| 0 | Button 1 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 0 | Button 1 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CT |
| 0 | Button 1 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CT |
| 0 | Button 1 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 0 | Button 1 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 0 | Button 1 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 0 | Button 1 | Step Count Scene | 1 Byte | 18.1 scene control | CT |
| 0 | Button 1 | Switching | 1 Bit | 1.1 switch | CT |
| 0 | Button 1 | Up Down | 1 Bit | 1.8 up/down | CT |
| 0 | Button 1 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 0 | Button 1 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 0 | Button 1 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 0 | Button 1 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 0 | Button 1 | Value 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 0 | Button 1 | Scene | 1 Byte | 18.1 scene control | CT |
| 0 | Button 1 | Toggle | 1 Bit | 1.1 switch | CT |
| 0 | Button 1 | Short Press Switching | 1 Bit | 1.1 switch | CT |
| 0 | Button 1 | Short Press Toggle | 1 Bit | 1.1 switch | CT |
| 0 | Button 1 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 0 | Button 1 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 0 | Button 1 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 0 | Button 1 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 0 | Button 1 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 0 | Button 1 | Long Press Status | 2 Bytes | 7.1 pulses | CR |
| 1 | Button 1 | Dimming | 4 Bit | 3.7 dimming control | CT |
| 1 | Button 1 | Stop Slat Angle | 1 Bit | 1.1 switch | CT |
| 1 | Button 1 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 1 | Button 1 | Long Press Switching | 1 Bit | 1.1 switch | CT |
| 1 | Button 1 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 1 | Button 1 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 1 | Button 1 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 1 | Button 1 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 1 | Button 1 | Long Press Toggle | 1 Bit | 1.1 switch | CT |
| 2 | Button 1 | Status | 1 Bit | 1.1 switch | CR |
| 2 | Button 1 | Short Press Status | 1 Bit | 1.11 state | CR |
| 3 | Button 1 | Long Press Status | 1 Bit | 1.1 switch | CR |
| 4 | Button 1 | Locking | 1 Bit | 1.3 enable | CWU |
| 5 | Button 2 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 5 | Button 2 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CT |
| 5 | Button 2 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CT |
| 5 | Button 2 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 5 | Button 2 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 5 | Button 2 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 5 | Button 2 | Step Count Scene | 1 Byte | 18.1 scene control | CT |
| 5 | Button 2 | Switching | 1 Bit | 1.1 switch | CT |
| 5 | Button 2 | Up Down | 1 Bit | 1.8 up/down | CT |
| 5 | Button 2 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 5 | Button 2 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 5 | Button 2 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 5 | Button 2 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 5 | Button 2 | Value 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 5 | Button 2 | Scene | 1 Byte | 18.1 scene control | CT |
| 5 | Button 2 | Toggle | 1 Bit | 1.1 switch | CT |
| 5 | Button 2 | Short Press Switching | 1 Bit | 1.1 switch | CT |
| 5 | Button 2 | Short Press Toggle | 1 Bit | 1.1 switch | CT |
| 5 | Button 2 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 5 | Button 2 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 5 | Button 2 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 5 | Button 2 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 5 | Button 2 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 6 | Button 2 | Long Press Switching | 1 Bit | 1.1 switch | CT |
| 6 | Button 2 | Dimming | 4 Bit | 3.7 dimming control | CT |
| 6 | Button 2 | Stop Slat Angle | 1 Bit | 1.1 switch | CT |
| 6 | Button 2 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 6 | Button 2 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 6 | Button 2 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 6 | Button 2 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 6 | Button 2 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 6 | Button 2 | Long Press Toggle | 1 Bit | 1.1 switch | CT |
| 7 | Button 2 | Status | 1 Bit | 1.1 switch | CR |
| 7 | Button 2 | Short Press Status | 1 Bit | 1.11 state | CR |
| 8 | Button 2 | Long Press Status | 1 Bit | 1.1 switch | CR |
| 9 | Button 2 | Locking | 1 Bit | 1.3 enable | CWU |
| 10 | Button 3 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 10 | Button 3 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CT |
| 10 | Button 3 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CT |
| 10 | Button 3 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 10 | Button 3 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 10 | Button 3 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 10 | Button 3 | Step Count Scene | 1 Byte | 18.1 scene control | CT |
| 10 | Button 3 | Switching | 1 Bit | 1.1 switch | CT |
| 10 | Button 3 | Up Down | 1 Bit | 1.8 up/down | CT |
| 10 | Button 3 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 10 | Button 3 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 10 | Button 3 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 10 | Button 3 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 10 | Button 3 | Value 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 10 | Button 3 | Scene | 1 Byte | 18.1 scene control | CT |
| 10 | Button 3 | Toggle | 1 Bit | 1.1 switch | CT |
| 10 | Button 3 | Short Press Switching | 1 Bit | 1.1 switch | CT |
| 10 | Button 3 | Short Press Toggle | 1 Bit | 1.1 switch | CT |
| 10 | Button 3 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 10 | Button 3 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 10 | Button 3 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 10 | Button 3 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 10 | Button 3 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 11 | Button 3 | Long Press Switching | 1 Bit | 1.1 switch | CT |
| 11 | Button 3 | Dimming | 4 Bit | 3.7 dimming control | CT |
| 11 | Button 3 | Stop Slat Angle | 1 Bit | 1.1 switch | CT |
| 11 | Button 3 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 11 | Button 3 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 11 | Button 3 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 11 | Button 3 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 11 | Button 3 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 11 | Button 3 | Long Press Toggle | 1 Bit | 1.1 switch | CT |
| 12 | Button 3 | Status | 1 Bit | 1.1 switch | CR |
| 12 | Button 3 | Short Press Status | 1 Bit | 1.11 state | CR |
| 13 | Button 3 | Long Press Status | 1 Bit | 1.1 switch | CR |
| 14 | Button 3 | Locking | 1 Bit | 1.3 enable | CWU |
| 15 | Button 4 | Switching | 1 Bit | 1.1 switch | CT |
| 15 | Button 4 | Up Down | 1 Bit | 1.8 up/down | CT |
| 15 | Button 4 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 15 | Button 4 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 15 | Button 4 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 15 | Button 4 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 15 | Button 4 | Value 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 15 | Button 4 | Scene | 1 Byte | 18.1 scene control | CT |
| 15 | Button 4 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 15 | Button 4 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 15 | Button 4 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 15 | Button 4 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 15 | Button 4 | Step Count Scene | 1 Byte | 18.1 scene control | CT |
| 15 | Button 4 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CT |
| 15 | Button 4 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CT |
| 15 | Button 4 | Toggle | 1 Bit | 1.1 switch | CT |
| 15 | Button 4 | Short Press Switching | 1 Bit | 1.1 switch | CT |
| 15 | Button 4 | Short Press Toggle | 1 Bit | 1.1 switch | CT |
| 15 | Button 4 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 15 | Button 4 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 15 | Button 4 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 15 | Button 4 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 15 | Button 4 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 16 | Button 4 | Long Press Switching | 1 Bit | 1.1 switch | CT |
| 16 | Button 4 | Dimming | 4 Bit | 3.7 dimming control | CT |
| 16 | Button 4 | Stop Slat Angle | 1 Bit | 1.1 switch | CT |
| 16 | Button 4 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 16 | Button 4 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 16 | Button 4 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 16 | Button 4 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 16 | Button 4 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 16 | Button 4 | Long Press Toggle | 1 Bit | 1.1 switch | CT |
| 17 | Button 4 | Status | 1 Bit | 1.1 switch | CR |
| 17 | Button 4 | Short Press Status | 1 Bit | 1.11 state | CR |
| 18 | Button 4 | Long Press Status | 1 Bit | 1.1 switch | CR |
| 19 | Button 4 | Locking | 1 Bit | 1.3 enable | CWU |
| 20 | Button 5 | Switching | 1 Bit | 1.1 switch | CT |
| 20 | Button 5 | Up Down | 1 Bit | 1.8 up/down | CT |
| 20 | Button 5 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 20 | Button 5 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 20 | Button 5 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 20 | Button 5 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 20 | Button 5 | Value 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 20 | Button 5 | Scene | 1 Byte | 18.1 scene control | CT |
| 20 | Button 5 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 20 | Button 5 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 20 | Button 5 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 20 | Button 5 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 20 | Button 5 | Step Count Scene | 1 Byte | 18.1 scene control | CT |
| 20 | Button 5 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CT |
| 20 | Button 5 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CT |
| 20 | Button 5 | Toggle | 1 Bit | 1.1 switch | CT |
| 20 | Button 5 | Short Press Switching | 1 Bit | 1.1 switch | CT |
| 20 | Button 5 | Short Press Toggle | 1 Bit | 1.1 switch | CT |
| 20 | Button 5 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 20 | Button 5 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 20 | Button 5 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 20 | Button 5 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 20 | Button 5 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 21 | Button 5 | Long Press Switching | 1 Bit | 1.1 switch | CT |
| 21 | Button 5 | Dimming | 4 Bit | 3.7 dimming control | CT |
| 21 | Button 5 | Stop Slat Angle | 1 Bit | 1.1 switch | CT |
| 21 | Button 5 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 21 | Button 5 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 21 | Button 5 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 21 | Button 5 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 21 | Button 5 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 21 | Button 5 | Long Press Toggle | 1 Bit | 1.1 switch | CT |
| 22 | Button 5 | Status | 1 Bit | 1.1 switch | CR |
| 22 | Button 5 | Short Press Status | 1 Bit | 1.11 state | CR |
| 23 | Button 5 | Long Press Status | 1 Bit | 1.1 switch | CR |
| 24 | Button 5 | Locking | 1 Bit | 1.3 enable | CWU |
| 25 | Button 6 | Switching | 1 Bit | 1.1 switch | CT |
| 25 | Button 6 | Up Down | 1 Bit | 1.8 up/down | CT |
| 25 | Button 6 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 25 | Button 6 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 25 | Button 6 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 25 | Button 6 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 25 | Button 6 | Value 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 25 | Button 6 | Scene | 1 Byte | 18.1 scene control | CT |
| 25 | Button 6 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 25 | Button 6 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 25 | Button 6 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 25 | Button 6 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 25 | Button 6 | Step Count Scene | 1 Byte | 18.1 scene control | CT |
| 25 | Button 6 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CT |
| 25 | Button 6 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CT |
| 25 | Button 6 | Toggle | 1 Bit | 1.1 switch | CT |
| 25 | Button 6 | Short Press Switching | 1 Bit | 1.1 switch | CT |
| 25 | Button 6 | Short Press Toggle | 1 Bit | 1.1 switch | CT |
| 25 | Button 6 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 25 | Button 6 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 25 | Button 6 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 25 | Button 6 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 25 | Button 6 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 26 | Button 6 | Long Press Switching | 1 Bit | 1.1 switch | CT |
| 26 | Button 6 | Dimming | 4 Bit | 3.7 dimming control | CT |
| 26 | Button 6 | Stop Slat Angle | 1 Bit | 1.1 switch | CT |
| 26 | Button 6 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 26 | Button 6 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 26 | Button 6 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 26 | Button 6 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 26 | Button 6 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 26 | Button 6 | Long Press Toggle | 1 Bit | 1.1 switch | CT |
| 27 | Button 6 | Status | 1 Bit | 1.1 switch | CR |
| 27 | Button 6 | Short Press Status | 1 Bit | 1.11 state | CR |
| 28 | Button 6 | Long Press Status | 1 Bit | 1.1 switch | CR |
| 29 | Button 6 | Locking | 1 Bit | 1.3 enable | CWU |
| 30 | Button 7 | Switching | 1 Bit | 1.1 switch | CT |
| 30 | Button 7 | Up Down | 1 Bit | 1.8 up/down | CT |
| 30 | Button 7 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 30 | Button 7 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 30 | Button 7 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 30 | Button 7 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 30 | Button 7 | Value 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 30 | Button 7 | Scene | 1 Byte | 18.1 scene control | CT |
| 30 | Button 7 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 30 | Button 7 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 30 | Button 7 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 30 | Button 7 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 30 | Button 7 | Step Count Scene | 1 Byte | 18.1 scene control | CT |
| 30 | Button 7 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CT |
| 30 | Button 7 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CT |
| 30 | Button 7 | Toggle | 1 Bit | 1.1 switch | CT |
| 30 | Button 7 | Short Press Switching | 1 Bit | 1.1 switch | CT |
| 30 | Button 7 | Short Press Toggle | 1 Bit | 1.1 switch | CT |
| 30 | Button 7 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 30 | Button 7 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 30 | Button 7 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 30 | Button 7 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 30 | Button 7 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 31 | Button 7 | Dimming | 4 Bit | 3.7 dimming control | CT |
| 31 | Button 7 | Stop Slat Angle | 1 Bit | 1.1 switch | CT |
| 31 | Button 7 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 31 | Button 7 | Long Press Switching | 1 Bit | 1.1 switch | CT |
| 31 | Button 7 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 31 | Button 7 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 31 | Button 7 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 31 | Button 7 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 31 | Button 7 | Long Press Toggle | 1 Bit | 1.1 switch | CT |
| 32 | Button 7 | Status | 1 Bit | 1.1 switch | CR |
| 32 | Button 7 | Short Press Status | 1 Bit | 1.11 state | CR |
| 33 | Button 7 | Long Press Status | 1 Bit | 1.1 switch | CR |
| 34 | Button 7 | Locking | 1 Bit | 1.3 enable | CWU |
| 35 | Button 8 | Switching | 1 Bit | 1.1 switch | CT |
| 35 | Button 8 | Up Down | 1 Bit | 1.8 up/down | CT |
| 35 | Button 8 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 35 | Button 8 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 35 | Button 8 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 35 | Button 8 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 35 | Button 8 | Value 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 35 | Button 8 | Scene | 1 Byte | 18.1 scene control | CT |
| 35 | Button 8 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 35 | Button 8 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 35 | Button 8 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 35 | Button 8 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 35 | Button 8 | Step Count Scene | 1 Byte | 18.1 scene control | CT |
| 35 | Button 8 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CT |
| 35 | Button 8 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CT |
| 35 | Button 8 | Toggle | 1 Bit | 1.1 switch | CT |
| 35 | Button 8 | Short Press Switching | 1 Bit | 1.1 switch | CT |
| 35 | Button 8 | Short Press Toggle | 1 Bit | 1.1 switch | CT |
| 35 | Button 8 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 35 | Button 8 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 35 | Button 8 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 35 | Button 8 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 35 | Button 8 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 36 | Button 8 | Long Press Switching | 1 Bit | 1.1 switch | CT |
| 36 | Button 8 | Dimming | 4 Bit | 3.7 dimming control | CT |
| 36 | Button 8 | Stop Slat Angle | 1 Bit | 1.1 switch | CT |
| 36 | Button 8 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 36 | Button 8 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 36 | Button 8 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 36 | Button 8 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 36 | Button 8 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 36 | Button 8 | Long Press Toggle | 1 Bit | 1.1 switch | CT |
| 37 | Button 8 | Status | 1 Bit | 1.1 switch | CR |
| 37 | Button 8 | Short Press Status | 1 Bit | 1.11 state | CR |
| 38 | Button 8 | Long Press Status | 1 Bit | 1.1 switch | CR |
| 39 | Button 8 | Locking | 1 Bit | 1.3 enable | CWU |
| 40 | Internal RTC | [AC] On Off Heating | 1 Bit | 1.1 switch | CT |
| 41 | Internal RTC | [AC] On Off Heating Status | 1 Bit | 1.11 state | CWU |
| 42 | Internal RTC | Threshold Low | 1 Bit | 1.2 boolean | CRT |
| 43 | Internal RTC | Threshold High | 1 Bit | 1.2 boolean | CRT |
| 44 | Internal RTC | Heating - Cooling Mode Change | 1 Bit | 1.100 cooling/heating | CT |
| 44 | Internal RTC | HVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CT |
| 45 | Internal RTC | Heating - Cooling Mode Status | 1 Bit | 1.100 cooling/heating | CRWU |
| 45 | Internal RTC | HVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CRWU |
| 46 | Internal RTC | Command Value For Heating Bit | 1 Bit | 1.1 switch | CT |
| 47 | Internal RTC | Command Value For Heating Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 48 | Internal RTC | Command Value For Cooling Bit | 1 Bit | 1.1 switch | CT |
| 49 | Internal RTC | Command Value For Cooling Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 50 | Internal RTC | Command Value For Heating-Cooling Bit | 1 Bit | 1.1 switch | CT |
| 51 | Internal RTC | Command Value For Heating-Cooling Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 52 | Internal RTC | Control Of Additional Heating Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 52 | Internal RTC | Control Of Additional Heating Bit | 1 Bit | 1.1 switch | CT |
| 53 | Internal RTC | Control Of Additional Cooling Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 53 | Internal RTC | Control Of Additional Cooling Bit | 1 Bit | 1.1 switch | CT |
| 54 | Internal RTC | Fan Automatic - Manual | 1 Bit | 1.2 boolean | CT |
| 55 | Internal RTC | Fan Automatic - Manual Status | 1 Bit | 1.2 boolean | CRWU |
| 56 | Internal RTC | Control Fan Level 1 | 1 Bit | 1.3 enable | CT |
| 57 | Internal RTC | Control Fan Level 2 | 1 Bit | 1.3 enable | CT |
| 58 | Internal RTC | Control Fan Level 3 | 1 Bit | 1.3 enable | CT |
| 59 | Internal RTC | Status Fan Level 1 | 1 Bit | 1.11 state | CRWU |
| 60 | Internal RTC | Status Fan Level 2 | 1 Bit | 1.11 state | CRWU |
| 61 | Internal RTC | Status Fan Level 3 | 1 Bit | 1.11 state | CRWU |
| 62 | Internal RTC | Fan Controller Stage | 1 Byte | 5.100 fan stage (0..255) | CT |
| 62 | Internal RTC | Fan Controller Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 63 | Internal RTC | Fan Controller Stage Status | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 63 | Internal RTC | Fan Controller Percentage Status | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 64 | Internal RTC | [RM] On Off | 1 Bit | 1.1 switch | CWU |
| 65 | Internal RTC | [RM] Status | 1 Bit | 1.11 state | CRT |
| 66 | Internal RTC | [RM] Setpoint + / - Control | 1 Bit | 1.7 step | CWU |
| 67 | Internal RTC | [RM] Actual Internal Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 67 | Internal RTC | [RM] Actual Internal Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRT |
| 68 | Internal RTC | [RM] Actual Setpoint Temperature Control °C | 2 Bytes | 9.1 temperature (°C) | CWU |
| 68 | Internal RTC | [RM] Actual Setpoint Temperature Control °F | 2 Bytes | 9.27 temperature (°F) | CWU |
| 69 | Internal RTC | [RM] Actual Setpoint Temperature Status °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 69 | Internal RTC | [RM] Actual Setpoint Temperature Status °F | 2 Bytes | 9.27 temperature (°F) | CRT |
| 70 | Internal RTC | [RM] HVAC Mode Change | 1 Byte | 20.102 HVAC mode | CWU |
| 71 | Internal RTC | [RM] HVAC Mode Status | 1 Byte | 20.102 HVAC mode | CRT |
| 72 | Internal RTC | [RM] Reset Manual Setpoint Operation | 1 Bit | 1.15 reset | CWU |
| 73 | Internal RTC | [RM] Disable Additional Heating | 1 Bit | 1.3 enable | CWU |
| 74 | Internal RTC | [RM] Disable Additional Cooling | 1 Bit | 1.3 enable | CWU |
| 75 | Internal RTC | [RM] Fan Automatic Manual | 1 Bit | 1.2 boolean | CWU |
| 76 | Internal RTC | [RM] Fan Automatic Manual Status | 1 Bit | 1.2 boolean | CRT |
| 77 | Internal RTC | [RM] Heating - Cooling Mode Change | 1 Bit | 1.100 cooling/heating | CWU |
| 77 | Internal RTC | [RM] HVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CWU |
| 78 | Internal RTC | [RM] Heating - Cooling Mode Status | 1 Bit | 1.100 cooling/heating | CRT |
| 78 | Internal RTC | [RM] HVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CRT |
| 79 | Internal RTC | [RM] Fan Controller Stage | 1 Byte | 5.100 fan stage (0..255) | CWU |
| 79 | Internal RTC | [RM] Fan Controller Percentage | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 80 | Internal RTC | [RM] Fan Controller Stage Status | 1 Byte | 5.100 fan stage (0..255) | CRT |
| 80 | Internal RTC | [RM] Fan Controller Percentage Status | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 81 | Internal RTC | [AC] On Off Cooling | 1 Bit | 1.1 switch | CT |
| 82 | Internal RTC | [AC] On Off Cooling Status | 1 Bit | 1.11 state | CWU |
| 83 | External 1 RTC | [AC] On Off Heating | 1 Bit | 1.1 switch | CT |
| 84 | External 1 RTC | [AC] On Off Heating Status | 1 Bit | 1.11 state | CWU |
| 85 | External 1 RTC | Threshold Low | 1 Bit | 1.2 boolean | CRT |
| 86 | External 1 RTC | Threshold High | 1 Bit | 1.2 boolean | CRT |
| 87 | External 1 RTC | Heating - Cooling Mode Change | 1 Bit | 1.100 cooling/heating | CT |
| 87 | External 1 RTC | HVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CT |
| 88 | External 1 RTC | Heating - Cooling Mode Status | 1 Bit | 1.100 cooling/heating | CRWU |
| 88 | External 1 RTC | HVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CRWU |
| 89 | External 1 RTC | Command Value For Heating Bit | 1 Bit | 1.1 switch | CT |
| 90 | External 1 RTC | Command Value For Heating Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 91 | External 1 RTC | Command Value For Cooling Bit | 1 Bit | 1.1 switch | CT |
| 92 | External 1 RTC | Command Value For Cooling Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 93 | External 1 RTC | Command Value For Heating-Cooling Bit | 1 Bit | 1.1 switch | CT |
| 94 | External 1 RTC | Command Value For Heating-Cooling Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 95 | External 1 RTC | Control Of Additional Heating Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 95 | External 1 RTC | Control Of Additional Heating Bit | 1 Bit | 1.1 switch | CT |
| 96 | External 1 RTC | Control Of Additional Cooling Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 96 | External 1 RTC | Control Of Additional Cooling Bit | 1 Bit | 1.1 switch | CT |
| 97 | External 1 RTC | Fan Automatic - Manual | 1 Bit | 1.2 boolean | CT |
| 98 | External 1 RTC | Fan Automatic - Manual Status | 1 Bit | 1.2 boolean | CRWU |
| 99 | External 1 RTC | Control Fan Level 1 | 1 Bit | 1.3 enable | CT |
| 100 | External 1 RTC | Control Fan Level 2 | 1 Bit | 1.3 enable | CT |
| 101 | External 1 RTC | Control Fan Level 3 | 1 Bit | 1.3 enable | CT |
| 102 | External 1 RTC | Status Fan Level 1 | 1 Bit | 1.11 state | CRWU |
| 103 | External 1 RTC | Status Fan Level 2 | 1 Bit | 1.11 state | CRWU |
| 104 | External 1 RTC | Status Fan Level 3 | 1 Bit | 1.11 state | CRWU |
| 105 | External 1 RTC | Fan Controller Stage | 1 Byte | 5.100 fan stage (0..255) | CT |
| 105 | External 1 RTC | Fan Controller Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 106 | External 1 RTC | Fan Controller Stage Status | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 106 | External 1 RTC | Fan Controller Percentage Status | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 107 | External 1 RTC | [RM] On Off | 1 Bit | 1.1 switch | CWU |
| 108 | External 1 RTC | [RM] Status | 1 Bit | 1.11 state | CRT |
| 109 | External 1 RTC | [RM] Setpoint + / - Control | 1 Bit | 1.7 step | CWU |
| 110 | External 1 RTC | [RM] Actual Internal Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 110 | External 1 RTC | [RM] Actual Internal Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRT |
| 110 | External Input 1 | Long Press Status | 2 Bytes | 7.1 pulses | CR |
| 110 | External Input 1 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CT |
| 110 | External Input 1 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 110 | External Input 1 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 110 | External Input 1 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 110 | External Input 1 | Step Count Scene | 1 Byte | 18.1 scene control | CT |
| 110 | External Input 1 | Switching | 1 Bit | 1.1 switch | CT |
| 110 | External Input 1 | Up Down | 1 Bit | 1.8 up/down | CT |
| 110 | External Input 1 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 110 | External Input 1 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 110 | External Input 1 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 110 | External Input 1 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CT |
| 110 | External Input 1 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 110 | External Input 1 | Short Press Toggle | 1 Bit | 1.1 switch | CT |
| 110 | External Input 1 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 110 | External Input 1 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 110 | External Input 1 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 110 | External Input 1 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 110 | External Input 1 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 110 | External Input 1 | Value 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 110 | External Input 1 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 110 | External Input 1 | Toggle | 1 Bit | 1.1 switch | CT |
| 110 | External Input 1 | Scene | 1 Byte | 18.1 scene control | CT |
| 110 | External Input 1 | Short Press Switching | 1 Bit | 1.1 switch | CT |
| 111 | External 1 RTC | [RM] Actual Setpoint Temperature Control °C | 2 Bytes | 9.1 temperature (°C) | CWU |
| 111 | External 1 RTC | [RM] Actual Setpoint Temperature Control °F | 2 Bytes | 9.27 temperature (°F) | CWU |
| 111 | External Input 1 | Stop Slat Angle | 1 Bit | 1.1 switch | CT |
| 111 | External Input 1 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 111 | External Input 1 | Dimming | 4 Bit | 3.7 dimming control | CT |
| 111 | External Input 1 | Long Press Switching | 1 Bit | 1.1 switch | CT |
| 111 | External Input 1 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 111 | External Input 1 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 111 | External Input 1 | Long Press Toggle | 1 Bit | 1.1 switch | CT |
| 111 | External Input 1 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 111 | External Input 1 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 112 | External 1 RTC | [RM] Actual Setpoint Temperature Status °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 112 | External 1 RTC | [RM] Actual Setpoint Temperature Status °F | 2 Bytes | 9.27 temperature (°F) | CRT |
| 113 | External 1 RTC | [RM] HVAC Mode Change | 1 Byte | 20.102 HVAC mode | CWU |
| 114 | External 1 RTC | [RM] HVAC Mode Status | 1 Byte | 20.102 HVAC mode | CRT |
| 114 | External Input 1 | Locking | 1 Bit | 1.3 enable | CWU |
| 115 | External 1 RTC | [RM] Reset Manual Setpoint Operation | 1 Bit | 1.15 reset | CWU |
| 115 | External Input 1 | Status | 1 Bit | 1.2 boolean | CR |
| 115 | External Input 1 | Short Press Status | 1 Bit | 1.11 state | CR |
| 116 | External 1 RTC | [RM] Disable Additional Heating | 1 Bit | 1.3 enable | CWU |
| 116 | External Input 1 | Long Press Status | 1 Bit | 1.1 switch | CR |
| 117 | External 1 RTC | [RM] Disable Additional Cooling | 1 Bit | 1.3 enable | CWU |
| 118 | External 1 RTC | [RM] Fan Automatic Manual | 1 Bit | 1.2 boolean | CWU |
| 119 | External 1 RTC | [RM] Fan Automatic Manual Status | 1 Bit | 1.2 boolean | CRT |
| 120 | External 1 RTC | [RM] Heating - Cooling Mode Change | 1 Bit | 1.100 cooling/heating | CWU |
| 120 | External 1 RTC | [RM] HVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CWU |
| 121 | External 1 RTC | [RM] Heating - Cooling Mode Status | 1 Bit | 1.100 cooling/heating | CRT |
| 121 | External 1 RTC | [RM] HVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CRT |
| 122 | External 1 RTC | [RM] Fan Controller Stage | 1 Byte | 5.100 fan stage (0..255) | CWU |
| 122 | External 1 RTC | [RM] Fan Controller Percentage | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 123 | External 1 RTC | [RM] Fan Controller Stage Status | 1 Byte | 5.100 fan stage (0..255) | CRT |
| 123 | External 1 RTC | [RM] Fan Controller Percentage Status | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 124 | External 1 RTC | [AC] On Off Cooling | 1 Bit | 1.1 switch | CT |
| 125 | External 1 RTC | [AC] On Off Cooling Status | 1 Bit | 1.11 state | CWU |
| 126 | External 2 RTC | [AC] On Off Heating | 1 Bit | 1.1 switch | CT |
| 127 | External 2 RTC | [AC] On Off Heating Status | 1 Bit | 1.11 state | CWU |
| 128 | External 2 RTC | Threshold Low | 1 Bit | 1.2 boolean | CRT |
| 129 | External 2 RTC | Threshold High | 1 Bit | 1.2 boolean | CRT |
| 130 | External 2 RTC | Heating - Cooling Mode Change | 1 Bit | 1.100 cooling/heating | CT |
| 130 | External 2 RTC | HVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CT |
| 131 | External 2 RTC | Heating - Cooling Mode Status | 1 Bit | 1.100 cooling/heating | CRWU |
| 131 | External 2 RTC | HVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CRWU |
| 132 | External 2 RTC | Command Value For Heating Bit | 1 Bit | 1.1 switch | CT |
| 133 | External 2 RTC | Command Value For Heating Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 134 | External 2 RTC | Command Value For Cooling Bit | 1 Bit | 1.1 switch | CT |
| 135 | External 2 RTC | Command Value For Cooling Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 136 | External 2 RTC | Command Value For Heating-Cooling Bit | 1 Bit | 1.1 switch | CT |
| 137 | External 2 RTC | Command Value For Heating-Cooling Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 138 | External 2 RTC | Control Of Additional Heating Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 138 | External 2 RTC | Control Of Additional Heating Bit | 1 Bit | 1.1 switch | CT |
| 139 | External 2 RTC | Control Of Additional Cooling Byte | 1 Byte | 5.1 percentage (0..100%) | CT |
| 139 | External 2 RTC | Control Of Additional Cooling Bit | 1 Bit | 1.1 switch | CT |
| 140 | External 2 RTC | Fan Automatic - Manual | 1 Bit | 1.2 boolean | CT |
| 141 | External 2 RTC | Fan Automatic - Manual Status | 1 Bit | 1.2 boolean | CRWU |
| 142 | External 2 RTC | Control Fan Level 1 | 1 Bit | 1.3 enable | CT |
| 143 | External 2 RTC | Control Fan Level 2 | 1 Bit | 1.3 enable | CT |
| 144 | External 2 RTC | Control Fan Level 3 | 1 Bit | 1.3 enable | CT |
| 145 | External 2 RTC | Status Fan Level 1 | 1 Bit | 1.11 state | CRWU |
| 146 | External 2 RTC | Status Fan Level 2 | 1 Bit | 1.11 state | CRWU |
| 147 | External 2 RTC | Status Fan Level 3 | 1 Bit | 1.11 state | CRWU |
| 148 | External 2 RTC | Fan Controller Stage | 1 Byte | 5.100 fan stage (0..255) | CT |
| 148 | External 2 RTC | Fan Controller Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 149 | External 2 RTC | Fan Controller Stage Status | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 149 | External 2 RTC | Fan Controller Percentage Status | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 150 | External 2 RTC | [RM] On Off | 1 Bit | 1.1 switch | CWU |
| 151 | External 2 RTC | [RM] Status | 1 Bit | 1.11 state | CRT |
| 152 | External 2 RTC | [RM] Setpoint + / - Control | 1 Bit | 1.7 step | CWU |
| 153 | External 2 RTC | [RM] Actual Internal Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 153 | External 2 RTC | [RM] Actual Internal Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRT |
| 153 | External Input 2 | Long Press Status | 2 Bytes | 7.1 pulses | CR |
| 153 | External Input 2 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CT |
| 153 | External Input 2 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 153 | External Input 2 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 153 | External Input 2 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 153 | External Input 2 | Step Count Scene | 1 Byte | 18.1 scene control | CT |
| 153 | External Input 2 | Switching | 1 Bit | 1.1 switch | CT |
| 153 | External Input 2 | Up Down | 1 Bit | 1.8 up/down | CT |
| 153 | External Input 2 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 153 | External Input 2 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 153 | External Input 2 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 153 | External Input 2 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CT |
| 153 | External Input 2 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 153 | External Input 2 | Short Press Toggle | 1 Bit | 1.1 switch | CT |
| 153 | External Input 2 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 153 | External Input 2 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 153 | External Input 2 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 153 | External Input 2 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 153 | External Input 2 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 153 | External Input 2 | Value 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 153 | External Input 2 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 153 | External Input 2 | Toggle | 1 Bit | 1.1 switch | CT |
| 153 | External Input 2 | Scene | 1 Byte | 18.1 scene control | CT |
| 153 | External Input 2 | Short Press Switching | 1 Bit | 1.1 switch | CT |
| 154 | External 2 RTC | [RM] Actual Setpoint Temperature Control °C | 2 Bytes | 9.1 temperature (°C) | CWU |
| 154 | External 2 RTC | [RM] Actual Setpoint Temperature Control °F | 2 Bytes | 9.27 temperature (°F) | CWU |
| 154 | External Input 2 | Stop Slat Angle | 1 Bit | 1.1 switch | CT |
| 154 | External Input 2 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 154 | External Input 2 | Dimming | 4 Bit | 3.7 dimming control | CT |
| 154 | External Input 2 | Long Press Switching | 1 Bit | 1.1 switch | CT |
| 154 | External Input 2 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CT |
| 154 | External Input 2 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CT |
| 154 | External Input 2 | Long Press Toggle | 1 Bit | 1.1 switch | CT |
| 154 | External Input 2 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 154 | External Input 2 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CT |
| 155 | External 2 RTC | [RM] Actual Setpoint Temperature Status °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 155 | External 2 RTC | [RM] Actual Setpoint Temperature Status °F | 2 Bytes | 9.27 temperature (°F) | CRT |
| 156 | External 2 RTC | [RM] HVAC Mode Change | 1 Byte | 20.102 HVAC mode | CWU |
| 157 | External 2 RTC | [RM] HVAC Mode Status | 1 Byte | 20.102 HVAC mode | CRT |
| 157 | External Input 2 | Locking | 1 Bit | 1.3 enable | CWU |
| 158 | External 2 RTC | [RM] Reset Manual Setpoint Operation | 1 Bit | 1.15 reset | CWU |
| 158 | External Input 2 | Status | 1 Bit | 1.2 boolean | CR |
| 158 | External Input 2 | Short Press Status | 1 Bit | 1.11 state | CR |
| 159 | External 2 RTC | [RM] Disable Additional Heating | 1 Bit | 1.3 enable | CWU |
| 159 | External Input 2 | Long Press Status | 1 Bit | 1.1 switch | CR |
| 160 | External 2 RTC | [RM] Disable Additional Cooling | 1 Bit | 1.3 enable | CWU |
| 161 | External 2 RTC | [RM] Fan Automatic Manual | 1 Bit | 1.2 boolean | CWU |
| 162 | External 2 RTC | [RM] Fan Automatic Manual Status | 1 Bit | 1.2 boolean | CRT |
| 163 | External 2 RTC | [RM] Heating - Cooling Mode Change | 1 Bit | 1.100 cooling/heating | CWU |
| 163 | External 2 RTC | [RM] HVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CWU |
| 164 | External 2 RTC | [RM] Heating - Cooling Mode Status | 1 Bit | 1.100 cooling/heating | CRT |
| 164 | External 2 RTC | [RM] HVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry] | 1 Byte | 20.105 HVAC control mode | CRT |
| 165 | External 2 RTC | [RM] Fan Controller Stage | 1 Byte | 5.100 fan stage (0..255) | CWU |
| 165 | External 2 RTC | [RM] Fan Controller Percentage | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 166 | External 2 RTC | [RM] Fan Controller Stage Status | 1 Byte | 5.100 fan stage (0..255) | CRT |
| 166 | External 2 RTC | [RM] Fan Controller Percentage Status | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 167 | External 2 RTC | [AC] On Off Cooling | 1 Bit | 1.1 switch | CT |
| 168 | External 2 RTC | [AC] On Off Cooling Status | 1 Bit | 1.11 state | CWU |
| 212 | Converter 1 | Input 1 Bit | 1 Bit | 1.1 switch | CWU |
| 212 | Converter 1 | Input 2 Bit | 2 Bit | 2.1 switch control | CWU |
| 212 | Converter 1 | Input 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CWU |
| 212 | Converter 1 | Input 2 Byte | 2 Bytes | 7.1 pulses | CWU |
| 213 | Converter 1 | Output 1 Bit | 1 Bit | 1.1 switch | CRT |
| 213 | Converter 1 | Output 2 Bit | 2 Bit | 2.1 switch control | CRT |
| 213 | Converter 1 | Output 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 213 | Converter 1 | Output 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 214 | Converter 2 | Input 1 Bit | 1 Bit | 1.1 switch | CWU |
| 214 | Converter 2 | Input 2 Bit | 2 Bit | 2.1 switch control | CWU |
| 214 | Converter 2 | Input 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CWU |
| 214 | Converter 2 | Input 2 Byte | 2 Bytes | 7.1 pulses | CWU |
| 215 | Converter 2 | Output 1 Bit | 1 Bit | 1.1 switch | CRT |
| 215 | Converter 2 | Output 2 Bit | 2 Bit | 2.1 switch control | CRT |
| 215 | Converter 2 | Output 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 215 | Converter 2 | Output 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 216 | Converter 3 | Input 1 Bit | 1 Bit | 1.1 switch | CWU |
| 216 | Converter 3 | Input 2 Bit | 2 Bit | 2.1 switch control | CWU |
| 216 | Converter 3 | Input 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CWU |
| 216 | Converter 3 | Input 2 Byte | 2 Bytes | 7.1 pulses | CWU |
| 217 | Converter 3 | Output 1 Bit | 1 Bit | 1.1 switch | CRT |
| 217 | Converter 3 | Output 2 Bit | 2 Bit | 2.1 switch control | CRT |
| 217 | Converter 3 | Output 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 217 | Converter 3 | Output 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 218 | Converter 4 | Input 1 Bit | 1 Bit | 1.1 switch | CWU |
| 218 | Converter 4 | Input 2 Bit | 2 Bit | 2.1 switch control | CWU |
| 218 | Converter 4 | Input 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CWU |
| 218 | Converter 4 | Input 2 Byte | 2 Bytes | 7.1 pulses | CWU |
| 219 | Converter 4 | Output 1 Bit | 1 Bit | 1.1 switch | CRT |
| 219 | Converter 4 | Output 2 Bit | 2 Bit | 2.1 switch control | CRT |
| 219 | Converter 4 | Output 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 219 | Converter 4 | Output 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 224 | Logic Gate 1 | Input 1 | 1 Bit | 1.2 boolean | CWU |
| 225 | Logic Gate 1 | Input 2 | 1 Bit | 1.2 boolean | CWU |
| 226 | Logic Gate 1 | Input 3 | 1 Bit | 1.2 boolean | CWU |
| 227 | Logic Gate 1 | Input 4 | 1 Bit | 1.2 boolean | CWU |
| 228 | Logic Gate 1 | Output 1 | 1 Bit | 1.2 boolean | CRT |
| 229 | Logic Gate 2 | Input 1 | 1 Bit | 1.2 boolean | CWU |
| 230 | Logic Gate 2 | Input 2 | 1 Bit | 1.2 boolean | CWU |
| 231 | Logic Gate 2 | Input 3 | 1 Bit | 1.2 boolean | CWU |
| 232 | Logic Gate 2 | Input 4 | 1 Bit | 1.2 boolean | CWU |
| 233 | Logic Gate 2 | Output 2 | 1 Bit | 1.2 boolean | CRT |
| 234 | Logic Gate 3 | Input 1 | 1 Bit | 1.2 boolean | CWU |
| 235 | Logic Gate 3 | Input 2 | 1 Bit | 1.2 boolean | CWU |
| 236 | Logic Gate 3 | Input 3 | 1 Bit | 1.2 boolean | CWU |
| 237 | Logic Gate 3 | Input 4 | 1 Bit | 1.2 boolean | CWU |
| 238 | Logic Gate 3 | Output 3 | 1 Bit | 1.2 boolean | CRT |
| 239 | Logic Gate 4 | Input 1 | 1 Bit | 1.2 boolean | CWU |
| 240 | Logic Gate 4 | Input 2 | 1 Bit | 1.2 boolean | CWU |
| 241 | Logic Gate 4 | Input 3 | 1 Bit | 1.2 boolean | CWU |
| 242 | Logic Gate 4 | Input 4 | 1 Bit | 1.2 boolean | CWU |
| 243 | Logic Gate 4 | Output 4 | 1 Bit | 1.2 boolean | CRT |
| 254 | ASQ-MS8T.1.1 | Device Notification | 1 Bit | 1.2 boolean | CT |