| Downloaderkennung | list | Downloaded |
| Hardwaretype | list | $00 0A 00 00 00 4E |
| Delay after bus voltage return
Minutes (0...59) | unsignedInt 0…59 | 0 |
| Seconds (0...59) | unsignedInt 0…59 | 17 |
| Basic sensitivity of all
PIR sectors | list | high |
| Basisempfindlichkeit
PIR Sektor C | list | high |
| Basisempfindlichkeit
PIR Sektor B | list | high |
| Basisempfindlichkeit
PIR-Sektor A | list | high |
| Sensitivity
PIR-Sector A | list | 100% |
| Sensitivity
PIR-Sector B | list | 100% |
| Sensitivity
PIR-Sector C | list | 100% |
| Adjuster for
sensitivity PIR-Sectors A-C | list | activated |
| Interlock of all PIR-sectors
by external telegram when | list | OFF |
| Interlock time
seconds (0...59) | unsignedInt 0…59 | 3 |
| Sending the brightness value | list | on change |
| Send on brightness change by
(5...200 lux) | list | 20 lux |
| Time for cyclical transmission
Minutes (0...59) | unsignedInt 0…59 | 3 |
| Seconds (0...59) | unsignedInt 0…59 | 0 |
| Sensor calibration | list | Factory calibration |
| Behaviour in the case of non-executed
calibration | list | Do not send brightness value |
| Walking test after
ETSprogramming | list | deactivated |
| Display of motion impulses
via walking testLED | list | only with active walking test |
| Use function block 1? | list | yes |
| Gruppenzuordnung
Funktionsblock 1 | list | no group assigned |
| Use function block 2? | list | no |
| Group assignment
function block 2 | list | no group assigned |
| Use function block 3? | list | no |
| Group assignment
function block 3 | list | no group assigned |
| Use function block 4? | list | no |
| Group assignment
function block 4 | list | no group assigned |
| Use function block 5? | list | no |
| Group assignment
function block 5 | list | no group assigned |
| Use switch-over of the function
block groups? | list | no |
| Polarity function block groups
switch-over | list | 0 = Group 1 / 1 = Group 2 |
| Switch-over behaviour | list | immediately |
| Active group after
bus voltage return | list | Group 1 active |
| Application | list | Motion detector |
| Application type | list | Single device |
| Operating mode | list | Fully automatic (Auto ON, Auto OFF) |
| Behaviour after
bus voltage return | list | no reaction |
| Behaviour after
ETS programming | list | no reaction |
| Function ouput 1 | list | Switching |
| Function ouput 2 | list | no function |
| Function ouput 1 | list | Signalling |
| Allocation
PIR-Sector A | list | assigned |
| Allocation
PIR-Sector B | list | assigned |
| Allocation
PIR-Sector C | list | assigned |
| detection of the brightness value
by | list | internal sensor |
| Weighting of the brightness value
internal to external | list | 50% to 50% |
| Evaluation of the twilight level ? | list | yes (brightness dependent operation) |
| Twilight level
(10...2,000 Lux) | unsignedInt 10…2000 | 500 |
| Overwrite twilight level in device
for ETS-Download ? | list | yes |
| Object
"Presetting twilight level" | list | disabled |
| Feedback
"Active twilight level" | list | active signalling object |
| Evaluation of the twilight level
on external motion telegram | list | yes (brightness dependent operation) |
| Use Teach function ? | list | no |
| Polarity for object
"Teach twilight level" | list | 0 = inactive / 1 = active |
| Evaluation of the twilight level | list | in main unit and extension |
| Send cyclical transmission during
the detection? | list | no |
| Time for cyclical transmission
Minutes (0...59) | unsignedInt 0…59 | 0 |
| Seconds (0...59) | unsignedInt 0…59 | 10 |
| Use evaluation
delay? | list | no |
| Delay time
Minutes (0...59) | unsignedInt 0…59 | 0 |
| Seconds (0...59) | unsignedInt 0…59 | 30 |
| Monitoring time
minutes (0...59) | unsignedInt 0…59 | 0 |
| Number of motion impulses in the
monitoring time (1...255) (typ. 20) | unsignedInt 1…255 | 20 |
| Type of additional
transmission delay | list | according to parameter |
| Additional transmission delay
Minutes (0...59) | unsignedInt 0…59 | 0 |
| Time extension for
additional transmission delay | list | no extension |
| Minimum additional transmission delay
minutes (0...59) | unsignedInt 0…59 | 0 |
| Maximum additional transmission delay
minutes (0...59) | unsignedInt 0…59 | 3 |
| Evaluation
brief presence | list | no |
| Time window detec. of brief presence
Seconds (10...59) | unsignedInt 10…59 | 10 |
| Measurement of the time period after
end of the last motion | list | deactivated |
| Feedback
"Time after last motion" | list | active signalling object |
| Cycle time for autom. transmission of
Hours (0...59) | unsignedInt 0…59 | 0 |
| Minutes (10...59) | unsignedInt 10…59 | 10 |
| Main unit "Staircase function"
with run-on-time in the actuator? | list | no |
| Hysteresis for switch-off brightness
presence detector (10...800 lux) | unsignedInt 10…800 | 300 |
| Teach function
for switch-off brightness | list | disabled |
| Overwrite switch-off brightness in
device for ETS-Download ? | list | yes |
| Operating mode
Teach | list | 0 = inactive / 1 = active |
| Transmission delay after reaching
the switch-off brightness | list | like additional transmission delay |
| Time for switch-off delay
Minutes (0...59) | unsignedInt 0…59 | 5 |
| Function of the output:
"Switching" | list | can be set under "FB - General" |
| Send telegram at the beginning
of the detection? | list | yes |
| Telegram at the beginning
of the detection | list | ON telegram |
| Telegram triggering on
retriggering? | list | no |
| Send telegram at the end of the
detection? | list | yes |
| Telegram at the end
of the detection | list | OFF telegram |
| Function of the output:
"Staircase function" | list | can be set under "FB - General" |
| Function of the output:
"Switching with forced position" | list | can be set under "FB - General" |
| Forced position at the beginning
of the detection | list | Forced position active, ON |
| Forced position at the end
of the detection | list | Forced position active, OFF |
| Function of the output:
"Dimming value transmitter" | list | can be set under "FB - General" |
| Dimming value at the beginning
of the detection(0...100 %) | unsignedInt 0…100 | 100 |
| Dimming value at the end
of the detection(0...100 %) | unsignedInt 0…100 | 0 |
| Function of the output:
"Light scene extension" | list | can be set under "FB - General" |
| Light scene number at the beginning
of the detection (1...64) | unsignedInt 1…64 | 1 |
| Light scene number at the end
of the detection (1...64) | unsignedInt 1…64 | 1 |
| Function of the output:
"Temperature value transmitter" | list | can be set under "FB - General" |
| Temperature value at the beginning
of the detection | list | 23 °C |
| Temperature value at the end
of the detection | list | 21 °C |
| Function of the output:
"Brightness value transmitter" | list | can be set under "FB - General" |
| Brightness value at the beginning
of the detection | list | 1,000 lux |
| Brightness value at the end
of the detection | list | 750 lux |
| Function of the output:
"Operat mode room temperature ctrl" | list | can be set under "FB - General" |
| Operating mode at the beginning
of the detection | list | Comfort |
| Operating mode at the end
of the detection | list | Standby |
| Function of the output:
"No function" | list | can be set under "FB - General" |
| Send telegram at the beginning
of the detection? | list | no |
| Send telegram at the end of the
detection? | list | no |
| Polarity of the
disabling object | list | 0 = enable / 1 = disable |
| Behaviour at the beginning
of the disabling function | list | disable and send no telegram |
| Telegram at the beginning of the
disabling function | list | OFF telegram |
| Forced position at the beginningof
disabling function | list | Forced position active, OFF |
| Dimming value at the beginning of the
disabling function (0...100 %) | unsignedInt 0…100 | 0 |
| Light scene number at beginning of
disabling function (1...64) | unsignedInt 1…64 | 1 |
| Telegram at the beginning of the
disabling function | list | 21 °C |
| Brightness at the beginning of the
disabling function | list | 750 lux |
| Operating mode at the beginning
of disabling function | list | Standby |
| Behaviour at the end of
the disabling function | list | enable and send no telegram |
| Function of the output:
"Detector" | list | can be set under "FB - General" |
| Message telegram at beginning of the
detection | list | ON telegram |
| Message telegram at the end
of the detection | list | OFF telegram |