KNX Database
Eelectron HA08A01KNX HA08A01KNX Din Rail 8 Input / 8 Triac Output Module - A01

HA08A01KNX Din Rail 8 Input / 8 Triac Output Module - A01 HA08A01KNX

Eelectron · Order number HA08A01KNX · Room Temperature Controller › Heating Actuator

Download .knxprod HA08A01KNX I/O 8+8 Heating Actuator 1.0 · 630 KB

Product

ManufacturerEelectron
Product nameHA08A01KNX Din Rail 8 Input / 8 Triac Output Module - A01
Order numberHA08A01KNX
Product textDin Rail 8 Input / 8 Triac Output Module - A01
HardwareHA08A01KNX
MediumTwisted Pair
Bus current (mA)15
Rail mountedYes
Width (mm)72
RegistrationCertified · 2019-12-02
Languagesfr-FR, it-IT, en-US, de-DE, es-ES, ru-RU
Catalog entryM-006C_H-HA08A01KNX-0_HP-08D0-10-9F61_CI-HA08A01KNX-1
Fingerprint9F61
SHA-2567d14ee40b1ef4b36b68f4b3faf045f9b5987911feb5bb608a788703e5b5afde8
First seen2026-11-25
Markets59 markets

Application program: HA08A01KNX I/O 8+8 Heating Actuator 1.0

Application number$08D0
Version1.0
Mask versionMV-0021 (2.1)
KNX Data SecureNo
Minimum ETS version4.0
Parameters3285
Group objects1648
Group objects (1648)
NoNameFunctionSizeDPTFlags
0<Global All> All Valve ClosedAll Valve Closed1 Bit1.1 switchCRT
1<Global All> External Valve ClosedExternal Valve Closed1 Bit1.1 switchCW
1<Global All> External Valve ClosedExternal Valve Closed1 Bit1.1 switchCWTU
2<Global All> LockLock1 Bit1.1 switchCW
3<General 1-4> Overcurrent/OvervoltageNo alarm/Alarm1 Bit1.5 alarmCRT
4<General 1-4> No Line/Lack VoltageNo alarm/Alarm1 Bit1.5 alarmCRT
5<General 5-8> Overcurrent/OvervoltageNo alarm/Alarm1 Bit1.5 alarmCRT
6<General 5-8> No Line/Lack VoltageNo alarm/Alarm1 Bit1.5 alarmCRT
7<Temperature 1> AlarmNo alarm/Alarm1 Bit1.5 alarmCRT
8<Temperature 2> AlarmNo alarm/Alarm1 Bit1.5 alarmCRT
9<Temperature 3> AlarmNo alarm/Alarm1 Bit1.5 alarmCRT
10<Temperature 4> AlarmNo alarm/Alarm1 Bit1.5 alarmCRT
11<Input 1> RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
11<Temperature 1> Actual TemperatureValue °C2 Bytes9.1 temperature (°C)CRT
11<Input 1> Red0-2551 Byte5.10 counter pulses (0..255)CRT
11<Input 1> Press Action0-2551 Byte5.10 counter pulses (0..255)CRT
11<Input 1> Press Action0-100%1 Byte5.1 percentage (0..100%)CRT
11<Input 1> Press ActionHVAC Mode1 Byte20.102 HVAC modeCRT
11<Input 1> Press - Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
11<Input 1> Press - Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
11<Input 1> Press - Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
11<Input 1> Short - Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
11<Input 1> Short - Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
11<Input 1> Short - Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
11<Input 1> Recall/Learn SceneScene1 Byte18.1 scene controlCRT
11<Input 1> Sequence Command A 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
11<Input 1> Sequence Command A 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
11<Input 1> Sequence Command A HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
11<Input 1> Sequence Command A 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
11<Input 1> Sequence Command A 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
11<Input 1> Sequence Command A HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
11<Input 1> Press ActionOff/On1 Bit1.1 switchCRWT
11<Input 1> Press - Release ActionOff/On1 Bit1.1 switchCRWT
11<Input 1> Short - Long PressOff/On1 Bit1.1 switchCRWT
11<Input 1> Dimming On/OffOff/On1 Bit1.1 switchCRWT
11<Input 1> Object AOff/On1 Bit1.1 switchCRT
11<Input 1> Shutter - Up/DownUp/Down1 Bit1.8 up/downCRWT
11<Input 1> Sequence Command A Off/OnOff/On1 Bit1.1 switchCRT
11<Input 1> Sequence Command A Off/On-ToggleOff/On1 Bit1.1 switchCRT
11<Input 1> Make Up RoomOff/On1 Bit1.1 switchCRT
11<LED 1> CommandOff/On1 Bit1.1 switchCW
12<Temperature 1> KNX Probe TemperatureValue °C2 Bytes9.1 temperature (°C)CW
12<Input 1> Green0-2551 Byte5.10 counter pulses (0..255)CRT
12<Input 1> Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
12<Input 1> Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
12<Input 1> Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
12<Input 1> Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
12<Input 1> Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
12<Input 1> Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
12<Input 1> Sequence Command B 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
12<Input 1> Sequence Command B 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
12<Input 1> Sequence Command B HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
12<Input 1> Sequence Command B 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
12<Input 1> Sequence Command B 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
12<Input 1> Sequence Command B HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
12<Input 1> Loop Value OutputLoop Value Output1 Byte5.10 counter pulses (0..255)CRT
12<Input 1> Dimming ControlBrighter/Darker4 Bit3.7 dimming controlCRT
12<Input 1> Long PressOff/On1 Bit1.1 switchCRWT
12<Input 1> Release ActionOff/On1 Bit1.1 switchCRWT
12<Input 1> Object BOff/On1 Bit1.1 switchCRT
12<Input 1> Shutter - Step/StopStep/Stop1 Bit1.7 stepCRT
12<Input 1> Sequence Command B Off/OnOff/On1 Bit1.1 switchCRT
12<Input 1> Sequence Command B Off/On-ToggleOff/On1 Bit1.1 switchCRT
12<Input 1> Send Learn Scene TriggerDisable/Enable1 Bit1.3 enableCW
12<Input 1> Do Not DisturbOff/On1 Bit1.1 switchCRT
13<Input 1> Additional Object RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
13<Input 1> Blue0-2551 Byte5.10 counter pulses (0..255)CRT
13<Input 1> Sequence Command C 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
13<Input 1> Sequence Command C 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
13<Input 1> Sequence Command C HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
13<Input 1> Sequence Command C 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
13<Input 1> Sequence Command C 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
13<Input 1> Sequence Command C HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
13<Input 1> Loop Value FeedbackLoop Value Feedback1 Byte5.10 counter pulses (0..255)CW
13<Input 1> Sequence Command C Off/OnOff/On1 Bit1.1 switchCRT
13<Input 1> Sequence Command C Off/On-ToggleOff/On1 Bit1.1 switchCRT
13<Input 1> FeedbackOff/On1 Bit1.1 switchCW
13<Input 1> FeedbackUp/Down1 Bit1.8 up/downCW
13<Input 1> Object COff/On1 Bit1.1 switchCRT
13<T.Sensor 1> Enable InputDisable/Enable1 Bit1.3 enableCW
13<Thermostat 1> Heat/Cool ModeHeat/Cool1 Bit1.100 heating/coolingCW
13<Thermostat 1> Heat/Cool ModeHeat/Cool1 Bit1.100 heating/coolingCRT
14<T.Sensor 1> Setpoint UpperValue °C2 Bytes9.1 temperature (°C)CW
14<Input 1> Enable InputDisable/Enable1 Bit1.3 enableCW
14<Thermostat 1> Window ContactClose/Open1 Bit1.19 window/doorCW
15<T.Sensor 1> Telegram UpperOff/On1 Bit1.1 switchCRT
15<Thermostat 1> Comfort ModeOff/On1 Bit1.1 switchCW
15<Thermostat 1> Enable CoolingOff/On1 Bit1.1 switchCW
15<Thermostat 1> Enable HeatingOff/On1 Bit1.1 switchCW
15<Thermostat 1> Lock Heat/CoolLock1 Bit1.1 switchCW
16<T.Sensor 1> Setpoint LowerValue °C2 Bytes9.1 temperature (°C)CW
16<Thermostat 1> HVAC ModeComf/Standby/Eco/B.protection1 Byte20.102 HVAC modeCRW
17<Thermostat 1> Actual SetpointValue °C2 Bytes9.1 temperature (°C)CRT
17<T.Sensor 1> Telegram LowerOff/On1 Bit1.1 switchCRT
18<Thermostat 1> Setpoint AdjustmentValue °C2 Bytes9.1 temperature (°C)CW
18<Thermostat 1> Setpoint AdjustmentValue °C1 Bit1.7 stepCW
19<Thermostat 1> Base SetpointValue °C2 Bytes9.1 temperature (°C)CW
19<Thermostat 1> SP Economy HeatingValue °C2 Bytes9.1 temperature (°C)CW
19<Thermostat 1> SP EconomyValue °C2 Bytes9.1 temperature (°C)CW
20<Thermostat 1> SP Standby HeatingValue °C2 Bytes9.1 temperature (°C)CW
20<Thermostat 1> SP StandbyValue °C2 Bytes9.1 temperature (°C)CW
21<Thermostat 1> SP Comfort HeatingValue °C2 Bytes9.1 temperature (°C)CW
21<Thermostat 1> SP ComfortValue °C2 Bytes9.1 temperature (°C)CW
22<Thermostat 1> SP Economy CoolingValue °C2 Bytes9.1 temperature (°C)CW
23<Thermostat 1> SP Standby CoolingValue °C2 Bytes9.1 temperature (°C)CW
24<Thermostat 1> SP Comfort CoolingValue °C2 Bytes9.1 temperature (°C)CW
25<Thermostat 1> Heating0-100%1 Byte5.1 percentage (0..100%)CRT
25<Thermostat 1> HeatingOff/On1 Bit1.1 switchCRT
26<Thermostat 1> Cooling0-100%1 Byte5.1 percentage (0..100%)CRT
26<Thermostat 1> CoolingOff/On1 Bit1.1 switchCRT
27<Thermostat 1> 0-100% 2nd Stage Heating0-100%1 Byte5.1 percentage (0..100%)CRT
27<Thermostat 1> Off/On 2nd Stage HeatingOff/On1 Bit1.1 switchCRT
28<Thermostat 1> 0-100% 2nd Stage Cooling0-100%1 Byte5.1 percentage (0..100%)CRT
28<Thermostat 1> Off/On 2nd Stage CoolingOff/On1 Bit1.1 switchCRT
29<Thermostat 1> OFF ThermostatOff/On1 Bit1.1 switchCRWT
30<Additional Valve 1> Percentage0-100%1 Byte5.1 percentage (0..100%)CRT
30<Additional Valve 1> Valve 6 Ways0-100%1 Byte5.1 percentage (0..100%)CRT
30<Additional Valve 1> PWMOff/On1 Bit1.1 switchCRT
31<Input 2> RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
31<Temperature 2> Actual TemperatureValue °C2 Bytes9.1 temperature (°C)CRT
31<Input 2> Red0-2551 Byte5.10 counter pulses (0..255)CRT
31<Input 2> Press Action0-2551 Byte5.10 counter pulses (0..255)CRT
31<Input 2> Press Action0-100%1 Byte5.1 percentage (0..100%)CRT
31<Input 2> Press ActionHVAC Mode1 Byte20.102 HVAC modeCRT
31<Input 2> Press - Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
31<Input 2> Press - Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
31<Input 2> Press - Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
31<Input 2> Short - Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
31<Input 2> Short - Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
31<Input 2> Short - Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
31<Input 2> Recall/Learn SceneScene1 Byte18.1 scene controlCRT
31<Input 2> Sequence Command A 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
31<Input 2> Sequence Command A 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
31<Input 2> Sequence Command A HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
31<Input 2> Sequence Command A 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
31<Input 2> Sequence Command A 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
31<Input 2> Sequence Command A HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
31<Input 2> Press ActionOff/On1 Bit1.1 switchCRWT
31<Input 2> Press - Release ActionOff/On1 Bit1.1 switchCRWT
31<Input 2> Short - Long PressOff/On1 Bit1.1 switchCRWT
31<Input 2> Dimming On/OffOff/On1 Bit1.1 switchCRWT
31<Input 2> Object AOff/On1 Bit1.1 switchCRT
31<Input 2> Shutter - Up/DownUp/Down1 Bit1.8 up/downCRWT
31<Input 2> Sequence Command A Off/OnOff/On1 Bit1.1 switchCRT
31<Input 2> Sequence Command A Off/On-ToggleOff/On1 Bit1.1 switchCRT
31<Input 2> Make Up RoomOff/On1 Bit1.1 switchCRT
31<LED 2> CommandOff/On1 Bit1.1 switchCW
32<Temperature 2> KNX Probe TemperatureValue °C2 Bytes9.1 temperature (°C)CW
32<Input 2> Green0-2551 Byte5.10 counter pulses (0..255)CRT
32<Input 2> Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
32<Input 2> Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
32<Input 2> Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
32<Input 2> Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
32<Input 2> Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
32<Input 2> Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
32<Input 2> Sequence Command B 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
32<Input 2> Sequence Command B 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
32<Input 2> Sequence Command B HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
32<Input 2> Sequence Command B 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
32<Input 2> Sequence Command B 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
32<Input 2> Sequence Command B HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
32<Input 2> Loop Value OutputLoop Value Output1 Byte5.10 counter pulses (0..255)CRT
32<Input 2> Dimming ControlBrighter/Darker4 Bit3.7 dimming controlCRT
32<Input 2> Long PressOff/On1 Bit1.1 switchCRWT
32<Input 2> Release ActionOff/On1 Bit1.1 switchCRWT
32<Input 2> Object BOff/On1 Bit1.1 switchCRT
32<Input 2> Shutter - Step/StopStep/Stop1 Bit1.7 stepCRT
32<Input 2> Sequence Command B Off/OnOff/On1 Bit1.1 switchCRT
32<Input 2> Sequence Command B Off/On-ToggleOff/On1 Bit1.1 switchCRT
32<Input 2> Send Learn Scene TriggerDisable/Enable1 Bit1.3 enableCW
32<Input 2> Do Not DisturbOff/On1 Bit1.1 switchCRT
33<Input 2> Additional Object RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
33<Input 2> Blue0-2551 Byte5.10 counter pulses (0..255)CRT
33<Input 2> Sequence Command C 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
33<Input 2> Sequence Command C 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
33<Input 2> Sequence Command C HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
33<Input 2> Sequence Command C 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
33<Input 2> Sequence Command C 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
33<Input 2> Sequence Command C HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
33<Input 2> Loop Value FeedbackLoop Value Feedback1 Byte5.10 counter pulses (0..255)CW
33<Input 2> Sequence Command C Off/OnOff/On1 Bit1.1 switchCRT
33<Input 2> Sequence Command C Off/On-ToggleOff/On1 Bit1.1 switchCRT
33<Input 2> FeedbackOff/On1 Bit1.1 switchCW
33<Input 2> FeedbackUp/Down1 Bit1.8 up/downCW
33<Input 2> Object COff/On1 Bit1.1 switchCRT
33<T.Sensor 2> Enable InputDisable/Enable1 Bit1.3 enableCW
33<Thermostat 2> Heat/Cool ModeHeat/Cool1 Bit1.100 heating/coolingCW
33<Thermostat 2> Heat/Cool ModeHeat/Cool1 Bit1.100 heating/coolingCRT
34<T.Sensor 2> Setpoint UpperValue °C2 Bytes9.1 temperature (°C)CW
34<Input 2> Enable InputDisable/Enable1 Bit1.3 enableCW
34<Thermostat 2> Window ContactClose/Open1 Bit1.19 window/doorCW
35<T.Sensor 2> Telegram UpperOff/On1 Bit1.1 switchCRT
35<Thermostat 2> Comfort ModeOff/On1 Bit1.1 switchCW
35<Thermostat 2> Enable CoolingOff/On1 Bit1.1 switchCW
35<Thermostat 2> Enable HeatingOff/On1 Bit1.1 switchCW
35<Thermostat 2> Lock Heat/CoolLock1 Bit1.1 switchCW
36<T.Sensor 2> Setpoint LowerValue °C2 Bytes9.1 temperature (°C)CW
36<Thermostat 2> HVAC ModeComf/Standby/Eco/B.protection1 Byte20.102 HVAC modeCRW
37<Thermostat 2> Actual SetpointValue °C2 Bytes9.1 temperature (°C)CRT
37<T.Sensor 2> Telegram LowerOff/On1 Bit1.1 switchCRT
38<Thermostat 2> Setpoint AdjustmentValue °C2 Bytes9.1 temperature (°C)CW
38<Thermostat 2> Setpoint AdjustmentValue °C1 Bit1.7 stepCW
39<Thermostat 2> Base SetpointValue °C2 Bytes9.1 temperature (°C)CW
39<Thermostat 2> SP Economy HeatingValue °C2 Bytes9.1 temperature (°C)CW
39<Thermostat 2> SP EconomyValue °C2 Bytes9.1 temperature (°C)CW
40<Thermostat 2> SP Standby HeatingValue °C2 Bytes9.1 temperature (°C)CW
40<Thermostat 2> SP StandbyValue °C2 Bytes9.1 temperature (°C)CW
41<Thermostat 2> SP Comfort HeatingValue °C2 Bytes9.1 temperature (°C)CW
41<Thermostat 2> SP ComfortValue °C2 Bytes9.1 temperature (°C)CW
42<Thermostat 2> SP Economy CoolingValue °C2 Bytes9.1 temperature (°C)CW
43<Thermostat 2> SP Standby CoolingValue °C2 Bytes9.1 temperature (°C)CW
44<Thermostat 2> SP Comfort CoolingValue °C2 Bytes9.1 temperature (°C)CW
45<Thermostat 2> Heating0-100%1 Byte5.1 percentage (0..100%)CRT
45<Thermostat 2> HeatingOff/On1 Bit1.1 switchCRT
46<Thermostat 2> Cooling0-100%1 Byte5.1 percentage (0..100%)CRT
46<Thermostat 2> CoolingOff/On1 Bit1.1 switchCRT
47<Thermostat 2> 0-100% 2nd Stage Heating0-100%1 Byte5.1 percentage (0..100%)CRT
47<Thermostat 2> Off/On 2nd Stage HeatingOff/On1 Bit1.1 switchCRT
48<Thermostat 2> 0-100% 2nd Stage Cooling0-100%1 Byte5.1 percentage (0..100%)CRT
48<Thermostat 2> Off/On 2nd Stage CoolingOff/On1 Bit1.1 switchCRT
49<Thermostat 2> OFF ThermostatOff/On1 Bit1.1 switchCRWT
50<Additional Valve 2> Percentage0-100%1 Byte5.1 percentage (0..100%)CRT
50<Additional Valve 2> Valve 6 Ways0-100%1 Byte5.1 percentage (0..100%)CRT
50<Additional Valve 2> PWMOff/On1 Bit1.1 switchCRT
51<Input 3> RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
51<Temperature 3> Actual TemperatureValue °C2 Bytes9.1 temperature (°C)CRT
51<Input 3> Red0-2551 Byte5.10 counter pulses (0..255)CRT
51<Input 3> Press Action0-2551 Byte5.10 counter pulses (0..255)CRT
51<Input 3> Press Action0-100%1 Byte5.1 percentage (0..100%)CRT
51<Input 3> Press ActionHVAC Mode1 Byte20.102 HVAC modeCRT
51<Input 3> Press - Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
51<Input 3> Press - Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
51<Input 3> Press - Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
51<Input 3> Short - Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
51<Input 3> Short - Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
51<Input 3> Short - Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
51<Input 3> Recall/Learn SceneScene1 Byte18.1 scene controlCRT
51<Input 3> Sequence Command A 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
51<Input 3> Sequence Command A 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
51<Input 3> Sequence Command A HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
51<Input 3> Sequence Command A 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
51<Input 3> Sequence Command A 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
51<Input 3> Sequence Command A HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
51<Input 3> Press ActionOff/On1 Bit1.1 switchCRWT
51<Input 3> Press - Release ActionOff/On1 Bit1.1 switchCRWT
51<Input 3> Short - Long PressOff/On1 Bit1.1 switchCRWT
51<Input 3> Dimming On/OffOff/On1 Bit1.1 switchCRWT
51<Input 3> Object AOff/On1 Bit1.1 switchCRT
51<Input 3> Shutter - Up/DownUp/Down1 Bit1.8 up/downCRWT
51<Input 3> Sequence Command A Off/OnOff/On1 Bit1.1 switchCRT
51<Input 3> Sequence Command A Off/On-ToggleOff/On1 Bit1.1 switchCRT
51<Input 3> Make Up RoomOff/On1 Bit1.1 switchCRT
51<LED 3> CommandOff/On1 Bit1.1 switchCW
52<Temperature 3> KNX Probe TemperatureValue °C2 Bytes9.1 temperature (°C)CW
52<Input 3> Green0-2551 Byte5.10 counter pulses (0..255)CRT
52<Input 3> Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
52<Input 3> Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
52<Input 3> Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
52<Input 3> Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
52<Input 3> Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
52<Input 3> Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
52<Input 3> Sequence Command B 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
52<Input 3> Sequence Command B 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
52<Input 3> Sequence Command B HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
52<Input 3> Sequence Command B 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
52<Input 3> Sequence Command B 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
52<Input 3> Sequence Command B HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
52<Input 3> Loop Value OutputLoop Value Output1 Byte5.10 counter pulses (0..255)CRT
52<Input 3> Dimming ControlBrighter/Darker4 Bit3.7 dimming controlCRT
52<Input 3> Long PressOff/On1 Bit1.1 switchCRWT
52<Input 3> Release ActionOff/On1 Bit1.1 switchCRWT
52<Input 3> Object BOff/On1 Bit1.1 switchCRT
52<Input 3> Shutter - Step/StopStep/Stop1 Bit1.7 stepCRT
52<Input 3> Sequence Command B Off/OnOff/On1 Bit1.1 switchCRT
52<Input 3> Sequence Command B Off/On-ToggleOff/On1 Bit1.1 switchCRT
52<Input 3> Send Learn Scene TriggerDisable/Enable1 Bit1.3 enableCW
52<Input 3> Do Not DisturbOff/On1 Bit1.1 switchCRT
53<Input 3> Additional Object RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
53<Input 3> Blue0-2551 Byte5.10 counter pulses (0..255)CRT
53<Input 3> Sequence Command C 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
53<Input 3> Sequence Command C 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
53<Input 3> Sequence Command C HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
53<Input 3> Sequence Command C 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
53<Input 3> Sequence Command C 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
53<Input 3> Sequence Command C HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
53<Input 3> Loop Value FeedbackLoop Value Feedback1 Byte5.10 counter pulses (0..255)CW
53<Input 3> Sequence Command C Off/OnOff/On1 Bit1.1 switchCRT
53<Input 3> Sequence Command C Off/On-ToggleOff/On1 Bit1.1 switchCRT
53<Input 3> FeedbackOff/On1 Bit1.1 switchCW
53<Input 3> FeedbackUp/Down1 Bit1.8 up/downCW
53<Input 3> Object COff/On1 Bit1.1 switchCRT
53<T.Sensor 3> Enable InputDisable/Enable1 Bit1.3 enableCW
53<Thermostat 3> Heat/Cool ModeHeat/Cool1 Bit1.100 heating/coolingCW
53<Thermostat 3> Heat/Cool ModeHeat/Cool1 Bit1.100 heating/coolingCRT
54<T.Sensor 3> Setpoint UpperValue °C2 Bytes9.1 temperature (°C)CW
54<Input 3> Enable InputDisable/Enable1 Bit1.3 enableCW
54<Thermostat 3> Window ContactClose/Open1 Bit1.19 window/doorCW
55<T.Sensor 3> Telegram UpperOff/On1 Bit1.1 switchCRT
55<Thermostat 3> Comfort ModeOff/On1 Bit1.1 switchCW
55<Thermostat 3> Enable CoolingOff/On1 Bit1.1 switchCW
55<Thermostat 3> Enable HeatingOff/On1 Bit1.1 switchCW
55<Thermostat 3> Lock Heat/CoolLock1 Bit1.1 switchCW
56<T.Sensor 3> Setpoint LowerValue °C2 Bytes9.1 temperature (°C)CW
56<Thermostat 3> HVAC ModeComf/Standby/Eco/B.protection1 Byte20.102 HVAC modeCRW
57<Thermostat 3> Actual SetpointValue °C2 Bytes9.1 temperature (°C)CRT
57<T.Sensor 3> Telegram LowerOff/On1 Bit1.1 switchCRT
58<Thermostat 3> Setpoint AdjustmentValue °C2 Bytes9.1 temperature (°C)CW
58<Thermostat 3> Setpoint AdjustmentValue °C1 Bit1.7 stepCW
59<Thermostat 3> Base SetpointValue °C2 Bytes9.1 temperature (°C)CW
59<Thermostat 3> SP Economy HeatingValue °C2 Bytes9.1 temperature (°C)CW
59<Thermostat 3> SP EconomyValue °C2 Bytes9.1 temperature (°C)CW
60<Thermostat 3> SP Standby HeatingValue °C2 Bytes9.1 temperature (°C)CW
60<Thermostat 3> SP StandbyValue °C2 Bytes9.1 temperature (°C)CW
61<Thermostat 3> SP Comfort HeatingValue °C2 Bytes9.1 temperature (°C)CW
61<Thermostat 3> SP ComfortValue °C2 Bytes9.1 temperature (°C)CW
62<Thermostat 3> SP Economy CoolingValue °C2 Bytes9.1 temperature (°C)CW
63<Thermostat 3> SP Standby CoolingValue °C2 Bytes9.1 temperature (°C)CW
64<Thermostat 3> SP Comfort CoolingValue °C2 Bytes9.1 temperature (°C)CW
65<Thermostat 3> Heating0-100%1 Byte5.1 percentage (0..100%)CRT
65<Thermostat 3> HeatingOff/On1 Bit1.1 switchCRT
66<Thermostat 3> Cooling0-100%1 Byte5.1 percentage (0..100%)CRT
66<Thermostat 3> CoolingOff/On1 Bit1.1 switchCRT
67<Thermostat 3> 0-100% 2nd Stage Heating0-100%1 Byte5.1 percentage (0..100%)CRT
67<Thermostat 3> Off/On 2nd Stage HeatingOff/On1 Bit1.1 switchCRT
68<Thermostat 3> 0-100% 2nd Stage Cooling0-100%1 Byte5.1 percentage (0..100%)CRT
68<Thermostat 3> Off/On 2nd Stage CoolingOff/On1 Bit1.1 switchCRT
69<Thermostat 3> OFF ThermostatOff/On1 Bit1.1 switchCRWT
70<Additional Valve 3> Percentage0-100%1 Byte5.1 percentage (0..100%)CRT
70<Additional Valve 3> Valve 6 Ways0-100%1 Byte5.1 percentage (0..100%)CRT
70<Additional Valve 3> PWMOff/On1 Bit1.1 switchCRT
71<Input 4> RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
71<Temperature 4> Actual TemperatureValue °C2 Bytes9.1 temperature (°C)CRT
71<Input 4> Red0-2551 Byte5.10 counter pulses (0..255)CRT
71<Input 4> Press Action0-2551 Byte5.10 counter pulses (0..255)CRT
71<Input 4> Press Action0-100%1 Byte5.1 percentage (0..100%)CRT
71<Input 4> Press ActionHVAC Mode1 Byte20.102 HVAC modeCRT
71<Input 4> Press - Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
71<Input 4> Press - Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
71<Input 4> Press - Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
71<Input 4> Short - Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
71<Input 4> Short - Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
71<Input 4> Short - Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
71<Input 4> Recall/Learn SceneScene1 Byte18.1 scene controlCRT
71<Input 4> Sequence Command A 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
71<Input 4> Sequence Command A 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
71<Input 4> Sequence Command A HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
71<Input 4> Sequence Command A 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
71<Input 4> Sequence Command A 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
71<Input 4> Sequence Command A HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
71<Input 4> Press ActionOff/On1 Bit1.1 switchCRWT
71<Input 4> Press - Release ActionOff/On1 Bit1.1 switchCRWT
71<Input 4> Short - Long PressOff/On1 Bit1.1 switchCRWT
71<Input 4> Dimming On/OffOff/On1 Bit1.1 switchCRWT
71<Input 4> Object AOff/On1 Bit1.1 switchCRT
71<Input 4> Shutter - Up/DownUp/Down1 Bit1.8 up/downCRWT
71<Input 4> Sequence Command A Off/OnOff/On1 Bit1.1 switchCRT
71<Input 4> Sequence Command A Off/On-ToggleOff/On1 Bit1.1 switchCRT
71<Input 4> Make Up RoomOff/On1 Bit1.1 switchCRT
71<LED 4> CommandOff/On1 Bit1.1 switchCW
72<Temperature 4> KNX Probe TemperatureValue °C2 Bytes9.1 temperature (°C)CW
72<Input 4> Green0-2551 Byte5.10 counter pulses (0..255)CRT
72<Input 4> Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
72<Input 4> Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
72<Input 4> Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
72<Input 4> Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
72<Input 4> Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
72<Input 4> Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
72<Input 4> Sequence Command B 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
72<Input 4> Sequence Command B 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
72<Input 4> Sequence Command B HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
72<Input 4> Sequence Command B 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
72<Input 4> Sequence Command B 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
72<Input 4> Sequence Command B HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
72<Input 4> Loop Value OutputLoop Value Output1 Byte5.10 counter pulses (0..255)CRT
72<Input 4> Dimming ControlBrighter/Darker4 Bit3.7 dimming controlCRT
72<Input 4> Long PressOff/On1 Bit1.1 switchCRWT
72<Input 4> Release ActionOff/On1 Bit1.1 switchCRWT
72<Input 4> Object BOff/On1 Bit1.1 switchCRT
72<Input 4> Shutter - Step/StopStep/Stop1 Bit1.7 stepCRT
72<Input 4> Sequence Command B Off/OnOff/On1 Bit1.1 switchCRT
72<Input 4> Sequence Command B Off/On-ToggleOff/On1 Bit1.1 switchCRT
72<Input 4> Send Learn Scene TriggerDisable/Enable1 Bit1.3 enableCW
72<Input 4> Do Not DisturbOff/On1 Bit1.1 switchCRT
73<Input 4> Additional Object RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
73<Input 4> Blue0-2551 Byte5.10 counter pulses (0..255)CRT
73<Input 4> Sequence Command C 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
73<Input 4> Sequence Command C 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
73<Input 4> Sequence Command C HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
73<Input 4> Sequence Command C 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
73<Input 4> Sequence Command C 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
73<Input 4> Sequence Command C HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
73<Input 4> Loop Value FeedbackLoop Value Feedback1 Byte5.10 counter pulses (0..255)CW
73<Input 4> Sequence Command C Off/OnOff/On1 Bit1.1 switchCRT
73<Input 4> Sequence Command C Off/On-ToggleOff/On1 Bit1.1 switchCRT
73<Input 4> FeedbackOff/On1 Bit1.1 switchCW
73<Input 4> FeedbackUp/Down1 Bit1.8 up/downCW
73<Input 4> Object COff/On1 Bit1.1 switchCRT
73<T.Sensor 4> Enable InputDisable/Enable1 Bit1.3 enableCW
73<Thermostat 4> Heat/Cool ModeHeat/Cool1 Bit1.100 heating/coolingCW
73<Thermostat 4> Heat/Cool ModeHeat/Cool1 Bit1.100 heating/coolingCRT
74<T.Sensor 4> Setpoint UpperValue °C2 Bytes9.1 temperature (°C)CW
74<Input 4> Enable InputDisable/Enable1 Bit1.3 enableCW
74<Thermostat 4> Window ContactClose/Open1 Bit1.19 window/doorCW
75<T.Sensor 4> Telegram UpperOff/On1 Bit1.1 switchCRT
75<Thermostat 4> Comfort ModeOff/On1 Bit1.1 switchCW
75<Thermostat 4> Enable CoolingOff/On1 Bit1.1 switchCW
75<Thermostat 4> Enable HeatingOff/On1 Bit1.1 switchCW
75<Thermostat 4> Lock Heat/CoolLock1 Bit1.1 switchCW
76<T.Sensor 4> Setpoint LowerValue °C2 Bytes9.1 temperature (°C)CW
76<Thermostat 4> HVAC ModeComf/Standby/Eco/B.protection1 Byte20.102 HVAC modeCRW
77<Thermostat 4> Actual SetpointValue °C2 Bytes9.1 temperature (°C)CRT
77<T.Sensor 4> Telegram LowerOff/On1 Bit1.1 switchCRT
78<Thermostat 4> Setpoint AdjustmentValue °C2 Bytes9.1 temperature (°C)CW
78<Thermostat 4> Setpoint AdjustmentValue °C1 Bit1.7 stepCW
79<Thermostat 4> Base SetpointValue °C2 Bytes9.1 temperature (°C)CW
79<Thermostat 4> SP Economy HeatingValue °C2 Bytes9.1 temperature (°C)CW
79<Thermostat 4> SP EconomyValue °C2 Bytes9.1 temperature (°C)CW
80<Thermostat 4> SP Standby HeatingValue °C2 Bytes9.1 temperature (°C)CW
80<Thermostat 4> SP StandbyValue °C2 Bytes9.1 temperature (°C)CW
81<Thermostat 4> SP Comfort HeatingValue °C2 Bytes9.1 temperature (°C)CW
81<Thermostat 4> SP ComfortValue °C2 Bytes9.1 temperature (°C)CW
82<Thermostat 4> SP Economy CoolingValue °C2 Bytes9.1 temperature (°C)CW
83<Thermostat 4> SP Standby CoolingValue °C2 Bytes9.1 temperature (°C)CW
84<Thermostat 4> SP Comfort CoolingValue °C2 Bytes9.1 temperature (°C)CW
85<Thermostat 4> Heating0-100%1 Byte5.1 percentage (0..100%)CRT
85<Thermostat 4> HeatingOff/On1 Bit1.1 switchCRT
86<Thermostat 4> Cooling0-100%1 Byte5.1 percentage (0..100%)CRT
86<Thermostat 4> CoolingOff/On1 Bit1.1 switchCRT
87<Thermostat 4> 0-100% 2nd Stage Heating0-100%1 Byte5.1 percentage (0..100%)CRT
87<Thermostat 4> Off/On 2nd Stage HeatingOff/On1 Bit1.1 switchCRT
88<Thermostat 4> 0-100% 2nd Stage Cooling0-100%1 Byte5.1 percentage (0..100%)CRT
88<Thermostat 4> Off/On 2nd Stage CoolingOff/On1 Bit1.1 switchCRT
89<Thermostat 4> OFF ThermostatOff/On1 Bit1.1 switchCRWT
90<Additional Valve 4> Percentage0-100%1 Byte5.1 percentage (0..100%)CRT
90<Additional Valve 4> Valve 6 Ways0-100%1 Byte5.1 percentage (0..100%)CRT
90<Additional Valve 4> PWMOff/On1 Bit1.1 switchCRT
91<Output A1 | 01> Open/CloseOpen/Close1 Bit1.1 switchCW
91<Output B1 | 01-02> Open/CloseOpen/Close1 Bit1.1 switchCW
92<Output A1 | 01> PWM %PWM %1 Byte5.1 percentage (0..100%)CW
92<Output B1 | 01-02> Position %Position %1 Byte5.1 percentage (0..100%)CW
93<Output A1 | 01> LockLock1 Bit1.1 switchCW
93<Output B1 | 01-02> Position 1Off/On1 Bit1.1 switchCW
94<Output A1 | 01> StatusOpen/Close1 Bit1.1 switchCRT
94<Output B1 | 01-02> Position 2Off/On1 Bit1.1 switchCW
95<Output A1 | 01> PWM Status %PWM %1 Byte5.1 percentage (0..100%)CRT
95<Output B1 | 01-02> Position 3Off/On1 Bit1.1 switchCW
96<Output A1 | 01> Valve StatusOpen/Close1 Bit1.9 open/closeCW
96<Output B1 | 01-02> LockLock1 Bit1.1 switchCW
97<Output A1 | 01> Valve AlarmAlarm1 Bit1.5 alarmCRT
97<Output B1 | 01-02> StatusOpen/Close1 Bit1.1 switchCRT
98<Output B1 | 01-02> Position Status %Position %1 Byte5.1 percentage (0..100%)CRT
98<Output A2 | 02> Open/CloseOpen/Close1 Bit1.1 switchCW
99<Output A2 | 02> PWM %PWM %1 Byte5.1 percentage (0..100%)CW
99<Output B1 | 01-02> Opening StatusOff/On1 Bit1.1 switchCRT
100<Output A2 | 02> LockLock1 Bit1.1 switchCW
100<Output B1 | 01-02> Closing StatusOff/On1 Bit1.1 switchCRT
101<Output A2 | 02> StatusOpen/Close1 Bit1.1 switchCRT
102<Output A2 | 02> PWM Status %PWM %1 Byte5.1 percentage (0..100%)CRT
103<Output A2 | 02> Valve StatusOpen/Close1 Bit1.9 open/closeCW
104<Output A2 | 02> Valve AlarmAlarm1 Bit1.5 alarmCRT
105<Output A3 | 03> Open/CloseOpen/Close1 Bit1.1 switchCW
105<Output B2 | 03-04> Open/CloseOpen/Close1 Bit1.1 switchCW
106<Output A3 | 03> PWM %PWM %1 Byte5.1 percentage (0..100%)CW
106<Output B2 | 03-04> Position %Position %1 Byte5.1 percentage (0..100%)CW
107<Output A3 | 03> LockLock1 Bit1.1 switchCW
107<Output B2 | 03-04> Position 1Off/On1 Bit1.1 switchCW
108<Output A3 | 03> StatusOpen/Close1 Bit1.1 switchCRT
108<Output B2 | 03-04> Position 2Off/On1 Bit1.1 switchCW
109<Output A3 | 03> PWM Status %PWM %1 Byte5.1 percentage (0..100%)CRT
109<Output B2 | 03-04> Position 3Off/On1 Bit1.1 switchCW
110<Output A3 | 03> Valve StatusOpen/Close1 Bit1.9 open/closeCW
110<Output B2 | 03-04> LockLock1 Bit1.1 switchCW
111<Output A3 | 03> Valve AlarmAlarm1 Bit1.5 alarmCRT
111<Output B2 | 03-04> StatusOpen/Close1 Bit1.1 switchCRT
112<Output B2 | 03-04> Position Status %Position %1 Byte5.1 percentage (0..100%)CRT
112<Output A4 | 04> Open/CloseOpen/Close1 Bit1.1 switchCW
113<Output A4 | 04> PWM %PWM %1 Byte5.1 percentage (0..100%)CW
113<Output B2 | 03-04> Opening StatusOff/On1 Bit1.1 switchCRT
114<Output A4 | 04> LockLock1 Bit1.1 switchCW
114<Output B2 | 03-04> Closing StatusOff/On1 Bit1.1 switchCRT
115<Output A4 | 04> StatusOpen/Close1 Bit1.1 switchCRT
116<Output A4 | 04> PWM Status %PWM %1 Byte5.1 percentage (0..100%)CRT
117<Output A4 | 04> Valve StatusOpen/Close1 Bit1.9 open/closeCW
118<Output A4 | 04> Valve AlarmAlarm1 Bit1.5 alarmCRT
119<Output A5 | 05> Open/CloseOpen/Close1 Bit1.1 switchCW
119<Output B3 | 05-06> Open/CloseOpen/Close1 Bit1.1 switchCW
120<Output A5 | 05> PWM %PWM %1 Byte5.1 percentage (0..100%)CW
120<Output B3 | 05-06> Position %Position %1 Byte5.1 percentage (0..100%)CW
121<Output A5 | 05> LockLock1 Bit1.1 switchCW
121<Output B3 | 05-06> Position 1Off/On1 Bit1.1 switchCW
122<Output A5 | 05> StatusOpen/Close1 Bit1.1 switchCRT
122<Output B3 | 05-06> Position 2Off/On1 Bit1.1 switchCW
123<Output A5 | 05> PWM Status %PWM %1 Byte5.1 percentage (0..100%)CRT
123<Output B3 | 05-06> Position 3Off/On1 Bit1.1 switchCW
124<Output A5 | 05> Valve StatusOpen/Close1 Bit1.9 open/closeCW
124<Output B3 | 05-06> LockLock1 Bit1.1 switchCW
125<Output A5 | 05> Valve AlarmAlarm1 Bit1.5 alarmCRT
125<Output B3 | 05-06> StatusOpen/Close1 Bit1.1 switchCRT
126<Output B3 | 05-06> Position Status %Position %1 Byte5.1 percentage (0..100%)CRT
126<Output A6 | 06> Open/CloseOpen/Close1 Bit1.1 switchCW
127<Output A6 | 06> PWM %PWM %1 Byte5.1 percentage (0..100%)CW
127<Output B3 | 05-06> Opening StatusOff/On1 Bit1.1 switchCRT
128<Output A6 | 06> LockLock1 Bit1.1 switchCW
128<Output B3 | 05-06> Closing StatusOff/On1 Bit1.1 switchCRT
129<Output A6 | 06> StatusOpen/Close1 Bit1.1 switchCRT
130<Output A6 | 06> PWM Status %PWM %1 Byte5.1 percentage (0..100%)CRT
131<Output A6 | 06> Valve StatusOpen/Close1 Bit1.9 open/closeCW
132<Output A6 | 06> Valve AlarmAlarm1 Bit1.5 alarmCRT
133<Output A7 | 07> Open/CloseOpen/Close1 Bit1.1 switchCW
133<Output B4 | 07-08> Open/CloseOpen/Close1 Bit1.1 switchCW
134<Output A7 | 07> PWM %PWM %1 Byte5.1 percentage (0..100%)CW
134<Output B4 | 07-08> Position %Position %1 Byte5.1 percentage (0..100%)CW
135<Output A7 | 07> LockLock1 Bit1.1 switchCW
135<Output B4 | 07-08> Position 1Off/On1 Bit1.1 switchCW
136<Output A7 | 07> StatusOpen/Close1 Bit1.1 switchCRT
136<Output B4 | 07-08> Position 2Off/On1 Bit1.1 switchCW
137<Output A7 | 07> PWM Status %PWM %1 Byte5.1 percentage (0..100%)CRT
137<Output B4 | 07-08> Position 3Off/On1 Bit1.1 switchCW
138<Output A7 | 07> Valve StatusOpen/Close1 Bit1.9 open/closeCW
138<Output B4 | 07-08> LockLock1 Bit1.1 switchCW
139<Output A7 | 07> Valve AlarmAlarm1 Bit1.5 alarmCRT
139<Output B4 | 07-08> StatusOpen/Close1 Bit1.1 switchCRT
140<Output B4 | 07-08> Position Status %Position %1 Byte5.1 percentage (0..100%)CRT
140<Output A8 | 08> Open/CloseOpen/Close1 Bit1.1 switchCW
141<Output A8 | 08> PWM %PWM %1 Byte5.1 percentage (0..100%)CW
141<Output B4 | 07-08> Opening StatusOff/On1 Bit1.1 switchCRT
142<Output A8 | 08> LockLock1 Bit1.1 switchCW
142<Output B4 | 07-08> Closing StatusOff/On1 Bit1.1 switchCRT
143<Output A8 | 08> StatusOpen/Close1 Bit1.1 switchCRT
144<Output A8 | 08> PWM Status %PWM %1 Byte5.1 percentage (0..100%)CRT
145<Output A8 | 08> Valve StatusOpen/Close1 Bit1.9 open/closeCW
146<Output A8 | 08> Valve AlarmAlarm1 Bit1.5 alarmCRT
147<Input 5> RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
147<Input 5> Red0-2551 Byte5.10 counter pulses (0..255)CRT
147<Input 5> Press Action0-2551 Byte5.10 counter pulses (0..255)CRT
147<Input 5> Press Action0-100%1 Byte5.1 percentage (0..100%)CRT
147<Input 5> Press ActionHVAC Mode1 Byte20.102 HVAC modeCRT
147<Input 5> Press - Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
147<Input 5> Press - Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
147<Input 5> Press - Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
147<Input 5> Short - Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
147<Input 5> Short - Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
147<Input 5> Short - Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
147<Input 5> Recall/Learn SceneScene1 Byte18.1 scene controlCRT
147<Input 5> Sequence Command A 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
147<Input 5> Sequence Command A 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
147<Input 5> Sequence Command A HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
147<Input 5> Sequence Command A 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
147<Input 5> Sequence Command A 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
147<Input 5> Sequence Command A HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
147<Input 5> Press ActionOff/On1 Bit1.1 switchCRWT
147<Input 5> Press - Release ActionOff/On1 Bit1.1 switchCRWT
147<Input 5> Short - Long PressOff/On1 Bit1.1 switchCRWT
147<Input 5> Dimming On/OffOff/On1 Bit1.1 switchCRWT
147<Input 5> Object AOff/On1 Bit1.1 switchCRT
147<Input 5> Shutter - Up/DownUp/Down1 Bit1.8 up/downCRWT
147<Input 5> Sequence Command A Off/OnOff/On1 Bit1.1 switchCRT
147<Input 5> Sequence Command A Off/On-ToggleOff/On1 Bit1.1 switchCRT
147<Input 5> Make Up RoomOff/On1 Bit1.1 switchCRT
148<Input 5> Green0-2551 Byte5.10 counter pulses (0..255)CRT
148<Input 5> Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
148<Input 5> Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
148<Input 5> Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
148<Input 5> Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
148<Input 5> Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
148<Input 5> Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
148<Input 5> Sequence Command B 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
148<Input 5> Sequence Command B 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
148<Input 5> Sequence Command B HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
148<Input 5> Sequence Command B 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
148<Input 5> Sequence Command B 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
148<Input 5> Sequence Command B HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
148<Input 5> Loop Value OutputLoop Value Output1 Byte5.10 counter pulses (0..255)CRT
148<Input 5> Dimming ControlBrighter/Darker4 Bit3.7 dimming controlCRT
148<Input 5> Long PressOff/On1 Bit1.1 switchCRWT
148<Input 5> Release ActionOff/On1 Bit1.1 switchCRWT
148<Input 5> Object BOff/On1 Bit1.1 switchCRT
148<Input 5> Shutter - Step/StopStep/Stop1 Bit1.7 stepCRT
148<Input 5> Sequence Command B Off/OnOff/On1 Bit1.1 switchCRT
148<Input 5> Sequence Command B Off/On-ToggleOff/On1 Bit1.1 switchCRT
148<Input 5> Send Learn Scene TriggerDisable/Enable1 Bit1.3 enableCW
148<Input 5> Do Not DisturbOff/On1 Bit1.1 switchCRT
149<Input 5> Additional Object RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
149<Input 5> Blue0-2551 Byte5.10 counter pulses (0..255)CRT
149<Input 5> Sequence Command C 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
149<Input 5> Sequence Command C 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
149<Input 5> Sequence Command C HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
149<Input 5> Sequence Command C 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
149<Input 5> Sequence Command C 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
149<Input 5> Sequence Command C HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
149<Input 5> Loop Value FeedbackLoop Value Feedback1 Byte5.10 counter pulses (0..255)CW
149<Input 5> Sequence Command C Off/OnOff/On1 Bit1.1 switchCRT
149<Input 5> Sequence Command C Off/On-ToggleOff/On1 Bit1.1 switchCRT
149<Input 5> FeedbackOff/On1 Bit1.1 switchCW
149<Input 5> FeedbackUp/Down1 Bit1.8 up/downCW
149<Input 5> Object COff/On1 Bit1.1 switchCRT
150<Input 5> Enable InputDisable/Enable1 Bit1.3 enableCW
151<Input 6> RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
151<Input 6> Red0-2551 Byte5.10 counter pulses (0..255)CRT
151<Input 6> Press Action0-2551 Byte5.10 counter pulses (0..255)CRT
151<Input 6> Press Action0-100%1 Byte5.1 percentage (0..100%)CRT
151<Input 6> Press ActionHVAC Mode1 Byte20.102 HVAC modeCRT
151<Input 6> Press - Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
151<Input 6> Press - Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
151<Input 6> Press - Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
151<Input 6> Short - Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
151<Input 6> Short - Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
151<Input 6> Short - Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
151<Input 6> Recall/Learn SceneScene1 Byte18.1 scene controlCRT
151<Input 6> Sequence Command A 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
151<Input 6> Sequence Command A 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
151<Input 6> Sequence Command A HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
151<Input 6> Sequence Command A 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
151<Input 6> Sequence Command A 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
151<Input 6> Sequence Command A HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
151<Input 6> Press ActionOff/On1 Bit1.1 switchCRWT
151<Input 6> Press - Release ActionOff/On1 Bit1.1 switchCRWT
151<Input 6> Short - Long PressOff/On1 Bit1.1 switchCRWT
151<Input 6> Dimming On/OffOff/On1 Bit1.1 switchCRWT
151<Input 6> Object AOff/On1 Bit1.1 switchCRT
151<Input 6> Shutter - Up/DownUp/Down1 Bit1.8 up/downCRWT
151<Input 6> Sequence Command A Off/OnOff/On1 Bit1.1 switchCRT
151<Input 6> Sequence Command A Off/On-ToggleOff/On1 Bit1.1 switchCRT
151<Input 6> Make Up RoomOff/On1 Bit1.1 switchCRT
152<Input 6> Green0-2551 Byte5.10 counter pulses (0..255)CRT
152<Input 6> Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
152<Input 6> Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
152<Input 6> Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
152<Input 6> Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
152<Input 6> Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
152<Input 6> Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
152<Input 6> Sequence Command B 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
152<Input 6> Sequence Command B 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
152<Input 6> Sequence Command B HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
152<Input 6> Sequence Command B 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
152<Input 6> Sequence Command B 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
152<Input 6> Sequence Command B HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
152<Input 6> Loop Value OutputLoop Value Output1 Byte5.10 counter pulses (0..255)CRT
152<Input 6> Dimming ControlBrighter/Darker4 Bit3.7 dimming controlCRT
152<Input 6> Long PressOff/On1 Bit1.1 switchCRWT
152<Input 6> Release ActionOff/On1 Bit1.1 switchCRWT
152<Input 6> Object BOff/On1 Bit1.1 switchCRT
152<Input 6> Shutter - Step/StopStep/Stop1 Bit1.7 stepCRT
152<Input 6> Sequence Command B Off/OnOff/On1 Bit1.1 switchCRT
152<Input 6> Sequence Command B Off/On-ToggleOff/On1 Bit1.1 switchCRT
152<Input 6> Send Learn Scene TriggerDisable/Enable1 Bit1.3 enableCW
152<Input 6> Do Not DisturbOff/On1 Bit1.1 switchCRT
153<Input 6> Additional Object RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
153<Input 6> Blue0-2551 Byte5.10 counter pulses (0..255)CRT
153<Input 6> Sequence Command C 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
153<Input 6> Sequence Command C 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
153<Input 6> Sequence Command C HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
153<Input 6> Sequence Command C 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
153<Input 6> Sequence Command C 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
153<Input 6> Sequence Command C HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
153<Input 6> Loop Value FeedbackLoop Value Feedback1 Byte5.10 counter pulses (0..255)CW
153<Input 6> Sequence Command C Off/OnOff/On1 Bit1.1 switchCRT
153<Input 6> Sequence Command C Off/On-ToggleOff/On1 Bit1.1 switchCRT
153<Input 6> FeedbackOff/On1 Bit1.1 switchCW
153<Input 6> FeedbackUp/Down1 Bit1.8 up/downCW
153<Input 6> Object COff/On1 Bit1.1 switchCRT
154<Input 6> Enable InputDisable/Enable1 Bit1.3 enableCW
155<Input 7> RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
155<Input 7> Red0-2551 Byte5.10 counter pulses (0..255)CRT
155<Input 7> Press Action0-2551 Byte5.10 counter pulses (0..255)CRT
155<Input 7> Press Action0-100%1 Byte5.1 percentage (0..100%)CRT
155<Input 7> Press ActionHVAC Mode1 Byte20.102 HVAC modeCRT
155<Input 7> Press - Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
155<Input 7> Press - Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
155<Input 7> Press - Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
155<Input 7> Short - Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
155<Input 7> Short - Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
155<Input 7> Short - Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
155<Input 7> Recall/Learn SceneScene1 Byte18.1 scene controlCRT
155<Input 7> Sequence Command A 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
155<Input 7> Sequence Command A 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
155<Input 7> Sequence Command A HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
155<Input 7> Sequence Command A 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
155<Input 7> Sequence Command A 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
155<Input 7> Sequence Command A HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
155<Input 7> Press ActionOff/On1 Bit1.1 switchCRWT
155<Input 7> Press - Release ActionOff/On1 Bit1.1 switchCRWT
155<Input 7> Short - Long PressOff/On1 Bit1.1 switchCRWT
155<Input 7> Dimming On/OffOff/On1 Bit1.1 switchCRWT
155<Input 7> Object AOff/On1 Bit1.1 switchCRT
155<Input 7> Shutter - Up/DownUp/Down1 Bit1.8 up/downCRWT
155<Input 7> Sequence Command A Off/OnOff/On1 Bit1.1 switchCRT
155<Input 7> Sequence Command A Off/On-ToggleOff/On1 Bit1.1 switchCRT
155<Input 7> Make Up RoomOff/On1 Bit1.1 switchCRT
156<Input 7> Green0-2551 Byte5.10 counter pulses (0..255)CRT
156<Input 7> Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
156<Input 7> Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
156<Input 7> Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
156<Input 7> Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
156<Input 7> Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
156<Input 7> Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
156<Input 7> Sequence Command B 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
156<Input 7> Sequence Command B 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
156<Input 7> Sequence Command B HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
156<Input 7> Sequence Command B 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
156<Input 7> Sequence Command B 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
156<Input 7> Sequence Command B HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
156<Input 7> Loop Value OutputLoop Value Output1 Byte5.10 counter pulses (0..255)CRT
156<Input 7> Dimming ControlBrighter/Darker4 Bit3.7 dimming controlCRT
156<Input 7> Long PressOff/On1 Bit1.1 switchCRWT
156<Input 7> Release ActionOff/On1 Bit1.1 switchCRWT
156<Input 7> Object BOff/On1 Bit1.1 switchCRT
156<Input 7> Shutter - Step/StopStep/Stop1 Bit1.7 stepCRT
156<Input 7> Sequence Command B Off/OnOff/On1 Bit1.1 switchCRT
156<Input 7> Sequence Command B Off/On-ToggleOff/On1 Bit1.1 switchCRT
156<Input 7> Send Learn Scene TriggerDisable/Enable1 Bit1.3 enableCW
156<Input 7> Do Not DisturbOff/On1 Bit1.1 switchCRT
157<Input 7> Additional Object RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
157<Input 7> Blue0-2551 Byte5.10 counter pulses (0..255)CRT
157<Input 7> Sequence Command C 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
157<Input 7> Sequence Command C 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
157<Input 7> Sequence Command C HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
157<Input 7> Sequence Command C 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
157<Input 7> Sequence Command C 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
157<Input 7> Sequence Command C HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
157<Input 7> Loop Value FeedbackLoop Value Feedback1 Byte5.10 counter pulses (0..255)CW
157<Input 7> Sequence Command C Off/OnOff/On1 Bit1.1 switchCRT
157<Input 7> Sequence Command C Off/On-ToggleOff/On1 Bit1.1 switchCRT
157<Input 7> FeedbackOff/On1 Bit1.1 switchCW
157<Input 7> FeedbackUp/Down1 Bit1.8 up/downCW
157<Input 7> Object COff/On1 Bit1.1 switchCRT
158<Input 7> Enable InputDisable/Enable1 Bit1.3 enableCW
159<Input 8> RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
159<Input 8> Red0-2551 Byte5.10 counter pulses (0..255)CRT
159<Input 8> Press Action0-2551 Byte5.10 counter pulses (0..255)CRT
159<Input 8> Press Action0-100%1 Byte5.1 percentage (0..100%)CRT
159<Input 8> Press ActionHVAC Mode1 Byte20.102 HVAC modeCRT
159<Input 8> Press - Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
159<Input 8> Press - Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
159<Input 8> Press - Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
159<Input 8> Short - Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
159<Input 8> Short - Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
159<Input 8> Short - Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
159<Input 8> Recall/Learn SceneScene1 Byte18.1 scene controlCRT
159<Input 8> Sequence Command A 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
159<Input 8> Sequence Command A 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
159<Input 8> Sequence Command A HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
159<Input 8> Sequence Command A 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
159<Input 8> Sequence Command A 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
159<Input 8> Sequence Command A HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
159<Input 8> Press ActionOff/On1 Bit1.1 switchCRWT
159<Input 8> Press - Release ActionOff/On1 Bit1.1 switchCRWT
159<Input 8> Short - Long PressOff/On1 Bit1.1 switchCRWT
159<Input 8> Dimming On/OffOff/On1 Bit1.1 switchCRWT
159<Input 8> Object AOff/On1 Bit1.1 switchCRT
159<Input 8> Shutter - Up/DownUp/Down1 Bit1.8 up/downCRWT
159<Input 8> Sequence Command A Off/OnOff/On1 Bit1.1 switchCRT
159<Input 8> Sequence Command A Off/On-ToggleOff/On1 Bit1.1 switchCRT
159<Input 8> Make Up RoomOff/On1 Bit1.1 switchCRT
160<Input 8> Green0-2551 Byte5.10 counter pulses (0..255)CRT
160<Input 8> Long Press0-2551 Byte5.10 counter pulses (0..255)CRT
160<Input 8> Long Press0-100%1 Byte5.1 percentage (0..100%)CRT
160<Input 8> Long PressHVAC Mode1 Byte20.102 HVAC modeCRT
160<Input 8> Release Action0-2551 Byte5.10 counter pulses (0..255)CRT
160<Input 8> Release Action0-100%1 Byte5.1 percentage (0..100%)CRT
160<Input 8> Release ActionHVAC Mode1 Byte20.102 HVAC modeCRT
160<Input 8> Sequence Command B 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
160<Input 8> Sequence Command B 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
160<Input 8> Sequence Command B HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
160<Input 8> Sequence Command B 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
160<Input 8> Sequence Command B 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
160<Input 8> Sequence Command B HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
160<Input 8> Loop Value OutputLoop Value Output1 Byte5.10 counter pulses (0..255)CRT
160<Input 8> Dimming ControlBrighter/Darker4 Bit3.7 dimming controlCRT
160<Input 8> Long PressOff/On1 Bit1.1 switchCRWT
160<Input 8> Release ActionOff/On1 Bit1.1 switchCRWT
160<Input 8> Object BOff/On1 Bit1.1 switchCRT
160<Input 8> Shutter - Step/StopStep/Stop1 Bit1.7 stepCRT
160<Input 8> Sequence Command B Off/OnOff/On1 Bit1.1 switchCRT
160<Input 8> Sequence Command B Off/On-ToggleOff/On1 Bit1.1 switchCRT
160<Input 8> Send Learn Scene TriggerDisable/Enable1 Bit1.3 enableCW
160<Input 8> Do Not DisturbOff/On1 Bit1.1 switchCRT
161<Input 8> Additional Object RGB3 Bytes3 Bytes232.600 RGB value 3x(0..255)CRT
161<Input 8> Blue0-2551 Byte5.10 counter pulses (0..255)CRT
161<Input 8> Sequence Command C 0-2550-2551 Byte5.10 counter pulses (0..255)CRT
161<Input 8> Sequence Command C 0-100%0-100%1 Byte5.1 percentage (0..100%)CRT
161<Input 8> Sequence Command C HVAC ModeHVAC Mode1 Byte20.102 HVAC modeCRT
161<Input 8> Sequence Command C 0-255-Toggle0-2551 Byte5.10 counter pulses (0..255)CRT
161<Input 8> Sequence Command C 0-100%-Toggle0-100%1 Byte5.1 percentage (0..100%)CRT
161<Input 8> Sequence Command C HVAC Mode-ToggleHVAC Mode1 Byte20.102 HVAC modeCRT
161<Input 8> Loop Value FeedbackLoop Value Feedback1 Byte5.10 counter pulses (0..255)CW
161<Input 8> Sequence Command C Off/OnOff/On1 Bit1.1 switchCRT
161<Input 8> Sequence Command C Off/On-ToggleOff/On1 Bit1.1 switchCRT
161<Input 8> FeedbackOff/On1 Bit1.1 switchCW
161<Input 8> FeedbackUp/Down1 Bit1.8 up/downCW
161<Input 8> Object COff/On1 Bit1.1 switchCRT
162<Input 8> Enable InputDisable/Enable1 Bit1.3 enableCW
163<Logic {{2323:1}}> Output 4Byte CountOutput 4Byte Count4 Bytes13.1 counter pulses (signed)CRT
163<Logic {{2323:1}}> Output 4Byte UCountOutput 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CRT
163<Logic {{2323:1}}> Output 4Byte FloatOutput 4Byte Float4 Bytes14.56 power (W)CRT
163<Logic {{2323:1}}> Input SurveillanceInput 4Byte Count4 Bytes13.1 counter pulses (signed)CW
163<Logic {{2323:1}}> Input SurveillanceInput 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
163<Logic {{2323:1}}> Input SurveillanceInput 4Byte Float4 Bytes14.56 power (W)CW
163<Logic {{2323:1}}> Output 2Byte CountOutput 2Byte Count2 Bytes8.1 pulses differenceCRT
163<Logic {{2323:1}}> Output 2Byte UCountOutput 2Byte UCount2 Bytes7.1 pulsesCRT
163<Logic {{2323:1}}> Output 2Byte FloatOutput 2Byte Float2 Bytes9.1 temperature (°C)CRT
163<Logic {{2323:1}}> Input TemperatureValue °C2 Bytes9.1 temperature (°C)CW
163<Logic {{2323:1}}> Input SurveillanceInput 2Byte Count2 Bytes8.1 pulses differenceCW
163<Logic {{2323:1}}> Input SurveillanceInput 2Byte UCount2 Bytes7.1 pulsesCW
163<Logic {{2323:1}}> Input SurveillanceInput 2Byte Float2 Bytes9.1 temperature (°C)CW
163<Logic {{2323:1}}> Output1 Byte1 Byte5.10 counter pulses (0..255)CRT
163<Logic {{2323:1}}> Output CountOutput Count1 Byte6.10 counter pulses (-128..127)CRT
163<Logic {{2323:1}}> Output UCountOutput UCount1 Byte5.10 counter pulses (0..255)CRT
163<Logic {{2323:1}}> Output Value %Value %1 Byte5.1 percentage (0..100%)CRT
163<Logic {{2323:1}}> Input Value %Value %1 Byte5.1 percentage (0..100%)CW
163<Logic {{2323:1}}> Input SurveillanceInput Count1 Byte6.10 counter pulses (-128..127)CW
163<Logic {{2323:1}}> Input SurveillanceInput UCount1 Byte5.10 counter pulses (0..255)CW
163<Temperature 5> AlarmNo Alarm/Alarm1 Bit1.5 alarmCRT
163<Logic {{2323:1}}> Output1 Bit1 Bit1.2 booleanCRT
163<Logic {{2323:1}}> OutputLogic1 Bit1.2 booleanCRT
163<Logic {{2323:1}}> Output BitOutput Bit1 Bit1.2 booleanCRT
163<Logic {{2323:1}}> Input SurveillanceInput Bit1 Bit1.1 switchCW
164<Logic {{2323:1}}> Input4 Bytes4 Bytes14.56 power (W)CW
164<Logic {{2323:1}}> Input A 4Byte CountInput A 4Byte Count4 Bytes13.1 counter pulses (signed)CW
164<Logic {{2323:1}}> Input A 4Byte UCountInput A 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
164<Logic {{2323:1}}> Input A 4Byte FloatInput A 4Byte Float4 Bytes14.56 power (W)CW
164<Logic {{2323:1}}> Input StatusInput 4Byte Count4 Bytes13.1 counter pulses (signed)CW
164<Logic {{2323:1}}> Input StatusInput 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
164<Logic {{2323:1}}> Input StatusInput 4Byte Float4 Bytes14.56 power (W)CW
164<Logic {{2323:1}}> Input2 Bytes2 Bytes9.1 temperature (°C)CW
164<Logic {{2323:1}}> Input A 2Byte CountInput A 2Byte Count2 Bytes8.1 pulses differenceCW
164<Logic {{2323:1}}> Input A 2Byte UCountInput A 2Byte UCount2 Bytes7.1 pulsesCW
164<Logic {{2323:1}}> Input A 2Byte FloatInput A 2Byte Float2 Bytes9.1 temperature (°C)CW
164<Logic {{2323:1}}> Input SetpointValue °C2 Bytes9.1 temperature (°C)CW
164<Logic {{2323:1}}> Input Relative HumidityHumidity %2 Bytes9.7 humidity (%)CW
164<Logic {{2323:1}}> Input StatusInput 2Byte Count2 Bytes8.1 pulses differenceCW
164<Logic {{2323:1}}> Input StatusInput 2Byte UCount2 Bytes7.1 pulsesCW
164<Logic {{2323:1}}> Input StatusInput 2Byte Float2 Bytes9.1 temperature (°C)CW
164<Temperature 5> KNX Probe TemperatureValue °C2 Bytes9.1 temperature (°C)CW
164<Logic {{2323:1}}> Input1 Byte1 Byte5.10 counter pulses (0..255)CW
164<Logic {{2323:1}}> Input A CountInput A Count1 Byte6.10 counter pulses (-128..127)CW
164<Logic {{2323:1}}> Input A UCountInput A UCount1 Byte5.10 counter pulses (0..255)CW
164<Logic {{2323:1}}> Input HVACComf/Standby/Eco/B.protection1 Byte20.102 HVAC modeCW
164<Logic {{2323:1}}> Input StatusInput Count1 Byte6.10 counter pulses (-128..127)CW
164<Logic {{2323:1}}> Input StatusInput UCount1 Byte5.10 counter pulses (0..255)CW
164<Logic {{2323:1}}> Input1 Bit1 Bit1.2 booleanCW
164<Logic {{2323:1}}> InputLogic1 Bit1.2 booleanCW
164<Logic {{2323:1}}> Input ALogic1 Bit1.2 booleanCW
164<Logic {{2323:1}}> Input A BitInput A Bit1 Bit1.2 booleanCW
164<Logic {{2323:1}}> Input Speed 1Off/On1 Bit1.1 switchCW
164<Logic {{2323:1}}> Output Speed 1Off/On1 Bit1.1 switchCRT
164<Logic {{2323:1}}> Input StatusInput Bit1 Bit1.1 switchCW
165<Logic {{2323:1}}> Input B 4Byte CountInput B 4Byte Count4 Bytes13.1 counter pulses (signed)CW
165<Logic {{2323:1}}> Input B 4Byte UCountInput B 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
165<Logic {{2323:1}}> Input B 4Byte FloatInput B 4Byte Float4 Bytes14.56 power (W)CW
165<Logic {{2323:1}}> Input B 2Byte CountInput B 2Byte Count2 Bytes8.1 pulses differenceCW
165<Logic {{2323:1}}> Input B 2Byte UCountInput B 2Byte UCount2 Bytes7.1 pulsesCW
165<Logic {{2323:1}}> Input B 2Byte FloatInput B 2Byte Float2 Bytes9.1 temperature (°C)CW
165<Logic {{2323:1}}> Input Regulation TemperatureValue °C2 Bytes9.1 temperature (°C)CW
165<Logic {{2323:1}}> Input B CountInput B Count1 Byte6.10 counter pulses (-128..127)CW
165<Logic {{2323:1}}> Input B UCountInput B UCount1 Byte5.10 counter pulses (0..255)CW
165<Logic {{2323:1}}> Input BLogic1 Bit1.2 booleanCW
165<Logic {{2323:1}}> Input B BitInput B Bit1 Bit1.2 booleanCW
165<Logic {{2323:1}}> Input Heat/CoolHeat/Cool1 Bit1.100 heating/coolingCW
165<Logic {{2323:1}}> Input Speed 2Off/On1 Bit1.1 switchCW
165<Logic {{2323:1}}> Output Speed 2Off/On1 Bit1.1 switchCRT
165<Logic {{2323:1}}> Input ResetOff/On1 Bit1.1 switchCW
165<R. Thresholds 5> Enable InputDisable/Enable1 Bit1.3 enableCW
165<Thermostat 5> Heat/Cool ModeHeat/Cool1 Bit1.100 heating/coolingCW
165<Thermostat 5> Heat/Cool ModeHeat/Cool1 Bit1.100 heating/coolingCRT
166<Logic {{2323:1}}> Input C 4Byte CountInput C 4Byte Count4 Bytes13.1 counter pulses (signed)CW
166<Logic {{2323:1}}> Input C 4Byte UCountInput C 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
166<Logic {{2323:1}}> Input C 4Byte FloatInput C 4Byte Float4 Bytes14.56 power (W)CW
166<Logic {{2323:1}}> Input C 2Byte CountInput C 2Byte Count2 Bytes8.1 pulses differenceCW
166<Logic {{2323:1}}> Input C 2Byte UCountInput C 2Byte UCount2 Bytes7.1 pulsesCW
166<Logic {{2323:1}}> Input C 2Byte FloatInput C 2Byte Float2 Bytes9.1 temperature (°C)CW
166<Logic {{2323:1}}> Output Dew Point TemperatureValue °C2 Bytes9.1 temperature (°C)CRT
166<R. Thresholds 5> Setpoint UpperValue °C2 Bytes9.1 temperature (°C)CW
166<Logic {{2323:1}}> Input C CountInput C Count1 Byte6.10 counter pulses (-128..127)CW
166<Logic {{2323:1}}> Input C UCountInput C UCount1 Byte5.10 counter pulses (0..255)CW
166<Logic {{2323:1}}> Output Valve %Value %1 Byte5.1 percentage (0..100%)CRT
166<Logic {{2323:1}}> Output Heat Valve %Value %1 Byte5.1 percentage (0..100%)CRT
166<Logic {{2323:1}}> Input C BitInput C Bit1 Bit1.2 booleanCW
166<Logic {{2323:1}}> Input Speed 3Off/On1 Bit1.1 switchCW
166<Logic {{2323:1}}> Output Speed 3Off/On1 Bit1.1 switchCRT
166<Logic {{2323:1}}> Output AlarmOff/On1 Bit1.1 switchCRT
166<Thermostat 5> Window ContactClose/Open1 Bit1.19 window/doorCW
167<Logic {{2323:1}}> Input D 4Byte CountInput D 4Byte Count4 Bytes13.1 counter pulses (signed)CW
167<Logic {{2323:1}}> Input D 4Byte UCountInput D 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
167<Logic {{2323:1}}> Input D 4Byte FloatInput D 4Byte Float4 Bytes14.56 power (W)CW
167<Logic {{2323:1}}> Input D 2Byte CountInput D 2Byte Count2 Bytes8.1 pulses differenceCW
167<Logic {{2323:1}}> Input D 2Byte UCountInput D 2Byte UCount2 Bytes7.1 pulsesCW
167<Logic {{2323:1}}> Input D 2Byte FloatInput D 2Byte Float2 Bytes9.1 temperature (°C)CW
167<Logic {{2323:1}}> Input D CountInput D Count1 Byte6.10 counter pulses (-128..127)CW
167<Logic {{2323:1}}> Input D UCountInput D UCount1 Byte5.10 counter pulses (0..255)CW
167<Logic {{2323:1}}> Output Cool Valve %Value %1 Byte5.1 percentage (0..100%)CRT
167<Logic {{2323:1}}> Output Value %Value %1 Byte5.1 percentage (0..100%)CRT
167<Logic {{2323:1}}> Input D BitInput D Bit1 Bit1.2 booleanCW
167<Logic {{2323:1}}> Input Enable/DisableDisable/Enable1 Bit1.3 enableCW
167<Logic {{2323:1}}> Output CommandOff/On1 Bit1.1 switchCRT
167<R. Thresholds 5> Telegram UpperOff/On1 Bit1.1 switchCRT
167<Thermostat 5> Comfort ModeOff/On1 Bit1.1 switchCW
167<Thermostat 5> Enable CoolingOff/On1 Bit1.1 switchCW
167<Thermostat 5> Enable HeatingOff/On1 Bit1.1 switchCW
167<Thermostat 5> Lock Heat/CoolLock1 Bit1.1 switchCW
168<Logic {{2402:2}}> Output 4Byte CountOutput 4Byte Count4 Bytes13.1 counter pulses (signed)CRT
168<Logic {{2402:2}}> Output 4Byte UCountOutput 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CRT
168<Logic {{2402:2}}> Output 4Byte FloatOutput 4Byte Float4 Bytes14.56 power (W)CRT
168<Logic {{2402:2}}> Input SurveillanceInput 4Byte Count4 Bytes13.1 counter pulses (signed)CW
168<Logic {{2402:2}}> Input SurveillanceInput 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
168<Logic {{2402:2}}> Input SurveillanceInput 4Byte Float4 Bytes14.56 power (W)CW
168<Logic {{2402:2}}> Output 2Byte CountOutput 2Byte Count2 Bytes8.1 pulses differenceCRT
168<Logic {{2402:2}}> Output 2Byte UCountOutput 2Byte UCount2 Bytes7.1 pulsesCRT
168<Logic {{2402:2}}> Output 2Byte FloatOutput 2Byte Float2 Bytes9.1 temperature (°C)CRT
168<Logic {{2402:2}}> Input TemperatureValue °C2 Bytes9.1 temperature (°C)CW
168<Logic {{2402:2}}> Input SurveillanceInput 2Byte Count2 Bytes8.1 pulses differenceCW
168<Logic {{2402:2}}> Input SurveillanceInput 2Byte UCount2 Bytes7.1 pulsesCW
168<Logic {{2402:2}}> Input SurveillanceInput 2Byte Float2 Bytes9.1 temperature (°C)CW
168<R. Thresholds 5> Setpoint LowerValue °C2 Bytes9.1 temperature (°C)CW
168<Thermostat 5> Base SetpointValue °C2 Bytes9.1 temperature (°C)CW
168<Logic {{2402:2}}> Output1 Byte1 Byte5.10 counter pulses (0..255)CRT
168<Logic {{2402:2}}> Output CountOutput Count1 Byte6.10 counter pulses (-128..127)CRT
168<Logic {{2402:2}}> Output UCountOutput UCount1 Byte5.10 counter pulses (0..255)CRT
168<Logic {{2402:2}}> Output Value %Value %1 Byte5.1 percentage (0..100%)CRT
168<Logic {{2402:2}}> Input Value %Value %1 Byte5.1 percentage (0..100%)CW
168<Logic {{2402:2}}> Input SurveillanceInput Count1 Byte6.10 counter pulses (-128..127)CW
168<Logic {{2402:2}}> Input SurveillanceInput UCount1 Byte5.10 counter pulses (0..255)CW
168<Thermostat 5> HVAC ModeComf/Standby/Eco/B.protection1 Byte20.102 HVAC modeCRW
168<Logic {{2402:2}}> Output1 Bit1 Bit1.2 booleanCRT
168<Logic {{2402:2}}> OutputLogic1 Bit1.2 booleanCRT
168<Logic {{2402:2}}> Output BitOutput Bit1 Bit1.2 booleanCRT
168<Logic {{2402:2}}> Input SurveillanceInput Bit1 Bit1.1 switchCW
169<Logic {{2402:2}}> Input4 Bytes4 Bytes14.56 power (W)CW
169<Logic {{2402:2}}> Input A 4Byte CountInput A 4Byte Count4 Bytes13.1 counter pulses (signed)CW
169<Logic {{2402:2}}> Input A 4Byte UCountInput A 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
169<Logic {{2402:2}}> Input A 4Byte FloatInput A 4Byte Float4 Bytes14.56 power (W)CW
169<Logic {{2402:2}}> Input StatusInput 4Byte Count4 Bytes13.1 counter pulses (signed)CW
169<Logic {{2402:2}}> Input StatusInput 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
169<Logic {{2402:2}}> Input StatusInput 4Byte Float4 Bytes14.56 power (W)CW
169<Logic {{2402:2}}> Input2 Bytes2 Bytes9.1 temperature (°C)CW
169<Logic {{2402:2}}> Input A 2Byte CountInput A 2Byte Count2 Bytes8.1 pulses differenceCW
169<Logic {{2402:2}}> Input A 2Byte UCountInput A 2Byte UCount2 Bytes7.1 pulsesCW
169<Logic {{2402:2}}> Input A 2Byte FloatInput A 2Byte Float2 Bytes9.1 temperature (°C)CW
169<Logic {{2402:2}}> Input SetpointValue °C2 Bytes9.1 temperature (°C)CW
169<Logic {{2402:2}}> Input Relative HumidityHumidity %2 Bytes9.7 humidity (%)CW
169<Logic {{2402:2}}> Input StatusInput 2Byte Count2 Bytes8.1 pulses differenceCW
169<Logic {{2402:2}}> Input StatusInput 2Byte UCount2 Bytes7.1 pulsesCW
169<Logic {{2402:2}}> Input StatusInput 2Byte Float2 Bytes9.1 temperature (°C)CW
169<Thermostat 5> Actual SetpointValue °C2 Bytes9.1 temperature (°C)CRT
169<Logic {{2402:2}}> Input1 Byte1 Byte5.10 counter pulses (0..255)CW
169<Logic {{2402:2}}> Input A CountInput A Count1 Byte6.10 counter pulses (-128..127)CW
169<Logic {{2402:2}}> Input A UCountInput A UCount1 Byte5.10 counter pulses (0..255)CW
169<Logic {{2402:2}}> Input HVACComf/Standby/Eco/B.protection1 Byte20.102 HVAC modeCW
169<Logic {{2402:2}}> Input StatusInput Count1 Byte6.10 counter pulses (-128..127)CW
169<Logic {{2402:2}}> Input StatusInput UCount1 Byte5.10 counter pulses (0..255)CW
169<Logic {{2402:2}}> Input1 Bit1 Bit1.2 booleanCW
169<Logic {{2402:2}}> InputLogic1 Bit1.2 booleanCW
169<Logic {{2402:2}}> Input ALogic1 Bit1.2 booleanCW
169<Logic {{2402:2}}> Input A BitInput A Bit1 Bit1.2 booleanCW
169<Logic {{2402:2}}> Input Speed 1Off/On1 Bit1.1 switchCW
169<Logic {{2402:2}}> Output Speed 1Off/On1 Bit1.1 switchCRT
169<Logic {{2402:2}}> Input StatusInput Bit1 Bit1.1 switchCW
169<R. Thresholds 5> Telegram LowerOff/On1 Bit1.1 switchCRT
170<Logic {{2402:2}}> Input B 4Byte CountInput B 4Byte Count4 Bytes13.1 counter pulses (signed)CW
170<Logic {{2402:2}}> Input B 4Byte UCountInput B 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
170<Logic {{2402:2}}> Input B 4Byte FloatInput B 4Byte Float4 Bytes14.56 power (W)CW
170<Logic {{2402:2}}> Input B 2Byte CountInput B 2Byte Count2 Bytes8.1 pulses differenceCW
170<Logic {{2402:2}}> Input B 2Byte UCountInput B 2Byte UCount2 Bytes7.1 pulsesCW
170<Logic {{2402:2}}> Input B 2Byte FloatInput B 2Byte Float2 Bytes9.1 temperature (°C)CW
170<Logic {{2402:2}}> Input Regulation TemperatureValue °C2 Bytes9.1 temperature (°C)CW
170<Thermostat 5> Setpoint AdjustmentValue °C2 Bytes9.1 temperature (°C)CW
170<Logic {{2402:2}}> Input B CountInput B Count1 Byte6.10 counter pulses (-128..127)CW
170<Logic {{2402:2}}> Input B UCountInput B UCount1 Byte5.10 counter pulses (0..255)CW
170<Logic {{2402:2}}> Input BLogic1 Bit1.2 booleanCW
170<Logic {{2402:2}}> Input B BitInput B Bit1 Bit1.2 booleanCW
170<Logic {{2402:2}}> Input Heat/CoolHeat/Cool1 Bit1.100 heating/coolingCW
170<Logic {{2402:2}}> Input Speed 2Off/On1 Bit1.1 switchCW
170<Logic {{2402:2}}> Output Speed 2Off/On1 Bit1.1 switchCRT
170<Logic {{2402:2}}> Input ResetOff/On1 Bit1.1 switchCW
170<Thermostat 5> Setpoint AdjustmentValue °C1 Bit1.7 stepCW
171<Logic {{2402:2}}> Input C 4Byte CountInput C 4Byte Count4 Bytes13.1 counter pulses (signed)CW
171<Logic {{2402:2}}> Input C 4Byte UCountInput C 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
171<Logic {{2402:2}}> Input C 4Byte FloatInput C 4Byte Float4 Bytes14.56 power (W)CW
171<Logic {{2402:2}}> Input C 2Byte CountInput C 2Byte Count2 Bytes8.1 pulses differenceCW
171<Logic {{2402:2}}> Input C 2Byte UCountInput C 2Byte UCount2 Bytes7.1 pulsesCW
171<Logic {{2402:2}}> Input C 2Byte FloatInput C 2Byte Float2 Bytes9.1 temperature (°C)CW
171<Logic {{2402:2}}> Output Dew Point TemperatureValue °C2 Bytes9.1 temperature (°C)CRT
171<Logic {{2402:2}}> Input C CountInput C Count1 Byte6.10 counter pulses (-128..127)CW
171<Logic {{2402:2}}> Input C UCountInput C UCount1 Byte5.10 counter pulses (0..255)CW
171<Logic {{2402:2}}> Output Valve %Value %1 Byte5.1 percentage (0..100%)CRT
171<Logic {{2402:2}}> Output Heat Valve %Value %1 Byte5.1 percentage (0..100%)CRT
171<Thermostat 5> Heating/Cooling0-100%1 Byte5.1 percentage (0..100%)CRT
171<Logic {{2402:2}}> Input C BitInput C Bit1 Bit1.2 booleanCW
171<Logic {{2402:2}}> Input Speed 3Off/On1 Bit1.1 switchCW
171<Logic {{2402:2}}> Output Speed 3Off/On1 Bit1.1 switchCRT
171<Logic {{2402:2}}> Output AlarmOff/On1 Bit1.1 switchCRT
171<Thermostat 5> Heating/CoolingOff/On1 Bit1.1 switchCRT
172<Logic {{2402:2}}> Input D 4Byte CountInput D 4Byte Count4 Bytes13.1 counter pulses (signed)CW
172<Logic {{2402:2}}> Input D 4Byte UCountInput D 4Byte UCount4 Bytes12.1 counter pulses (unsigned)CW
172<Logic {{2402:2}}> Input D 4Byte FloatInput D 4Byte Float4 Bytes14.56 power (W)CW
172<Logic {{2402:2}}> Input D 2Byte CountInput D 2Byte Count2 Bytes8.1 pulses differenceCW
172<Logic {{2402:2}}> Input D 2Byte UCountInput D 2Byte UCount2 Bytes7.1 pulsesCW
172<Logic {{2402:2}}> Input D 2Byte FloatInput D 2Byte Float2 Bytes9.1 temperature (°C)CW
172<Logic {{2402:2}}> Input D CountInput D Count1 Byte6.10 counter pulses (-128..127)CW
172<Logic {{2402:2}}> Input D UCountInput D UCount1 Byte5.10 counter pulses (0..255)CW

First 1000 of 1648 group objects shown. Download the .knxprod for the full list.

Parameters (362)
ParameterTypeDefault
Delay on Power up (3-15 seconds)unsignedInt 3…153
Delay between simultaneous commutations [ms]list200
Economy mode: switch OFF leds after inactivitylistnever switch OFF
Local buttons enable/disablelistenabled
Thermal driving 1-4list230V
Thermal driving 5-8list230V
All Valve Closedlistdisabled
External Valve Closedlistdisabled
External valve is closed when receivinglisttelegram 0
Request telegram at power ONlistno
Global Locklistdisabled
Temperature alarm object 1listdisabled
Temperature alarm object 2listdisabled
Temperature alarm object 3listdisabled
Temperature alarm object 4listdisabled
Input 1listinput
Temperature functionlistthermostat
Input 2listinput
Input 3listinput
Input 4listinput
Outputs 1-4list4 single outputs
Block 1 dimensionlist1
Output A1 | 01listsingle relay
Output B1 | 01-02listshutter
Block 2 dimensionlist1
Output A2 | 02listsingle relay
Block 3 dimensionlist1
Output A3 | 03listsingle relay
Output B2 | 03-04listshutter
Block 4 dimensionlist1
Output A4 | 04listsingle relay
Outputs 5-8list4 single outputs
Block 5 dimensionlist1
Output A5 | 05listsingle relay
Output B3 | 05-06listshutter
Block 6 dimensionlist1
Output A6 | 06listsingle relay
Block 7 dimensionlist1
Output A7 | 07listsingle relay
Output B4 | 07-08listshutter
Block 8 dimensionlist1
Output A8 | 08listsingle relay
Functionlistnothing
Contact typelistnormally open
Debounce time for inputslist80 ms
Object enablelistdisabled
Initial enable statelistenabled
Enable activation telegramlisttelegram "1"
Telegram associatedlist1 bit
Long or short cyclic timeslistshort
Command associated with pressliston
Cyclic sending when button pressedlistnever
Feedback objectlistdisabled
Command associated with presslistvalue 0-100%
Value associated with pressunsignedInt 0…2550
Value associated with presslist0%
Value associated with presslistauto
Command associated with presslistnothing
Command associated with releaselistnothing
Command typelistvalue 0-100%
Value associated with releaseunsignedInt 0…2550
Value associated with releaselist0%
Value associated with releaselistauto
Communication object on releaselistdisabled
Cyclic sending when button releasedlistnever
Minimum time long press buttonlist0.5 s
Command associated with short presslistnothing
Command associated with long presslistnothing
Value associated with short pressunsignedInt 0…2550
Value associated with short presslist0%
Value associated with short presslistauto
Value associated with long pressunsignedInt 0…2550
Value associated with long presslist0%
Value associated with long presslistauto
Communication object on long presslistdisabled
Dimming modelistbrighter/darker
Dimming steplistmaximum brightness
Dimming steplistminimum brightness
Dimming steplistmaximum/minimum brightness
Command drive shutterlistmove up/move down
Minimum time long press buttonlist2.0 s
Scene number (1-64)list1
Store scene on long presslistdisabled
Object enable scene learning from buslistdisabled
Delay between commandsunsignedInt 0…2550
Telegram associated with command Alist1 bit
Telegram associated with command Blist1 bit
Telegram associated with command Clist1 bit
Command typelistnothing
Value associated with operation 1unsignedInt 0…2550
Value associated with operation 1list0%
Value associated with operation 1listauto
Value associated with operation 2unsignedInt 0…2550
Value associated with operation 2list0%
Value associated with operation 2listauto
Command associated with operation 1listnothing
Command associated with operation 2listnothing
Number of objectslist2 objects
Send only changed objectslistdisabled
Number of steps in the sequencelist2
Long press to restart sequencelistdisabled
Min. time long press to restart sequencelist1.0 s
Restart functionlistrestart and send first
Value step longlista=off b=off c=off
Value step longlista=off b=off
Value step 1lista=off b=off c=off
Value step 2lista=off b=off c=off
Value step 3lista=off b=off c=off
Value step 4lista=off b=off c=off
Value step 5lista=off b=off c=off
Value step 6lista=off b=off c=off
Value step 7lista=off b=off c=off
Value step 8lista=off b=off c=off
Value step 1lista=off b=off
Value step 2lista=off b=off
Value step 3lista=off b=off
Value step 4lista=off b=off
Set valuelistred
Long press to change colorlistlong press disabled
Enable sending colors during transitionslistdisabled
RGB objects typelist3 objects of 1 byte
Command associatedlistreset all
Action associated with presslistenable
Color associated to "reset all"text#FFFFFF
Color associated to "make up room"text#00FF00
Color associated to "do not disturb"text#FF0000
Additional objectlistnone
Active edgelistsend on press
Number of valueslist3 values
Value AunsignedInt 0…2550
Value BunsignedInt 0…2551
Value CunsignedInt 0…2552
Value DunsignedInt 0…2553
Value EunsignedInt 0…2554
Value FunsignedInt 0…2555
Value GunsignedInt 0…2556
Value HunsignedInt 0…2557
Value IunsignedInt 0…2558
LED configurationlistbus controlled
LED activation telegramlisttelegram "1"
LED initial Statelistoff
LED blink periodlistfixed
Temperature sourcelistwired probe
Temperature objectlistdisabled
Sensor codelistTS01A01ACC
Weight wired probelist50%
Wired sensor calibration [0.1°C]signedInt -100…1000
KNX sensor calibration [0.1°C]signedInt -100…1000
Sending intervallistnever
Sending on variationlistnever
Surveillance time for KNX probe (0=disabled) [min]unsignedInt 0…25515
Activation telegramlisttelegram "1"
State after downloadlistenabled
Hysteresislist0.5°C
Upper setpoint valuelist+25°C
Telegram when value is above setpointliston
Telegram when value is below setpointlistoff
Telegram when probe is disabledlistoff
Cyclic sending time of telegramlistno cyclic send
Lower setpoint valuelist+20°C
Telegram when value is above setpointlistoff
Telegram when value is below setpointliston
Enable 2nd stage controllistdisabled
Enable additional valvelistdisabled
Thermostat control modelistHVAC mode (switched heat/cool)
Value of heat/cool object after downloadlist1 = heating
Value of HVAC mode object after downloadlistcomfort
Enable 1bit comfort objectlistdisabled
Additional functionlistno function
Version (HVAC auto)listold version
Control type when comfort endsliststandby
Comfort object prioritylistno
Comfort object timinglisttime unlimited
Comfort overwrite time [min]unsignedInt 1…2551
EnableHeatOrCool or LockHClistenable heat or cool
Enable objectlistcooling
Enable telegramlisttelegram "1"
Lock telegramlisttelegram "1"
Enable setpoint adjustment objectlistenabled
Window contactlistdisabled
Window contact activation telegramlisttelegram "1"
Thermostat OFF objectlistdisabled
Thermostat OFF activation telegramlisttelegram "1"
Setpoint frost protectionlist7°C
Setpoint economy heating (Teh)list16°C
Setpoint standby heating (Tsh)list18°C
Setpoint comfort heating (Tch)list20°C
Setpoint high temperature protectionlist35°C
Setpoint economy cooling (Tec)list28°C
Setpoint standby cooling (Tsc)list26°C
Setpoint comfort cooling (Tcc)list24°C
Action to execute for setpointlistmodify absolute
Value of base setpoint object after downloadlist20°C
Dead bandlist2°C
Comfort setpointlistsetpoint H/C
Control algorithmlist2 points on/off control
Time period for on/off cyclic sendinglistno cyclic sending
Regulation differential value - heatinglist0.4°C
Heating systemlistwarm water (3 °C / 150 min)
Proportional band [Bp]list1°C
Cycle timelist10 min
Integration time [min] [Ti]unsignedInt 5…250200
Regulation differential value - coolinglist0.4°C
Cooling systemlistceiling cooling (5 °C / 240 min)
Reset SP adjustment on HEAT/COOL changelistno reset
Reset SP adjustment on HVAC economylistno reset
Adjustment allowedlist-/+ 3°C
Setpoint adjustment value formatlist2 bytes object - temperature value
Increase setpoint adjustment withlisttelegram "1"
Resolutionlist0.5°C
Keep SP adjustment on power uplistenabled
2nd stage heatinglistenabled
2nd stage heating telegramlist1 bit
Activation telegram 2nd stage heatinglisttelegram "1"
Bandgaplist0°C
Control typelistproportional
Proportional band [Bp]list2.0°C
Integration time [min] [Ti]unsignedInt 5…250120
Integration time [min] [Ti]unsignedInt 5…255120
Time period for cyclic sendinglistno cyclic sending
2nd stage coolinglistenabled
2nd stage cooling telegramlist1 bit
Activation telegram 2nd stage coolinglisttelegram "1"
Control algorithmlistintegral proportional control PWM
Control algorithm 6 wayslistnothing
Enable valve whenlistcooling
Integration time heat [min] [Ti]unsignedInt 5…250120
Integration time cool [min] [Ti]unsignedInt 5…250120
Percentage 100% coollist0%
Percentage 0% coollist33%
Value to send for valve fully closedlist50%
Percentage 0% heatlist67%
Percentage 100% heatlist100%
Set the differential values of the heat bandlistno
Set the differential values of the cool bandlistno
Proportional band heat [Bp]list2°C
Proportional band cool [Bp]list2°C
Regulation differential valve heat 0%list0°C
Regulation differential valve heat 100%list2.0°C
Regulation differential valve cool 0%list0°C
Regulation differential valve cool 100%list2.0°C
Valve position when output not energizedlistopen
Telegram for valve openlisttelegram 1
Global all valve closedlistnot subordinate
Cycle base time for PWM [min] (only for 1 Byte object)unsignedInt 5…25510
PWM lower limit valuelist0 %
PWM upper limit valuelist100 %
Consider opening/closing times for PWMlistdo not consider
Time for openinglistno delay
Value for valve open/closelist100%
Time for closinglistno delay
Lock sourceslistdo not use lock objects
Feedback sourcelisttriac state
Extra time for valve open [min]unsignedInt 0…105
Feedback statelistdisabled
Telegram value for valve status sendinglisttelegram 0 is close
Feedback PWM %listdisabled
Anti-lock Functionlistdisabled
Anti-lock movement frequencylistevery day
Behaviour on power uplistnone
Behaviour on power downlistnone
Lock state after downloadlistunlocked
Telegram for lock activationlistactivate lock on ON telegram
Automatic unlocking time (0 = never automatically unlock) [min]unsignedInt 0…12030
Action on locklistnone
Action on unlocklistnone
Total revolution time [s]unsignedInt 0…300010
Extra time for valve opening [s]list5
Extra time for valve closing [s]list5
Stop time between 2 same valve movementslist200 ms
Stop time between 2 opposite valve movementslist200 ms
Telegram for openlisttelegram 1
Position 1list30%
Position 2list65%
Position 3list100%
Behaviour on power upliststop - no movement
Telegram value for status sendinglisttelegram 0 is close
Feedback position %listdisabled
Feedback opening and closinglistdisabled
Action on lockliststop - no movement
Logic 1-2listlogic
Temperature alarm object 5listdisabled
Logic 3-4listlogic
Temperature alarm object 6listdisabled
Logic 5-6listlogic
Temperature alarm object 7listdisabled
Logic 7-8listlogic
Temperature alarm object 8listdisabled
Temperature function 5listsmart thermostat
Temperature function 6listsmart thermostat
Temperature function 7listsmart thermostat
Temperature function 8listsmart thermostat
Logic functionlistdisabled
Logic nametext
Logic delaylist0
Number of transmissions on outputlist1
Retransmission timelistshort
Retransmission delaylist2 s
Retransmission delaylist1 min
Value sent when 0 is receivedunsignedInt 0…2550
Value sent when 1 is receivedunsignedInt 0…255128
Byte valueunsignedInt 0…255128
Output bit when byte is receivedlist1
Output bit otherwiselist0
Threshold valueunsignedInt 0…255128
Output bit when input > thresholdlist1
Output bit when input <= thresholdlist0
Threshold valuefloat -671088…6707600
Threshold valuefloat -9223372036854776000…87622034350120370000
Control modelistsetpoint
Setpoint frost protection [°C]float -300…3007
Setpoint economy heating [°C]float -300…30016
Setpoint standby heating [°C]float -300…30018
Setpoint comfort heating [°C]float -300…30020
Setpoint high temperature protection [°C]float -300…30035
Setpoint economy cooling [°C]float -300…30028
Setpoint standby cooling [°C]float -300…30026
Setpoint comfort cooling [°C]float -300…30024
Setpoint after download [°C]float -300…3000
HVAC object after downloadlistcomfort
Heat/Cool object after downloadlist0 = cooling
Dead band [0.1°C]unsignedInt 0…25520
Proportional band [Bp] [0.1°C]unsignedInt 0…25530
System typelist2 pipes
Proportional conversionlistbit to proportional
Lower limit valueunsignedInt 0…2550
Value to send for speed 1unsignedInt 0…25585
Limit value speed 1/2unsignedInt 0…25585
Value to send for speed 2unsignedInt 0…255170
Limit value speed 2/3unsignedInt 0…255170
Value to send for speed 3unsignedInt 0…255255
Bandgap [0.1°C]signedInt -128…1270
Altitude (tens of meters above sea level)unsignedInt 0…25550
Output typelistoff/on
Inverted controllistno
Surveillance time [min]unsignedInt 1…25510
DPT Surveillance/statuslist1 bit
Status controllistlast surveillance value
Status valuelistvalue 0
Status valuesignedInt -128…1270
Status valueunsignedInt 0…2550
Status valuesignedInt -32768…327670
Status valueunsignedInt 0…655350
Status valuefloat -671088…6707600
Status valuesignedInt -2147483648…21474836470
Status valueunsignedInt 0…42949672950
Status valuefloat -9223372036854776000…87622034350120370000
Status also clears alarmlistno
Alarm telegramlisttelegram "1"
Alarm cyclic sendinglistno cyclic send
Reset telegramlisttelegram "1"
DPT Outputlist1 bit
DPT Input Alist1 bit
Trigger on Input Alisttrigger
DPT Input Blist1 bit
Trigger on Input Blisttrigger
DPT Input Clist1 bit
Trigger on Input Clisttrigger
DPT Input Dlist1 bit
Trigger on Input Dlisttrigger
Logic expressiontext0
Surveillance time for KNX probe (0=disabled) [min]unsignedInt 0…25515

Version history

ApplicationApp noFingerprintFirst seenSizeFile
HA08A01KNX I/O 8+8 Heating Actuator 1.0 latest$08D09F612026-11-25630 KBDownload

About this file

This is the official ETS product database for the Eelectron HA08A01KNX Din Rail 8 Input / 8 Triac Output Module - A01 (HA08A01KNX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.