KNX eTR 102 FC 7132X
Elsner Elektronik GmbH · Order number 7132X · Sensoren › Innensensoren
Download .knxprod KNX eTR 102 FC 1.0 · 345 KB
Product
| Manufacturer | Elsner Elektronik GmbH |
|---|---|
| Product name | KNX eTR 102 FC |
| Order number | 7132X |
| Hardware | KNX eTR 102 FC |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Certified · 2023-08-30 |
| Languages | en-US, es-ES, fr-FR, it-IT, de-DE |
| Catalog entry | M-00C9_H-7132X.5F10-0_HP-10BC-10-3C88_CI-7132X-1 |
| Fingerprint | 3C88 |
| SHA-256 | 19a7403768d736e386b3b73c7182e3ccd215eaa7baefe92662ba069cade156cd |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: KNX eTR 102 FC 1.0
| Application number | $10BC |
|---|---|
| Version | 1.0 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 417 |
| Group objects | 154 |
Group objects (154)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Softwareversion | Ausgang | 2 Bytes | 217.1 DPT version | CRT |
| 20 | Temperatursensor: Störung | Ausgang | 1 Bit | 1.1 switch | CRT |
| 21 | Temperatursensor: Messwert Extern | Eingang | 2 Bytes | 9.1 temperature (°C) | CWT |
| 22 | Temperatursensor: Messwert | Ausgang | 2 Bytes | 9.1 temperature (°C) | CRT |
| 22 | Temperatursensor: Messwert Intern | Ausgang | 2 Bytes | 9.1 temperature (°C) | CRT |
| 23 | Temperatursensor: Messwert Gesamt | Ausgang | 2 Bytes | 9.1 temperature (°C) | CRT |
| 24 | Temperatursensor: Messwert Min/Max Anfrage | Eingang | 1 Bit | 1.17 trigger | CW |
| 25 | Temperatursensor: Messwert Minimal | Ausgang | 2 Bytes | 9.1 temperature (°C) | CRT |
| 26 | Temperatursensor: Messwert Maximal | Ausgang | 2 Bytes | 9.1 temperature (°C) | CRT |
| 27 | Temperatursensor: Messwert Min/Max Reset | Eingang | 1 Bit | 1.17 trigger | CW |
| 30 | Temp. Grenzwert 1: Absolutwert | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 31 | Temp. Grenzwert 1: (1:+ | 0:-) | Eingang | 1 Bit | 1.1 switch | CW |
| 32 | Temp. Grenzwert 1: Schaltverzögerung von 0 auf 1 | Eingang | 2 Bytes | 7.5 time (s) | CW |
| 33 | Temp. Grenzwert 1: Schaltverzögerung von 1 auf 0 | Eingang | 2 Bytes | 7.5 time (s) | CW |
| 34 | Temp. Grenzwert 1: Schaltausgang | Ausgang | 1 Bit | 1.1 switch | CRT |
| 35 | Temp. Grenzwert 1: Schaltausgang Sperre | Eingang | 1 Bit | 1.1 switch | CW |
| 36 | Temp. Grenzwert 2: Absolutwert | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 37 | Temp. Grenzwert 2: (1:+ | 0:-) | Eingang | 1 Bit | 1.1 switch | CW |
| 38 | Temp. Grenzwert 2: Schaltverzögerung von 0 auf 1 | Eingang | 2 Bytes | 7.5 time (s) | CW |
| 39 | Temp. Grenzwert 2: Schaltverzögerung von 1 auf 0 | Eingang | 2 Bytes | 7.5 time (s) | CW |
| 40 | Temp. Grenzwert 2: Schaltausgang | Ausgang | 1 Bit | 1.1 switch | CRT |
| 41 | Temp. Grenzwert 2: Schaltausgang Sperre | Eingang | 1 Bit | 1.1 switch | CW |
| 50 | Temp.Regler: HVAC Modus (Priorität 1) | Eingang / Ausgang | 1 Byte | 20.102 HVAC mode | CRWTU |
| 50 | Temp.Regler: Modus (1: Eco | 0: Standby) | Eingang / Ausgang | 1 Bit | 1.1 switch | CRWTU |
| 50 | Temp.Regler: HVAC Modus (Priorität 1) | Eingang | 1 Byte | 20.102 HVAC mode | CWU |
| 50 | Temp.Regler: Modus (1: Eco | 0: Standby) | Eingang | 1 Bit | 1.1 switch | CWU |
| 51 | Temp.Regler: HVAC Modus (Priorität 2) | Eingang / Ausgang | 1 Byte | 20.102 HVAC mode | CRWT |
| 51 | Temp.Regler: Modus Komfort Aktivierung | Eingang / Ausgang | 1 Bit | 1.1 switch | CRWT |
| 51 | Temp.Regler: HVAC Modus (Priorität 2) | Eingang | 1 Byte | 20.102 HVAC mode | CWU |
| 51 | Temp.Regler: Modus Komfort Aktivierung | Eingang | 1 Bit | 1.1 switch | CWU |
| 52 | Temp.Regler: Modus Frost-/Hitzeschutz Aktivierung | Eingang / Ausgang | 1 Bit | 1.1 switch | CRWT |
| 52 | Temp.Regler: Modus Frost-/Hitzeschutz Aktivierung | Eingang | 1 Bit | 1.1 switch | CWU |
| 53 | Temp.Regler: Ein/Aus (1 = Ein | 0 = Aus) | Eingang / Ausgang | 1 Bit | 1.1 switch | CRWT |
| 53 | Temp.Regler: Ein/Aus (0 = Ein | 1 = Aus) | Eingang / Ausgang | 1 Bit | 1.1 switch | CRWT |
| 53 | Temp.Regler: Ein/Aus (1 = Ein | 0 = Aus) | Eingang / Ausgang | 1 Bit | 1.1 switch | CRWTU |
| 53 | Temp.Regler: Ein/Aus (0 = Ein | 1 = Aus) | Eingang / Ausgang | 1 Bit | 1.1 switch | CRWTU |
| 54 | Temp.Regler: Sollwert Aktuell | Ausgang | 2 Bytes | 9.1 temperature (°C) | CRT |
| 55 | Temp.Regler: Umschaltung (Heizen = 0 | Kühlen = 1) | Eingang | 1 Bit | 1.1 switch | CW |
| 55 | Temp.Regler: Umschaltung (Heizen = 1 | Kühlen = 0) | Ausgang | 1 Bit | 1.1 switch | CRWT |
| 55 | Temp.Regler: Status (Heizen = 0 | Kühlen = 1) | Ausgang | 1 Bit | 1.1 switch | CRT |
| 55 | Temp.Regler: Status (Heizen = 1 | Kühlen = 0) | Ausgang | 1 Bit | 1.1 switch | CRT |
| 55 | Temp.Regler: Umschaltung (Heizen = 1 | Kühlen = 0) | Eingang | 1 Bit | 1.1 switch | CW |
| 55 | Temp.Regler: Status (Heizen = 0 | Kühlen = 1) | Eingang | 1 Bit | 1.1 switch | CWTU |
| 55 | Temp.Regler: Status (Heizen = 1 | Kühlen = 0) | Eingang | 1 Bit | 1.1 switch | CWTU |
| 56 | Temp.Regler: Sollwert Komfort Heizung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 56 | Temp.Regler: Sollwert Komfort | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 56 | Temp.Regler: Sollwert Komfort Heizung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 57 | Temp.Regler: Sollwert Komfort Heizung (1:+ | 0:-) | Eingang | 1 Bit | 1.1 switch | CW |
| 57 | Temp.Regler: Sollwert Komfort (1:+ | 0:-) | Eingang | 1 Bit | 1.1 switch | CW |
| 57 | Temp.Regler: Sollwert Komfort Heizung (1:+ | 0:-) | Ausgang | 1 Bit | 1.1 switch | CT |
| 58 | Temp.Regler: Sollwert Komfort Kühlung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 58 | Temp.Regler: Sollwert Komfort | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 58 | Temp.Regler: Sollwert Komfort Kühlung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 59 | Temp.Regler: Sollwert Komfort Kühlung (1:+ | 0:-) | Eingang | 1 Bit | 1.1 switch | CW |
| 59 | Temp.Regler: Sollwert Komfort (1:+ | 0:-) | Eingang | 1 Bit | 1.1 switch | CW |
| 59 | Temp.Regler: Sollwert Komfort Kühlung (1:+ | 0:-) | Ausgang | 1 Bit | 1.1 switch | CT |
| 59 | Temp.Regler: Sollwert Komfort (1:+ | 0:-) | Ausgang | 1 Bit | 1.1 switch | CT |
| 60 | Temp.Regler: Basissollwertverschiebung 16 Bit | Eingang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 60 | Temp.Regler: Basissollwertverschiebung 16 Bit | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 61 | Temp.Regler: Sollwert Standby Heizung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 61 | Temp.Regler: Sollwert Standby Heizung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 62 | Temp.Regler: Sollwert Standby Heizung (1:+ | 0:-) | Eingang | 1 Bit | 1.1 switch | CW |
| 62 | Temp.Regler: Sollwert Standby Heizung (1:+ | 0:-) | Ausgang | 1 Bit | 1.1 switch | CT |
| 63 | Temp.Regler: Sollwert Standby Kühlung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 63 | Temp.Regler: Sollwert Standby Kühlung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 64 | Temp.Regler: Sollwert Standby Kühlung (1:+ | 0:-) | Eingang | 1 Bit | 1.1 switch | CW |
| 64 | Temp.Regler: Sollwert Standby Kühlung (1:+ | 0:-) | Ausgang | 1 Bit | 1.1 switch | CT |
| 65 | Temp.Regler: Sollwert Eco Heizung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 65 | Temp.Regler: Sollwert Eco Heizung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 66 | Temp.Regler: Sollwert Eco Heizung (1:+ | 0:-) | Eingang | 1 Bit | 1.1 switch | CW |
| 66 | Temp.Regler: Sollwert Eco Heizung (1:+ | 0:-) | Ausgang | 1 Bit | 1.1 switch | CT |
| 67 | Temp.Regler: Sollwert Eco Kühlung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 67 | Temp.Regler: Sollwert Eco Kühlung | Eingang / Ausgang | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 68 | Temp.Regler: Sollwert Eco Kühlung (1:+ | 0:-) | Eingang | 1 Bit | 1.1 switch | CW |
| 68 | Temp.Regler: Sollwert Eco Kühlung (1:+ | 0:-) | Ausgang | 1 Bit | 1.1 switch | CT |
| 69 | Temp.Regler: Stellgröße Heizung (1. Stufe) | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 69 | Temp.Regler: Stellgröße (1. Stufe) | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 70 | Temp.Regler: Stellgröße Heizung (2. Stufe) | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 70 | Temp.Regler: Stellgröße Heizung (2. Stufe) | Ausgang | 1 Bit | 1.1 switch | CRT |
| 70 | Temp.Regler: Stellgröße (2. Stufe) | Ausgang | 1 Bit | 1.1 switch | CRT |
| 70 | Temp.Regler: Stellgröße (2. Stufe) | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 71 | Temp.Regler: Stellgröße Kühlung (1. Stufe) | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 72 | Temp.Regler: Stellgröße Kühlung (2. Stufe) | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 72 | Temp.Regler: Stellgröße Kühlung (2. Stufe) | Ausgang | 1 Bit | 1.1 switch | CRT |
| 73 | Temp.Regler: Stellgröße für 4/6 Wegeventil | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 74 | Temp.Regler: Status Heizung Stufe 1 (1:AN | 0:AUS) | Ausgang | 1 Bit | 1.1 switch | CRT |
| 75 | Temp.Regler: Status Heizung Stufe 2 (1:AN | 0:AUS) | Ausgang | 1 Bit | 1.1 switch | CRT |
| 76 | Temp.Regler: Status Kühlung Stufe 1 (1:AN | 0:AUS) | Ausgang | 1 Bit | 1.1 switch | CRT |
| 77 | Temp.Regler: Status Kühlung Stufe 2 (1:AN | 0:AUS) | Ausgang | 1 Bit | 1.1 switch | CRT |
| 78 | Temp.Regler: Komfort Verlängerungsstatus | Eingang | 1 Bit | 1.1 switch | CW |
| 78 | Temp.Regler: Komfort Verlängerungsstatus | Eingang | 1 Bit | 1.1 switch | CWTU |
| 79 | Temp.Regler: Komfort Verlängerungszeit | Eingang | 2 Bytes | 7.5 time (s) | CRWT |
| 80 | Temp. Regler: Fan Coil Stufe 0 bis 3 | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 80 | Temp. Regler: Fan Coil Stufe 0 bis 3 | Eingang / Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 81 | Temp. Regler: Fan Coil Stufe 1 | Ausgang | 1 Bit | 1.1 switch | CRT |
| 82 | Temp. Regler: Fan Coil Stufe 2 | Ausgang | 1 Bit | 1.1 switch | CRT |
| 83 | Temp. Regler: Fan Coil Stufe 3 | Ausgang | 1 Bit | 1.1 switch | CRT |
| 84 | Temp. Regler: Fan Coil Auto=1 Manuell=0 | Eingang / Ausgang | 1 Bit | 1.1 switch | CRWTU |
| 86 | Alle LEDs An/Aus | Eingang | 1 Bit | 1.1 switch | CW |
| 87 | Alle LEDs Helligkeit | Eingang | 1 Byte | 5.1 percentage (0..100%) | CW |
| 88 | LEDs Temperaturanzeige An/Aus | Eingang | 1 Bit | 1.1 switch | CW |
| 89 | LEDs Temperaturanzeige Sperre | Eingang | 1 Bit | 1.1 switch | CW |
| 90 | LED 1 An/Aus | Eingang | 1 Bit | 1.1 switch | CW |
| 91 | LED 1 Sperre | Eingang | 1 Bit | 1.1 switch | CW |
| 92 | LED 2 An/Aus | Eingang | 1 Bit | 1.1 switch | CW |
| 93 | LED 2 Sperre | Eingang | 1 Bit | 1.1 switch | CW |
| 107 | Logikeingang 1 | Eingang | 1 Bit | 1.2 boolean | CW |
| 108 | Logikeingang 2 | Eingang | 1 Bit | 1.2 boolean | CW |
| 109 | Logikeingang 3 | Eingang | 1 Bit | 1.2 boolean | CW |
| 110 | Logikeingang 4 | Eingang | 1 Bit | 1.2 boolean | CW |
| 111 | Logikeingang 5 | Eingang | 1 Bit | 1.2 boolean | CW |
| 112 | Logikeingang 6 | Eingang | 1 Bit | 1.2 boolean | CW |
| 113 | Logikeingang 7 | Eingang | 1 Bit | 1.2 boolean | CW |
| 114 | Logikeingang 8 | Eingang | 1 Bit | 1.2 boolean | CW |
| 117 | UND Logik 1: 1 Bit Schaltausgang | Ausgang | 1 Bit | 1.2 boolean | CRT |
| 118 | UND Logik 1: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 118 | UND Logik 1: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 118 | UND Logik 1: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.3 angle (degrees) | CRT |
| 118 | UND Logik 1: 8 Bit Ausgang A | Ausgang | 1 Byte | 17.1 scene number | CRT |
| 119 | UND Logik 1: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 119 | UND Logik 1: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 119 | UND Logik 1: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.3 angle (degrees) | CRT |
| 119 | UND Logik 1: 8 Bit Ausgang B | Ausgang | 1 Byte | 17.1 scene number | CRT |
| 120 | UND Logik 1: Sperre | Eingang | 1 Bit | 1.1 switch | CW |
| 121 | UND Logik 2: 1 Bit Schaltausgang | Ausgang | 1 Bit | 1.2 boolean | CRT |
| 122 | UND Logik 2: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 122 | UND Logik 2: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 122 | UND Logik 2: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.3 angle (degrees) | CRT |
| 122 | UND Logik 2: 8 Bit Ausgang A | Ausgang | 1 Byte | 17.1 scene number | CRT |
| 123 | UND Logik 2: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 123 | UND Logik 2: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 123 | UND Logik 2: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.3 angle (degrees) | CRT |
| 123 | UND Logik 2: 8 Bit Ausgang B | Ausgang | 1 Byte | 17.1 scene number | CRT |
| 124 | UND Logik 2: Sperre | Eingang | 1 Bit | 1.1 switch | CW |
| 125 | ODER Logik 1: 1 Bit Schaltausgang | Ausgang | 1 Bit | 1.2 boolean | CRT |
| 126 | ODER Logik 1: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 126 | ODER Logik 1: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 126 | ODER Logik 1: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.3 angle (degrees) | CRT |
| 126 | ODER Logik 1: 8 Bit Ausgang A | Ausgang | 1 Byte | 17.1 scene number | CRT |
| 127 | ODER Logik 1: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 127 | ODER Logik 1: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 127 | ODER Logik 1: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.3 angle (degrees) | CRT |
| 127 | ODER Logik 1: 8 Bit Ausgang B | Ausgang | 1 Byte | 17.1 scene number | CRT |
| 128 | ODER Logik 1: Sperre | Eingang | 1 Bit | 1.1 switch | CW |
| 129 | ODER Logik 2: 1 Bit Schaltausgang | Ausgang | 1 Bit | 1.2 boolean | CRT |
| 130 | ODER Logik 2: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 130 | ODER Logik 2: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 130 | ODER Logik 2: 8 Bit Ausgang A | Ausgang | 1 Byte | 5.3 angle (degrees) | CRT |
| 130 | ODER Logik 2: 8 Bit Ausgang A | Ausgang | 1 Byte | 17.1 scene number | CRT |
| 131 | ODER Logik 2: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 131 | ODER Logik 2: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 131 | ODER Logik 2: 8 Bit Ausgang B | Ausgang | 1 Byte | 5.3 angle (degrees) | CRT |
| 131 | ODER Logik 2: 8 Bit Ausgang B | Ausgang | 1 Byte | 17.1 scene number | CRT |
| 132 | ODER Logik 2: Sperre | Eingang | 1 Bit | 1.1 switch | CW |
Parameters (193)
| Parameter | Type | Default |
|---|---|---|
| Sendeverzögerungen nach Reset/Buswiederkehr | unsignedInt 5…300 | 5 |
| Maximale Telegrammrate | list | 10 Telegramme pro Sekunde |
| Offset in 0,1°C | signedInt -50…50 | 0 |
| Externen Messwert verwenden | list | Nein |
| Sendeverhalten | list | nicht |
| Sendezyklus | list | 10 s |
| ab Änderung von | list | 0,5°C |
| Ext. Messwertanteil am Gesamtmesswert | list | 50% |
| Sendeverhalten für Messwert Intern und Gesamt | list | nicht |
| Minimal- und Maximalwert verwenden | list | Nein |
| Logikeingänge verwenden | list | Nein |
| - Logikeingang 1 | list | 0 |
| - Logikeingang 2 | list | 0 |
| - Logikeingang 3 | list | 0 |
| - Logikeingang 4 | list | 0 |
| - Logikeingang 5 | list | 0 |
| - Logikeingang 6 | list | 0 |
| - Logikeingang 7 | list | 0 |
| - Logikeingang 8 | list | 0 |
| UND Logik 1 | list | nicht aktiv |
| UND Logik 2 | list | nicht aktiv |
| ODER Logik 1 | list | nicht aktiv |
| ODER Logik 2 | list | nicht aktiv |
| 1. Eingang | list | nicht verwenden |
| 2. Eingang | list | nicht verwenden |
| 3. Eingang | list | nicht verwenden |
| 4. Eingang | list | nicht verwenden |
| Ausgangsart | list | ein 1 Bit-Objekt |
| Ausgangswert wenn Logik = 1 | unsignedInt 0…1 | 1 |
| Ausgangswert wenn Logik = 0 | unsignedInt 0…1 | 0 |
| Ausgangswert wenn Sperre aktiv | unsignedInt 0…1 | 0 |
| Ausgangswert wenn Überwachungszeit überschritten | unsignedInt 0…1 | 0 |
| Objektart | list | Wert (0 ... 255) |
| Ausgangswert Objekt A wenn Logik = 1 | unsignedInt 0…255 | 1 |
| Ausgangswert Objekt B wenn Logik = 1 | unsignedInt 0…255 | 1 |
| Ausgangswert Objekt A wenn Logik = 0 | unsignedInt 0…255 | 0 |
| Ausgangswert Objekt B wenn Logik = 0 | unsignedInt 0…255 | 0 |
| Ausgangswert Objekt A wenn Sperre aktiv | unsignedInt 0…255 | 0 |
| Ausgangswert Objekt B wenn Sperre aktiv | unsignedInt 0…255 | 0 |
| Ausgangswert Objekt A wenn Überwachungszeit überschritten | unsignedInt 0…255 | 0 |
| Ausgangswert Objekt B wenn Überwachungszeit überschritten | unsignedInt 0…255 | 0 |
| Ausgangswert Objekt A wenn Logik = 1 | unsignedInt 0…100 | 1 |
| Ausgangswert Objekt B wenn Logik = 1 | unsignedInt 0…100 | 1 |
| Ausgangswert Objekt A wenn Logik = 0 | unsignedInt 0…100 | 0 |
| Ausgangswert Objekt B wenn Logik = 0 | unsignedInt 0…100 | 0 |
| Ausgangswert Objekt A wenn Sperre aktiv | unsignedInt 0…100 | 0 |
| Ausgangswert Objekt B wenn Sperre aktiv | unsignedInt 0…100 | 0 |
| Ausgangswert Objekt A wenn Überwachungszeit überschritten | unsignedInt 0…100 | 0 |
| Ausgangswert Objekt B wenn Überwachungszeit überschritten | unsignedInt 0…100 | 0 |
| Ausgangswert Objekt A wenn Logik = 1 | signedInt 0…360 | 1 |
| Ausgangswert Objekt B wenn Logik = 1 | signedInt 0…360 | 1 |
| Ausgangswert Objekt A wenn Logik = 0 | signedInt 0…360 | 0 |
| Ausgangswert Objekt B wenn Logik = 0 | signedInt 0…360 | 0 |
| Ausgangswert Objekt A wenn Sperre aktiv | signedInt 0…360 | 0 |
| Ausgangswert Objekt B wenn Sperre aktiv | signedInt 0…360 | 0 |
| Ausgangswert Objekt A wenn Überwachungszeit überschritten | signedInt 0…360 | 0 |
| Ausgangswert Objekt B wenn Überwachungszeit überschritten | signedInt 0…360 | 0 |
| Ausgangswert Objekt A wenn Logik = 1 | unsignedInt 0…63 | 1 |
| Ausgangswert Objekt B wenn Logik = 1 | unsignedInt 0…63 | 1 |
| Ausgangswert Objekt A wenn Logik = 0 | unsignedInt 0…63 | 0 |
| Ausgangswert Objekt B wenn Logik = 0 | unsignedInt 0…63 | 0 |
| Ausgangswert Objekt A wenn Sperre aktiv | unsignedInt 0…63 | 0 |
| Ausgangswert Objekt B wenn Sperre aktiv | unsignedInt 0…63 | 0 |
| Ausgangswert Objekt A wenn Überwachungszeit überschritten | unsignedInt 0…63 | 0 |
| Ausgangswert Objekt B wenn Überwachungszeit überschritten | unsignedInt 0…63 | 0 |
| Sendeverhalten | list | bei Änderung der Logik |
| Sperre verwenden | list | Nein |
| Auswertung des Sperrobjekts | list | 1 = sperren | 0 = freigeben |
| Sperrobjektwert vor 1. Kommunikation | list | 0 |
| beim Sperren | list | kein Telegramm senden |
| beim Freigeben (mit 2 Sek. Freigabeverzögerung) | list | kein Telegramm senden |
| Eingangsüberwachung verwenden | list | Nein |
| Überwachung von Eingang | list | 1 + 2 + 3 + 4 |
| Überwachungszeitraum | list | 1 min |
| Ausgangsverhalten bei Überschreitung der Überwachungszeit | list | kein Telegramm senden |
| Störobjekt verwenden | list | Nein |
| Download Indikator | list | Ja |
| Reserve_Objekte_Verwenden | list | Nein |
| Funktion LED 1 (links) | list | An nach Tastendruck für einstellbare Zeit |
| Funktion LED 2 (rechts) | list | An nach Tastendruck für einstellbare Zeit |
| LED Modus | list | Alle LEDs als Ambiente-Beleuchtung |
| Objekte verwenden | list | Nein |
| Objektwert An/Aus nach Reset | list | 1 |
| Helligkeit | unsignedInt 0…100 | 30 |
| Automatisches Ausschalten nach Tastendruck verwenden | list | Ja |
| Ausschalten nach | unsignedInt 1…255 | 30 |
| Sperrobjekt verwenden | list | Nein |
| Leuchtdauer nach Bedienung | unsignedInt 1…255 | 3 |
| Objektwert nach Reset | list | 1 |
| Grenzwert 1 verwenden | list | Nein |
| Grenzwert 2 verwenden | list | Nein |
| Grenzwerte und Verzögerungen sollen | list | nicht |
| Grenzwertvorgabe per | list | Parameter |
| Grenzwert in 0,1°C | signedInt -300…800 | 200 |
| Startgrenzwert in 0,1°C gültig bis zur 1. Kommunikation | signedInt -300…800 | 200 |
| Objektwertbegrenzung (min) in 0,1°C | signedInt -300…800 | -300 |
| Objektwertbegrenzung (max) in 0,1°C | signedInt -300…800 | 800 |
| Art der Grenzwertveränderung | list | Absolutwert |
| Schrittweite | list | 0,1°C |
| Einstellung des Schaltabstands (Hysterese) | list | absolut |
| Schaltabstand (Hysterese) in % des Grenzwerts | unsignedInt 0…50 | 20 |
| Schaltabstand (Hysterese) in 0,1°C | unsignedInt 0…1100 | 50 |
| Ausgang ist bei (GW = Grenzwert) (Schaltab. = Schaltabstand) | list | GW über = 1 | GW - Schaltab. unter = 0 |
| Verzögerungen über Objekte einstellbar (in Sekunden) | list | Nein |
| Verzögerung von 0 auf 1 | list | keine |
| Verzögerung von 1 auf 0 | list | keine |
| Verzögerung von 0 auf 1 gültig bis zur 1. Kommunikation | list | keine |
| Verzögerung von 1 auf 0 gültig bis zur 1. Kommunikation | list | keine |
| Schaltausgang sendet | list | bei Änderung |
| Sperrung des Schaltausgangs verwenden | list | Nein |
| Auswertung des Sperrobjekts | list | bei Wert 1: sperren | bei Wert 0: freigeben |
| Wert des Sperrobjekts vor 1. Kommunikation | list | 0 |
| Aktion beim Sperren | list | kein Telegramm senden |
| Aktion beim Freigeben (mit 2 Sekunden Freigabeverzögerung) | list | kein Telegramm senden |
| Zyklus | list | 5 s |
| Regelung verwenden | list | Nein |
| Verwendung als | list | Eigenständiger Regler |
| Sollwerte und Verlängerungszeit sollen | list | nach Spannungswiederkehr |
| Modusumschaltung über | list | zwei 8 Bit Objekte (HVAC Modi) |
| Modus nach Reset | list | Komfort |
| Verhalten des Ein-/Aus-Ojekts bei Wert | list | 1 = Ein | 0 = Aus |
| Wert des Ein-/Aus-Ojekts nach Reset | list | 1 |
| Stellgrößen senden | list | bei Änderung |
| ab Änderung von (in % absolut) | unsignedInt 1…10 | 2 |
| Zyklus | list | 5 min |
| Statusobjekte senden | list | bei Änderung |
| Art der Regelung | list | Einstufen Heizung |
| Geänderte Sollwerte nach Moduswechsel erhalten | list | Ja |
| Einstellung der Sollwerte | list | separat |
| Schrittweite für Sollwertänderungen (in 0,1°C) | unsignedInt 1…50 | 10 |
| Komfort Verlängerungszeit in Sekunden (Nur im Eco Modus aktivierbar) | unsignedInt 1…36000 | 3600 |
| Startsollwert Heizen (in 0,1°C) gültig bis zur 1.Kommunikation | signedInt -300…800 | 210 |
| Min. Objektwert Heizen (in 0,1°C) | signedInt -300…800 | 160 |
| Max. Objektwert Heizen (in 0,1°C) | signedInt -300…800 | 280 |
| Startsollwert Heizen (in 0,1°C) gültig bis zur 1.Kommunikation | signedInt -300…800 | 180 |
| Startsollwert Heizen (in 0,1°C) gültig bis zur 1.Kommunikation | signedInt -300…800 | 160 |
| Minimaler Basissollwert (in 0,1°C) | signedInt -300…800 | 160 |
| Maximaler Basissollwert (in 0,1°C) | signedInt -300…800 | 280 |
| Begrenzung für Sollwertänderung verwenden | list | Ja |
| Absenkung um bis zu (in 0,1°C) | signedInt 1…100 | 50 |
| Anhebung um bis zu (in 0,1°C) | signedInt 1…100 | 50 |
| Absenkung Heizsollwert (in 0,1°C) | unsignedInt 0…200 | 30 |
| Absenkung Heizsollwert (in 0,1°C) | unsignedInt 0…200 | 50 |
| Sollwert Frostschutz (in 0,1°C) | signedInt -300…800 | 70 |
| Aktivierungsverzögerung | list | 5 min |
| Stellgröße für 4/6 Wegeventil verwenden | list | Nein |
| Einstellen des Reglers durch | list | vorgegebene Anwendungen |
| Maximale Stellgröße wird erreicht bei Soll-/Ist-Differenz von (in °C) | unsignedInt 1…5 | 4 |
| Nachstellzeit (in min) | unsignedInt 1…255 | 100 |
| Anwendung | list | Warmwasserheizung |
| Beim Sperren soll Stellgröße | list | einen bestimmten Wert senden |
| Wert (in %) | unsignedInt 0…100 | 0 |
| Sollwertdifferenz zwischen 1. und 2. Stufe (in 0,1°C) | unsignedInt 0…100 | 40 |
| Regelungsart | list | 2-Punkt-Regelung |
| Maximale Stellgröße wird erreicht bei Soll-/Ist-Differenz von (in °C) | unsignedInt 1…5 | 5 |
| Nachstellzeit (in min) | unsignedInt 1…255 | 150 |
| Schaltabstand (Hysterese) (in 0,1°C) | unsignedInt 0…100 | 20 |
| Stellgröße ist ein | list | 1 Bit-Objekt |
| Wert | list | 0 |
| Wert (in %) | unsignedInt 0…100 | 100 |
| Startsollwert Kühlen (in 0,1°C) gültig bis zur 1.Kommunikation | signedInt -300…800 | 210 |
| Min. Objektwert Kühlen (in 0,1°C) | signedInt -300…800 | 160 |
| Max. Objektwert Kühlen (in 0,1°C) | signedInt -300…800 | 280 |
| Startsollwert Kühlen (in 0,1°C) gültig bis zur 1.Kommunikation | signedInt -300…800 | 240 |
| Startsollwert Kühlen (in 0,1°C) gültig bis zur 1.Kommunikation | signedInt -300…800 | 280 |
| Anhebung Kühlsollwert (in 0,1°C) | unsignedInt 0…200 | 30 |
| Anhebung Kühlsollwert (in 0,1°C) | unsignedInt 0…200 | 60 |
| Sollwert Hitzeschutz (in 0,1°C) | signedInt -300…800 | 350 |
| Nachstellzeit (in min) | unsignedInt 1…255 | 30 |
| Anwendung | list | Kühldecke |
| Einstellung der Sollwerte | list | mit separaten Sollwerten mit Umschaltobjekt |
| Verhalten des Umschaltobjekts bei Wert | list | 0 = Heizen | 1 = Kühlen |
| Wert des Umschaltobjektes nach Reset | list | 0 |
| Auswertung des Statusobjekts | list | 0 = Heizen | 1 = Kühlen |
| Totzone zwischen Heizen und Kühlen (in 0,1°C) | unsignedInt 1…100 | 50 |
| Startsollwert (in 0,1°C) gültig bis zur 1.Kommunikation | signedInt -300…800 | 210 |
| Für Heizen und Kühlen werden | list | getrennte Stellgrößen verwendet |
| Fan Coil-Steuerung verwenden | list | Nein |
| Ausgang wird gesteuert von Stellgröße | list | Heizen 1 |
| Ausgang wird gesteuert von Stellgröße | list | Kühlen 1 |
| Stufe 1 auch bei Stufe 2 und 3 einschalten | list | Nein |
| Stufe 2 auch bei Stufe 3 einschalten | list | Nein |
| Modus nach Reset | list | Automatik (wie Reglerstellgröße) |
| Manuell Stufe nach Reset | list | 0 |
| Funktion LEDs für Temperaturanzeige | list | An nach Tastendruck für einstellbare Zeit |
| Temperaturanzeige | list | zeigen Istwert und Sollwert/Basisverschiebung an |
| Komfort | list | Ja |
| Standby | list | Ja |
| Eco | list | Ja |
| Schutz | list | Nein |
| Regler Informationen spätestens nach | unsignedInt 5…60 | 10 |
| Sollwerte bei Bedienung der +/- Tasten ändern und senden | list | Nein |
| Schrittweite für Sollwertänderungen | unsignedInt 1…50 | 5 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| KNX eTR 102 FC 1.0 latest | $10BC | 3C88 | 2026-11-25 | 345 KB | Download |
About this file
This is the official ETS product database for the Elsner Elektronik GmbH KNX eTR 102 FC (7132X), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Elsner Elektronik GmbH
- Suntracer KNX 3090
- Suntracer KNX-GPS 3093
- Suntracer KNX basic 3095
- CO485 7011
- KNX L 70119
- KNX TH-AP 70120
- KNX T-AP 70121
- KNX W Wind Sensor 70122
- KNX R 70124
- KNX Rain/Wind Sensor 70126
- KNX LW 70128
- KNX FS6 70136