[ASQ-MS8T.1.1] Asay Q Deluxe Series KNX Thermostat Internal Temp. Sensor + 2 External Inputs ASQ-MS8T.1.1

Asay Q · Order number ASQ-MS8T.1.1 · THERMOSTAT

Download .knxprod ASQ-MS8T.1.1 0.3 · 684 KB

Product

ManufacturerAsay Q
Product name[ASQ-MS8T.1.1] Asay Q Deluxe Series KNX Thermostat Internal Temp. Sensor + 2 External Inputs
Order numberASQ-MS8T.1.1
Product textAsay Q Deluxe Series KNX Thermostat Internal Temp. Sensor + 2 External inputs
HardwareAsay Q Deluxe Series KNX Thermostat Internal Temp. Sensor + 2 External inputs
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2025-04-25
Languagesen-US, de-DE, tr-TR
Catalog entryM-0304_H-00000007-2-O0164_HP-0007-03-FB80-O0164_CI-ASQ.2DMS8T.2E1.2E1-1
FingerprintFB80
SHA-25647985e9ddc2bd8ade99aa409609241fab28406e9b7868efed301524109c2f91b
First seen2026-11-25
Markets69 markets

Application program: ASQ-MS8T.1.1 0.3

Application number$0007
Version0.3
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version5.0
Parameters1166
Group objects584
Group objects (584)
NoNameFunctionSizeDPTFlags
0Button 1Step Count Percentage1 Byte5.1 percentage (0..100%)CT
0Button 1Step Count Temperature °C2 Bytes9.1 temperature (°C)CT
0Button 1Step Count Temperature °F2 Bytes9.27 temperature (°F)CT
0Button 1Step Count Luminosity2 Bytes9.4 lux (Lux)CT
0Button 1Step Count 1 Byte1 Byte5.10 counter pulses (0..255)CT
0Button 1Step Count 2 Byte2 Bytes7.1 pulsesCT
0Button 1Step Count Scene1 Byte18.1 scene controlCT
0Button 1Switching1 Bit1.1 switchCT
0Button 1Up Down1 Bit1.8 up/downCT
0Button 1Value 1 Byte1 Byte5.10 counter pulses (0..255)CT
0Button 1Value Percentage1 Byte5.1 percentage (0..100%)CT
0Button 1Value Temperature2 Bytes9.1 temperature (°C)CT
0Button 1Value Luminosity2 Bytes9.4 lux (Lux)CT
0Button 1Value 2 Byte2 Bytes7.1 pulsesCT
0Button 1Scene1 Byte18.1 scene controlCT
0Button 1Toggle1 Bit1.1 switchCT
0Button 1Short Press Switching1 Bit1.1 switchCT
0Button 1Short Press Toggle1 Bit1.1 switchCT
0Button 1Short Press Percentage1 Byte5.1 percentage (0..100%)CT
0Button 1Short Press Temperature2 Bytes9.1 temperature (°C)CT
0Button 1Short Press Luminosity2 Bytes9.4 lux (Lux)CT
0Button 1Short Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
0Button 1Short Press 2 Byte2 Bytes7.1 pulsesCT
0Button 1Long Press Status2 Bytes7.1 pulsesCR
1Button 1Dimming4 Bit3.7 dimming controlCT
1Button 1Stop Slat Angle1 Bit1.1 switchCT
1Button 1Long Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
1Button 1Long Press Switching1 Bit1.1 switchCT
1Button 1Long Press Luminosity2 Bytes9.4 lux (Lux)CT
1Button 1Long Press Percentage1 Byte5.1 percentage (0..100%)CT
1Button 1Long Press Temperature2 Bytes9.1 temperature (°C)CT
1Button 1Long Press 2 Byte2 Bytes7.1 pulsesCT
1Button 1Long Press Toggle1 Bit1.1 switchCT
2Button 1Status1 Bit1.1 switchCR
2Button 1Short Press Status1 Bit1.11 stateCR
3Button 1Long Press Status1 Bit1.1 switchCR
4Button 1Locking1 Bit1.3 enableCWU
5Button 2Step Count Percentage1 Byte5.1 percentage (0..100%)CT
5Button 2Step Count Temperature °C2 Bytes9.1 temperature (°C)CT
5Button 2Step Count Temperature °F2 Bytes9.27 temperature (°F)CT
5Button 2Step Count Luminosity2 Bytes9.4 lux (Lux)CT
5Button 2Step Count 1 Byte1 Byte5.10 counter pulses (0..255)CT
5Button 2Step Count 2 Byte2 Bytes7.1 pulsesCT
5Button 2Step Count Scene1 Byte18.1 scene controlCT
5Button 2Switching1 Bit1.1 switchCT
5Button 2Up Down1 Bit1.8 up/downCT
5Button 2Value 1 Byte1 Byte5.10 counter pulses (0..255)CT
5Button 2Value Percentage1 Byte5.1 percentage (0..100%)CT
5Button 2Value Temperature2 Bytes9.1 temperature (°C)CT
5Button 2Value Luminosity2 Bytes9.4 lux (Lux)CT
5Button 2Value 2 Byte2 Bytes7.1 pulsesCT
5Button 2Scene1 Byte18.1 scene controlCT
5Button 2Toggle1 Bit1.1 switchCT
5Button 2Short Press Switching1 Bit1.1 switchCT
5Button 2Short Press Toggle1 Bit1.1 switchCT
5Button 2Short Press Percentage1 Byte5.1 percentage (0..100%)CT
5Button 2Short Press Temperature2 Bytes9.1 temperature (°C)CT
5Button 2Short Press Luminosity2 Bytes9.4 lux (Lux)CT
5Button 2Short Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
5Button 2Short Press 2 Byte2 Bytes7.1 pulsesCT
6Button 2Long Press Switching1 Bit1.1 switchCT
6Button 2Dimming4 Bit3.7 dimming controlCT
6Button 2Stop Slat Angle1 Bit1.1 switchCT
6Button 2Long Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
6Button 2Long Press Luminosity2 Bytes9.4 lux (Lux)CT
6Button 2Long Press Percentage1 Byte5.1 percentage (0..100%)CT
6Button 2Long Press Temperature2 Bytes9.1 temperature (°C)CT
6Button 2Long Press 2 Byte2 Bytes7.1 pulsesCT
6Button 2Long Press Toggle1 Bit1.1 switchCT
7Button 2Status1 Bit1.1 switchCR
7Button 2Short Press Status1 Bit1.11 stateCR
8Button 2Long Press Status1 Bit1.1 switchCR
9Button 2Locking1 Bit1.3 enableCWU
10Button 3Step Count Percentage1 Byte5.1 percentage (0..100%)CT
10Button 3Step Count Temperature °C2 Bytes9.1 temperature (°C)CT
10Button 3Step Count Temperature °F2 Bytes9.27 temperature (°F)CT
10Button 3Step Count Luminosity2 Bytes9.4 lux (Lux)CT
10Button 3Step Count 1 Byte1 Byte5.10 counter pulses (0..255)CT
10Button 3Step Count 2 Byte2 Bytes7.1 pulsesCT
10Button 3Step Count Scene1 Byte18.1 scene controlCT
10Button 3Switching1 Bit1.1 switchCT
10Button 3Up Down1 Bit1.8 up/downCT
10Button 3Value 1 Byte1 Byte5.10 counter pulses (0..255)CT
10Button 3Value Percentage1 Byte5.1 percentage (0..100%)CT
10Button 3Value Temperature2 Bytes9.1 temperature (°C)CT
10Button 3Value Luminosity2 Bytes9.4 lux (Lux)CT
10Button 3Value 2 Byte2 Bytes7.1 pulsesCT
10Button 3Scene1 Byte18.1 scene controlCT
10Button 3Toggle1 Bit1.1 switchCT
10Button 3Short Press Switching1 Bit1.1 switchCT
10Button 3Short Press Toggle1 Bit1.1 switchCT
10Button 3Short Press Percentage1 Byte5.1 percentage (0..100%)CT
10Button 3Short Press Temperature2 Bytes9.1 temperature (°C)CT
10Button 3Short Press Luminosity2 Bytes9.4 lux (Lux)CT
10Button 3Short Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
10Button 3Short Press 2 Byte2 Bytes7.1 pulsesCT
11Button 3Long Press Switching1 Bit1.1 switchCT
11Button 3Dimming4 Bit3.7 dimming controlCT
11Button 3Stop Slat Angle1 Bit1.1 switchCT
11Button 3Long Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
11Button 3Long Press Luminosity2 Bytes9.4 lux (Lux)CT
11Button 3Long Press Percentage1 Byte5.1 percentage (0..100%)CT
11Button 3Long Press Temperature2 Bytes9.1 temperature (°C)CT
11Button 3Long Press 2 Byte2 Bytes7.1 pulsesCT
11Button 3Long Press Toggle1 Bit1.1 switchCT
12Button 3Status1 Bit1.1 switchCR
12Button 3Short Press Status1 Bit1.11 stateCR
13Button 3Long Press Status1 Bit1.1 switchCR
14Button 3Locking1 Bit1.3 enableCWU
15Button 4Switching1 Bit1.1 switchCT
15Button 4Up Down1 Bit1.8 up/downCT
15Button 4Value 1 Byte1 Byte5.10 counter pulses (0..255)CT
15Button 4Value Percentage1 Byte5.1 percentage (0..100%)CT
15Button 4Value Temperature2 Bytes9.1 temperature (°C)CT
15Button 4Value Luminosity2 Bytes9.4 lux (Lux)CT
15Button 4Value 2 Byte2 Bytes7.1 pulsesCT
15Button 4Scene1 Byte18.1 scene controlCT
15Button 4Step Count 1 Byte1 Byte5.10 counter pulses (0..255)CT
15Button 4Step Count 2 Byte2 Bytes7.1 pulsesCT
15Button 4Step Count Luminosity2 Bytes9.4 lux (Lux)CT
15Button 4Step Count Percentage1 Byte5.1 percentage (0..100%)CT
15Button 4Step Count Scene1 Byte18.1 scene controlCT
15Button 4Step Count Temperature °C2 Bytes9.1 temperature (°C)CT
15Button 4Step Count Temperature °F2 Bytes9.27 temperature (°F)CT
15Button 4Toggle1 Bit1.1 switchCT
15Button 4Short Press Switching1 Bit1.1 switchCT
15Button 4Short Press Toggle1 Bit1.1 switchCT
15Button 4Short Press Percentage1 Byte5.1 percentage (0..100%)CT
15Button 4Short Press Temperature2 Bytes9.1 temperature (°C)CT
15Button 4Short Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
15Button 4Short Press 2 Byte2 Bytes7.1 pulsesCT
15Button 4Short Press Luminosity2 Bytes9.4 lux (Lux)CT
16Button 4Long Press Switching1 Bit1.1 switchCT
16Button 4Dimming4 Bit3.7 dimming controlCT
16Button 4Stop Slat Angle1 Bit1.1 switchCT
16Button 4Long Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
16Button 4Long Press Luminosity2 Bytes9.4 lux (Lux)CT
16Button 4Long Press Percentage1 Byte5.1 percentage (0..100%)CT
16Button 4Long Press Temperature2 Bytes9.1 temperature (°C)CT
16Button 4Long Press 2 Byte2 Bytes7.1 pulsesCT
16Button 4Long Press Toggle1 Bit1.1 switchCT
17Button 4Status1 Bit1.1 switchCR
17Button 4Short Press Status1 Bit1.11 stateCR
18Button 4Long Press Status1 Bit1.1 switchCR
19Button 4Locking1 Bit1.3 enableCWU
20Button 5Switching1 Bit1.1 switchCT
20Button 5Up Down1 Bit1.8 up/downCT
20Button 5Value 1 Byte1 Byte5.10 counter pulses (0..255)CT
20Button 5Value Percentage1 Byte5.1 percentage (0..100%)CT
20Button 5Value Temperature2 Bytes9.1 temperature (°C)CT
20Button 5Value Luminosity2 Bytes9.4 lux (Lux)CT
20Button 5Value 2 Byte2 Bytes7.1 pulsesCT
20Button 5Scene1 Byte18.1 scene controlCT
20Button 5Step Count 1 Byte1 Byte5.10 counter pulses (0..255)CT
20Button 5Step Count 2 Byte2 Bytes7.1 pulsesCT
20Button 5Step Count Luminosity2 Bytes9.4 lux (Lux)CT
20Button 5Step Count Percentage1 Byte5.1 percentage (0..100%)CT
20Button 5Step Count Scene1 Byte18.1 scene controlCT
20Button 5Step Count Temperature °C2 Bytes9.1 temperature (°C)CT
20Button 5Step Count Temperature °F2 Bytes9.27 temperature (°F)CT
20Button 5Toggle1 Bit1.1 switchCT
20Button 5Short Press Switching1 Bit1.1 switchCT
20Button 5Short Press Toggle1 Bit1.1 switchCT
20Button 5Short Press Percentage1 Byte5.1 percentage (0..100%)CT
20Button 5Short Press Luminosity2 Bytes9.4 lux (Lux)CT
20Button 5Short Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
20Button 5Short Press 2 Byte2 Bytes7.1 pulsesCT
20Button 5Short Press Temperature2 Bytes9.1 temperature (°C)CT
21Button 5Long Press Switching1 Bit1.1 switchCT
21Button 5Dimming4 Bit3.7 dimming controlCT
21Button 5Stop Slat Angle1 Bit1.1 switchCT
21Button 5Long Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
21Button 5Long Press Luminosity2 Bytes9.4 lux (Lux)CT
21Button 5Long Press Percentage1 Byte5.1 percentage (0..100%)CT
21Button 5Long Press Temperature2 Bytes9.1 temperature (°C)CT
21Button 5Long Press 2 Byte2 Bytes7.1 pulsesCT
21Button 5Long Press Toggle1 Bit1.1 switchCT
22Button 5Status1 Bit1.1 switchCR
22Button 5Short Press Status1 Bit1.11 stateCR
23Button 5Long Press Status1 Bit1.1 switchCR
24Button 5Locking1 Bit1.3 enableCWU
25Button 6Switching1 Bit1.1 switchCT
25Button 6Up Down1 Bit1.8 up/downCT
25Button 6Value 1 Byte1 Byte5.10 counter pulses (0..255)CT
25Button 6Value Percentage1 Byte5.1 percentage (0..100%)CT
25Button 6Value Temperature2 Bytes9.1 temperature (°C)CT
25Button 6Value Luminosity2 Bytes9.4 lux (Lux)CT
25Button 6Value 2 Byte2 Bytes7.1 pulsesCT
25Button 6Scene1 Byte18.1 scene controlCT
25Button 6Step Count 1 Byte1 Byte5.10 counter pulses (0..255)CT
25Button 6Step Count 2 Byte2 Bytes7.1 pulsesCT
25Button 6Step Count Luminosity2 Bytes9.4 lux (Lux)CT
25Button 6Step Count Percentage1 Byte5.1 percentage (0..100%)CT
25Button 6Step Count Scene1 Byte18.1 scene controlCT
25Button 6Step Count Temperature °C2 Bytes9.1 temperature (°C)CT
25Button 6Step Count Temperature °F2 Bytes9.27 temperature (°F)CT
25Button 6Toggle1 Bit1.1 switchCT
25Button 6Short Press Switching1 Bit1.1 switchCT
25Button 6Short Press Toggle1 Bit1.1 switchCT
25Button 6Short Press Percentage1 Byte5.1 percentage (0..100%)CT
25Button 6Short Press Temperature2 Bytes9.1 temperature (°C)CT
25Button 6Short Press Luminosity2 Bytes9.4 lux (Lux)CT
25Button 6Short Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
25Button 6Short Press 2 Byte2 Bytes7.1 pulsesCT
26Button 6Long Press Switching1 Bit1.1 switchCT
26Button 6Dimming4 Bit3.7 dimming controlCT
26Button 6Stop Slat Angle1 Bit1.1 switchCT
26Button 6Long Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
26Button 6Long Press Luminosity2 Bytes9.4 lux (Lux)CT
26Button 6Long Press Percentage1 Byte5.1 percentage (0..100%)CT
26Button 6Long Press Temperature2 Bytes9.1 temperature (°C)CT
26Button 6Long Press 2 Byte2 Bytes7.1 pulsesCT
26Button 6Long Press Toggle1 Bit1.1 switchCT
27Button 6Status1 Bit1.1 switchCR
27Button 6Short Press Status1 Bit1.11 stateCR
28Button 6Long Press Status1 Bit1.1 switchCR
29Button 6Locking1 Bit1.3 enableCWU
30Button 7Switching1 Bit1.1 switchCT
30Button 7Up Down1 Bit1.8 up/downCT
30Button 7Value 1 Byte1 Byte5.10 counter pulses (0..255)CT
30Button 7Value Percentage1 Byte5.1 percentage (0..100%)CT
30Button 7Value Temperature2 Bytes9.1 temperature (°C)CT
30Button 7Value Luminosity2 Bytes9.4 lux (Lux)CT
30Button 7Value 2 Byte2 Bytes7.1 pulsesCT
30Button 7Scene1 Byte18.1 scene controlCT
30Button 7Step Count 1 Byte1 Byte5.10 counter pulses (0..255)CT
30Button 7Step Count 2 Byte2 Bytes7.1 pulsesCT
30Button 7Step Count Luminosity2 Bytes9.4 lux (Lux)CT
30Button 7Step Count Percentage1 Byte5.1 percentage (0..100%)CT
30Button 7Step Count Scene1 Byte18.1 scene controlCT
30Button 7Step Count Temperature °C2 Bytes9.1 temperature (°C)CT
30Button 7Step Count Temperature °F2 Bytes9.27 temperature (°F)CT
30Button 7Toggle1 Bit1.1 switchCT
30Button 7Short Press Switching1 Bit1.1 switchCT
30Button 7Short Press Toggle1 Bit1.1 switchCT
30Button 7Short Press Percentage1 Byte5.1 percentage (0..100%)CT
30Button 7Short Press Temperature2 Bytes9.1 temperature (°C)CT
30Button 7Short Press Luminosity2 Bytes9.4 lux (Lux)CT
30Button 7Short Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
30Button 7Short Press 2 Byte2 Bytes7.1 pulsesCT
31Button 7Dimming4 Bit3.7 dimming controlCT
31Button 7Stop Slat Angle1 Bit1.1 switchCT
31Button 7Long Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
31Button 7Long Press Switching1 Bit1.1 switchCT
31Button 7Long Press Luminosity2 Bytes9.4 lux (Lux)CT
31Button 7Long Press Percentage1 Byte5.1 percentage (0..100%)CT
31Button 7Long Press Temperature2 Bytes9.1 temperature (°C)CT
31Button 7Long Press 2 Byte2 Bytes7.1 pulsesCT
31Button 7Long Press Toggle1 Bit1.1 switchCT
32Button 7Status1 Bit1.1 switchCR
32Button 7Short Press Status1 Bit1.11 stateCR
33Button 7Long Press Status1 Bit1.1 switchCR
34Button 7Locking1 Bit1.3 enableCWU
35Button 8Switching1 Bit1.1 switchCT
35Button 8Up Down1 Bit1.8 up/downCT
35Button 8Value 1 Byte1 Byte5.10 counter pulses (0..255)CT
35Button 8Value Percentage1 Byte5.1 percentage (0..100%)CT
35Button 8Value Temperature2 Bytes9.1 temperature (°C)CT
35Button 8Value Luminosity2 Bytes9.4 lux (Lux)CT
35Button 8Value 2 Byte2 Bytes7.1 pulsesCT
35Button 8Scene1 Byte18.1 scene controlCT
35Button 8Step Count 1 Byte1 Byte5.10 counter pulses (0..255)CT
35Button 8Step Count 2 Byte2 Bytes7.1 pulsesCT
35Button 8Step Count Luminosity2 Bytes9.4 lux (Lux)CT
35Button 8Step Count Percentage1 Byte5.1 percentage (0..100%)CT
35Button 8Step Count Scene1 Byte18.1 scene controlCT
35Button 8Step Count Temperature °C2 Bytes9.1 temperature (°C)CT
35Button 8Step Count Temperature °F2 Bytes9.27 temperature (°F)CT
35Button 8Toggle1 Bit1.1 switchCT
35Button 8Short Press Switching1 Bit1.1 switchCT
35Button 8Short Press Toggle1 Bit1.1 switchCT
35Button 8Short Press Percentage1 Byte5.1 percentage (0..100%)CT
35Button 8Short Press Temperature2 Bytes9.1 temperature (°C)CT
35Button 8Short Press Luminosity2 Bytes9.4 lux (Lux)CT
35Button 8Short Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
35Button 8Short Press 2 Byte2 Bytes7.1 pulsesCT
36Button 8Long Press Switching1 Bit1.1 switchCT
36Button 8Dimming4 Bit3.7 dimming controlCT
36Button 8Stop Slat Angle1 Bit1.1 switchCT
36Button 8Long Press Luminosity2 Bytes9.4 lux (Lux)CT
36Button 8Long Press Percentage1 Byte5.1 percentage (0..100%)CT
36Button 8Long Press Temperature2 Bytes9.1 temperature (°C)CT
36Button 8Long Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
36Button 8Long Press 2 Byte2 Bytes7.1 pulsesCT
36Button 8Long Press Toggle1 Bit1.1 switchCT
37Button 8Status1 Bit1.1 switchCR
37Button 8Short Press Status1 Bit1.11 stateCR
38Button 8Long Press Status1 Bit1.1 switchCR
39Button 8Locking1 Bit1.3 enableCWU
40Internal RTC[AC] On Off Heating1 Bit1.1 switchCT
41Internal RTC[AC] On Off Heating Status1 Bit1.11 stateCWU
42Internal RTCThreshold Low1 Bit1.2 booleanCRT
43Internal RTCThreshold High1 Bit1.2 booleanCRT
44Internal RTCHeating - Cooling Mode Change1 Bit1.100 cooling/heatingCT
44Internal RTCHVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCT
45Internal RTCHeating - Cooling Mode Status1 Bit1.100 cooling/heatingCRWU
45Internal RTCHVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCRWU
46Internal RTCCommand Value For Heating Bit1 Bit1.1 switchCT
47Internal RTCCommand Value For Heating Byte1 Byte5.1 percentage (0..100%)CT
48Internal RTCCommand Value For Cooling Bit1 Bit1.1 switchCT
49Internal RTCCommand Value For Cooling Byte1 Byte5.1 percentage (0..100%)CT
50Internal RTCCommand Value For Heating-Cooling Bit1 Bit1.1 switchCT
51Internal RTCCommand Value For Heating-Cooling Byte1 Byte5.1 percentage (0..100%)CT
52Internal RTCControl Of Additional Heating Byte1 Byte5.1 percentage (0..100%)CT
52Internal RTCControl Of Additional Heating Bit1 Bit1.1 switchCT
53Internal RTCControl Of Additional Cooling Byte1 Byte5.1 percentage (0..100%)CT
53Internal RTCControl Of Additional Cooling Bit1 Bit1.1 switchCT
54Internal RTCFan Automatic - Manual1 Bit1.2 booleanCT
55Internal RTCFan Automatic - Manual Status1 Bit1.2 booleanCRWU
56Internal RTCControl Fan Level 11 Bit1.3 enableCT
57Internal RTCControl Fan Level 21 Bit1.3 enableCT
58Internal RTCControl Fan Level 31 Bit1.3 enableCT
59Internal RTCStatus Fan Level 11 Bit1.11 stateCRWU
60Internal RTCStatus Fan Level 21 Bit1.11 stateCRWU
61Internal RTCStatus Fan Level 31 Bit1.11 stateCRWU
62Internal RTCFan Controller Stage1 Byte5.100 fan stage (0..255)CT
62Internal RTCFan Controller Percentage1 Byte5.1 percentage (0..100%)CT
63Internal RTCFan Controller Stage Status1 Byte5.100 fan stage (0..255)CRWU
63Internal RTCFan Controller Percentage Status1 Byte5.1 percentage (0..100%)CRWU
64Internal RTC[RM] On Off1 Bit1.1 switchCWU
65Internal RTC[RM] Status1 Bit1.11 stateCRT
66Internal RTC[RM] Setpoint + / - Control1 Bit1.7 stepCWU
67Internal RTC[RM] Actual Internal Temperature °C2 Bytes9.1 temperature (°C)CRT
67Internal RTC[RM] Actual Internal Temperature °F2 Bytes9.27 temperature (°F)CRT
68Internal RTC[RM] Actual Setpoint Temperature Control °C2 Bytes9.1 temperature (°C)CWU
68Internal RTC[RM] Actual Setpoint Temperature Control °F2 Bytes9.27 temperature (°F)CWU
69Internal RTC[RM] Actual Setpoint Temperature Status °C2 Bytes9.1 temperature (°C)CRT
69Internal RTC[RM] Actual Setpoint Temperature Status °F2 Bytes9.27 temperature (°F)CRT
70Internal RTC[RM] HVAC Mode Change1 Byte20.102 HVAC modeCWU
71Internal RTC[RM] HVAC Mode Status1 Byte20.102 HVAC modeCRT
72Internal RTC[RM] Reset Manual Setpoint Operation1 Bit1.15 resetCWU
73Internal RTC[RM] Disable Additional Heating1 Bit1.3 enableCWU
74Internal RTC[RM] Disable Additional Cooling1 Bit1.3 enableCWU
75Internal RTC[RM] Fan Automatic Manual1 Bit1.2 booleanCWU
76Internal RTC[RM] Fan Automatic Manual Status1 Bit1.2 booleanCRT
77Internal RTC[RM] Heating - Cooling Mode Change1 Bit1.100 cooling/heatingCWU
77Internal RTC[RM] HVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCWU
78Internal RTC[RM] Heating - Cooling Mode Status1 Bit1.100 cooling/heatingCRT
78Internal RTC[RM] HVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCRT
79Internal RTC[RM] Fan Controller Stage1 Byte5.100 fan stage (0..255)CWU
79Internal RTC[RM] Fan Controller Percentage1 Byte5.1 percentage (0..100%)CWU
80Internal RTC[RM] Fan Controller Stage Status1 Byte5.100 fan stage (0..255)CRT
80Internal RTC[RM] Fan Controller Percentage Status1 Byte5.1 percentage (0..100%)CRT
81Internal RTC[AC] On Off Cooling1 Bit1.1 switchCT
82Internal RTC[AC] On Off Cooling Status1 Bit1.11 stateCWU
83External 1 RTC[AC] On Off Heating1 Bit1.1 switchCT
84External 1 RTC[AC] On Off Heating Status1 Bit1.11 stateCWU
85External 1 RTCThreshold Low1 Bit1.2 booleanCRT
86External 1 RTCThreshold High1 Bit1.2 booleanCRT
87External 1 RTCHeating - Cooling Mode Change1 Bit1.100 cooling/heatingCT
87External 1 RTCHVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCT
88External 1 RTCHeating - Cooling Mode Status1 Bit1.100 cooling/heatingCRWU
88External 1 RTCHVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCRWU
89External 1 RTCCommand Value For Heating Bit1 Bit1.1 switchCT
90External 1 RTCCommand Value For Heating Byte1 Byte5.1 percentage (0..100%)CT
91External 1 RTCCommand Value For Cooling Bit1 Bit1.1 switchCT
92External 1 RTCCommand Value For Cooling Byte1 Byte5.1 percentage (0..100%)CT
93External 1 RTCCommand Value For Heating-Cooling Bit1 Bit1.1 switchCT
94External 1 RTCCommand Value For Heating-Cooling Byte1 Byte5.1 percentage (0..100%)CT
95External 1 RTCControl Of Additional Heating Byte1 Byte5.1 percentage (0..100%)CT
95External 1 RTCControl Of Additional Heating Bit1 Bit1.1 switchCT
96External 1 RTCControl Of Additional Cooling Byte1 Byte5.1 percentage (0..100%)CT
96External 1 RTCControl Of Additional Cooling Bit1 Bit1.1 switchCT
97External 1 RTCFan Automatic - Manual1 Bit1.2 booleanCT
98External 1 RTCFan Automatic - Manual Status1 Bit1.2 booleanCRWU
99External 1 RTCControl Fan Level 11 Bit1.3 enableCT
100External 1 RTCControl Fan Level 21 Bit1.3 enableCT
101External 1 RTCControl Fan Level 31 Bit1.3 enableCT
102External 1 RTCStatus Fan Level 11 Bit1.11 stateCRWU
103External 1 RTCStatus Fan Level 21 Bit1.11 stateCRWU
104External 1 RTCStatus Fan Level 31 Bit1.11 stateCRWU
105External 1 RTCFan Controller Stage1 Byte5.100 fan stage (0..255)CT
105External 1 RTCFan Controller Percentage1 Byte5.1 percentage (0..100%)CT
106External 1 RTCFan Controller Stage Status1 Byte5.100 fan stage (0..255)CRWU
106External 1 RTCFan Controller Percentage Status1 Byte5.1 percentage (0..100%)CRWU
107External 1 RTC[RM] On Off1 Bit1.1 switchCWU
108External 1 RTC[RM] Status1 Bit1.11 stateCRT
109External 1 RTC[RM] Setpoint + / - Control1 Bit1.7 stepCWU
110External 1 RTC[RM] Actual Internal Temperature °C2 Bytes9.1 temperature (°C)CRT
110External 1 RTC[RM] Actual Internal Temperature °F2 Bytes9.27 temperature (°F)CRT
110External Input 1Long Press Status2 Bytes7.1 pulsesCR
110External Input 1Step Count Temperature °F2 Bytes9.27 temperature (°F)CT
110External Input 1Step Count Luminosity2 Bytes9.4 lux (Lux)CT
110External Input 1Step Count 1 Byte1 Byte5.10 counter pulses (0..255)CT
110External Input 1Step Count 2 Byte2 Bytes7.1 pulsesCT
110External Input 1Step Count Scene1 Byte18.1 scene controlCT
110External Input 1Switching1 Bit1.1 switchCT
110External Input 1Up Down1 Bit1.8 up/downCT
110External Input 1Value 1 Byte1 Byte5.10 counter pulses (0..255)CT
110External Input 1Value Percentage1 Byte5.1 percentage (0..100%)CT
110External Input 1Value Temperature2 Bytes9.1 temperature (°C)CT
110External Input 1Step Count Temperature °C2 Bytes9.1 temperature (°C)CT
110External Input 1Value Luminosity2 Bytes9.4 lux (Lux)CT
110External Input 1Short Press Toggle1 Bit1.1 switchCT
110External Input 1Short Press 2 Byte2 Bytes7.1 pulsesCT
110External Input 1Short Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
110External Input 1Short Press Luminosity2 Bytes9.4 lux (Lux)CT
110External Input 1Short Press Temperature2 Bytes9.1 temperature (°C)CT
110External Input 1Short Press Percentage1 Byte5.1 percentage (0..100%)CT
110External Input 1Value 2 Byte2 Bytes7.1 pulsesCT
110External Input 1Step Count Percentage1 Byte5.1 percentage (0..100%)CT
110External Input 1Toggle1 Bit1.1 switchCT
110External Input 1Scene1 Byte18.1 scene controlCT
110External Input 1Short Press Switching1 Bit1.1 switchCT
111External 1 RTC[RM] Actual Setpoint Temperature Control °C2 Bytes9.1 temperature (°C)CWU
111External 1 RTC[RM] Actual Setpoint Temperature Control °F2 Bytes9.27 temperature (°F)CWU
111External Input 1Stop Slat Angle1 Bit1.1 switchCT
111External Input 1Long Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
111External Input 1Dimming4 Bit3.7 dimming controlCT
111External Input 1Long Press Switching1 Bit1.1 switchCT
111External Input 1Long Press 2 Byte2 Bytes7.1 pulsesCT
111External Input 1Long Press Percentage1 Byte5.1 percentage (0..100%)CT
111External Input 1Long Press Toggle1 Bit1.1 switchCT
111External Input 1Long Press Temperature2 Bytes9.1 temperature (°C)CT
111External Input 1Long Press Luminosity2 Bytes9.4 lux (Lux)CT
112External 1 RTC[RM] Actual Setpoint Temperature Status °C2 Bytes9.1 temperature (°C)CRT
112External 1 RTC[RM] Actual Setpoint Temperature Status °F2 Bytes9.27 temperature (°F)CRT
113External 1 RTC[RM] HVAC Mode Change1 Byte20.102 HVAC modeCWU
114External 1 RTC[RM] HVAC Mode Status1 Byte20.102 HVAC modeCRT
114External Input 1Locking1 Bit1.3 enableCWU
115External 1 RTC[RM] Reset Manual Setpoint Operation1 Bit1.15 resetCWU
115External Input 1Status1 Bit1.2 booleanCR
115External Input 1Short Press Status1 Bit1.11 stateCR
116External 1 RTC[RM] Disable Additional Heating1 Bit1.3 enableCWU
116External Input 1Long Press Status1 Bit1.1 switchCR
117External 1 RTC[RM] Disable Additional Cooling1 Bit1.3 enableCWU
118External 1 RTC[RM] Fan Automatic Manual1 Bit1.2 booleanCWU
119External 1 RTC[RM] Fan Automatic Manual Status1 Bit1.2 booleanCRT
120External 1 RTC[RM] Heating - Cooling Mode Change1 Bit1.100 cooling/heatingCWU
120External 1 RTC[RM] HVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCWU
121External 1 RTC[RM] Heating - Cooling Mode Status1 Bit1.100 cooling/heatingCRT
121External 1 RTC[RM] HVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCRT
122External 1 RTC[RM] Fan Controller Stage1 Byte5.100 fan stage (0..255)CWU
122External 1 RTC[RM] Fan Controller Percentage1 Byte5.1 percentage (0..100%)CWU
123External 1 RTC[RM] Fan Controller Stage Status1 Byte5.100 fan stage (0..255)CRT
123External 1 RTC[RM] Fan Controller Percentage Status1 Byte5.1 percentage (0..100%)CRT
124External 1 RTC[AC] On Off Cooling1 Bit1.1 switchCT
125External 1 RTC[AC] On Off Cooling Status1 Bit1.11 stateCWU
126External 2 RTC[AC] On Off Heating1 Bit1.1 switchCT
127External 2 RTC[AC] On Off Heating Status1 Bit1.11 stateCWU
128External 2 RTCThreshold Low1 Bit1.2 booleanCRT
129External 2 RTCThreshold High1 Bit1.2 booleanCRT
130External 2 RTCHeating - Cooling Mode Change1 Bit1.100 cooling/heatingCT
130External 2 RTCHVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCT
131External 2 RTCHeating - Cooling Mode Status1 Bit1.100 cooling/heatingCRWU
131External 2 RTCHVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCRWU
132External 2 RTCCommand Value For Heating Bit1 Bit1.1 switchCT
133External 2 RTCCommand Value For Heating Byte1 Byte5.1 percentage (0..100%)CT
134External 2 RTCCommand Value For Cooling Bit1 Bit1.1 switchCT
135External 2 RTCCommand Value For Cooling Byte1 Byte5.1 percentage (0..100%)CT
136External 2 RTCCommand Value For Heating-Cooling Bit1 Bit1.1 switchCT
137External 2 RTCCommand Value For Heating-Cooling Byte1 Byte5.1 percentage (0..100%)CT
138External 2 RTCControl Of Additional Heating Byte1 Byte5.1 percentage (0..100%)CT
138External 2 RTCControl Of Additional Heating Bit1 Bit1.1 switchCT
139External 2 RTCControl Of Additional Cooling Byte1 Byte5.1 percentage (0..100%)CT
139External 2 RTCControl Of Additional Cooling Bit1 Bit1.1 switchCT
140External 2 RTCFan Automatic - Manual1 Bit1.2 booleanCT
141External 2 RTCFan Automatic - Manual Status1 Bit1.2 booleanCRWU
142External 2 RTCControl Fan Level 11 Bit1.3 enableCT
143External 2 RTCControl Fan Level 21 Bit1.3 enableCT
144External 2 RTCControl Fan Level 31 Bit1.3 enableCT
145External 2 RTCStatus Fan Level 11 Bit1.11 stateCRWU
146External 2 RTCStatus Fan Level 21 Bit1.11 stateCRWU
147External 2 RTCStatus Fan Level 31 Bit1.11 stateCRWU
148External 2 RTCFan Controller Stage1 Byte5.100 fan stage (0..255)CT
148External 2 RTCFan Controller Percentage1 Byte5.1 percentage (0..100%)CT
149External 2 RTCFan Controller Stage Status1 Byte5.100 fan stage (0..255)CRWU
149External 2 RTCFan Controller Percentage Status1 Byte5.1 percentage (0..100%)CRWU
150External 2 RTC[RM] On Off1 Bit1.1 switchCWU
151External 2 RTC[RM] Status1 Bit1.11 stateCRT
152External 2 RTC[RM] Setpoint + / - Control1 Bit1.7 stepCWU
153External 2 RTC[RM] Actual Internal Temperature °C2 Bytes9.1 temperature (°C)CRT
153External 2 RTC[RM] Actual Internal Temperature °F2 Bytes9.27 temperature (°F)CRT
153External Input 2Long Press Status2 Bytes7.1 pulsesCR
153External Input 2Step Count Temperature °F2 Bytes9.27 temperature (°F)CT
153External Input 2Step Count Luminosity2 Bytes9.4 lux (Lux)CT
153External Input 2Step Count 1 Byte1 Byte5.10 counter pulses (0..255)CT
153External Input 2Step Count 2 Byte2 Bytes7.1 pulsesCT
153External Input 2Step Count Scene1 Byte18.1 scene controlCT
153External Input 2Switching1 Bit1.1 switchCT
153External Input 2Up Down1 Bit1.8 up/downCT
153External Input 2Value 1 Byte1 Byte5.10 counter pulses (0..255)CT
153External Input 2Value Percentage1 Byte5.1 percentage (0..100%)CT
153External Input 2Value Temperature2 Bytes9.1 temperature (°C)CT
153External Input 2Step Count Temperature °C2 Bytes9.1 temperature (°C)CT
153External Input 2Value Luminosity2 Bytes9.4 lux (Lux)CT
153External Input 2Short Press Toggle1 Bit1.1 switchCT
153External Input 2Short Press 2 Byte2 Bytes7.1 pulsesCT
153External Input 2Short Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
153External Input 2Short Press Luminosity2 Bytes9.4 lux (Lux)CT
153External Input 2Short Press Temperature2 Bytes9.1 temperature (°C)CT
153External Input 2Short Press Percentage1 Byte5.1 percentage (0..100%)CT
153External Input 2Value 2 Byte2 Bytes7.1 pulsesCT
153External Input 2Step Count Percentage1 Byte5.1 percentage (0..100%)CT
153External Input 2Toggle1 Bit1.1 switchCT
153External Input 2Scene1 Byte18.1 scene controlCT
153External Input 2Short Press Switching1 Bit1.1 switchCT
154External 2 RTC[RM] Actual Setpoint Temperature Control °C2 Bytes9.1 temperature (°C)CWU
154External 2 RTC[RM] Actual Setpoint Temperature Control °F2 Bytes9.27 temperature (°F)CWU
154External Input 2Stop Slat Angle1 Bit1.1 switchCT
154External Input 2Long Press 1 Byte1 Byte5.10 counter pulses (0..255)CT
154External Input 2Dimming4 Bit3.7 dimming controlCT
154External Input 2Long Press Switching1 Bit1.1 switchCT
154External Input 2Long Press 2 Byte2 Bytes7.1 pulsesCT
154External Input 2Long Press Percentage1 Byte5.1 percentage (0..100%)CT
154External Input 2Long Press Toggle1 Bit1.1 switchCT
154External Input 2Long Press Temperature2 Bytes9.1 temperature (°C)CT
154External Input 2Long Press Luminosity2 Bytes9.4 lux (Lux)CT
155External 2 RTC[RM] Actual Setpoint Temperature Status °C2 Bytes9.1 temperature (°C)CRT
155External 2 RTC[RM] Actual Setpoint Temperature Status °F2 Bytes9.27 temperature (°F)CRT
156External 2 RTC[RM] HVAC Mode Change1 Byte20.102 HVAC modeCWU
157External 2 RTC[RM] HVAC Mode Status1 Byte20.102 HVAC modeCRT
157External Input 2Locking1 Bit1.3 enableCWU
158External 2 RTC[RM] Reset Manual Setpoint Operation1 Bit1.15 resetCWU
158External Input 2Status1 Bit1.2 booleanCR
158External Input 2Short Press Status1 Bit1.11 stateCR
159External 2 RTC[RM] Disable Additional Heating1 Bit1.3 enableCWU
159External Input 2Long Press Status1 Bit1.1 switchCR
160External 2 RTC[RM] Disable Additional Cooling1 Bit1.3 enableCWU
161External 2 RTC[RM] Fan Automatic Manual1 Bit1.2 booleanCWU
162External 2 RTC[RM] Fan Automatic Manual Status1 Bit1.2 booleanCRT
163External 2 RTC[RM] Heating - Cooling Mode Change1 Bit1.100 cooling/heatingCWU
163External 2 RTC[RM] HVAC Control Mode [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCWU
164External 2 RTC[RM] Heating - Cooling Mode Status1 Bit1.100 cooling/heatingCRT
164External 2 RTC[RM] HVAC Control Mode Status [0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry]1 Byte20.105 HVAC control modeCRT
165External 2 RTC[RM] Fan Controller Stage1 Byte5.100 fan stage (0..255)CWU
165External 2 RTC[RM] Fan Controller Percentage1 Byte5.1 percentage (0..100%)CWU
166External 2 RTC[RM] Fan Controller Stage Status1 Byte5.100 fan stage (0..255)CRT
166External 2 RTC[RM] Fan Controller Percentage Status1 Byte5.1 percentage (0..100%)CRT
167External 2 RTC[AC] On Off Cooling1 Bit1.1 switchCT
168External 2 RTC[AC] On Off Cooling Status1 Bit1.11 stateCWU
212Converter 1Input 1 Bit1 Bit1.1 switchCWU
212Converter 1Input 2 Bit2 Bit2.1 switch controlCWU
212Converter 1Input 1 Byte1 Byte5.10 counter pulses (0..255)CWU
212Converter 1Input 2 Byte2 Bytes7.1 pulsesCWU
213Converter 1Output 1 Bit1 Bit1.1 switchCRT
213Converter 1Output 2 Bit2 Bit2.1 switch controlCRT
213Converter 1Output 1 Byte1 Byte5.10 counter pulses (0..255)CRT
213Converter 1Output 2 Byte2 Bytes7.1 pulsesCRT
214Converter 2Input 1 Bit1 Bit1.1 switchCWU
214Converter 2Input 2 Bit2 Bit2.1 switch controlCWU
214Converter 2Input 1 Byte1 Byte5.10 counter pulses (0..255)CWU
214Converter 2Input 2 Byte2 Bytes7.1 pulsesCWU
215Converter 2Output 1 Bit1 Bit1.1 switchCRT
215Converter 2Output 2 Bit2 Bit2.1 switch controlCRT
215Converter 2Output 1 Byte1 Byte5.10 counter pulses (0..255)CRT
215Converter 2Output 2 Byte2 Bytes7.1 pulsesCRT
216Converter 3Input 1 Bit1 Bit1.1 switchCWU
216Converter 3Input 2 Bit2 Bit2.1 switch controlCWU
216Converter 3Input 1 Byte1 Byte5.10 counter pulses (0..255)CWU
216Converter 3Input 2 Byte2 Bytes7.1 pulsesCWU
217Converter 3Output 1 Bit1 Bit1.1 switchCRT
217Converter 3Output 2 Bit2 Bit2.1 switch controlCRT
217Converter 3Output 1 Byte1 Byte5.10 counter pulses (0..255)CRT
217Converter 3Output 2 Byte2 Bytes7.1 pulsesCRT
218Converter 4Input 1 Bit1 Bit1.1 switchCWU
218Converter 4Input 2 Bit2 Bit2.1 switch controlCWU
218Converter 4Input 1 Byte1 Byte5.10 counter pulses (0..255)CWU
218Converter 4Input 2 Byte2 Bytes7.1 pulsesCWU
219Converter 4Output 1 Bit1 Bit1.1 switchCRT
219Converter 4Output 2 Bit2 Bit2.1 switch controlCRT
219Converter 4Output 1 Byte1 Byte5.10 counter pulses (0..255)CRT
219Converter 4Output 2 Byte2 Bytes7.1 pulsesCRT
224Logic Gate 1Input 11 Bit1.2 booleanCWU
225Logic Gate 1Input 21 Bit1.2 booleanCWU
226Logic Gate 1Input 31 Bit1.2 booleanCWU
227Logic Gate 1Input 41 Bit1.2 booleanCWU
228Logic Gate 1Output 11 Bit1.2 booleanCRT
229Logic Gate 2Input 11 Bit1.2 booleanCWU
230Logic Gate 2Input 21 Bit1.2 booleanCWU
231Logic Gate 2Input 31 Bit1.2 booleanCWU
232Logic Gate 2Input 41 Bit1.2 booleanCWU
233Logic Gate 2Output 21 Bit1.2 booleanCRT
234Logic Gate 3Input 11 Bit1.2 booleanCWU
235Logic Gate 3Input 21 Bit1.2 booleanCWU
236Logic Gate 3Input 31 Bit1.2 booleanCWU
237Logic Gate 3Input 41 Bit1.2 booleanCWU
238Logic Gate 3Output 31 Bit1.2 booleanCRT
239Logic Gate 4Input 11 Bit1.2 booleanCWU
240Logic Gate 4Input 21 Bit1.2 booleanCWU
241Logic Gate 4Input 31 Bit1.2 booleanCWU
242Logic Gate 4Input 41 Bit1.2 booleanCWU
243Logic Gate 4Output 41 Bit1.2 booleanCRT
254ASQ-MS8T.1.1Device Notification1 Bit1.2 booleanCT
Parameters (223)
ParameterTypeDefault
Step Count 1unsignedInt 0…1000
Step Count 1unsignedInt 0…500
Step Count 1unsignedInt 32…12232
Step Count 1unsignedInt 0…100000
Step Count 1unsignedInt 0…2550
Step Count 1unsignedInt 0…655350
Step Count 1unsignedInt 1…641
Step Count 2unsignedInt 0…1000
Step Count 2unsignedInt 0…500
Step Count 2unsignedInt 32…12232
Step Count 2unsignedInt 0…100000
Step Count 2unsignedInt 0…2550
Step Count 2unsignedInt 0…655350
Step Count 2unsignedInt 1…641
Step Count 3unsignedInt 0…1000
Step Count 3unsignedInt 0…500
Step Count 3unsignedInt 32…12232
Step Count 3unsignedInt 0…100000
Step Count 3unsignedInt 0…2550
Step Count 3unsignedInt 0…655350
Step Count 3unsignedInt 1…641
Step Count 4unsignedInt 0…1000
Step Count 4unsignedInt 0…500
Step Count 4unsignedInt 32…12232
Step Count 4unsignedInt 0…100000
Step Count 4unsignedInt 0…2550
Step Count 4unsignedInt 0…655350
Step Count 4unsignedInt 1…641
Step Count 5unsignedInt 0…1000
Step Count 5unsignedInt 0…500
Step Count 5unsignedInt 32…12232
Step Count 5unsignedInt 0…100000
Step Count 5unsignedInt 0…2550
Step Count 5unsignedInt 0…655350
Step Count 5unsignedInt 1…641
SelectionlistPercentage
Step Count BehaviorlistCycle Mode
Step NumberunsignedInt 1…51
Temperature UnitlistCelcius [°C]
Module Alive NotificationunsignedInt 0…10
Module Alive PeriodlistDisable
Button 1listDisabled
Button 2listDisabled
Button 3listDisabled
Button 4listDisabled
Button 5listDisabled
Button 6listDisabled
On Press / On ReleaselistOn / -
Storage FunctionunsignedInt 0…10
Periodical SendingunsignedInt 0…10
LockinglistDisabled
Sending DelayunsignedInt 0…2550
Periodical Sending IntervalunsignedInt 1…2551
On Press / On ReleaselistToggle / -
Dimming SelectionlistDimming With 1 Button
DirectionlistUp
Long Press Durationlist0.4 sec
SelectionlistShutter / Blinds With 1 Button
ValueunsignedInt 0…1000
ValueunsignedInt 0…500
ValueunsignedInt 0…100000
ValueunsignedInt 0…2550
ValueunsignedInt 0…655350
On Press / On ReleaselistSend / -
On Short PresslistDisable
On Long PresslistDisable
Button 7listDisabled
Button 8listDisabled
Convert FunctionunsignedInt 0…10
Convert 1unsignedInt 0…10
Logic Gate 1listDisable
Logic Gate FunctionunsignedInt 0…10
Convert 2unsignedInt 0…10
Convert 3unsignedInt 0…10
Convert 4unsignedInt 0…10
Logic Gate 2listDisable
Logic Gate 3listDisable
Logic Gate 4listDisable
Send StatuslistEach Input Event
Number of Inputslist1 Input
Output BehaviourlistNormal
Switch On DelayunsignedInt 0…2550
Switch Off DelayunsignedInt 0…2550
Cyclical Sending of StatuslistDisable
Convert Input Typelist1 Bit
Convert Output Typelist1 Bit
Convert Input ValueunsignedInt 0…655350
Convert Output ValueunsignedInt 0…655350
Convert Input ValueunsignedInt 0…2550
Convert Input ValueunsignedInt 0…30
Convert Input ValueunsignedInt 0…10
Convert Output ValueunsignedInt 0…2550
Convert Output ValueunsignedInt 0…30
Convert Output ValueunsignedInt 0…10
Scene NumberunsignedInt 1…641
Proportional Band (K)text4.0 K
Integral Timetext90
Proportional Band (K)text5.0 K
Integral Timetext240
Integral Timetext150
Integral Timetext100
Long Pres DurationunsignedInt 5…1005
Short PresslistStop / Step
pidChecklist
Fahrenheitfloat -1800…18500
Degree Celciusfloat -1800…18500
External Input 1listDisabled
External Input 2listDisabled
Temperature UnitlistCelcius
Temperature Sensor SelectlistInternal
Min ± Value Of Temperature To Send To BUSlistDisabled
Temperature ThresholdlistDisable
Sensor CalibrationsignedInt -50…500
External Sensor CalibrationsignedInt -50…500
Lower Limitlist5 °C
Lower Limitlist41.0 °F
Higher Limitlist30 °C
Higher Limitlist86.0 °F
Sending Interval For TemperatureunsignedInt 1…255180
Room Controller FunctionlistHeating
Command Value Objectlist1 Common Object
Heating Cooling ChangeoverlistAutomatic
Operation Mode After ResetlistAuto
Type Of Heating SystemlistWarm Water Heating
Type Of Cooling SystemlistCool Ceiling
Heating Control Typelist2 - Points
Cooling Control Typelist2 - Points
Heating Hysteresislist0.2 °C
Cooling Hysteresislist0.2 °C
Heating Sending Of Command Value PeriodunsignedInt 0…2550
Cooling Sending Of Command Value PeriodunsignedInt 0…2550
Heating Minimum Control Valuelist0 %
Heating Maximum Control Valuelist70 %
Cooling Minimum Control Valuelist0 %
Cooling Maximum Control Valuelist70 %
Heating Minimum Oscillation Value SendunsignedInt 1…1001
Cooling Minimum Oscillation Value SendunsignedInt 1…1001
Additional Heating SystemunsignedInt 0…10
Additional Cooling SystemunsignedInt 0…10
Heating Control Data TypelistSwitching (1 Bit)
Cooling Control Data TypelistSwitching (1 Bit)
Heating Offset From Setpoint Activelist1.0 °C
Cooling Offset From Setpoint Activelist1.0 °C
Heating Additional Hysteresislist0.2 °C
Cooling Additional Hysteresislist0.2 °C
Heating Sending Of Control Value PeriodicallyunsignedInt 0…2550
Cooling Sending Of Control Value PeriodicallyunsignedInt 0…2550
Disable Additional HeatingunsignedInt 0…10
Disable Additional CoolingunsignedInt 0…10
Sending Of SetpointlistOn Change
Period Of SendingunsignedInt 1…1001
Maximum Manual Setpoint Adjustment Allowedlist± 1.0 °C
End Of Manual OperationlistReset Manual Operation Object
Behaviour After Receiving New Mode SetpointlistReset Manual Operation
Setpoint Temperature After Power FailurelistNo Reaction
Heating Setpoint Comfort Modelist10.0 °C
Heating Setpoint Standby Modelist10.0 °C
Heating Setpoint Night Modelist10.0 °C
Heating Setpoint Frost Protectionlist0.0 °C
Cooling Setpoint Comfort Modelist10.0 °C
Cooling Setpoint Standby Modelist10.0 °C
Cooling Setpoint Night Modelist27.0 °C
Cooling Setpoint Heat Protectionlist25.0 °C
Minimum Dead Bandlist1.0 °C
Number Of Fan LevellistDisable
Fan Control ConnectlistHeating
Fan Level Control Individual ObjectunsignedInt 0…10
Fan Level Control Object ByteunsignedInt 0…10
Manual / Automatic Control Objectlist0: Manual / 1: Auto
Fan Level 1 Lower LimitunsignedInt 1…1001
Fan Level 2 Lower LimitunsignedInt 1…1001
Fan Level 3 Lower LimitunsignedInt 1…1001
Feedback Fan Level Individual ObjectunsignedInt 0…10
Feedback Fan Level Control ObjectunsignedInt 0…10
Feedback Manual / Automatic Objectlist0: Manual / 1: Auto
Fan Level After ResetlistAutomatic
Pwm Cycle TimeunsignedInt 1…1001
Maximum Manual Setpoint Adjustment Allowedlist± 1.0 °F
Heating Hysteresislist0.4 °F
Cooling Hsyteresislist0.4 °F
Minimum Dead Bandlist1.0 °F
Heating Setpoint Comfort Modelist50.0 °F
Heating Setpoint Standby Modelist50.0 °F
Heating Setpoint Night Modelist50.0 °F
Cooling Setpoint Comfort Modelist50.0 °F
Cooling Setpoint Standby Modelist50.0 °F
Cooling Setpoint Night Modelist50.0 °F
Heating Offset From Setpoint Activelist1.0 °F
Cooling Offset From Setpoint Activelist1.0 °F
Heating Setpoint Frost Protectionlist32.0 °F
Cooling Setpoint Heat Protectionlist77.0 °F
Command Value Data TypelistSwitching (1 Bit)
AC ControlunsignedInt 0…10
Heating Additional Hysteresislist1.2 °F
Cooling Additional Hysteresislist1.2 °F
Fan Level After ResetlistLevel 1
Send Temperature Value PeriodicallyunsignedInt 0…10
HVAC Control Mode SelectionlistDPT 1.100 [Bit]
Operation Heating Cooling Mode After ResetlistHeating
Fan Has Auto ModeunsignedInt 0…10
Fan Control TypelistScaling [DPT 5.001: %]
Heating Setpoint Auto Modelist10.0 °C
Cooling Setpoint Auto Modelist10.0 °C
Heating Setpoint Auto Modelist50.0 °F
Cooling Setpoint Auto Modelist50.0 °F
LED ConfigurationlistAlways Off
LED Color For OnlistOff
LED Color For OfflistOff
PolaritylistNormal
LEDs Backlight BrightnessunsignedInt 0…1000
LEDs Backlight DarkerunsignedInt 0…1000
LEDs Backlight Darker DelayunsignedInt 0…2551
DirectionlistBrighter
picPpicture
Temperature Sensor Typepicture
Setpoint Lower LimitunsignedInt 0…990
Setpoint Upper LimitunsignedInt 0…990
Source SelectionlistInternal Sensor
On / Off Button ActiveunsignedInt 0…10
Mode Button ActiveunsignedInt 0…10
Fan Button ActiveunsignedInt 0…10
emptyFillunsignedInt 0…2550
Thermostat State After Power FailurelistNo Reaction

Version history

ApplicationApp noFingerprintFirst seenSizeFile
ASQ-MS8T.1.1 0.3 latest$0007FB802026-11-25684 KBDownload
ASQ-MS8T.1.1 0.2$00076CEC2026-11-25679 KBDownload

About this file

This is the official ETS product database for the Asay Q [ASQ-MS8T.1.1] Asay Q Deluxe Series KNX Thermostat Internal Temp. Sensor + 2 External Inputs (ASQ-MS8T.1.1), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.