| 1 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 2 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 3 | {{0}} | Status indication ON/OFF | 1 Bit | 1.1 switch | CRT |
| 4 | {{0}} | Status valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 5 | {{0}} | Command value monitoring failure | 1 Bit | 1.5 alarm | CRT |
| 6 | {{0}} | Short circuit/Overload status indication | 1 Bit | 1.5 alarm | CRT |
| 7 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 8 | {{0}} | Priority (1 bit) | 1 Bit | 1.3 enable | CWTU |
| 9 | {{0}} | Status indication priority | 1 Bit | 1.3 enable | CRT |
| 10 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 11 | {{0}} | Command value limitation activation | 1 Bit | 1.3 enable | CWTU |
| 12 | {{0}} | Hours counter value (h) | 2 Bytes | 7.7 time (h) | CRT |
| 13 | {{0}} | Hours counter value (s) | 4 Bytes | 13.100 time lag (s) | CRT |
| 14 | {{0}} | Reset hours counter value | 1 Bit | 1.15 reset | CWTU |
| 15 | {{0}} | Hours counter setpoint reached | 1 Bit | 1.11 state | CRT |
| 16 | {{0}} | Hours counter setpoint (h) | 2 Bytes | 7.7 time (h) | CWTU |
| 17 | {{0}} | Hours counter setpoint (s) | 4 Bytes | 13.100 time lag (s) | CWTU |
| 18 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 19 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 20 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 21 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 22 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 23 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 24 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 25 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 26 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 27 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CWTU |
| 28 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 29 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 30 | {{0}} | Status indication ON/OFF | 1 Bit | 1.1 switch | CRT |
| 31 | {{0}} | Status valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | {{0}} | Command value monitoring failure | 1 Bit | 1.5 alarm | CRT |
| 33 | {{0}} | Short circuit/Overload status indication | 1 Bit | 1.5 alarm | CRT |
| 34 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 35 | {{0}} | Priority (1 bit) | 1 Bit | 1.3 enable | CWTU |
| 36 | {{0}} | Status indication priority | 1 Bit | 1.3 enable | CRT |
| 37 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 38 | {{0}} | Command value limitation activation | 1 Bit | 1.3 enable | CWTU |
| 39 | {{0}} | Hours counter value (h) | 2 Bytes | 7.7 time (h) | CRT |
| 40 | {{0}} | Hours counter value (s) | 4 Bytes | 13.100 time lag (s) | CRT |
| 41 | {{0}} | Reset hours counter value | 1 Bit | 1.15 reset | CWTU |
| 42 | {{0}} | Hours counter setpoint reached | 1 Bit | 1.11 state | CRT |
| 43 | {{0}} | Hours counter setpoint (h) | 2 Bytes | 7.7 time (h) | CWTU |
| 44 | {{0}} | Hours counter setpoint (s) | 4 Bytes | 13.100 time lag (s) | CWTU |
| 45 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 46 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 47 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 48 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 49 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 50 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 51 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 52 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 53 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 54 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CWTU |
| 55 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 56 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 57 | {{0}} | Status indication ON/OFF | 1 Bit | 1.1 switch | CRT |
| 58 | {{0}} | Status valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 59 | {{0}} | Command value monitoring failure | 1 Bit | 1.5 alarm | CRT |
| 60 | {{0}} | Short circuit/Overload status indication | 1 Bit | 1.5 alarm | CRT |
| 61 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 62 | {{0}} | Priority (1 bit) | 1 Bit | 1.3 enable | CWTU |
| 63 | {{0}} | Status indication priority | 1 Bit | 1.3 enable | CRT |
| 64 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 65 | {{0}} | Command value limitation activation | 1 Bit | 1.3 enable | CWTU |
| 66 | {{0}} | Hours counter value (h) | 2 Bytes | 7.7 time (h) | CRT |
| 67 | {{0}} | Hours counter value (s) | 4 Bytes | 13.100 time lag (s) | CRT |
| 68 | {{0}} | Reset hours counter value | 1 Bit | 1.15 reset | CWTU |
| 69 | {{0}} | Hours counter setpoint reached | 1 Bit | 1.11 state | CRT |
| 70 | {{0}} | Hours counter setpoint (h) | 2 Bytes | 7.7 time (h) | CWTU |
| 71 | {{0}} | Hours counter setpoint (s) | 4 Bytes | 13.100 time lag (s) | CWTU |
| 72 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 73 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 74 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 75 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 76 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 77 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 78 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 79 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 80 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 81 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CWTU |
| 82 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 83 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 84 | {{0}} | Status indication ON/OFF | 1 Bit | 1.1 switch | CRT |
| 85 | {{0}} | Status valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 86 | {{0}} | Command value monitoring failure | 1 Bit | 1.5 alarm | CRT |
| 87 | {{0}} | Short circuit/Overload status indication | 1 Bit | 1.5 alarm | CRT |
| 88 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 89 | {{0}} | Priority (1 bit) | 1 Bit | 1.3 enable | CWTU |
| 90 | {{0}} | Status indication priority | 1 Bit | 1.3 enable | CRT |
| 91 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 92 | {{0}} | Command value limitation activation | 1 Bit | 1.3 enable | CWTU |
| 93 | {{0}} | Hours counter value (h) | 2 Bytes | 7.7 time (h) | CRT |
| 94 | {{0}} | Hours counter value (s) | 4 Bytes | 13.100 time lag (s) | CRT |
| 95 | {{0}} | Reset hours counter value | 1 Bit | 1.15 reset | CWTU |
| 96 | {{0}} | Hours counter setpoint reached | 1 Bit | 1.11 state | CRT |
| 97 | {{0}} | Hours counter setpoint (h) | 2 Bytes | 7.7 time (h) | CWTU |
| 98 | {{0}} | Hours counter setpoint (s) | 4 Bytes | 13.100 time lag (s) | CWTU |
| 99 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 100 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 101 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 102 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 103 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 104 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 105 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 106 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 107 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 108 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CWTU |
| 109 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 110 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 111 | {{0}} | Status indication ON/OFF | 1 Bit | 1.1 switch | CRT |
| 112 | {{0}} | Status valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 113 | {{0}} | Command value monitoring failure | 1 Bit | 1.5 alarm | CRT |
| 114 | {{0}} | Short circuit/Overload status indication | 1 Bit | 1.5 alarm | CRT |
| 115 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 116 | {{0}} | Priority (1 bit) | 1 Bit | 1.3 enable | CWTU |
| 117 | {{0}} | Status indication priority | 1 Bit | 1.3 enable | CRT |
| 118 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 119 | {{0}} | Command value limitation activation | 1 Bit | 1.3 enable | CWTU |
| 120 | {{0}} | Hours counter value (h) | 2 Bytes | 7.7 time (h) | CRT |
| 121 | {{0}} | Hours counter value (s) | 4 Bytes | 13.100 time lag (s) | CRT |
| 122 | {{0}} | Reset hours counter value | 1 Bit | 1.15 reset | CWTU |
| 123 | {{0}} | Hours counter setpoint reached | 1 Bit | 1.11 state | CRT |
| 124 | {{0}} | Hours counter setpoint (h) | 2 Bytes | 7.7 time (h) | CWTU |
| 125 | {{0}} | Hours counter setpoint (s) | 4 Bytes | 13.100 time lag (s) | CWTU |
| 126 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 127 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 128 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 129 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 130 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 131 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 132 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 133 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 134 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 135 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CWTU |
| 136 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 137 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 138 | {{0}} | Status indication ON/OFF | 1 Bit | 1.1 switch | CRT |
| 139 | {{0}} | Status valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 140 | {{0}} | Command value monitoring failure | 1 Bit | 1.5 alarm | CRT |
| 141 | {{0}} | Short circuit/Overload status indication | 1 Bit | 1.5 alarm | CRT |
| 142 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 143 | {{0}} | Priority (1 bit) | 1 Bit | 1.3 enable | CWTU |
| 144 | {{0}} | Status indication priority | 1 Bit | 1.3 enable | CRT |
| 145 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 146 | {{0}} | Command value limitation activation | 1 Bit | 1.3 enable | CWTU |
| 147 | {{0}} | Hours counter value (h) | 2 Bytes | 7.7 time (h) | CRT |
| 148 | {{0}} | Hours counter value (s) | 4 Bytes | 13.100 time lag (s) | CRT |
| 149 | {{0}} | Reset hours counter value | 1 Bit | 1.15 reset | CWTU |
| 150 | {{0}} | Hours counter setpoint reached | 1 Bit | 1.11 state | CRT |
| 151 | {{0}} | Hours counter setpoint (h) | 2 Bytes | 7.7 time (h) | CWTU |
| 152 | {{0}} | Hours counter setpoint (s) | 4 Bytes | 13.100 time lag (s) | CWTU |
| 153 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 154 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 155 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 156 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 157 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 158 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 159 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 160 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 161 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 162 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CWTU |
| 163 | General | Heating activation | 1 Bit | 1.1 switch | CWTU |
| 164 | General | Heat requirement | 1 Bit | 1.2 boolean | CRT |
| 165 | {{0}} | Setpoint selection | 1 Byte | 20.102 HVAC mode | CWTU |
| 166 | {{0}} | Comfort | 1 Bit | 1.1 switch | CWTU |
| 167 | {{0}} | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 168 | {{0}} | Night setpoint | 1 Bit | 1.1 switch | CWTU |
| 169 | {{0}} | Frost/heat protection | 1 Bit | 1.1 switch | CWTU |
| 170 | {{0}} | Setpoint selection automatic control | 1 Byte | 20.102 HVAC mode | CWTU |
| 171 | {{0}} | Automatic control deactivation | 1 Bit | 1.3 enable | CWTU |
| 172 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 173 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 174 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CWTU |
| 175 | {{0}} | Priority | 1 Byte | 20.102 HVAC mode | CWTU |
| 176 | {{0}} | Windows contact | 1 Bit | 1.19 window/door | CWTU |
| 177 | {{0}} | Scene | 1 Byte | 18.1 scene control | CWTU |
| 178 | {{0}} | Status indication setpoint selection | 1 Byte | 20.102 HVAC mode | CRT |
| 179 | {{0}} | Automatic control deactivation status | 1 Bit | 1.3 enable | CRT |
| 180 | {{0}} | Heating/Cooling - status indication | 1 Bit | 1.100 cooling/heating | CRT |
| 181 | {{0}} | Status indication heating active | 1 Bit | 1.11 state | CRT |
| 182 | {{0}} | Status indication cooling active | 1 Bit | 1.11 state | CRT |
| 183 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CRT |
| 184 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 185 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 186 | {{0}} | ON/OFF - basic cooling | 1 Bit | 1.1 switch | CRT |
| 187 | {{0}} | Valve position in % - basic cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 188 | {{0}} | ON/OFF - additional heating | 1 Bit | 1.1 switch | CRT |
| 189 | {{0}} | Valve position in % - additional heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 190 | {{0}} | ON/OFF - additional cooling | 1 Bit | 1.1 switch | CRT |
| 191 | {{0}} | Valve position in % - additional cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 192 | {{0}} | Room temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 193 | {{0}} | Room temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 194 | {{0}} | Room temperature 3 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 195 | {{0}} | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 196 | {{0}} | Status indication room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 197 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CRT |
| 198 | {{0}} | Minimum room temperature | 1 Bit | 1.5 alarm | CRT |
| 199 | {{0}} | Maximum room temperature | 1 Bit | 1.5 alarm | CRT |
| 200 | {{0}} | Ventilation automatic/manual mode | 1 Bit | 1.1 switch | CWTU |
| 201 | {{0}} | Status ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 202 | {{0}} | Status ventilation step 1 | 1 Bit | 1.1 switch | CWTU |
| 203 | {{0}} | Status ventilation step 2 | 1 Bit | 1.1 switch | CWTU |
| 204 | {{0}} | Status ventilation step 3 | 1 Bit | 1.1 switch | CWTU |
| 205 | {{0}} | Status ventilation step 4 | 1 Bit | 1.1 switch | CWTU |
| 206 | {{0}} | Status ventilation step 5 | 1 Bit | 1.1 switch | CWTU |
| 207 | {{0}} | Status ventilation step 6 | 1 Bit | 1.1 switch | CWTU |
| 208 | {{0}} | Ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 209 | {{0}} | Ventilation step 1 | 1 Bit | 1.1 switch | CRT |
| 210 | {{0}} | Ventilation step 2 | 1 Bit | 1.1 switch | CRT |
| 211 | {{0}} | Ventilation step 3 | 1 Bit | 1.1 switch | CRT |
| 212 | {{0}} | Ventilation step 4 | 1 Bit | 1.1 switch | CRT |
| 213 | {{0}} | Ventilation step 5 | 1 Bit | 1.1 switch | CRT |
| 214 | {{0}} | Ventilation step 6 | 1 Bit | 1.1 switch | CRT |
| 215 | {{0}} | Comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 215 | {{0}} | Reference setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 216 | {{0}} | Standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 217 | {{0}} | Night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 218 | {{0}} | Frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 219 | {{0}} | Setpoints heating | 8 Bytes | | CWTU |
| 220 | {{0}} | Comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 221 | {{0}} | Standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 222 | {{0}} | Night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 223 | {{0}} | Heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 224 | {{0}} | Setpoints cooling | 8 Bytes | | CWTU |
| 225 | {{0}} | Setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 226 | {{0}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 227 | {{0}} | Status indication setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 228 | {{0}} | Status indication reference setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 229 | {{0}} | Status indication comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 230 | {{0}} | Status indication standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 231 | {{0}} | Status indication night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 232 | {{0}} | Status indication frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 233 | {{0}} | Status indication setpoints heating | 8 Bytes | | CRT |
| 234 | {{0}} | Status indication comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 235 | {{0}} | Status indication standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 236 | {{0}} | Status indication night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 237 | {{0}} | Status indication heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 238 | {{0}} | Status indication setpoints cooling | 8 Bytes | | CRT |
| 239 | {{0}} | Status current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 240 | {{0}} | Presence | 1 Bit | 1.1 switch | CWTU |
| 241 | {{0}} | Lock-up additional step | 1 Bit | 1.1 switch | CWTU |
| 242 | {{0}} | Heating deactivation | 1 Bit | 1.3 enable | CWTU |
| 243 | {{0}} | Cooling deactivation | 1 Bit | 1.3 enable | CWTU |
| 244 | {{0}} | Heating deactivation status | 1 Bit | 1.3 enable | CRT |
| 245 | {{0}} | Cooling deactivation status | 1 Bit | 1.3 enable | CRT |
| 246 | {{0}} | Thermostat deactivation | 1 Bit | 1.3 enable | CWTU |
| 247 | {{0}} | Status indication thermostat deactivation | 1 Bit | 1.3 enable | CRT |
| 248 | {{0}} | Timer | 1 Bit | 1.10 start/stop | CWTU |
| 249 | {{0}} | Timer duration | 3 Bytes | 10.1 time of day | CWTU |
| 250 | {{0}} | Timer | 1 Byte | 20.102 HVAC mode | CWTU |
| 251 | {{0}} | Preset 1 | 1 Bit | 1.3 enable | CWTU |
| 252 | {{0}} | Preset 2 | 1 Bit | 1.3 enable | CWTU |
| 253 | {{0}} | Preset 1 authorization | 1 Bit | 1.3 enable | CWTU |
| 254 | {{0}} | Preset 2 authorization | 1 Bit | 1.3 enable | CWTU |
| 255 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 256 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 257 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 258 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 259 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 260 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 261 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 262 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 263 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 264 | {{0}} | Setpoint selection | 1 Byte | 20.102 HVAC mode | CWTU |
| 265 | {{0}} | Comfort | 1 Bit | 1.1 switch | CWTU |
| 266 | {{0}} | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 267 | {{0}} | Night setpoint | 1 Bit | 1.1 switch | CWTU |
| 268 | {{0}} | Frost/heat protection | 1 Bit | 1.1 switch | CWTU |
| 269 | {{0}} | Setpoint selection automatic control | 1 Byte | 20.102 HVAC mode | CWTU |
| 270 | {{0}} | Automatic control deactivation | 1 Bit | 1.3 enable | CWTU |
| 271 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 272 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 273 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CWTU |
| 274 | {{0}} | Priority | 1 Byte | 20.102 HVAC mode | CWTU |
| 275 | {{0}} | Windows contact | 1 Bit | 1.19 window/door | CWTU |
| 276 | {{0}} | Scene | 1 Byte | 18.1 scene control | CWTU |
| 277 | {{0}} | Status indication setpoint selection | 1 Byte | 20.102 HVAC mode | CRT |
| 278 | {{0}} | Automatic control deactivation status | 1 Bit | 1.3 enable | CRT |
| 279 | {{0}} | Heating/Cooling - status indication | 1 Bit | 1.100 cooling/heating | CRT |
| 280 | {{0}} | Status indication heating active | 1 Bit | 1.11 state | CRT |
| 281 | {{0}} | Status indication cooling active | 1 Bit | 1.11 state | CRT |
| 282 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CRT |
| 283 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 284 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 285 | {{0}} | ON/OFF - basic cooling | 1 Bit | 1.1 switch | CRT |
| 286 | {{0}} | Valve position in % - basic cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 287 | {{0}} | ON/OFF - additional heating | 1 Bit | 1.1 switch | CRT |
| 288 | {{0}} | Valve position in % - additional heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 289 | {{0}} | ON/OFF - additional cooling | 1 Bit | 1.1 switch | CRT |
| 290 | {{0}} | Valve position in % - additional cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 291 | {{0}} | Room temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 292 | {{0}} | Room temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 293 | {{0}} | Room temperature 3 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 294 | {{0}} | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 295 | {{0}} | Status indication room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 296 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CRT |
| 297 | {{0}} | Minimum room temperature | 1 Bit | 1.5 alarm | CRT |
| 298 | {{0}} | Maximum room temperature | 1 Bit | 1.5 alarm | CRT |
| 299 | {{0}} | Ventilation automatic/manual mode | 1 Bit | 1.1 switch | CWTU |
| 300 | {{0}} | Status ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 301 | {{0}} | Status ventilation step 1 | 1 Bit | 1.1 switch | CWTU |
| 302 | {{0}} | Status ventilation step 2 | 1 Bit | 1.1 switch | CWTU |
| 303 | {{0}} | Status ventilation step 3 | 1 Bit | 1.1 switch | CWTU |
| 304 | {{0}} | Status ventilation step 4 | 1 Bit | 1.1 switch | CWTU |
| 305 | {{0}} | Status ventilation step 5 | 1 Bit | 1.1 switch | CWTU |
| 306 | {{0}} | Status ventilation step 6 | 1 Bit | 1.1 switch | CWTU |
| 307 | {{0}} | Ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 308 | {{0}} | Ventilation step 1 | 1 Bit | 1.1 switch | CRT |
| 309 | {{0}} | Ventilation step 2 | 1 Bit | 1.1 switch | CRT |
| 310 | {{0}} | Ventilation step 3 | 1 Bit | 1.1 switch | CRT |
| 311 | {{0}} | Ventilation step 4 | 1 Bit | 1.1 switch | CRT |
| 312 | {{0}} | Ventilation step 5 | 1 Bit | 1.1 switch | CRT |
| 313 | {{0}} | Ventilation step 6 | 1 Bit | 1.1 switch | CRT |
| 314 | {{0}} | Comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 314 | {{0}} | Reference setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 315 | {{0}} | Standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 316 | {{0}} | Night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 317 | {{0}} | Frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 318 | {{0}} | Setpoints heating | 8 Bytes | | CWTU |
| 319 | {{0}} | Comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 320 | {{0}} | Standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 321 | {{0}} | Night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 322 | {{0}} | Heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 323 | {{0}} | Setpoints cooling | 8 Bytes | | CWTU |
| 324 | {{0}} | Setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 325 | {{0}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 326 | {{0}} | Status indication setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 327 | {{0}} | Status indication reference setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 328 | {{0}} | Status indication comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 329 | {{0}} | Status indication standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 330 | {{0}} | Status indication night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 331 | {{0}} | Status indication frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 332 | {{0}} | Status indication setpoints heating | 8 Bytes | | CRT |
| 333 | {{0}} | Status indication comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 334 | {{0}} | Status indication standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 335 | {{0}} | Status indication night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 336 | {{0}} | Status indication heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 337 | {{0}} | Status indication setpoints cooling | 8 Bytes | | CRT |
| 338 | {{0}} | Status current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 339 | {{0}} | Presence | 1 Bit | 1.1 switch | CWTU |
| 340 | {{0}} | Lock-up additional step | 1 Bit | 1.1 switch | CWTU |
| 341 | {{0}} | Heating deactivation | 1 Bit | 1.3 enable | CWTU |
| 342 | {{0}} | Cooling deactivation | 1 Bit | 1.3 enable | CWTU |
| 343 | {{0}} | Heating deactivation status | 1 Bit | 1.3 enable | CRT |
| 344 | {{0}} | Cooling deactivation status | 1 Bit | 1.3 enable | CRT |
| 345 | {{0}} | Thermostat deactivation | 1 Bit | 1.3 enable | CWTU |
| 346 | {{0}} | Status indication thermostat deactivation | 1 Bit | 1.3 enable | CRT |
| 347 | {{0}} | Timer | 1 Bit | 1.10 start/stop | CWTU |
| 348 | {{0}} | Timer duration | 3 Bytes | 10.1 time of day | CWTU |
| 349 | {{0}} | Timer | 1 Byte | 20.102 HVAC mode | CWTU |
| 350 | {{0}} | Preset 1 | 1 Bit | 1.3 enable | CWTU |
| 351 | {{0}} | Preset 2 | 1 Bit | 1.3 enable | CWTU |
| 352 | {{0}} | Preset 1 authorization | 1 Bit | 1.3 enable | CWTU |
| 353 | {{0}} | Preset 2 authorization | 1 Bit | 1.3 enable | CWTU |
| 354 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 355 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 356 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 357 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 358 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 359 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 360 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 361 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 362 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 363 | {{0}} | Setpoint selection | 1 Byte | 20.102 HVAC mode | CWTU |
| 364 | {{0}} | Comfort | 1 Bit | 1.1 switch | CWTU |
| 365 | {{0}} | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 366 | {{0}} | Night setpoint | 1 Bit | 1.1 switch | CWTU |
| 367 | {{0}} | Frost/heat protection | 1 Bit | 1.1 switch | CWTU |
| 368 | {{0}} | Setpoint selection automatic control | 1 Byte | 20.102 HVAC mode | CWTU |
| 369 | {{0}} | Automatic control deactivation | 1 Bit | 1.3 enable | CWTU |
| 370 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 371 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 372 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CWTU |
| 373 | {{0}} | Priority | 1 Byte | 20.102 HVAC mode | CWTU |
| 374 | {{0}} | Windows contact | 1 Bit | 1.19 window/door | CWTU |
| 375 | {{0}} | Scene | 1 Byte | 18.1 scene control | CWTU |
| 376 | {{0}} | Status indication setpoint selection | 1 Byte | 20.102 HVAC mode | CRT |
| 377 | {{0}} | Automatic control deactivation status | 1 Bit | 1.3 enable | CRT |
| 378 | {{0}} | Heating/Cooling - status indication | 1 Bit | 1.100 cooling/heating | CRT |
| 379 | {{0}} | Status indication heating active | 1 Bit | 1.11 state | CRT |
| 380 | {{0}} | Status indication cooling active | 1 Bit | 1.11 state | CRT |
| 381 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CRT |
| 382 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 383 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 384 | {{0}} | ON/OFF - basic cooling | 1 Bit | 1.1 switch | CRT |
| 385 | {{0}} | Valve position in % - basic cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 386 | {{0}} | ON/OFF - additional heating | 1 Bit | 1.1 switch | CRT |
| 387 | {{0}} | Valve position in % - additional heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 388 | {{0}} | ON/OFF - additional cooling | 1 Bit | 1.1 switch | CRT |
| 389 | {{0}} | Valve position in % - additional cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 390 | {{0}} | Room temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 391 | {{0}} | Room temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 392 | {{0}} | Room temperature 3 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 393 | {{0}} | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 394 | {{0}} | Status indication room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 395 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CRT |
| 396 | {{0}} | Minimum room temperature | 1 Bit | 1.5 alarm | CRT |
| 397 | {{0}} | Maximum room temperature | 1 Bit | 1.5 alarm | CRT |
| 398 | {{0}} | Ventilation automatic/manual mode | 1 Bit | 1.1 switch | CWTU |
| 399 | {{0}} | Status ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 400 | {{0}} | Status ventilation step 1 | 1 Bit | 1.1 switch | CWTU |
| 401 | {{0}} | Status ventilation step 2 | 1 Bit | 1.1 switch | CWTU |
| 402 | {{0}} | Status ventilation step 3 | 1 Bit | 1.1 switch | CWTU |
| 403 | {{0}} | Status ventilation step 4 | 1 Bit | 1.1 switch | CWTU |
| 404 | {{0}} | Status ventilation step 5 | 1 Bit | 1.1 switch | CWTU |
| 405 | {{0}} | Status ventilation step 6 | 1 Bit | 1.1 switch | CWTU |
| 406 | {{0}} | Ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 407 | {{0}} | Ventilation step 1 | 1 Bit | 1.1 switch | CRT |
| 408 | {{0}} | Ventilation step 2 | 1 Bit | 1.1 switch | CRT |
| 409 | {{0}} | Ventilation step 3 | 1 Bit | 1.1 switch | CRT |
| 410 | {{0}} | Ventilation step 4 | 1 Bit | 1.1 switch | CRT |
| 411 | {{0}} | Ventilation step 5 | 1 Bit | 1.1 switch | CRT |
| 412 | {{0}} | Ventilation step 6 | 1 Bit | 1.1 switch | CRT |
| 413 | {{0}} | Comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 413 | {{0}} | Reference setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 414 | {{0}} | Standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 415 | {{0}} | Night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 416 | {{0}} | Frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 417 | {{0}} | Setpoints heating | 8 Bytes | | CWTU |
| 418 | {{0}} | Comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 419 | {{0}} | Standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 420 | {{0}} | Night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 421 | {{0}} | Heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 422 | {{0}} | Setpoints cooling | 8 Bytes | | CWTU |
| 423 | {{0}} | Setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 424 | {{0}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 425 | {{0}} | Status indication setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 426 | {{0}} | Status indication reference setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 427 | {{0}} | Status indication comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 428 | {{0}} | Status indication standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 429 | {{0}} | Status indication night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 430 | {{0}} | Status indication frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 431 | {{0}} | Status indication setpoints heating | 8 Bytes | | CRT |
| 432 | {{0}} | Status indication comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 433 | {{0}} | Status indication standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 434 | {{0}} | Status indication night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 435 | {{0}} | Status indication heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 436 | {{0}} | Status indication setpoints cooling | 8 Bytes | | CRT |
| 437 | {{0}} | Status current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 438 | {{0}} | Presence | 1 Bit | 1.1 switch | CWTU |
| 439 | {{0}} | Lock-up additional step | 1 Bit | 1.1 switch | CWTU |
| 440 | {{0}} | Heating deactivation | 1 Bit | 1.3 enable | CWTU |
| 441 | {{0}} | Cooling deactivation | 1 Bit | 1.3 enable | CWTU |
| 442 | {{0}} | Heating deactivation status | 1 Bit | 1.3 enable | CRT |
| 443 | {{0}} | Cooling deactivation status | 1 Bit | 1.3 enable | CRT |
| 444 | {{0}} | Thermostat deactivation | 1 Bit | 1.3 enable | CWTU |
| 445 | {{0}} | Status indication thermostat deactivation | 1 Bit | 1.3 enable | CRT |
| 446 | {{0}} | Timer | 1 Bit | 1.10 start/stop | CWTU |
| 447 | {{0}} | Timer duration | 3 Bytes | 10.1 time of day | CWTU |
| 448 | {{0}} | Timer | 1 Byte | 20.102 HVAC mode | CWTU |
| 449 | {{0}} | Preset 1 | 1 Bit | 1.3 enable | CWTU |
| 450 | {{0}} | Preset 2 | 1 Bit | 1.3 enable | CWTU |
| 451 | {{0}} | Preset 1 authorization | 1 Bit | 1.3 enable | CWTU |
| 452 | {{0}} | Preset 2 authorization | 1 Bit | 1.3 enable | CWTU |
| 453 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 454 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 455 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 456 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 457 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 458 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 459 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 460 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 461 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 462 | {{0}} | Setpoint selection | 1 Byte | 20.102 HVAC mode | CWTU |
| 463 | {{0}} | Comfort | 1 Bit | 1.1 switch | CWTU |
| 464 | {{0}} | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 465 | {{0}} | Night setpoint | 1 Bit | 1.1 switch | CWTU |
| 466 | {{0}} | Frost/heat protection | 1 Bit | 1.1 switch | CWTU |
| 467 | {{0}} | Setpoint selection automatic control | 1 Byte | 20.102 HVAC mode | CWTU |
| 468 | {{0}} | Automatic control deactivation | 1 Bit | 1.3 enable | CWTU |
| 469 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 470 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 471 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CWTU |
| 472 | {{0}} | Priority | 1 Byte | 20.102 HVAC mode | CWTU |
| 473 | {{0}} | Windows contact | 1 Bit | 1.19 window/door | CWTU |
| 474 | {{0}} | Scene | 1 Byte | 18.1 scene control | CWTU |
| 475 | {{0}} | Status indication setpoint selection | 1 Byte | 20.102 HVAC mode | CRT |
| 476 | {{0}} | Automatic control deactivation status | 1 Bit | 1.3 enable | CRT |
| 477 | {{0}} | Heating/Cooling - status indication | 1 Bit | 1.100 cooling/heating | CRT |
| 478 | {{0}} | Status indication heating active | 1 Bit | 1.11 state | CRT |
| 479 | {{0}} | Status indication cooling active | 1 Bit | 1.11 state | CRT |
| 480 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CRT |
| 481 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 482 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 483 | {{0}} | ON/OFF - basic cooling | 1 Bit | 1.1 switch | CRT |
| 484 | {{0}} | Valve position in % - basic cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 485 | {{0}} | ON/OFF - additional heating | 1 Bit | 1.1 switch | CRT |
| 486 | {{0}} | Valve position in % - additional heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 487 | {{0}} | ON/OFF - additional cooling | 1 Bit | 1.1 switch | CRT |
| 488 | {{0}} | Valve position in % - additional cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 489 | {{0}} | Room temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 490 | {{0}} | Room temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 491 | {{0}} | Room temperature 3 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 492 | {{0}} | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 493 | {{0}} | Status indication room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 494 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CRT |
| 495 | {{0}} | Minimum room temperature | 1 Bit | 1.5 alarm | CRT |
| 496 | {{0}} | Maximum room temperature | 1 Bit | 1.5 alarm | CRT |
| 497 | {{0}} | Ventilation automatic/manual mode | 1 Bit | 1.1 switch | CWTU |
| 498 | {{0}} | Status ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 499 | {{0}} | Status ventilation step 1 | 1 Bit | 1.1 switch | CWTU |
| 500 | {{0}} | Status ventilation step 2 | 1 Bit | 1.1 switch | CWTU |
| 501 | {{0}} | Status ventilation step 3 | 1 Bit | 1.1 switch | CWTU |
| 502 | {{0}} | Status ventilation step 4 | 1 Bit | 1.1 switch | CWTU |
| 503 | {{0}} | Status ventilation step 5 | 1 Bit | 1.1 switch | CWTU |
| 504 | {{0}} | Status ventilation step 6 | 1 Bit | 1.1 switch | CWTU |
| 505 | {{0}} | Ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 506 | {{0}} | Ventilation step 1 | 1 Bit | 1.1 switch | CRT |
| 507 | {{0}} | Ventilation step 2 | 1 Bit | 1.1 switch | CRT |
| 508 | {{0}} | Ventilation step 3 | 1 Bit | 1.1 switch | CRT |
| 509 | {{0}} | Ventilation step 4 | 1 Bit | 1.1 switch | CRT |
| 510 | {{0}} | Ventilation step 5 | 1 Bit | 1.1 switch | CRT |
| 511 | {{0}} | Ventilation step 6 | 1 Bit | 1.1 switch | CRT |
| 512 | {{0}} | Comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 512 | {{0}} | Reference setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 513 | {{0}} | Standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 514 | {{0}} | Night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 515 | {{0}} | Frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 516 | {{0}} | Setpoints heating | 8 Bytes | | CWTU |
| 517 | {{0}} | Comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 518 | {{0}} | Standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 519 | {{0}} | Night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 520 | {{0}} | Heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 521 | {{0}} | Setpoints cooling | 8 Bytes | | CWTU |
| 522 | {{0}} | Setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 523 | {{0}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 524 | {{0}} | Status indication setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 525 | {{0}} | Status indication reference setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 526 | {{0}} | Status indication comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 527 | {{0}} | Status indication standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 528 | {{0}} | Status indication night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 529 | {{0}} | Status indication frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 530 | {{0}} | Status indication setpoints heating | 8 Bytes | | CRT |
| 531 | {{0}} | Status indication comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 532 | {{0}} | Status indication standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 533 | {{0}} | Status indication night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 534 | {{0}} | Status indication heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 535 | {{0}} | Status indication setpoints cooling | 8 Bytes | | CRT |
| 536 | {{0}} | Status current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 537 | {{0}} | Presence | 1 Bit | 1.1 switch | CWTU |
| 538 | {{0}} | Lock-up additional step | 1 Bit | 1.1 switch | CWTU |
| 539 | {{0}} | Heating deactivation | 1 Bit | 1.3 enable | CWTU |
| 540 | {{0}} | Cooling deactivation | 1 Bit | 1.3 enable | CWTU |
| 541 | {{0}} | Heating deactivation status | 1 Bit | 1.3 enable | CRT |
| 542 | {{0}} | Cooling deactivation status | 1 Bit | 1.3 enable | CRT |
| 543 | {{0}} | Thermostat deactivation | 1 Bit | 1.3 enable | CWTU |
| 544 | {{0}} | Status indication thermostat deactivation | 1 Bit | 1.3 enable | CRT |
| 545 | {{0}} | Timer | 1 Bit | 1.10 start/stop | CWTU |
| 546 | {{0}} | Timer duration | 3 Bytes | 10.1 time of day | CWTU |
| 547 | {{0}} | Timer | 1 Byte | 20.102 HVAC mode | CWTU |
| 548 | {{0}} | Preset 1 | 1 Bit | 1.3 enable | CWTU |
| 549 | {{0}} | Preset 2 | 1 Bit | 1.3 enable | CWTU |
| 550 | {{0}} | Preset 1 authorization | 1 Bit | 1.3 enable | CWTU |
| 551 | {{0}} | Preset 2 authorization | 1 Bit | 1.3 enable | CWTU |
| 552 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 553 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 554 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 555 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 556 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 557 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 558 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 559 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 560 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 561 | {{0}} | Setpoint selection | 1 Byte | 20.102 HVAC mode | CWTU |
| 562 | {{0}} | Comfort | 1 Bit | 1.1 switch | CWTU |
| 563 | {{0}} | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 564 | {{0}} | Night setpoint | 1 Bit | 1.1 switch | CWTU |
| 565 | {{0}} | Frost/heat protection | 1 Bit | 1.1 switch | CWTU |
| 566 | {{0}} | Setpoint selection automatic control | 1 Byte | 20.102 HVAC mode | CWTU |
| 567 | {{0}} | Automatic control deactivation | 1 Bit | 1.3 enable | CWTU |
| 568 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 569 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 570 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CWTU |
| 571 | {{0}} | Priority | 1 Byte | 20.102 HVAC mode | CWTU |
| 572 | {{0}} | Windows contact | 1 Bit | 1.19 window/door | CWTU |
| 573 | {{0}} | Scene | 1 Byte | 18.1 scene control | CWTU |
| 574 | {{0}} | Status indication setpoint selection | 1 Byte | 20.102 HVAC mode | CRT |
| 575 | {{0}} | Automatic control deactivation status | 1 Bit | 1.3 enable | CRT |
| 576 | {{0}} | Heating/Cooling - status indication | 1 Bit | 1.100 cooling/heating | CRT |
| 577 | {{0}} | Status indication heating active | 1 Bit | 1.11 state | CRT |
| 578 | {{0}} | Status indication cooling active | 1 Bit | 1.11 state | CRT |
| 579 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CRT |
| 580 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 581 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 582 | {{0}} | ON/OFF - basic cooling | 1 Bit | 1.1 switch | CRT |
| 583 | {{0}} | Valve position in % - basic cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 584 | {{0}} | ON/OFF - additional heating | 1 Bit | 1.1 switch | CRT |
| 585 | {{0}} | Valve position in % - additional heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 586 | {{0}} | ON/OFF - additional cooling | 1 Bit | 1.1 switch | CRT |
| 587 | {{0}} | Valve position in % - additional cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 588 | {{0}} | Room temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 589 | {{0}} | Room temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 590 | {{0}} | Room temperature 3 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 591 | {{0}} | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 592 | {{0}} | Status indication room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 593 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CRT |
| 594 | {{0}} | Minimum room temperature | 1 Bit | 1.5 alarm | CRT |
| 595 | {{0}} | Maximum room temperature | 1 Bit | 1.5 alarm | CRT |
| 596 | {{0}} | Ventilation automatic/manual mode | 1 Bit | 1.1 switch | CWTU |
| 597 | {{0}} | Status ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 598 | {{0}} | Status ventilation step 1 | 1 Bit | 1.1 switch | CWTU |
| 599 | {{0}} | Status ventilation step 2 | 1 Bit | 1.1 switch | CWTU |
| 600 | {{0}} | Status ventilation step 3 | 1 Bit | 1.1 switch | CWTU |
| 601 | {{0}} | Status ventilation step 4 | 1 Bit | 1.1 switch | CWTU |
| 602 | {{0}} | Status ventilation step 5 | 1 Bit | 1.1 switch | CWTU |
| 603 | {{0}} | Status ventilation step 6 | 1 Bit | 1.1 switch | CWTU |
| 604 | {{0}} | Ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 605 | {{0}} | Ventilation step 1 | 1 Bit | 1.1 switch | CRT |
| 606 | {{0}} | Ventilation step 2 | 1 Bit | 1.1 switch | CRT |
| 607 | {{0}} | Ventilation step 3 | 1 Bit | 1.1 switch | CRT |
| 608 | {{0}} | Ventilation step 4 | 1 Bit | 1.1 switch | CRT |
| 609 | {{0}} | Ventilation step 5 | 1 Bit | 1.1 switch | CRT |
| 610 | {{0}} | Ventilation step 6 | 1 Bit | 1.1 switch | CRT |
| 611 | {{0}} | Comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 611 | {{0}} | Reference setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 612 | {{0}} | Standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 613 | {{0}} | Night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 614 | {{0}} | Frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 615 | {{0}} | Setpoints heating | 8 Bytes | | CWTU |
| 616 | {{0}} | Comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 617 | {{0}} | Standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 618 | {{0}} | Night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 619 | {{0}} | Heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 620 | {{0}} | Setpoints cooling | 8 Bytes | | CWTU |
| 621 | {{0}} | Setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 622 | {{0}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 623 | {{0}} | Status indication setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 624 | {{0}} | Status indication reference setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 625 | {{0}} | Status indication comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 626 | {{0}} | Status indication standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 627 | {{0}} | Status indication night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 628 | {{0}} | Status indication frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 629 | {{0}} | Status indication setpoints heating | 8 Bytes | | CRT |
| 630 | {{0}} | Status indication comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 631 | {{0}} | Status indication standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 632 | {{0}} | Status indication night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 633 | {{0}} | Status indication heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 634 | {{0}} | Status indication setpoints cooling | 8 Bytes | | CRT |
| 635 | {{0}} | Status current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 636 | {{0}} | Presence | 1 Bit | 1.1 switch | CWTU |
| 637 | {{0}} | Lock-up additional step | 1 Bit | 1.1 switch | CWTU |
| 638 | {{0}} | Heating deactivation | 1 Bit | 1.3 enable | CWTU |
| 639 | {{0}} | Cooling deactivation | 1 Bit | 1.3 enable | CWTU |
| 640 | {{0}} | Heating deactivation status | 1 Bit | 1.3 enable | CRT |
| 641 | {{0}} | Cooling deactivation status | 1 Bit | 1.3 enable | CRT |
| 642 | {{0}} | Thermostat deactivation | 1 Bit | 1.3 enable | CWTU |
| 643 | {{0}} | Status indication thermostat deactivation | 1 Bit | 1.3 enable | CRT |
| 644 | {{0}} | Timer | 1 Bit | 1.10 start/stop | CWTU |
| 645 | {{0}} | Timer duration | 3 Bytes | 10.1 time of day | CWTU |
| 646 | {{0}} | Timer | 1 Byte | 20.102 HVAC mode | CWTU |
| 647 | {{0}} | Preset 1 | 1 Bit | 1.3 enable | CWTU |
| 648 | {{0}} | Preset 2 | 1 Bit | 1.3 enable | CWTU |
| 649 | {{0}} | Preset 1 authorization | 1 Bit | 1.3 enable | CWTU |
| 650 | {{0}} | Preset 2 authorization | 1 Bit | 1.3 enable | CWTU |
| 651 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 652 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 653 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 654 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 655 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 656 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 657 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 658 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 659 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 660 | {{0}} | Setpoint selection | 1 Byte | 20.102 HVAC mode | CWTU |
| 661 | {{0}} | Comfort | 1 Bit | 1.1 switch | CWTU |
| 662 | {{0}} | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 663 | {{0}} | Night setpoint | 1 Bit | 1.1 switch | CWTU |
| 664 | {{0}} | Frost/heat protection | 1 Bit | 1.1 switch | CWTU |
| 665 | {{0}} | Setpoint selection automatic control | 1 Byte | 20.102 HVAC mode | CWTU |
| 666 | {{0}} | Automatic control deactivation | 1 Bit | 1.3 enable | CWTU |
| 667 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 668 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 669 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CWTU |
| 670 | {{0}} | Priority | 1 Byte | 20.102 HVAC mode | CWTU |
| 671 | {{0}} | Windows contact | 1 Bit | 1.19 window/door | CWTU |
| 672 | {{0}} | Scene | 1 Byte | 18.1 scene control | CWTU |
| 673 | {{0}} | Status indication setpoint selection | 1 Byte | 20.102 HVAC mode | CRT |
| 674 | {{0}} | Automatic control deactivation status | 1 Bit | 1.3 enable | CRT |
| 675 | {{0}} | Heating/Cooling - status indication | 1 Bit | 1.100 cooling/heating | CRT |
| 676 | {{0}} | Status indication heating active | 1 Bit | 1.11 state | CRT |
| 677 | {{0}} | Status indication cooling active | 1 Bit | 1.11 state | CRT |
| 678 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CRT |
| 679 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 680 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 681 | {{0}} | ON/OFF - basic cooling | 1 Bit | 1.1 switch | CRT |
| 682 | {{0}} | Valve position in % - basic cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 683 | {{0}} | ON/OFF - additional heating | 1 Bit | 1.1 switch | CRT |
| 684 | {{0}} | Valve position in % - additional heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 685 | {{0}} | ON/OFF - additional cooling | 1 Bit | 1.1 switch | CRT |
| 686 | {{0}} | Valve position in % - additional cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 687 | {{0}} | Room temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 688 | {{0}} | Room temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 689 | {{0}} | Room temperature 3 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 690 | {{0}} | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 691 | {{0}} | Status indication room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 692 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CRT |
| 693 | {{0}} | Minimum room temperature | 1 Bit | 1.5 alarm | CRT |
| 694 | {{0}} | Maximum room temperature | 1 Bit | 1.5 alarm | CRT |
| 695 | {{0}} | Ventilation automatic/manual mode | 1 Bit | 1.1 switch | CWTU |
| 696 | {{0}} | Status ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 697 | {{0}} | Status ventilation step 1 | 1 Bit | 1.1 switch | CWTU |
| 698 | {{0}} | Status ventilation step 2 | 1 Bit | 1.1 switch | CWTU |
| 699 | {{0}} | Status ventilation step 3 | 1 Bit | 1.1 switch | CWTU |
| 700 | {{0}} | Status ventilation step 4 | 1 Bit | 1.1 switch | CWTU |
| 701 | {{0}} | Status ventilation step 5 | 1 Bit | 1.1 switch | CWTU |
| 702 | {{0}} | Status ventilation step 6 | 1 Bit | 1.1 switch | CWTU |
| 703 | {{0}} | Ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 704 | {{0}} | Ventilation step 1 | 1 Bit | 1.1 switch | CRT |
| 705 | {{0}} | Ventilation step 2 | 1 Bit | 1.1 switch | CRT |
| 706 | {{0}} | Ventilation step 3 | 1 Bit | 1.1 switch | CRT |
| 707 | {{0}} | Ventilation step 4 | 1 Bit | 1.1 switch | CRT |
| 708 | {{0}} | Ventilation step 5 | 1 Bit | 1.1 switch | CRT |
| 709 | {{0}} | Ventilation step 6 | 1 Bit | 1.1 switch | CRT |
| 710 | {{0}} | Comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 710 | {{0}} | Reference setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 711 | {{0}} | Standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 712 | {{0}} | Night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 713 | {{0}} | Frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 714 | {{0}} | Setpoints heating | 8 Bytes | | CWTU |
| 715 | {{0}} | Comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 716 | {{0}} | Standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 717 | {{0}} | Night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 718 | {{0}} | Heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 719 | {{0}} | Setpoints cooling | 8 Bytes | | CWTU |
| 720 | {{0}} | Setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 721 | {{0}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 722 | {{0}} | Status indication setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 723 | {{0}} | Status indication reference setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 724 | {{0}} | Status indication comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 725 | {{0}} | Status indication standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 726 | {{0}} | Status indication night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 727 | {{0}} | Status indication frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 728 | {{0}} | Status indication setpoints heating | 8 Bytes | | CRT |
| 729 | {{0}} | Status indication comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 730 | {{0}} | Status indication standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 731 | {{0}} | Status indication night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 732 | {{0}} | Status indication heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 733 | {{0}} | Status indication setpoints cooling | 8 Bytes | | CRT |
| 734 | {{0}} | Status current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 735 | {{0}} | Presence | 1 Bit | 1.1 switch | CWTU |
| 736 | {{0}} | Lock-up additional step | 1 Bit | 1.1 switch | CWTU |
| 737 | {{0}} | Heating deactivation | 1 Bit | 1.3 enable | CWTU |
| 738 | {{0}} | Cooling deactivation | 1 Bit | 1.3 enable | CWTU |
| 739 | {{0}} | Heating deactivation status | 1 Bit | 1.3 enable | CRT |
| 740 | {{0}} | Cooling deactivation status | 1 Bit | 1.3 enable | CRT |
| 741 | {{0}} | Thermostat deactivation | 1 Bit | 1.3 enable | CWTU |
| 742 | {{0}} | Status indication thermostat deactivation | 1 Bit | 1.3 enable | CRT |
| 743 | {{0}} | Timer | 1 Bit | 1.10 start/stop | CWTU |
| 744 | {{0}} | Timer duration | 3 Bytes | 10.1 time of day | CWTU |
| 745 | {{0}} | Timer | 1 Byte | 20.102 HVAC mode | CWTU |
| 746 | {{0}} | Preset 1 | 1 Bit | 1.3 enable | CWTU |
| 747 | {{0}} | Preset 2 | 1 Bit | 1.3 enable | CWTU |
| 748 | {{0}} | Preset 1 authorization | 1 Bit | 1.3 enable | CWTU |
| 749 | {{0}} | Preset 2 authorization | 1 Bit | 1.3 enable | CWTU |
| 750 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 751 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 752 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 753 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 754 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 755 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 756 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 757 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 758 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 759 | {{0}} | Setpoint selection | 1 Byte | 20.102 HVAC mode | CWTU |
| 760 | {{0}} | Comfort | 1 Bit | 1.1 switch | CWTU |
| 761 | {{0}} | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 762 | {{0}} | Night setpoint | 1 Bit | 1.1 switch | CWTU |
| 763 | {{0}} | Frost/heat protection | 1 Bit | 1.1 switch | CWTU |
| 764 | {{0}} | Setpoint selection automatic control | 1 Byte | 20.102 HVAC mode | CWTU |
| 765 | {{0}} | Automatic control deactivation | 1 Bit | 1.3 enable | CWTU |
| 766 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 767 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 768 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CWTU |
| 769 | {{0}} | Priority | 1 Byte | 20.102 HVAC mode | CWTU |
| 770 | {{0}} | Windows contact | 1 Bit | 1.19 window/door | CWTU |
| 771 | {{0}} | Scene | 1 Byte | 18.1 scene control | CWTU |
| 772 | {{0}} | Status indication setpoint selection | 1 Byte | 20.102 HVAC mode | CRT |
| 773 | {{0}} | Automatic control deactivation status | 1 Bit | 1.3 enable | CRT |
| 774 | {{0}} | Heating/Cooling - status indication | 1 Bit | 1.100 cooling/heating | CRT |
| 775 | {{0}} | Status indication heating active | 1 Bit | 1.11 state | CRT |
| 776 | {{0}} | Status indication cooling active | 1 Bit | 1.11 state | CRT |
| 777 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CRT |
| 778 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 779 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 780 | {{0}} | ON/OFF - basic cooling | 1 Bit | 1.1 switch | CRT |
| 781 | {{0}} | Valve position in % - basic cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 782 | {{0}} | ON/OFF - additional heating | 1 Bit | 1.1 switch | CRT |
| 783 | {{0}} | Valve position in % - additional heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 784 | {{0}} | ON/OFF - additional cooling | 1 Bit | 1.1 switch | CRT |
| 785 | {{0}} | Valve position in % - additional cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 786 | {{0}} | Room temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 787 | {{0}} | Room temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 788 | {{0}} | Room temperature 3 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 789 | {{0}} | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 790 | {{0}} | Status indication room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 791 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CRT |
| 792 | {{0}} | Minimum room temperature | 1 Bit | 1.5 alarm | CRT |
| 793 | {{0}} | Maximum room temperature | 1 Bit | 1.5 alarm | CRT |
| 794 | {{0}} | Ventilation automatic/manual mode | 1 Bit | 1.1 switch | CWTU |
| 795 | {{0}} | Status ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 796 | {{0}} | Status ventilation step 1 | 1 Bit | 1.1 switch | CWTU |
| 797 | {{0}} | Status ventilation step 2 | 1 Bit | 1.1 switch | CWTU |
| 798 | {{0}} | Status ventilation step 3 | 1 Bit | 1.1 switch | CWTU |
| 799 | {{0}} | Status ventilation step 4 | 1 Bit | 1.1 switch | CWTU |
| 800 | {{0}} | Status ventilation step 5 | 1 Bit | 1.1 switch | CWTU |
| 801 | {{0}} | Status ventilation step 6 | 1 Bit | 1.1 switch | CWTU |
| 802 | {{0}} | Ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 803 | {{0}} | Ventilation step 1 | 1 Bit | 1.1 switch | CRT |
| 804 | {{0}} | Ventilation step 2 | 1 Bit | 1.1 switch | CRT |
| 805 | {{0}} | Ventilation step 3 | 1 Bit | 1.1 switch | CRT |
| 806 | {{0}} | Ventilation step 4 | 1 Bit | 1.1 switch | CRT |
| 807 | {{0}} | Ventilation step 5 | 1 Bit | 1.1 switch | CRT |
| 808 | {{0}} | Ventilation step 6 | 1 Bit | 1.1 switch | CRT |
| 809 | {{0}} | Comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 809 | {{0}} | Reference setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 810 | {{0}} | Standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 811 | {{0}} | Night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 812 | {{0}} | Frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 813 | {{0}} | Setpoints heating | 8 Bytes | | CWTU |
| 814 | {{0}} | Comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 815 | {{0}} | Standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 816 | {{0}} | Night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 817 | {{0}} | Heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 818 | {{0}} | Setpoints cooling | 8 Bytes | | CWTU |
| 819 | {{0}} | Setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 820 | {{0}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 821 | {{0}} | Status indication setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 822 | {{0}} | Status indication reference setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 823 | {{0}} | Status indication comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 824 | {{0}} | Status indication standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 825 | {{0}} | Status indication night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 826 | {{0}} | Status indication frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 827 | {{0}} | Status indication setpoints heating | 8 Bytes | | CRT |
| 828 | {{0}} | Status indication comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 829 | {{0}} | Status indication standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 830 | {{0}} | Status indication night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 831 | {{0}} | Status indication heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 832 | {{0}} | Status indication setpoints cooling | 8 Bytes | | CRT |
| 833 | {{0}} | Status current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 834 | {{0}} | Presence | 1 Bit | 1.1 switch | CWTU |
| 835 | {{0}} | Lock-up additional step | 1 Bit | 1.1 switch | CWTU |
| 836 | {{0}} | Heating deactivation | 1 Bit | 1.3 enable | CWTU |
| 837 | {{0}} | Cooling deactivation | 1 Bit | 1.3 enable | CWTU |
| 838 | {{0}} | Heating deactivation status | 1 Bit | 1.3 enable | CRT |
| 839 | {{0}} | Cooling deactivation status | 1 Bit | 1.3 enable | CRT |
| 840 | {{0}} | Thermostat deactivation | 1 Bit | 1.3 enable | CWTU |
| 841 | {{0}} | Status indication thermostat deactivation | 1 Bit | 1.3 enable | CRT |
| 842 | {{0}} | Timer | 1 Bit | 1.10 start/stop | CWTU |
| 843 | {{0}} | Timer duration | 3 Bytes | 10.1 time of day | CWTU |
| 844 | {{0}} | Timer | 1 Byte | 20.102 HVAC mode | CWTU |
| 845 | {{0}} | Preset 1 | 1 Bit | 1.3 enable | CWTU |
| 846 | {{0}} | Preset 2 | 1 Bit | 1.3 enable | CWTU |
| 847 | {{0}} | Preset 1 authorization | 1 Bit | 1.3 enable | CWTU |
| 848 | {{0}} | Preset 2 authorization | 1 Bit | 1.3 enable | CWTU |
| 849 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 850 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 851 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 852 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 853 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 854 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 855 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 856 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 857 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 858 | {{0}} | Setpoint selection | 1 Byte | 20.102 HVAC mode | CWTU |
| 859 | {{0}} | Comfort | 1 Bit | 1.1 switch | CWTU |
| 860 | {{0}} | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 861 | {{0}} | Night setpoint | 1 Bit | 1.1 switch | CWTU |
| 862 | {{0}} | Frost/heat protection | 1 Bit | 1.1 switch | CWTU |
| 863 | {{0}} | Setpoint selection automatic control | 1 Byte | 20.102 HVAC mode | CWTU |
| 864 | {{0}} | Automatic control deactivation | 1 Bit | 1.3 enable | CWTU |
| 865 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 866 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 867 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CWTU |
| 868 | {{0}} | Priority | 1 Byte | 20.102 HVAC mode | CWTU |
| 869 | {{0}} | Windows contact | 1 Bit | 1.19 window/door | CWTU |
| 870 | {{0}} | Scene | 1 Byte | 18.1 scene control | CWTU |
| 871 | {{0}} | Status indication setpoint selection | 1 Byte | 20.102 HVAC mode | CRT |
| 872 | {{0}} | Automatic control deactivation status | 1 Bit | 1.3 enable | CRT |
| 873 | {{0}} | Heating/Cooling - status indication | 1 Bit | 1.100 cooling/heating | CRT |
| 874 | {{0}} | Status indication heating active | 1 Bit | 1.11 state | CRT |
| 875 | {{0}} | Status indication cooling active | 1 Bit | 1.11 state | CRT |
| 876 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CRT |
| 877 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 878 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 879 | {{0}} | ON/OFF - basic cooling | 1 Bit | 1.1 switch | CRT |
| 880 | {{0}} | Valve position in % - basic cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 881 | {{0}} | ON/OFF - additional heating | 1 Bit | 1.1 switch | CRT |
| 882 | {{0}} | Valve position in % - additional heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 883 | {{0}} | ON/OFF - additional cooling | 1 Bit | 1.1 switch | CRT |
| 884 | {{0}} | Valve position in % - additional cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 885 | {{0}} | Room temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 886 | {{0}} | Room temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 887 | {{0}} | Room temperature 3 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 888 | {{0}} | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 889 | {{0}} | Status indication room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 890 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CRT |
| 891 | {{0}} | Minimum room temperature | 1 Bit | 1.5 alarm | CRT |
| 892 | {{0}} | Maximum room temperature | 1 Bit | 1.5 alarm | CRT |
| 893 | {{0}} | Ventilation automatic/manual mode | 1 Bit | 1.1 switch | CWTU |
| 894 | {{0}} | Status ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 895 | {{0}} | Status ventilation step 1 | 1 Bit | 1.1 switch | CWTU |
| 896 | {{0}} | Status ventilation step 2 | 1 Bit | 1.1 switch | CWTU |
| 897 | {{0}} | Status ventilation step 3 | 1 Bit | 1.1 switch | CWTU |
| 898 | {{0}} | Status ventilation step 4 | 1 Bit | 1.1 switch | CWTU |
| 899 | {{0}} | Status ventilation step 5 | 1 Bit | 1.1 switch | CWTU |
| 900 | {{0}} | Status ventilation step 6 | 1 Bit | 1.1 switch | CWTU |
| 901 | {{0}} | Ventilation step 1-6 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 902 | {{0}} | Ventilation step 1 | 1 Bit | 1.1 switch | CRT |
| 903 | {{0}} | Ventilation step 2 | 1 Bit | 1.1 switch | CRT |
| 904 | {{0}} | Ventilation step 3 | 1 Bit | 1.1 switch | CRT |
| 905 | {{0}} | Ventilation step 4 | 1 Bit | 1.1 switch | CRT |
| 906 | {{0}} | Ventilation step 5 | 1 Bit | 1.1 switch | CRT |
| 907 | {{0}} | Ventilation step 6 | 1 Bit | 1.1 switch | CRT |
| 908 | {{0}} | Comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 908 | {{0}} | Reference setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 909 | {{0}} | Standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 910 | {{0}} | Night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 911 | {{0}} | Frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 912 | {{0}} | Setpoints heating | 8 Bytes | | CWTU |
| 913 | {{0}} | Comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 914 | {{0}} | Standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 915 | {{0}} | Night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 916 | {{0}} | Heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 917 | {{0}} | Setpoints cooling | 8 Bytes | | CWTU |
| 918 | {{0}} | Setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 919 | {{0}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 920 | {{0}} | Status indication setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 921 | {{0}} | Status indication reference setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 922 | {{0}} | Status indication comfort setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 923 | {{0}} | Status indication standby setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 924 | {{0}} | Status indication night setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 925 | {{0}} | Status indication frost protection setpoint heating | 2 Bytes | 9.1 temperature (°C) | CRT |
| 926 | {{0}} | Status indication setpoints heating | 8 Bytes | | CRT |
| 927 | {{0}} | Status indication comfort setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 928 | {{0}} | Status indication standby setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 929 | {{0}} | Status indication night setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 930 | {{0}} | Status indication heat protection setpoint cooling | 2 Bytes | 9.1 temperature (°C) | CRT |
| 931 | {{0}} | Status indication setpoints cooling | 8 Bytes | | CRT |
| 932 | {{0}} | Status current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 933 | {{0}} | Presence | 1 Bit | 1.1 switch | CWTU |
| 934 | {{0}} | Lock-up additional step | 1 Bit | 1.1 switch | CWTU |
| 935 | {{0}} | Heating deactivation | 1 Bit | 1.3 enable | CWTU |
| 936 | {{0}} | Cooling deactivation | 1 Bit | 1.3 enable | CWTU |
| 937 | {{0}} | Heating deactivation status | 1 Bit | 1.3 enable | CRT |
| 938 | {{0}} | Cooling deactivation status | 1 Bit | 1.3 enable | CRT |
| 939 | {{0}} | Thermostat deactivation | 1 Bit | 1.3 enable | CWTU |
| 940 | {{0}} | Status indication thermostat deactivation | 1 Bit | 1.3 enable | CRT |
| 941 | {{0}} | Timer | 1 Bit | 1.10 start/stop | CWTU |
| 942 | {{0}} | Timer duration | 3 Bytes | 10.1 time of day | CWTU |
| 943 | {{0}} | Timer | 1 Byte | 20.102 HVAC mode | CWTU |
| 944 | {{0}} | Preset 1 | 1 Bit | 1.3 enable | CWTU |
| 945 | {{0}} | Preset 2 | 1 Bit | 1.3 enable | CWTU |
| 946 | {{0}} | Preset 1 authorization | 1 Bit | 1.3 enable | CWTU |
| 947 | {{0}} | Preset 2 authorization | 1 Bit | 1.3 enable | CWTU |
| 948 | {{0}} | Lock-up 1 | 1 Bit | 1.3 enable | CWTU |
| 949 | {{0}} | Lock-up 2 | 1 Bit | 1.3 enable | CWTU |
| 950 | {{0}} | Status indication lock-up | 1 Bit | 1.3 enable | CRT |
| 951 | {{0}} | Valve protection date | 3 Bytes | 11.1 date | CWTU |
| 952 | {{0}} | Valve protection time | 3 Bytes | 10.1 time of day | CWTU |
| 953 | {{0}} | Valve protection date and time | 8 Bytes | 19.1 date time | CWTU |
| 954 | {{0}} | Valve protection duration | 2 Bytes | 7.6 time (min) | CWTU |
| 955 | {{0}} | Valve protection periodicity | 2 Bytes | 7.7 time (h) | CWTU |
| 956 | {{0}} | Valve protection start/stop | 1 Bit | 1.10 start/stop | CWTU |
| 957 | {{0}} | Setpoint selection | 1 Byte | 20.102 HVAC mode | CWTU |
| 958 | {{0}} | Comfort | 1 Bit | 1.1 switch | CWTU |
| 959 | {{0}} | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 960 | {{0}} | Night setpoint | 1 Bit | 1.1 switch | CWTU |
| 961 | {{0}} | Frost/heat protection | 1 Bit | 1.1 switch | CWTU |
| 962 | {{0}} | Setpoint selection automatic control | 1 Byte | 20.102 HVAC mode | CWTU |
| 963 | {{0}} | Automatic control deactivation | 1 Bit | 1.3 enable | CWTU |
| 964 | {{0}} | Heating/Cooling - changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 965 | {{0}} | Priority | 2 Bit | 2.2 boolean control | CWTU |
| 966 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CWTU |
| 967 | {{0}} | Priority | 1 Byte | 20.102 HVAC mode | CWTU |
| 968 | {{0}} | Windows contact | 1 Bit | 1.19 window/door | CWTU |
| 969 | {{0}} | Scene | 1 Byte | 18.1 scene control | CWTU |
| 970 | {{0}} | Status indication setpoint selection | 1 Byte | 20.102 HVAC mode | CRT |
| 971 | {{0}} | Automatic control deactivation status | 1 Bit | 1.3 enable | CRT |
| 972 | {{0}} | Heating/Cooling - status indication | 1 Bit | 1.100 cooling/heating | CRT |
| 973 | {{0}} | Status indication heating active | 1 Bit | 1.11 state | CRT |
| 974 | {{0}} | Status indication cooling active | 1 Bit | 1.11 state | CRT |
| 975 | {{0}} | Status indication priority | 1 Bit | 1.11 state | CRT |
| 976 | {{0}} | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 977 | {{0}} | Valve position in % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 978 | {{0}} | ON/OFF - basic cooling | 1 Bit | 1.1 switch | CRT |
| 979 | {{0}} | Valve position in % - basic cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 980 | {{0}} | ON/OFF - additional heating | 1 Bit | 1.1 switch | CRT |
| 981 | {{0}} | Valve position in % - additional heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 982 | {{0}} | ON/OFF - additional cooling | 1 Bit | 1.1 switch | CRT |
| 983 | {{0}} | Valve position in % - additional cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 984 | {{0}} | Room temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 985 | {{0}} | Room temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 986 | {{0}} | Room temperature 3 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 987 | {{0}} | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 988 | {{0}} | Status indication room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 989 | {{0}} | Room temperature failure | 1 Bit | 1.5 alarm | CRT |
| 990 | {{0}} | Minimum room temperature | 1 Bit | 1.5 alarm | CRT |
| 991 | {{0}} | Maximum room temperature | 1 Bit | 1.5 alarm | CRT |
| 992 | {{0}} | Ventilation automatic/manual mode | 1 Bit | 1.1 switch | CWTU |