| Sending "Device operating status" | list | On restart + cyclic |
| Sending "Fan automatic mode status" | list | On restart + on change |
| Sending "Fan manual mode status" | list | On restart + on change |
| Sending "Fan speed status" (0...max) | list | On restart + on change |
| Sending "Fan speed 1 status" | list | On restart + on change |
| Sending "Fan speed 2 status" | list | On restart + on change |
| Sending "Fan speed 3 status" | list | On restart + on change |
| Sending "Temperature display status"(in 0.5°C steps for display) | list | On restart + on change |
| Sending "Temperature regulation status"(in 0.1°C steps for regulation) | list | On restart + on change |
| Sending "Window open mode status" | list | On restart + on change |
| Sending"Binary input status" | list | On restart + on change |
| Sendrate limitation | list | 1s |
| Sending "Relay status" | list | On restart + on change |
| Sending "Cooling 0-100% status" | list | On restart + on change |
| Sending "Cooling output status" | list | On restart + on change |
| Sending "Overload 24VAC status" | list | On restart + on change |
| Sending "24VAC power status" | list | On restart + on change |
| Delay before starting to send after restart | list | 5s |
| Delay for cyclical sending | list | 1min |
| Local temperature sensor correction | list | 0° |
| Delay to fall back into automatic mode | list | 5min |
| Number of fan speeds | list | 3 |
| Fan starting time | list | 2s |
| Fan stopping time | list | 1s |
| Threshold for switching ON fan speed 1 | unsignedInt 0…255 | 51 |
| Threshold for switching ON fan speed 2 | unsignedInt 0…255 | 102 |
| Threshold for switching ON fan speed 3 | unsignedInt 0…255 | 204 |
| Threshold for switching OFF fan speed 3 | unsignedInt 0…255 | 179 |
| Threshold for switching OFF fan speed 2 | unsignedInt 0…255 | 77 |
| Threshold for switching OFF fan speed 1 | unsignedInt 0…255 | 26 |
| Fan trailing time | list | 1min |
| Monitoring delay before going into default | list | 10min |
| Default value in % (0...100) | unsignedInt 0…255 | 38 |
| Value for starting to open the valve in % (0...100) | unsignedInt 0…255 | 26 |
| Value for open full the valve in % (0...100) | unsignedInt 0…255 | 204 |
| Output for starting to open the valve | list | 3V / 30% Pulse ratio |
| Output for open full the valve | list | 9V / 90% Pulse ratio |
| Output when valve disabled | list | 0V / No Pulse |
| Valve behaviour in window open mode | list | No incidence |
| 0-10V or Pulse Width Modulating output | list | Analog 0-10V |
| PWM period | list | 30s |
| Threshold to automatic tripping of the relay "ON" in % (0...100) | unsignedInt 0…255 | 77 |
| Threshold to automatic tripping of the relay "OFF" in % (0...100) | unsignedInt 0…255 | 26 |
| Relay behaviour in window open mode | list | No incidence |
| Force level | list | Switch relay OFF if forcing |
| use local window contact | list | No |
| Polarity of local window contact | list | Contact closed = Window closed / Contact open = Window open |
| Polarity of binary input | list | 0 = contact open / 1 = contact closed |
| Using KNX window contact | list | No |
| Window open mode active if | list | At least KNX or local window is open |
| Delay after global window opening | list | 10s |
| Delay after global window closing | list | 5s |
| Sendrate limitation | list | No limitation |
| Use device for | list | Cooling |
| Relay forcing | list | No incidence |
| Valve output when forcing | list | 5V / 50% Pulse ratio |
| Value for forcing the valve in % (0...100) | unsignedInt 0…255 | 128 |
| Threshold for switching ON fan speed 2 | unsignedInt 0…100 | 40 |
| Threshold for switching ON fan speed 3 | unsignedInt 0…100 | 80 |
| Threshold for switching OFF fan speed 3 | unsignedInt 0…100 | 70 |
| Threshold for switching OFF fan speed 2 | unsignedInt 0…100 | 77 |
| Threshold for switching OFF fan speed 1 | unsignedInt 0…100 | 26 |
| Fan speed when forced | list | No fan |
| Threshold for switching ON fan speed 1 | unsignedInt 0…100 | 20 |
| Value for default | unsignedInt 0…100 | 15 |
| Threshold for starting to open valve | unsignedInt 0…100 | 10 |
| Threshold for full opening valve | unsignedInt 0…100 | 80 |
| Threshold for switching relay "ON" | unsignedInt 0…100 | 30 |
| Threshold for switching relay "OFF" | unsignedInt 0…100 | 10 |
| Sending "Heating 0-100% status" | list | On restart + on change |
| Sending "Heating output status" | list | On restart + on change |
| !!! CAUTION: Display NOT up-to Date!!! | unsignedInt 0…1 | 0 |
| Output for full opening valve | list | 9V / 90% Pulse ratio |
| Value for forcing the valve | unsignedInt 0…100 | 0 |
| Use local temperature sensor | list | No |
| Valve enabling | list | Always enabled |
| Local input | list | Not used |
| Sending local input | list | No |
| Fan speed when window open | list | No fan |
| Driving of relay | list | Driven by comm. object "Cooling switch" |
| Driving of relay | list | Driven by comm. object "Heating switch" |
| Minimum change for sending | list | 2 = 0.5VA |