KNX Database
EAE 48132 FCA100 Fan Coil Actuator

FCA100 Fan Coil Actuator 48132

EAE · Order number 48132 · Fan Coil Actuator

FCA100 Fan Coil Actuator

Download .knxprod FCA100 Fan Coil Actuator 1.0 · 121 KB

Product

ManufacturerEAE
Product nameFCA100 Fan Coil Actuator
Order number48132
HardwareFCA100 EAE KNX
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationRegistered · 2020-01-16
Languagesen-US, de-DE, es-ES, fr-FR, it-IT
Catalog entryM-011E_H-48132-1_HP-BC04-10-191F_CI-48132-1
Fingerprint191F
SHA-25656f75070589a6396e60ed06b3cac8c01906cf0084acd4f12de5481fc293ed561
First seen2026-11-25
Markets69 markets

Application program: FCA100 Fan Coil Actuator 1.0

Application number$BC04
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters237
Group objects148
Group objects (148)
NoNameFunctionSizeDPTFlags
0GeneralIn operation1 Bit1.2 booleanCRT
1Input ASwitch1 Bit1.1 switchCRWT
1Input ASwitch - short1 Bit1.1 switchCRWT
1Input AWindow contact1 Bit1.19 window/doorCRT
1Input ADew point alarm1 Bit1.5 alarmCRT
1Input AValue/Forced operation - short1 BitDPT.1CRT
1Input AValue/Forced operation - short1 Byte5.10 counter pulses (0..255)CRT
1Input AValue/Forced operation - short2 Bytes8.1 pulses differenceCRT
1Input AValue/Forced operation - short2 Bytes7.1 pulsesCRT
1Input AValue/Forced operation - short4 BytesDPT.14CRT
1Input AValue/Forced operation - short4 Bytes12.1 counter pulses (unsigned)CRT
1Input AValue/Forced operation - short2 Bit2.1 switch controlCRT
1Input AValue/Forced operation1 BitDPT.1CRT
1Input AValue/Forced operation2 Bit2.1 switch controlCRT
1Input AValue/Forced operation1 Byte5.10 counter pulses (0..255)CRT
1Input AValue/Forced operation2 Bytes8.1 pulses differenceCRT
1Input AValue/Forced operation2 Bytes7.1 pulsesCRT
1Input AValue/Forced operation4 BytesDPT.14CRT
1Input AValue/Forced operation4 Bytes12.1 counter pulses (unsigned)CRT
2Input ASwitch - long1 Bit1.1 switchCRWT
2Input AValue/Forced operation - long1 BitDPT.1CRT
2Input AValue/Forced operation - long2 Bit2.1 switch controlCRT
2Input AValue/Forced operation - long1 Byte5.10 counter pulses (0..255)CRT
2Input AValue/Forced operation - long2 Bytes8.1 pulses differenceCRT
2Input AValue/Forced operation - long2 Bytes7.1 pulsesCRT
2Input AValue/Forced operation - long4 BytesDPT.14CRT
2Input AValue/Forced operation - long4 Bytes12.1 counter pulses (unsigned)CRT
3Input ADisable1 Bit1.3 enableCW
4Input BSwitch1 Bit1.1 switchCRWT
4Input BSwitch - short1 Bit1.1 switchCRWT
4Input BWindow contact1 Bit1.19 window/doorCRT
4Input BDew point alarm1 Bit1.5 alarmCRT
4Input BValue/Forced operation1 BitDPT.1CRT
4Input BValue/Forced operation2 Bit2.1 switch controlCRT
4Input BValue/Forced operation1 Byte5.10 counter pulses (0..255)CRT
4Input BValue/Forced operation2 Bytes8.1 pulses differenceCRT
4Input BValue/Forced operation2 Bytes7.1 pulsesCRT
4Input BValue/Forced operation4 BytesDPT.14CRT
4Input BValue/Forced operation4 Bytes12.1 counter pulses (unsigned)CRT
4Input BValue/Forced operation - short4 Bytes12.1 counter pulses (unsigned)CRT
4Input BValue/Forced operation - short4 BytesDPT.14CRT
4Input BValue/Forced operation - short2 Bytes7.1 pulsesCRT
4Input BValue/Forced operation - short2 Bytes8.1 pulses differenceCRT
4Input BValue/Forced operation - short1 Byte5.10 counter pulses (0..255)CRT
4Input BValue/Forced operation - short2 Bit2.1 switch controlCRT
4Input BValue/Forced operation - short1 BitDPT.1CRT
5Input BSwitch - long1 Bit1.1 switchCRWT
5Input BValue/Forced operation - long1 BitDPT.1CRT
5Input BValue/Forced operation - long2 Bit2.1 switch controlCRT
5Input BValue/Forced operation - long1 Byte5.10 counter pulses (0..255)CRT
5Input BValue/Forced operation - long2 Bytes8.1 pulses differenceCRT
5Input BValue/Forced operation - long2 Bytes7.1 pulsesCRT
5Input BValue/Forced operation - long4 BytesDPT.14CRT
5Input BValue/Forced operation - long4 Bytes12.1 counter pulses (unsigned)CRT
6Input BDisable1 Bit1.3 enableCW
7Input CSwitch1 Bit1.1 switchCRWT
7Input CSwitch - short1 Bit1.1 switchCRWT
7Input CWindow contact1 Bit1.19 window/doorCRT
7Input CDew point alarm1 Bit1.5 alarmCRT
7Input CValue/Forced operation1 BitDPT.1CRT
7Input CValue/Forced operation2 Bit2.1 switch controlCRT
7Input CValue/Forced operation1 Byte5.10 counter pulses (0..255)CRT
7Input CValue/Forced operation2 Bytes8.1 pulses differenceCRT
7Input CValue/Forced operation2 Bytes7.1 pulsesCRT
7Input CValue/Forced operation4 BytesDPT.14CRT
7Input CValue/Forced operation4 Bytes12.1 counter pulses (unsigned)CRT
7Input CValue/Forced operation - short4 Bytes12.1 counter pulses (unsigned)CRT
7Input CValue/Forced operation - short4 BytesDPT.14CRT
7Input CValue/Forced operation - short2 Bytes7.1 pulsesCRT
7Input CValue/Forced operation - short2 Bytes8.1 pulses differenceCRT
7Input CValue/Forced operation - short1 Byte5.10 counter pulses (0..255)CRT
7Input CValue/Forced operation - short2 Bit2.1 switch controlCRT
7Input CValue/Forced operation - short1 BitDPT.1CRT
8Input CSwitch - long1 Bit1.1 switchCRWT
8Input CValue/Forced operation - long1 BitDPT.1CRT
8Input CValue/Forced operation - long2 Bit2.1 switch controlCRT
8Input CValue/Forced operation - long1 Byte5.10 counter pulses (0..255)CRT
8Input CValue/Forced operation - long2 Bytes8.1 pulses differenceCRT
8Input CValue/Forced operation - long2 Bytes7.1 pulsesCRT
8Input CValue/Forced operation - long4 BytesDPT.14CRT
8Input CValue/Forced operation - long4 Bytes12.1 counter pulses (unsigned)CRT
9Input CDisable1 Bit1.3 enableCW
10Input DSwitch1 Bit1.1 switchCRWT
10Input DSwitch - short1 Bit1.1 switchCRWT
10Input DWindow contact1 Bit1.19 window/doorCRT
10Input DDew point alarm1 Bit1.5 alarmCRT
10Input DValue/Forced operation1 BitDPT.1CRT
10Input DValue/Forced operation2 Bit2.1 switch controlCRT
10Input DValue/Forced operation1 Byte5.10 counter pulses (0..255)CRT
10Input DValue/Forced operation2 Bytes8.1 pulses differenceCRT
10Input DValue/Forced operation2 Bytes7.1 pulsesCRT
10Input DValue/Forced operation4 BytesDPT.14CRT
10Input DValue/Forced operation4 Bytes12.1 counter pulses (unsigned)CRT
10Input DValue/Forced operation - short4 Bytes12.1 counter pulses (unsigned)CRT
10Input DValue/Forced operation - short4 BytesDPT.14CRT
10Input DValue/Forced operation - short2 Bytes7.1 pulsesCRT
10Input DValue/Forced operation - short2 Bytes8.1 pulses differenceCRT
10Input DValue/Forced operation - short1 Byte5.10 counter pulses (0..255)CRT
10Input DValue/Forced operation - short2 Bit2.1 switch controlCRT
10Input DValue/Forced operation - short1 BitDPT.1CRT
11Input DSwitch - long1 Bit1.1 switchCRWT
11Input DValue/Forced operation - long1 BitDPT.1CRT
11Input DValue/Forced operation - long2 Bit2.1 switch controlCRT
11Input DValue/Forced operation - long1 Byte5.10 counter pulses (0..255)CRT
11Input DValue/Forced operation - long2 Bytes8.1 pulses differenceCRT
11Input DValue/Forced operation - long2 Bytes7.1 pulsesCRT
11Input DValue/Forced operation - long4 BytesDPT.14CRT
11Input DValue/Forced operation - long4 Bytes12.1 counter pulses (unsigned)CRT
12Input DDisable1 Bit1.3 enableCW
13Temp. Sensor 1Current Temperature 1 (°C)2 Bytes9.1 temperature (°C)CRT
13Temp. Sensor 1Current Temperature 1 (°F)2 Bytes9.27 temperature (°F)CRT
14Temp. Sensor 2Current Temperature 2 (°C)2 Bytes9.1 temperature (°C)CRT
14Temp. Sensor 2Current Temperature 2 (°F)2 Bytes9.27 temperature (°F)CRT
15Temp. Sensor 1&2Average Temperature (°C)2 Bytes9.1 temperature (°C)CRT
15Temp. Sensor 1&2Average Temperature (°F)2 Bytes9.27 temperature (°F)CRT
16Auxiliary OutputSwitch Auxiliary1 Bit1.1 switchCW
17Auxiliary OutputStatus Switch Auxiliary1 Bit1.1 switchCRT
18Switching Output 1Switch Output 11 Bit1.1 switchCW
19Switching Output 1Status Switch Output 11 Bit1.1 switchCRT
20Switching Output 2Switch Output 21 Bit1.1 switchCW
21Switching Output 2Status Switch Output 21 Bit1.1 switchCRT
22Switching Output 3Switch Output 31 Bit1.1 switchCW
23Switching Output 3Status Switch Output 31 Bit1.1 switchCRT
24Valve ControlHeating/Cooling Switchover1 Bit1.100 heating/coolingCW
24Valve ControlHeating/Cooling Switchover1 Byte20.105 HVAC control modeCW
25Valve ControlStatus Heating/Cooling Switchover1 Bit1.100 heating/coolingCRT
25Valve ControlStatus Heating/Cooling Switchover1 Byte20.105 HVAC control modeCRT
26Valve ControlHeat Control Value (0%...100%)1 Byte5.1 percentage (0..100%)CW
26Valve ControlHeat/Cool Control Value (0%...100%)1 Byte5.1 percentage (0..100%)CW
27Valve ControlCool Control Value (0%...100%)1 Byte5.1 percentage (0..100%)CW
28Valve ControlStatus Heat Control Value (0%...100%)1 Byte5.1 percentage (0..100%)CRT
28Valve ControlStatus Heat/Cool Control Value (0%...100%)1 Byte5.1 percentage (0..100%)CRT
29Valve ControlStatus Cool Control Value (0%...100%)1 Byte5.1 percentage (0..100%)CRT
30Valve ControlStatus Heat Mode1 Bit1.2 booleanCRT
31Valve ControlStatus Cool Mode1 Bit1.2 booleanCRT
32Fan ControlFan Speed (0%...100%)1 Byte5.1 percentage (0..100%)CW
33Fan ControlFan Speed 11 Bit1.1 switchCW
34Fan ControlFan Speed 21 Bit1.1 switchCW
35Fan ControlFan Speed 31 Bit1.1 switchCW
36Fan ControlStatus Fan Speed (0%...100%)1 Byte5.1 percentage (0..100%)CRT
37Fan ControlStatus Fan Speed 11 Bit1.1 switchCRT
38Fan ControlStatus Fan Speed 21 Bit1.1 switchCRT
39Fan ControlStatus Fan Speed 31 Bit1.1 switchCRT
40Fan ControlFan Automatic1 Bit1.3 enableCW
41Fan ControlFan Automatic Status1 Bit1.3 enableCRT
42Valve ControlHeating Valve Short Circuit1 Bit1.5 alarmCRT
42Valve ControlHeating/Cooling Valve Short Circuit1 Bit1.5 alarmCRT
43Valve ControlCooling Valve Short Circuit1 Bit1.5 alarmCRT
Parameters (109)
ParameterTypeDefault
In Operation TelegramlistDisable
Telegram Valuelist1
Telegram Transmit Intervaltime300
Telegram LimiterlistDisable
Time for Automatic Deactivationtime30
Time for Automatic DeactivationunsignedInt 0…10
Telegram Limit Periodlist50ms
Maximum Telegram Count in PeriodunsignedInt 1…25510
Manual Operation Deactivation Methodlistvia Push Button
Manual OperationlistEnable
Valve Control TypelistStandard
Fan Control TypelistStandard (1-3 step)
Control ModelistHeating
Type of Heating/Cooling Systemlist2-pipe
Heat/Cool Control Object TypelistCommon
Send Switchover Statusliston Change
Switchover Object Typelist1 Bit (DPT 1.100)
Cyclic Sending Intervaltime300
Heating/Cooling ModelistAs Before Bus Voltage Failure
Control ValuelistAs Before Bus Voltage Failure
ValueunsignedInt 0…1000
Heating/Cooling ModelistHeating
Control ValuelistUnchanged
Auxiliary OutputlistUnchanged
Switching Output 1listUnchanged
Switching Output 2listUnchanged
Switching Output 3listUnchanged
Fan OutputlistUnchanged
Fan OutputlistAs Before Bus Voltage Failure
Valve Drive Opening/Closing Timetime180
Reversing Delay Timetime500
Voltage Range Valve Control Valuelist0 - 10 V
Send Valve Status Valueliston Change
Minimum Valve Position Changelist5 %
Minimum Valve Positionlist0 %
Maximum Valve Positionlist100 %
Delay Between Heating and Coolinglist0 min
Cyclic Transmission of Heating Statustime100
Valve OutputlistThermoelectric (PWM)
Valve Drive Method, De-energizedlistClosed
PWM Cycle Timetime18
Number of Valve Control Until AdjustmentunsignedInt 1…25550
Valve Open When Control Value ≥unsignedInt 0…1001
Cyclic Transmission of Cooling Statustime100
Enable Start-up BehaviorlistNo
Minimum Holding Time at Switch-on Speedtime5
Fan Control Minimum Output Voltage (0% is always 0V)unsignedInt 0…100
Fan Control Maximum Output VoltageunsignedInt 0…1010
Switch-on at Fan SpeedunsignedInt 0…10030
Switch Fan Speed via 1-bit ObjectslistNo
Send Fan Speed Status Valueliston Change
Number of Fan Speedlist3 Speed
Fan ModelistChangeover
Switch-on Threshold for Fan Speed 1list10 %
Switch-on Threshold for Fan Speed 2list40 %
Switch-on Threshold for Fan Speed 3list70 %
Switch-on at Fan SpeedlistSpeed 1
Control Object TypelistFan Step (0 - 3)
Cyclic Sending Intervaltime450
Switch-on Auxiliary RelaylistIf Heating is Required
Output TypelistNormally Open
Send Auxiliary Output Status Valueliston Change
InputlistDeactivated
Sent Valuelist0
Sent ValuelistDisable Forced Positioning
Sent ValueunsignedInt 0…2550
Sent ValuesignedInt -32768…327670
Sent ValueunsignedInt 0…655350
Sent Valuefloat -2305048932…42865786870
Sent ValueunsignedInt 0…42949672950
Delay for Window Open Action (0 = No Wait)time10
Distinction Between Long and Short OperationlistNo
Long Operation Aftertime1
Number of Objects for Short/Long Operationlist1 Object
Reaction on Short OperationlistOFF
Reaction on Contact Opening (Falling edge)listOFF
Reaction on Long OperationlistON
Transmit Object Value After Bus Voltage RecoverylistNo
Value Type for Long OperationlistNo Reaction
Reaction on Contact Closing (Rising edge)listON
Number of Objects for Short/Long operationlist1 Object
Cyclic Sending Intervaltime10
Send Output Status Valueliston Change
Cable Resistance (total of fwd and rtn conductor)unsignedInt 0…10000500
Cable Resistance (Total of fwd and rtn conductor)unsignedInt 0…10000500
Temperature UnitlistCelcius ( °C )
Temperature MeasurementlistTemp. Sensor 1
Temperature Sensor TypelistNTC 10-01 [-15... +50]
Sensor OffsetsignedInt -128…1270
Cable Error CompensationlistNone
Cable LengthunsignedInt 1…10010
Cross-section of ConductorunsignedInt 1…150100
Sensor-2 WeightunsignedInt 1…9950
FilterlistInactive
Minimum ChangeunsignedInt 1…2551
Send TemperaturelistCyclically and on Change
Threshold Values HysteresisunsignedInt 0…200
__heating_valve_activeunsignedInt 0…10
__cooling_valve_activeunsignedInt 0…10
Switch-on Auxiliary Relaylistvia Object
Error for Threshold Numbers at 3 Steps.unsignedInt 0…10
Error for Threshold Numbers at 2 StepsunsignedInt 0…10
Window Open WhenlistContact Open
Contact TypelistNormally Close
Dew Point Alarm WhenlistContact Open
Delay for Window Open Action (0 = No Wait)time0
Cyclic Transmission of Valve Statustime100
Value Type for Short OperationlistNo Reaction
Value Typelist1-Bit Value

Version history

ApplicationApp noFingerprintFirst seenSizeFile
FCA100 Fan Coil Actuator 1.0 latest$BC04191F2026-11-25121 KBDownload

About this file

This is the official ETS product database for the EAE FCA100 Fan Coil Actuator (48132), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from EAE

All EAE products