76Energy counter Ch1Active energy counter (con.)4 BytesDPT.13CRT
77Energy counter Ch1Active energy counter (gen.)4 BytesDPT.13CRT
78Energy counter Ch1Reset counters1 BitDPT.1CW
79Energy counter Ch2Active energy counter (bal.)4 BytesDPT.13CRT
80Energy counter Ch2Active energy counter (con.)4 BytesDPT.13CRT
81Energy counter Ch2Active energy counter (gen.)4 BytesDPT.13CRT
82Energy counter Ch2Reset counters1 BitDPT.1CW
83Energy counter Ch3Active energy counter (bal.)4 BytesDPT.13CRT
84Energy counter Ch3Active energy counter (con.)4 BytesDPT.13CRT
85Energy counter Ch3Active energy counter (gen.)4 BytesDPT.13CRT
86Energy counter Ch3Reset counters1 BitDPT.1CW
87Energy counter three-phaseActive energy counter (bal.)4 BytesDPT.13CRT
88Energy counter three-phaseActive energy counter (con.)4 BytesDPT.13CRT
89Energy counter three-phaseActive energy counter (gen.)4 BytesDPT.13CRT
90Energy counter three-phaseReactive energy counter4 BytesDPT.13CRT
91Energy counter three-phaseReset counters1 BitDPT.1CW
92Tariff cost counter tariff 1Tariff cost counter (balance)4 BytesDPT.13CRT
93Tariff cost counter tariff 1Tariff cost counter (con.)4 BytesDPT.13CRT
94Tariff cost counter tariff 1Tariff cost counter (gen.)4 BytesDPT.13CRT
95Tariff cost counter tariff 1Reset counters1 BitDPT.1CW
96Tariff cost counter tariff 2Tariff cost counter (balance)4 BytesDPT.13CRT
97Tariff cost counter tariff 2Tariff cost counter (con.)4 BytesDPT.13CRT
98Tariff cost counter tariff 2Tariff cost counter (gen.)4 BytesDPT.13CRT
99Tariff cost counter tariff 2Reset counters1 BitDPT.1CW
100Tariff cost counter tariff 3Tariff cost counter (balance)4 BytesDPT.13CRT
101Tariff cost counter tariff 3Tariff cost counter (con.)4 BytesDPT.13CRT
102Tariff cost counter tariff 3Tariff cost counter (gen.)4 BytesDPT.13CRT
103Tariff cost counter tariff 3Reset counters1 BitDPT.1CW
104Intermediate counter 1Energy counter-current value4 BytesDPT.13CRT
105Intermediate counter 1Energy counter-previous value4 BytesDPT.13CRT
106Intermediate counter 1Cost counter-current value4 BytesDPT.13CRT
107Intermediate counter 1Cost counter-previous value4 BytesDPT.13CRT
108Intermediate counter 1Limit message1 BitDPT.1CT
109Intermediate counter 1External energy counter limit4 BytesDPT.13CRWT
110Intermediate counter 1External cost counter limit 4 BytesDPT.13CRWT
111Intermediate counter 1Reset counter value1 BitDPT.1CW
112Intermediate counter 2Energy counter-current value4 BytesDPT.13CRT
113Intermediate counter 2Energy counter-previous value4 BytesDPT.13CRT
114Intermediate counter 2Cost counter-current value4 BytesDPT.13CRT
115Intermediate counter 2Cost counter-previous value4 BytesDPT.13CRT
116Intermediate counter 2Limit message1 BitDPT.1CT
117Intermediate counter 2External energy counter limit4 BytesDPT.13CRWT
118Intermediate counter 2External cost counter limit 4 BytesDPT.13CRWT
119Intermediate counter 2Reset counter value1 BitDPT.1CW
120Intermediate counter 3Energy counter-current value4 BytesDPT.13CRT
121Intermediate counter 3Energy counter-previous value4 BytesDPT.13CRT
122Intermediate counter 3Cost counter-current value4 BytesDPT.13CRT
123Intermediate counter 3Cost counter-previous value4 BytesDPT.13CRT
124Intermediate counter 3Limit message1 BitDPT.1CT
125Intermediate counter 3External energy counter limit4 BytesDPT.13CRWT
126Intermediate counter 3External cost counter limit 4 BytesDPT.13CRWT
127Intermediate counter 3Reset counter value1 BitDPT.1CW
128Intermediate counter 4Energy counter-current value4 BytesDPT.13CRT
129Intermediate counter 4Energy counter-previous value4 BytesDPT.13CRT
130Intermediate counter 4Cost counter-current value4 BytesDPT.13CRT
131Intermediate counter 4Cost counter-previous value4 BytesDPT.13CRT
132Intermediate counter 4Limit message1 BitDPT.1CT
133Intermediate counter 4External energy counter limit4 BytesDPT.13CRWT
134Intermediate counter 4External cost counter limit 4 BytesDPT.13CRWT
135Intermediate counter 4Reset counter value1 BitDPT.1CW
136Intermediate counter 5Energy counter-current value4 BytesDPT.13CRT
137Intermediate counter 5Energy counter-previous value4 BytesDPT.13CRT
138Intermediate counter 5Cost counter-current value4 BytesDPT.13CRT
139Intermediate counter 5Cost counter-previous value4 BytesDPT.13CRT
140Intermediate counter 5Limit message1 BitDPT.1CT
141Intermediate counter 5External energy counter limit4 BytesDPT.13CRWT
142Intermediate counter 5External cost counter limit 4 BytesDPT.13CRWT
143Intermediate counter 5Reset counter value1 BitDPT.1CW
144Intermediate counter 6Energy counter-current value4 BytesDPT.13CRT
145Intermediate counter 6Energy counter-previous value4 BytesDPT.13CRT
146Intermediate counter 6Cost counter-current value4 BytesDPT.13CRT
147Intermediate counter 6Cost counter-previous value4 BytesDPT.13CRT
148Intermediate counter 6Limit message1 BitDPT.1CT
149Intermediate counter 6External energy counter limit4 BytesDPT.13CRWT
150Intermediate counter 6External cost counter limit 4 BytesDPT.13CRWT
151Intermediate counter 6Reset counter value1 BitDPT.1CW
152TariffTariff changeover1 ByteDPT.5CRWT
153Tariff 1Trigger (Tariff start)1 BitDPT.1CW
154Tariff 1Trigger (Tariff stop)1 BitDPT.1CW
155Tariff 1Rate (0.01 ct/kWh)2 BytesDPT.8CRWT
156Tariff 2Trigger (Tariff start)1 BitDPT.1CW
157Tariff 2Trigger (Tariff stop)1 BitDPT.1CW
158Tariff 2Rate (0.01 ct/kWh)2 BytesDPT.8CRWT
159Tariff 3Trigger (Tariff start)1 BitDPT.1CW
160Tariff 3Trigger (Tariff stop)1 BitDPT.1CW
161Tariff 3Rate (0.01 ct/kWh)2 BytesDPT.8CRWT
162GeneralDate3 Bytes11.1 dateCWU
Parameters (133)
ParameterTypeDefault
Transmission delay after bus voltage recovery (s)unsignedInt 2…2552
Transmission delay when sending intermediate counter values (s)unsignedInt 2…2552
Request time and date after bus voltage recoverylistNo
Value of group object 'Request Time'list0
Transmit group object 'In operation' (s)unsignedInt 0…655350
Value of group object 'In operation'list0
Reference current for limit values (x5A)unsignedInt 1…13417
Release frequency MeasurementlistNo
Transmit frequency cyclically (x10s)unsignedInt 0…172800
Transmit frequency at change (x0.1Hz)unsignedInt 0…6500
SD card recording modelistAll measurements without harmonics
SD card recording intervallist15min
Release group object 'Request measured values'listNo
Request measured valueslist0
Release group object 'Request power values'listNo
Request power valueslist0
Release channel 1listNo
Release channel 2listNo
Release channel 3listNo
Release three-phase valueslistNo
Transmit power and voltage measurements cyclicallylistNo
Transmit values cyclically (x10s)unsignedInt 0…172800
Transmit active power cyclicallylistNo
Transmit apparent power cyclicallylistNo
Transmit reactive power cyclicallylistNo
Transmit voltage cyclicallylistNo
Transmit power-, voltage- and current measurements at changelistNo
Transmit measured values at change (in % of current measured value)unsignedInt 0…2550
Transmit active power at changelistNo
Transmit apparent power at changelistNo
Transmit reactive power at changelistNo
Transmit voltage at changelistNo
Transmit current at changelistNo
Message at limit value (active power)listNo
Adopt limit value from buslistflighty
Limit value (x0.1%)signedInt -1000…10000
Hysteresis (x0.1%)signedInt -1000…10000
Message at limit value (voltage)listNo
Limit value (V)unsignedInt 0…8000
Message at voltage failure (voltage)listNo
Message at transient voltage peaklistNo
Transmit current and power quality measurements cyclicallylistNo
Transmit current cyclicallylistNo
Transmit power factor cyclicallylistNo
Transmit THD-U cyclicallylistNo
Transmit THD-I cyclicallylistNo
Transmit spectrum U cyclicallylistNo
Transmit spectrum I cyclicallylistNo
Message at limit value (current)listNo
Limit value (x0.1%)unsignedInt 0…10000
Message at transient current peaklistNo
Message at limit value (THD-U)listNo
Limit value (x0.1%)unsignedInt 0…2550
Message at limit value (THD-I)listNo
Message at limit value (current)ElistNo
Transmit three-phase values cyclicallylistNo
Transmit zero current cyclicallylistNo
Transmit unbalanced load cyclicallylistNo
Transmit power and current measurements at changelistNo
Transmit zero current at changelistNo
Message at limit value (three-phase-active power)listNo
Message at limit value (reactive power)listNo
Hysteresis (x0.1%)signedInt -1000…10001
Message at limit value (unbalanced load)listNo
Limit value (%)unsignedInt 0…1000
Message at limit value (zero current)listNo
Release energy counter - channel 1listNo
Release energy counter - channel 2listNo
Release energy counter - channel 3listNo
Release energy counter - three-phaselistNo
Release tariff cost counter - three-phaselistNo
Release tariff cost counter 1listNo
Release tariff cost counter 2listNo
Release tariff cost counter 3listNo
Release intermediate counter 1listNo
Release intermediate counter 2listNo
Release intermediate counter 3listNo
Release intermediate counter 4listNo
Release intermediate counter 5listNo
Release intermediate counter 6listNo
Transmit counter values cyclicallylistNo
Transmit counter values cyclically (x10s)unsignedInt 0…172800
Transmit active energy counter (balance) cyclicallylistNo
Transmit active energy counter (consumption) cyclicallylistNo
Transmit active energy counter (generation) cyclicallylistNo
Transmit counter values at changelistNo
Transmit counter values at change (in % of current measured value)unsignedInt 0…2550
Transmit active energy counter (balance) at changelistNo
Transmit active energy counter (consumption) at changelistNo
Transmit active energy counter (generation) at changelistNo
Counter after ETS downloadlistno reaction
Release group object “Reset counter values of channel 1“listNo
Release group object “Reset counter values of channel 2“listNo
Release group object “Reset counter values of channel 3“listNo
Transmit reactive energy counter cyclicallylistNo
Transmit reactive energy counter at changelistNo
Release group object “Reset counter values“listNo
Transmit tariff cost counter cyclicallylistNo
Transmit tariff cost counter cyclically (x10s)unsignedInt 0…172800
Transmit tariff cost counter 1 (balance) cyclicallylistNo
Transmit tariff cost counter 1 (con.) cyclicallylistNo
Transmit tariff cost counter 1 (gen.) cyclicallylistNo
Transmit tariff cost counter 2 (balance) cyclicallylistNo
Transmit tariff cost counter 2 (con.) cyclicallylistNo
Transmit tariff cost counter 2 (gen.) cyclicallylistNo
Transmit tariff cost counter 3 (balance) cyclicallylistNo
Transmit tariff cost counter 3 (con.) cyclicallylistNo
Transmit tariff cost counter 3 (gen.) cyclicallylistNo
Release group object “Reset Tariff counter values 1“listNo
Release group object “Reset Tariff counter values 2“listNo
Release group object “Reset Tariff counter values 3“listNo
Input counter value of intermediate counterlistActive energy counter (balance) - channel 1
Count intervallist1min
Transmit counter value before resettinglistYes
Transmit counter values cyclically (x10s)unsignedInt 0…172800
Message at limit valuelistNo
Limit value (Wh)signedInt -32767…327670
Limit value (Cent)signedInt -32767…327670
Release tariff 1listNo
Release tariff 2listNo
Release tariff 3listNo
Tariff after bus voltage recoverylistno tariff
Rate (0.01 ct/kWh)signedInt -10000…100000
Adopt rate from buslistflighty
Tariff changeover tariff 1listvia tariff-time switch
Start (hour)unsignedInt 0…230
Start (minute)unsignedInt 0…590
Start (weekday)listeveryday
End (hour)unsignedInt 0…230
End (minute)unsignedInt 0…590
End (weekday)listeveryday
Tariff changeover tariff 2listvia tariff-time switch
Tariff changeover tariff 3listvia tariff-time switch

Version history

ApplicationApp noFingerprintFirst seenSizeFile
SmartMeter 85A/85A RT/630A 0.0 latest$0005043A2026-11-25101 KBDownload

About this file

This is the official ETS product database for the Enertex Bayern GmbH SmartMeter 85A/85A RT/630A (00001149), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.