| 1 | LED - Input | Activate / deactivate operation LED | 1 Bit | 1.1 switch | CWT |
| 2 | LED - Input | Deactivate actuation LED | 1 Bit | 1.1 switch | CWT |
| 5 | Display - Input | Switch display on/off | 1 Bit | 1.1 switch | CW |
| 6 | Display - Input | Display brightness | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 7 | Display - Input | Display text, line 1, object 1 | 14 Bytes | DPT.16 | CW |
| 8 | Display - Input | Display text, line 1, object 2 | 14 Bytes | DPT.16 | CW |
| 9 | Display - Input | Display text, line 1, object 3 | 14 Bytes | DPT.16 | CW |
| 10 | Display - Input | Display text, line 2, object 1 | 14 Bytes | DPT.16 | CW |
| 11 | Display - Input | Display text, line 2, object 2 | 14 Bytes | DPT.16 | CW |
| 12 | Display - Input | Display text, line 2, object 3 | 14 Bytes | DPT.16 | CW |
| 13 | Display - Input/output | Temperature display in °F | 1 Bit | 1.1 switch | CRWTU |
| 13 | Display - Input/output | Temperature display in °C | 1 Bit | 1.1 switch | CRWTU |
| 15 | Object 1 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 16 | Object 2 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 17 | Object 3 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 18 | Object 4 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 19 | Object 5 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 20 | Object 6 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 21 | Object 7 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 22 | Object 8 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 23 | Object 9 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 24 | Object 10 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 25 | Object 11 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 26 | Object 12 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 27 | Object 13 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 28 | Object 14 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 29 | Object 15 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 30 | Object 16 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 31 | Object 17 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 32 | Object 18 for internal routing - Input/output | Dummy object | 2 Bytes | 9.1 temperature (°C) | WT |
| 35 | Comfort temperature, heating | | 2 Bytes | 9.1 temperature (°C) | WT |
| 36 | Comfort temperature, cooling | | 2 Bytes | 9.1 temperature (°C) | WT |
| 37 | Relative setpoints, heating | | 6 Bytes | 222.101 room temperature setpoint shift | WT |
| 38 | Relative setpoints, cooling | | 6 Bytes | 222.101 room temperature setpoint shift | WT |
| 39 | Relative setpoint, Extended Eco profile, heating | | 2 Bytes | 9.2 temperature difference (K) | WT |
| 40 | Relative setpoint, Extended Eco profile, cooling | | 2 Bytes | 9.2 temperature difference (K) | WT |
| 41 | Configuration of fan control | | 4 Bytes | 12.1 counter pulses (unsigned) | WT |
| 42 | Offset, temperature measurement | | 2 Bytes | 9.2 temperature difference (K) | WT |
| 43 | Factory reset | | 1 Bit | 1.15 reset | WT |
| 44 | Display contrast | | 1 Byte | 5.10 counter pulses (0..255) | WT |
| 45 | Display brightness | | 1 Byte | 5.10 counter pulses (0..255) | WT |
| 46 | Illumination length HBL | | 2 Bytes | 7.5 time (s) | WT |
| 50 | Controller ({{3589:Name}}) - input | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CWU |
| 50 | Controller ({{3589:Name}}) - input | Setpoint active operating mode | 2 Bytes | 9.1 temperature (°C) | CWU |
| 52 | Controller ({{3589:Name}}) - input | Operating mode switchover | 1 Byte | 20.102 HVAC mode | CWTU |
| 52 | Controller ({{3589:Name}}) - input | Comfort mode | 1 Bit | 1.1 switch | CWTU |
| 52 | RNST ({{80:Name}}) - Output | Operating mode switchover | 1 Byte | 20.102 HVAC mode | CRT |
| 52 | Controller ({{3589:Name}}) - input | Profile switchover | 1 Byte | 20.102 HVAC mode | CWTU |
| 52 | RNST ({{80:Name}}) - Output | Profile switchover | 1 Byte | 20.102 HVAC mode | CRT |
| 53 | Controller ({{3589:Name}}) - input | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 54 | Controller ({{3589:Name}}) - input | Night operation | 1 Bit | 1.1 switch | CWTU |
| 55 | Controller ({{3589:Name}}) - input | Frost/ heat protection | 1 Bit | 1.1 switch | CWTU |
| 56 | Controller ({{3589:Name}}) - input | Operating mode forced-control | 1 Byte | 20.102 HVAC mode | CWTU |
| 56 | Controller ({{3589:Name}}) - input | Forced object, profile switchover | 1 Byte | 20.102 HVAC mode | CWTU |
| 56 | RNST ({{3589:Name}}) - Output | Operating mode forced-control | 1 Byte | 20.102 HVAC mode | CRT |
| 56 | RNST ({{3589:Name}}) - Output | Forced object, profile switchover | 1 Byte | 20.102 HVAC mode | CRT |
| 57 | Controller ({{3589:Name}}) - input | Presence button | 1 Bit | 1.1 switch | CWTU |
| 57 | Controller ({{3589:Name}}) - input | Presence detector | 1 Bit | 1.1 switch | CWTU |
| 58 | Controller ({{3589:Name}}) - input | Window status | 1 Bit | 1.19 window/door | CWU |
| 59 | Controller ({{3589:Name}}) - input | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CWTU |
| 59 | Controller ({{3589:Name}}) - output | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CRT |
| 59 | RNST ({{80:Name}}) - Output | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CRT |
| 60 | Controller ({{3589:Name}}) - output | Controller status | 1 Byte | | CRT |
| 60 | Controller ({{3589:Name}}) - output | KNX status operating mode | 1 Byte | 20.102 HVAC mode | CRT |
| 60 | Controller ({{3589:Name}}) - output | Controller status, Comfort mode | 1 Bit | 1.1 switch | CRT |
| 60 | Controller ({{3589:Name}}) - output | Controller status, Standby mode | 1 Bit | 1.1 switch | CRT |
| 60 | Controller ({{3589:Name}}) - output | Controller status, night mode | 1 Bit | 1.1 switch | CRT |
| 60 | Controller ({{3589:Name}}) - output | Controller status, frost/heat protection | 1 Bit | 1.1 switch | CRT |
| 60 | Controller ({{3589:Name}}) - output | Controller status, contr. disabled | 1 Bit | 1.1 switch | CRT |
| 60 | Controller ({{3589:Name}}) - output | Contr. status, heating/cooling | 1 Bit | 1.1 switch | CRT |
| 60 | Controller ({{3589:Name}}) - output | Controller status contr. inactive | 1 Bit | 1.1 switch | CRT |
| 60 | Controller ({{3589:Name}}) - output | Controller status, frost alarm | 1 Bit | 1.1 switch | CRT |
| 60 | Controller ({{3589:Name}}) - output | KNX status profile | 1 Byte | 20.102 HVAC mode | CRT |
| 61 | Controller ({{3589:Name}}) - output | Currently active operating mode | 1 Byte | 20.102 HVAC mode | CRT |
| 61 | RNST ({{80:Name}}) - Input | Currently active operating mode | 1 Byte | 20.102 HVAC mode | CWTUI |
| 61 | Controller ({{3589:Name}}) - output | Currently active profile | 1 Byte | 20.102 HVAC mode | CRT |
| 61 | RNST ({{80:Name}}) - Input | Currently active profile | 1 Byte | 20.102 HVAC mode | CWTUI |
| 62 | Controller ({{3589:Name}}) - output | Currently active Standby profile | 1 Bit | 1.1 switch | CRT |
| 62 | RNST ({{80:Name}}) - Input | Currently active Standby profile | 1 Bit | 1.1 switch | CWTUI |
| 64 | Controller ({{3589:Name}}) - output | Set temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 64 | RNST ({{80:Name}}) - Input | Set temperature | 2 Bytes | 9.1 temperature (°C) | CWTUI |
| 66 | Controller ({{3589:Name}}) - output | Current setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 66 | RNST ({{80:Name}}) - Input | Current setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CWTUI |
| 67 | Controller ({{3589:Name}}) - input | Preset setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CWU |
| 67 | RNST ({{80:Name}}) - Output | Preset setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 68 | Controller ({{3589:Name}}) - output | Status signal addition | 1 Byte | | CRT |
| 68 | Controller ({{3589:Name}}) - output | KNX status | 2 Bytes | 22.101 RHCC status | CRT |
| 68 | RNST ({{80:Name}}) - Input | KNX status | 2 Bytes | 22.101 RHCC status | CWTUI |
| 69 | Controller ({{3589:Name}}) - output | KNX status forced operating mode | 1 Byte | 20.102 HVAC mode | CRT |
| 69 | Controller ({{3589:Name}}) - output | KNX status forced profile | 1 Byte | 20.102 HVAC mode | CRT |
| 70 | Controller ({{3589:Name}}) - input | Outdoor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 71 | Controller ({{3589:Name}}) - input | Limit of cooling setpoint temperature | 1 Bit | 1.1 switch | CWU |
| 72 | Controller ({{3589:Name}}) - input | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | W |
| 73 | Controller ({{3589:Name}}) - input | Temperature drop detection | 1 Bit | 1.19 window/door | W |
| 74 | Controller ({{3589:Name}}) - output | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | RT |
| 75 | Controller ({{3589:Name}}) - input | Controller signal | 1 Bit | 1.3 enable | W |
| 76 | Controller ({{3589:Name}}) - input | Controller signal | 1 Bit | 1.11 state | W |
| 77 | Controller ({{3589:Name}}) - input | Controller signal | 1 Bit | 1.11 state | W |
| 78 | Controller ({{3589:Name}}) - output | Set temperature | 2 Bytes | 9.1 temperature (°C) | RT |
| 79 | Controller ({{3589:Name}}) - output | Heating/cooling switchover | 1 Bit | 1.100 heating/cooling | T |
| 80 | Controller ({{3589:Name}}) - output | Set temperature, additional level | 2 Bytes | 9.1 temperature (°C) | RT |
| 81 | Controller ({{3589:Name}}) - output | Currently active operating mode | 1 Byte | 20.102 HVAC mode | T |
| 82 | Controller ({{3589:Name}}) - output | Currently active Extended Eco profile | 1 Bit | 1.1 switch | T |
| 83 | Controller ({{3589:Name}}) - input | Standby profile switchover | 1 Bit | 1.1 switch | CW |
| 83 | RNST ({{80:Name}}) - Output | Standby profile switchover | 1 Bit | 1.1 switch | CRT |
| 84 | Controller ({{3589:Name}}) - output | Status, Standby profile | 1 Bit | 1.1 switch | CRT |
| 85 | Controller ({{3589:Name}}) - input | Forced object, profile switchover, Standby | 1 Bit | 1.1 switch | CW |
| 86 | Controller ({{3589:Name}}) - output | Forced status, Standby profile | 1 Bit | 1.1 switch | CRT |
| 87 | Controller ({{3589:Name}}) - input/output | Comfort temperature, heating | 2 Bytes | 9.1 temperature (°C) | WT |
| 88 | Controller ({{3589:Name}}) - input/output | Comfort temperature, cooling | 2 Bytes | 9.1 temperature (°C) | WT |
| 89 | Controller ({{3589:Name}}) - input/output | Relative setpoints, heating | 6 Bytes | 222.101 room temperature setpoint shift | WT |
| 90 | Controller ({{3589:Name}}) - input/output | Relative setpoints, cooling | 6 Bytes | 222.101 room temperature setpoint shift | WT |
| 91 | Controller ({{3589:Name}}) - input/output | Relative setpoint, Extended Eco profile, heating | 2 Bytes | 9.2 temperature difference (K) | WT |
| 92 | Controller ({{3589:Name}}) - input/output | Relative setpoint, Extended Eco profile, cooling | 2 Bytes | 9.2 temperature difference (K) | WT |
| 93 | Controller ({{3589:Name}}) - input | Factory reset | 1 Bit | 1.15 reset | W |
| 94 | Controller ({{3589:Name}}) - output | Current setpoint shifting | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 94 | RNST ({{80:Name}}) - Input | Current setpoint shifting | 2 Bytes | 9.2 temperature difference (K) | CWTUI |
| 95 | RNST ({{80:Name}}) - Output | Preset setpoint shifting | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 95 | Controller ({{3589:Name}}) - input | Preset setpoint shifting | 2 Bytes | 9.2 temperature difference (K) | CWU |
| 98 | Controller ({{3589:Name}}) - input | Disable controller | 1 Bit | 1.1 switch | CWU |
| 100 | Controller ({{3589:Name}}) - output | Command value for heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 100 | Controller ({{3589:Name}}) - output | Command value heating (PWM) | 1 Bit | 1.1 switch | CRT |
| 100 | Controller ({{3589:Name}}) - output | Command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 100 | Controller ({{3589:Name}}) - output | Command value heating/cooling (PWM) | 1 Bit | 1.1 switch | CRT |
| 102 | Controller ({{3589:Name}}) - output | Command value cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 102 | Controller ({{3589:Name}}) - output | Command value cooling (PWM) | 1 Bit | 1.1 switch | CRT |
| 104 | Controller ({{3589:Name}}) - output | PWM command value for heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 104 | Controller ({{3589:Name}}) - output | PWM command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 106 | Controller ({{3589:Name}}) - output | PWM command value for cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 108 | Controller ({{3589:Name}}) - input | Command value limit | 1 Bit | 1.1 switch | CWU |
| 110 | Controller ({{3589:Name}}) - input | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 111 | Controller ({{3589:Name}}) - input | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | W |
| 111 | RNST ({{3589:Name}}) - Input | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | CWTUI |
| 112 | Controller ({{3589:Name}}) - input | Set temperature | 2 Bytes | 9.1 temperature (°C) | W |
| 113 | Controller ({{3589:Name}}) - input | Heating/cooling switchover | 1 Bit | 1.1 switch | W |
| 114 | Controller ({{3589:Name}}) - output | Heating indication | 1 Bit | 1.1 switch | CRT |
| 115 | Controller ({{3589:Name}}) - output | Cooling indication | 1 Bit | 1.1 switch | CRT |
| 116 | Controller ({{3589:Name}}) - output | Controller signal | 1 Bit | 1.3 enable | T |
| 117 | Controller ({{3589:Name}}) - output | Controller signal | 1 Bit | 1.11 state | T |
| 118 | Controller ({{3589:Name}}) - output | Controller signal | 1 Bit | 1.11 state | T |
| 119 | Controller ({{3589:Name}}) - input | Set temperature, additional level | 2 Bytes | 9.1 temperature (°C) | W |
| 120 | Controller ({{3589:Name}}) - output | Command value basic level | 1 Byte | 5.1 percentage (0..100%) | T |
| 121 | Controller ({{3589:Name}}) - output | Command value additional level | 1 Byte | 5.1 percentage (0..100%) | T |
| 124 | Sensor - Output | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 125 | Sensor - Input | External temperature value | 2 Bytes | 9.1 temperature (°C) | CW |
| 126 | Controller ({{3589:Name}}) - input | Measured temperature value | 2 Bytes | 9.1 temperature (°C) | W |
| 127 | Controller ({{3589:Name}}) - output | Temperature drop detection | 1 Bit | 1.19 window/door | CRT |
| 128 | Controller ({{3589:Name}}) - output | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | RT |
| 129 | Controller ({{3589:Name}}) - output | Temperature drop detection | 1 Bit | 1.19 window/door | RT |
| 130 | Controller ({{3589:Name}}) - input/output | Offset, temperature measurement | 2 Bytes | 9.2 temperature difference (K) | WT |
| 131 | Controller ({{3589:Name}}) - input | Factory reset | 1 Bit | 1.15 reset | W |
| 135 | Controller ({{3589:Name}}) - input | Ventilation, automatic/manual | 1 Bit | 1.1 switch | CW |
| 136 | Controller ({{3589:Name}}) - output | Ventilation, fan level 1-3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 136 | Controller ({{3589:Name}}) - output | Ventilation, fan level 1 | 1 Bit | 1.1 switch | CRT |
| 137 | Controller ({{3589:Name}}) - output | Ventilation, fan level 2 | 1 Bit | 1.1 switch | CRT |
| 138 | Controller ({{3589:Name}}) - output | Ventilation, fan level 3 | 1 Bit | 1.1 switch | CRT |
| 145 | Controller ({{3589:Name}}) - input | Ventilation, forced position | 1 Bit | 1.1 switch | CW |
| 146 | Controller ({{3589:Name}}) - input | Ventilation, level limit | 1 Bit | 1.1 switch | CW |
| 147 | Controller ({{3589:Name}}) - input | Ventilation, fan protection | 1 Bit | 1.1 switch | CW |
| 148 | Controller ({{3589:Name}}) - output | Ventilation visualisation | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 148 | RNST ({{80:Name}}) - Input | Ventilation visualisation | 1 Byte | 5.10 counter pulses (0..255) | CWTUI |
| 149 | Controller ({{3589:Name}}) - input | Specification, ventilation, automatic/manual | 1 Bit | 1.1 switch | CW |
| 149 | RNST ({{80:Name}}) - Output | Specification, ventilation, automatic/manual | 1 Bit | 1.1 switch | CRT |
| 150 | Controller ({{3589:Name}}) - output | Feedback, ventilation, automatic/manual | 1 Bit | 1.1 switch | CRT |
| 150 | RNST ({{80:Name}}) - Input | Feedback, ventilation, automatic/manual | 1 Bit | 1.1 switch | CWTUI |
| 151 | Controller ({{3589:Name}}) - input | Fan level specification | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 151 | RNST ({{80:Name}}) - Output | Fan level specification | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 152 | Controller ({{3589:Name}}) - output | Feedback for fan level | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 152 | RNST ({{80:Name}}) - Input | Feedback for fan level | 1 Byte | 5.10 counter pulses (0..255) | CWTUI |
| 153 | Controller ({{3589:Name}}) - input | Command value basic level | 1 Byte | 5.1 percentage (0..100%) | W |
| 154 | Controller ({{3589:Name}}) - input | Command value additional level | 1 Byte | 5.1 percentage (0..100%) | W |
| 155 | Controller ({{3589:Name}}) - input | Currently active operating mode | 1 Byte | 20.102 HVAC mode | W |
| 156 | Controller ({{3589:Name}}) - input | Currently active Extended Eco profile | 1 Bit | 1.1 switch | W |
| 157 | Controller ({{3589:Name}}) - input/output | Configuration of fan control | 4 Bytes | 12.1 counter pulses (unsigned) | WT |
| 158 | Controller ({{3589:Name}}) - input | Factory reset | 1 Bit | 1.15 reset | W |
| 159 | Controller ({{3589:Name}}) - input | Heating/cooling switchover | 1 Bit | 1.100 heating/cooling | W |
| 160 | Controller ({{3589:Name}}) - output | Output voltage rotation angle conversion | 2 Bytes | 9.20 voltage (mV) | CT |