Product

ManufacturerDATEC electronic AG
Product nameFancoil actuator
Order number1630.02120/55100
Product textFancoil actuator
HardwareFancoil actuator
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)106
RegistrationCertified
Languagesen-US
Catalog entryM-0103_H-1630.2E02120.2F55100-17_HP-0101-13-3A49_CI-1630.2E02120.2F55100-1
Fingerprint3A49
SHA-25624fbf79a3cfbf031f70fea3f350e7e8a03239eec630e2799185d7c5b1259834a
First seen2026-11-25
Markets13 markets

Application program: Fancoil actuator 1.3

Application number$0101
Version1.3
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters101
Group objects32
Group objects (32)
NoNameFunctionSizeDPTFlags
0Device operating status1 Bit1.11 stateCT
1Forcing mode1 Bit1.3 enableCW
2Fan automatic mode1 Bit1.3 enableCW
3Fan manual mode1 Bit1.3 enableCW
4Fan automatic mode status1 Bit1.11 stateCT
5Fan manual mode status1 Bit1.11 stateCT
6Fan manual speed 0-100%1 Byte5.1 percentage (0..100%)CW
7Fan manual speed counter1 Byte5.10 counter pulses (0..255)CW
8Fan manual speed 11 Bit1.3 enableCW
9Fan manual speed 21 Bit1.3 enableCW
10Fan manual speed 31 Bit1.3 enableCW
11Fan manual speed changing1 Bit1.7 stepCW
12Fan speed status1 Byte5.10 counter pulses (0..255)CT
13Fan speed 1 status1 Bit1.11 stateCT
14Fan speed 2 status1 Bit1.11 stateCT
15Fan speed 3 status1 Bit1.11 stateCT
16Temperature display status2 Bytes9.1 temperature (°C)CT
17Temperature regulation status2 Bytes9.1 temperature (°C)CT
18KNX window contact1 Bit1.19 window/doorCW
19Window open mode status1 Bit1.11 stateCT
20Binary input status1 Bit1.11 stateCT
21Cooling switch1 Bit1.1 switchCW
21Heating switch1 Bit1.1 switchCW
22Relay status1 Bit1.11 stateCT
23Cooling 0-100%1 Byte5.1 percentage (0..100%)CW
23Heating 0-100%1 Byte5.1 percentage (0..100%)CW
24Cooling 0-100% status1 Byte5.1 percentage (0..100%)CT
24Heating 0-100% status1 Byte5.1 percentage (0..100%)CT
25Cooling output status1 Byte5.1 percentage (0..100%)CT
25Heating output status1 Byte5.1 percentage (0..100%)CT
26Overload 24VAC status1 Bit1.5 alarmCT
2724VAC power status1 Byte5.10 counter pulses (0..255)CT
Parameters (82)
ParameterTypeDefault
Sending "Device operating status"listOn restart + cyclic
Sending "Fan automatic mode status"listOn restart + on change
Sending "Fan manual mode status"listOn restart + on change
Sending "Fan speed status" (0...max)listOn restart + on change
Sending "Fan speed 1 status"listOn restart + on change
Sending "Fan speed 2 status"listOn restart + on change
Sending "Fan speed 3 status"listOn restart + on change
Sending "Temperature display status"(in 0.5°C steps for display)listOn restart + on change
Sending "Temperature regulation status"(in 0.1°C steps for regulation)listOn restart + on change
Sending "Window open mode status"listOn restart + on change
Sending"Binary input status"listOn restart + on change
Sendrate limitationlist1s
Sending "Relay status"listOn restart + on change
Sending "Cooling 0-100% status"listOn restart + on change
Sending "Cooling output status"listOn restart + on change
Sending "Overload 24VAC status"listOn restart + on change
Sending "24VAC power status"listOn restart + on change
Delay before starting to send after restartlist5s
Delay for cyclical sendinglist1min
Local temperature sensor correctionlist0°
Delay to fall back into automatic modelist5min
Number of fan speedslist3
Fan starting timelist2s
Fan stopping timelist1s
Threshold for switching ON fan speed 1unsignedInt 0…25551
Threshold for switching ON fan speed 2unsignedInt 0…255102
Threshold for switching ON fan speed 3unsignedInt 0…255204
Threshold for switching OFF fan speed 3unsignedInt 0…255179
Threshold for switching OFF fan speed 2unsignedInt 0…25577
Threshold for switching OFF fan speed 1unsignedInt 0…25526
Fan trailing timelist1min
Monitoring delay before going into defaultlist10min
Default value in % (0...100)unsignedInt 0…25538
Value for starting to open the valve in % (0...100)unsignedInt 0…25526
Value for open full the valve in % (0...100)unsignedInt 0…255204
Output for starting to open the valvelist3V / 30% Pulse ratio
Output for open full the valvelist9V / 90% Pulse ratio
Output when valve disabledlist0V / No Pulse
Valve behaviour in window open modelistNo incidence
0-10V or Pulse Width Modulating outputlistAnalog 0-10V
PWM periodlist30s
Threshold to automatic tripping of the relay "ON" in % (0...100)unsignedInt 0…25577
Threshold to automatic tripping of the relay "OFF" in % (0...100)unsignedInt 0…25526
Relay behaviour in window open modelistNo incidence
Force levellistSwitch relay OFF if forcing
use local window contactlistNo
Polarity of local window contactlistContact closed = Window closed / Contact open = Window open
Polarity of binary inputlist0 = contact open / 1 = contact closed
Using KNX window contactlistNo
Window open mode active iflistAt least KNX or local window is open
Delay after global window openinglist10s
Delay after global window closinglist5s
Sendrate limitationlistNo limitation
Use device forlistCooling
Relay forcinglistNo incidence
Valve output when forcinglist5V / 50% Pulse ratio
Value for forcing the valve in % (0...100)unsignedInt 0…255128
Threshold for switching ON fan speed 2unsignedInt 0…10040
Threshold for switching ON fan speed 3unsignedInt 0…10080
Threshold for switching OFF fan speed 3unsignedInt 0…10070
Threshold for switching OFF fan speed 2unsignedInt 0…10077
Threshold for switching OFF fan speed 1unsignedInt 0…10026
Fan speed when forcedlistNo fan
Threshold for switching ON fan speed 1unsignedInt 0…10020
Value for defaultunsignedInt 0…10015
Threshold for starting to open valveunsignedInt 0…10010
Threshold for full opening valveunsignedInt 0…10080
Threshold for switching relay "ON"unsignedInt 0…10030
Threshold for switching relay "OFF"unsignedInt 0…10010
Sending "Heating 0-100% status"listOn restart + on change
Sending "Heating output status"listOn restart + on change
!!! CAUTION: Display NOT up-to Date!!!unsignedInt 0…10
Output for full opening valvelist9V / 90% Pulse ratio
Value for forcing the valveunsignedInt 0…1000
Use local temperature sensorlistNo
Valve enablinglistAlways enabled
Local inputlistNot used
Sending local inputlistNo
Fan speed when window openlistNo fan
Driving of relaylistDriven by comm. object "Cooling switch"
Driving of relaylistDriven by comm. object "Heating switch"
Minimum change for sendinglist2 = 0.5VA

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Fancoil actuator 1.3 latest$01013A492026-11-2578 KBDownload

About this file

This is the official ETS product database for the DATEC electronic AG Fancoil actuator (1630.02120/55100), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.