KNX Database

Presence detector Universal 3361-1

Albrecht Jung · Order number 3361-1 · Physical sensors › Movement

Präsenzmelder Universal A01112

Download .knxprod Presence detector Universal A01112 1.2 · 574 KB

Product

ManufacturerAlbrecht Jung
Product namePresence detector Universal
Order number3361-1
Product textPräsenzmelder / Deckenwächter Universal
HardwarePräsenzmelder Komfort
MediumTwisted Pair
Rail mountedNo
RegistrationRegistered · 2012-09-25
Languagesen-US, es-ES, fr-FR, nl-NL, it-IT, ru-RU
Catalog entryM-0004_H-4.20.2F.2F.203361.2D1-1-O000A_HP-A011-12-40DE-O000A_CI-3361.2D1-1
Fingerprint40DE
SHA-256cb7e284762d88a5355ac80e4412e6fe986c258289e8b9938279426530f51cb83
First seen2026-11-25
Markets59 markets

Application program: Presence detector Universal A01112 1.2

Application number$A011
Version1.2
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters3776
Group objects220
Group objects (220)
NoNameFunctionSizeDPTFlags
0Motion detection - InputInterlock PIR sensor1 BitDPT.1CW
1Brightness sensor - OutputMeasured brightness value2 Bytes9.4 lux (Lux)CRT
2Brightness sensor - InputSensor calibration2 Bytes9.4 lux (Lux)CW
3FB1 - Output 1Switching1 BitDPT.1CT
3FB1 - Output 1Signalling1 BitDPT.1CT
3FB1 - Output 1Switching staircase1 BitDPT.1CT
3FB1 - Output 1Forced position2 Bit2.1 switch controlCT
3FB1 - Output 1Dimming value1 Byte5.1 percentage (0..100%)CT
3FB1 - Output 1Scene extension1 Byte9.4 lux (Lux)CT
3FB1 - Output 1Brightness value2 Bytes9.4 lux (Lux)CT
3FB1 - Output 1Temperature value2 Bytes9.1 temperature (°C)CT
3FB1 - Output 1Operating mode1 Byte9.4 lux (Lux)CT
4FB1 - Output 2Operating mode1 Byte9.1 temperature (°C)CT
4FB1 - Output 2Temperature value2 Bytes9.1 temperature (°C)CT
4FB1 - Output 2Brightness value2 Bytes9.4 lux (Lux)CT
4FB1 - Output 2Scene extension1 Byte9.1 temperature (°C)CT
4FB1 - Output 2Dimming value1 Byte5.1 percentage (0..100%)CT
4FB1 - Output 2Forced position2 Bit2.1 switch controlCT
4FB1 - Output 2Switching staircase1 BitDPT.1CT
4FB1 - Output 2Switching1 BitDPT.1CT
5FB1 - InputPresetting twilight level2 Bytes9.4 lux (Lux)CW
6FB1 - InputTeach twilight level1 BitDPT.1CW
7FB1 - Feedback - OutputActive twilight level2 Bytes9.4 lux (Lux)CR
7FB1 - Feedback - OutputActive twilight level2 Bytes9.4 lux (Lux)CT
8FB1 - InputDeactivation of twilight level1 BitDPT.1CWT
8FB1 - Input / OutputDeactivation of twilight level1 BitDPT.1CWT
8FB1 - OutputDeactivation of twilight level1 BitDPT.1CT
9FB1 - InputSwitch-off brightness Teach1 BitDPT.1CW
10FB1 - InputExternal brightness sensor2 Bytes9.4 lux (Lux)CW
11FB1 - Feedback - OutputActive brightness value2 Bytes9.4 lux (Lux)CR
12FB1 - InputExternal motion1 BitDPT.1CW
13FB1 - OutputMovement1 BitDPT.1CT
14FB1 - InputFactor add. transmission delay1 Byte5.10 counter pulses (0..255)CW
15FB1 - InputLighting manual ON/OFF1 BitDPT.1CW
16FB1 - InputDisabling1 BitDPT.1CRW
17FB1 - OutputTime after last motion2 BytesDPT.7CT
17FB1 - OutputTime after last motion2 BytesDPT.7CR
18FB2 - Output 1Switching1 BitDPT.1CT
18FB2 - Output 1Signalling1 BitDPT.1CT
18FB2 - Output 1Switching staircase1 BitDPT.1CT
18FB2 - Output 1Forced position2 Bit2.1 switch controlCT
18FB2 - Output 1Dimming value1 Byte5.1 percentage (0..100%)CT
18FB2 - Output 1Scene extension1 Byte9.4 lux (Lux)CT
18FB2 - Output 1Brightness value2 Bytes9.4 lux (Lux)CT
18FB2 - Output 1Temperature value2 Bytes9.1 temperature (°C)CT
18FB2 - Output 1Operating mode1 Byte9.4 lux (Lux)CT
19FB2 - Output 2Operating mode1 Byte9.1 temperature (°C)CT
19FB2 - Output 2Temperature value2 Bytes9.1 temperature (°C)CT
19FB2 - Output 2Brightness value2 Bytes9.4 lux (Lux)CT
19FB2 - Output 2Scene extension1 Byte9.1 temperature (°C)CT
19FB2 - Output 2Dimming value1 Byte5.1 percentage (0..100%)CT
19FB2 - Output 2Forced position2 Bit2.1 switch controlCT
19FB2 - Output 2Switching staircase1 BitDPT.1CT
19FB2 - Output 2Switching1 BitDPT.1CT
20FB2 - InputPresetting twilight level2 Bytes9.4 lux (Lux)CW
21FB2 - InputTeach twilight level1 BitDPT.1CW
22FB2 - Feedback - OutputActive twilight level2 Bytes9.4 lux (Lux)CR
22FB2 - Feedback - OutputActive twilight level2 Bytes9.4 lux (Lux)CT
23FB2 - InputDeactivation of twilight level1 BitDPT.1CWT
23FB2 - Input / OutputDeactivation of twilight level1 BitDPT.1CWT
23FB2 - OutputDeactivation of twilight level1 BitDPT.1CT
24FB2 - InputSwitch-off brightness Teach1 BitDPT.1CW
25FB2 - InputExternal brightness sensor2 Bytes9.4 lux (Lux)CW
26FB2 - Feedback - OutputActive brightness value2 Bytes9.4 lux (Lux)CR
27FB2 - InputExternal motion1 BitDPT.1CW
28FB2 - OutputMovement1 BitDPT.1CT
29FB2 - InputFactor add. transmission delay1 Byte5.10 counter pulses (0..255)CW
30FB2 - InputLighting manual ON/OFF1 BitDPT.1CW
31FB2 - InputDisabling1 BitDPT.1CRW
32FB2 - OutputTime after last motion2 BytesDPT.7CT
32FB2 - OutputTime after last motion2 BytesDPT.7CR
33FB3 - Output 1Switching1 BitDPT.1CT
33FB3 - Output 1Signalling1 BitDPT.1CT
33FB3 - Output 1Switching staircase1 BitDPT.1CT
33FB3 - Output 1Forced position2 Bit2.1 switch controlCT
33FB3 - Output 1Dimming value1 Byte5.1 percentage (0..100%)CT
33FB3 - Output 1Scene extension1 Byte9.4 lux (Lux)CT
33FB3 - Output 1Brightness value2 Bytes9.4 lux (Lux)CT
33FB3 - Output 1Temperature value2 Bytes9.1 temperature (°C)CT
33FB3 - Output 1Operating mode1 Byte9.4 lux (Lux)CT
34FB3 - Output 2Operating mode1 Byte9.1 temperature (°C)CT
34FB3 - Output 2Temperature value2 Bytes9.1 temperature (°C)CT
34FB3 - Output 2Brightness value2 Bytes9.4 lux (Lux)CT
34FB3 - Output 2Scene extension1 Byte9.1 temperature (°C)CT
34FB3 - Output 2Dimming value1 Byte5.1 percentage (0..100%)CT
34FB3 - Output 2Forced position2 Bit2.1 switch controlCT
34FB3 - Output 2Switching staircase1 BitDPT.1CT
34FB3 - Output 2Switching1 BitDPT.1CT
35FB3 - InputPresetting twilight level2 Bytes9.4 lux (Lux)CW
36FB3 - InputTeach twilight level1 BitDPT.1CW
37FB3 - Feedback - OutputActive twilight level2 Bytes9.4 lux (Lux)CR
37FB3 - Feedback - OutputActive twilight level2 Bytes9.4 lux (Lux)CT
38FB3 - InputDeactivation of twilight level1 BitDPT.1CWT
38FB3 - Input / OutputDeactivation of twilight level1 BitDPT.1CWT
38FB3 - OutputDeactivation of twilight level1 BitDPT.1CT
39FB3 - InputSwitch-off brightness Teach1 BitDPT.1CW
40FB3 - InputExternal brightness sensor2 Bytes9.4 lux (Lux)CW
41FB3 - Feedback - OutputActive brightness value2 Bytes9.4 lux (Lux)CR
42FB3 - InputExternal motion1 BitDPT.1CW
43FB3 - OutputMovement1 BitDPT.1CT
44FB3 - InputFactor add. transmission delay1 Byte5.10 counter pulses (0..255)CW
45FB3 - InputLighting manual ON/OFF1 BitDPT.1CW
46FB3 - InputDisabling1 BitDPT.1CRW
47FB3 - OutputTime after last motion2 BytesDPT.7CT
47FB3 - OutputTime after last motion2 BytesDPT.7CR
48FB4 - Output 1Switching1 BitDPT.1CT
48FB4 - Output 1Signalling1 BitDPT.1CT
48FB4 - Output 1Switching staircase1 BitDPT.1CT
48FB4 - Output 1Forced position2 Bit2.1 switch controlCT
48FB4 - Output 1Dimming value1 Byte5.1 percentage (0..100%)CT
48FB4 - Output 1Scene extension1 Byte9.4 lux (Lux)CT
48FB4 - Output 1Brightness value2 Bytes9.4 lux (Lux)CT
48FB4 - Output 1Temperature value2 Bytes9.1 temperature (°C)CT
48FB4 - Output 1Operating mode1 Byte9.4 lux (Lux)CT
49FB4 - Output 2Operating mode1 Byte9.1 temperature (°C)CT
49FB4 - Output 2Temperature value2 Bytes9.1 temperature (°C)CT
49FB4 - Output 2Brightness value2 Bytes9.4 lux (Lux)CT
49FB4 - Output 2Scene extension1 Byte9.1 temperature (°C)CT
49FB4 - Output 2Dimming value1 Byte5.1 percentage (0..100%)CT
49FB4 - Output 2Forced position2 Bit2.1 switch controlCT
49FB4 - Output 2Switching staircase1 BitDPT.1CT
49FB4 - Output 2Switching1 BitDPT.1CT
50FB4 - InputPresetting twilight level2 Bytes9.4 lux (Lux)CW
51FB4 - InputTeach twilight level1 BitDPT.1CW
52FB4 - Feedback - OutputActive twilight level2 Bytes9.4 lux (Lux)CR
52FB4 - Feedback - OutputActive twilight level2 Bytes9.4 lux (Lux)CT
53FB4 - InputDeactivation of twilight level1 BitDPT.1CWT
53FB4 - Input / OutputDeactivation of twilight level1 BitDPT.1CWT
53FB4 - OutputDeactivation of twilight level1 BitDPT.1CT
54FB4 - InputSwitch-off brightness Teach1 BitDPT.1CW
55FB4 - InputExternal brightness sensor2 Bytes9.4 lux (Lux)CW
56FB4 - Feedback - OutputActive brightness value2 Bytes9.4 lux (Lux)CR
57FB4 - InputExternal motion1 BitDPT.1CW
58FB4 - OutputMovement1 BitDPT.1CT
59FB4 - InputFactor add. transmission delay1 Byte5.10 counter pulses (0..255)CW
60FB4 - InputLighting manual ON/OFF1 BitDPT.1CW
61FB4 - InputDisabling1 BitDPT.1CRW
62FB4 - OutputTime after last motion2 BytesDPT.7CT
62FB4 - OutputTime after last motion2 BytesDPT.7CR
63FB5 - Output 1Switching1 BitDPT.1CT
63FB5 - Output 1Signalling1 BitDPT.1CT
63FB5 - Output 1Switching staircase1 BitDPT.1CT
63FB5 - Output 1Forced position2 Bit2.1 switch controlCT
63FB5 - Output 1Dimming value1 Byte5.1 percentage (0..100%)CT
63FB5 - Output 1Scene extension1 Byte9.4 lux (Lux)CT
63FB5 - Output 1Brightness value2 Bytes9.4 lux (Lux)CT
63FB5 - Output 1Temperature value2 Bytes9.1 temperature (°C)CT
63FB5 - Output 1Operating mode1 Byte9.4 lux (Lux)CT
64FB5 - Output 2Operating mode1 Byte9.1 temperature (°C)CT
64FB5 - Output 2Temperature value2 Bytes9.1 temperature (°C)CT
64FB5 - Output 2Brightness value2 Bytes9.4 lux (Lux)CT
64FB5 - Output 2Scene extension1 Byte9.1 temperature (°C)CT
64FB5 - Output 2Dimming value1 Byte5.1 percentage (0..100%)CT
64FB5 - Output 2Forced position2 Bit2.1 switch controlCT
64FB5 - Output 2Switching staircase1 BitDPT.1CT
64FB5 - Output 2Switching1 BitDPT.1CT
65FB5 - InputPresetting twilight level2 Bytes9.4 lux (Lux)CW
66FB5 - InputTeach twilight level1 BitDPT.1CW
67FB5 - Feedback - OutputActive twilight level2 Bytes9.4 lux (Lux)CR
67FB5 - Feedback - OutputActive twilight level2 Bytes9.4 lux (Lux)CT
68FB5 - InputDeactivation of twilight level1 BitDPT.1CWT
68FB5 - Input / OutputDeactivation of twilight level1 BitDPT.1CWT
68FB5 - OutputDeactivation of twilight level1 BitDPT.1CT
69FB5 - InputSwitch-off brightness Teach1 BitDPT.1CW
70FB5 - InputExternal brightness sensor2 Bytes9.4 lux (Lux)CW
71FB5 - Feedback - OutputActive brightness value2 Bytes9.4 lux (Lux)CR
72FB5 - InputExternal motion1 BitDPT.1CW
73FB5 - OutputMovement1 BitDPT.1CT
74FB5 - InputFactor add. transmission delay1 Byte5.10 counter pulses (0..255)CW
75FB5 - InputLighting manual ON/OFF1 BitDPT.1CW
76FB5 - InputDisabling1 BitDPT.1CRW
77FB5 - OutputTime after last motion2 BytesDPT.7CT
77FB5 - OutputTime after last motion2 BytesDPT.7CR
78LC - Output channel 1Switching1 BitDPT.1CT
79LC - Output channel 1Dimming4 Bit3.7 dimming controlCT
80LC - Output channel 1Brightness value1 Byte5.1 percentage (0..100%)CT
81LC - Output channel 2Switching1 BitDPT.1CT
82LC - Output channel 2Brightness value1 Byte5.1 percentage (0..100%)CT
83LC - Output channel 3Switching1 BitDPT.1CT
84LC - Output channel 3Brightness value1 Byte5.1 percentage (0..100%)CT
85LC - Input channel 1Feedback brightness value1 Byte5.1 percentage (0..100%)CWTU
86LC - InputSetpoint Preset2 Bytes9.4 lux (Lux)CW
87LC - InputSetpoint Shift4 Bit3.7 dimming controlCW
88LC - InputSetpoint Reset1 BitDPT.1CW
89LC - InputSetpoint Teach1 BitDPT.1CW
90LC - Feedback - OutputSetpoint effective2 Bytes9.4 lux (Lux)CT
90LC - Feedback - OutputSetpoint effective2 Bytes9.4 lux (Lux)CR
91LC - InputDisabling1 BitDPT.1CW
92LC - Input / superimposed operationSwitching1 BitDPT.1CW
93LC - Input / superimposed operationDimming4 Bit3.7 dimming controlCW
94LC - Input / superimposed operationBrightness value1 Byte5.1 percentage (0..100%)CW
95LC - Input / superimposed operationScene extension1 ByteCW
96LC - Feedback - OutputStatus disabling fct light ctr1 BitDPT.1CT
96LC - Feedback - OutputStatus disabling fct light ctr1 BitDPT.1CR
97LC - InputPresence1 BitDPT.1CW
102BLV - OutputLimit. value 1 switching1 BitDPT.1CT
102BLV - OutputLimit. value 1 brightness val.1 Byte5.1 percentage (0..100%)CT
102BLV - OutputLimit. value 1 scene extension1 Byte5.1 percentage (0..100%)CT
103BLV - OutputLimit. value 2 switching1 BitDPT.1CT
103BLV - OutputLimit. value 2 brightness val.1 Byte5.1 percentage (0..100%)CT
103BLV - OutputLimit. value 2 scene extension1 Byte5.1 percentage (0..100%)CT
104BLV - OutputLimit. value 3 scene extension1 ByteCT
104BLV - OutputLimit. value 3 brightness val.1 Byte5.1 percentage (0..100%)CT
104BLV - OutputLimit. value 3 switching1 BitDPT.1CT
105BLV - InputLimit. value 1 ext. presetting2 Bytes9.4 lux (Lux)CW
106BLV - InputLimiting value 1 Teach1 BitDPT.1CW
107BLV - Feedback - OutputLimiting value 1 effective2 Bytes9.4 lux (Lux)CT
107BLV - Feedback - OutputLimiting value 1 effective2 Bytes9.4 lux (Lux)CR
108BLV - InputLimit. value 2 ext. presetting2 Bytes9.4 lux (Lux)CW
109BLV - InputLimiting value 2 Teach1 BitDPT.1CW
110BLV - Feedback - OutputLimiting value 2 effective2 Bytes9.4 lux (Lux)CT
110BLV - Feedback - OutputLimiting value 2 effective2 Bytes9.4 lux (Lux)CR
111BLV - InputLimit. value 3 ext. presetting2 Bytes9.4 lux (Lux)CW
112BLV - InputLimiting value 3 Teach1 BitDPT.1CW
113BLV - Feedback - OutputLimiting value 3 effective2 Bytes9.4 lux (Lux)CT
113BLV - Feedback - OutputLimiting value 3 effective2 Bytes9.4 lux (Lux)CR
114BLV - InputDisabling1 BitDPT.1CW
122IR - InputDisabling1 BitDPT.1CW
123FB groups - InputChange-over1 BitDPT.1CW
124FB groups - OutputStatus switch-over1 BitDPT.1CRT
Parameters (219)
ParameterTypeDefault
DownloaderkennunglistDownloaded
Hardwaretypelist$00 0A 00 00 00 4F
Delay after bus voltage return Minutes (0...59)unsignedInt 0…590
Seconds (0...59)unsignedInt 0…5917
Basic sensitivity of all PIR sectorslisthigh
Basisempfindlichkeit PIR-Sektor Alisthigh
Basisempfindlichkeit PIR Sektor Blisthigh
Basisempfindlichkeit PIR Sektor Clisthigh
Sensitivity PIR-Sector Alist100%
Sensitivity PIR-Sector Blist100%
Sensitivity PIR-Sector Clist100%
Adjuster for sensitivity PIR-Sectors A-Clistactivated
Interlock of all PIR-sectors by external telegram whenlistOFF
Interlock time seconds (0...59)unsignedInt 0…593
sending the brightness valueliston change
Send on brightness change by (5...200 lux)list20 lux
Time for cyclical transmission Minutes (0...59)unsignedInt 0…593
Seconds (0...59)unsignedInt 0…590
Sensor calibrationlistFactory calibration
Behaviour in the case of non-executed calibrationlistDo not send brightness value
Walking test after ETSprogramminglistdeactivated
Display of motion impulses via walking testLEDlistonly with active walking test
Use function block 1?listyes
Group assignment function block 1listno group assigned
Use function block 2?listno
Group assignment function block 2listno group assigned
Use function block 3?listno
Group assignment function block 3listno group assigned
Use function block 4?listno
Group assignment function block 4listno group assigned
Use function block 5?listno
Group assignment function block 5listno group assigned
Use switch-over of the function block groups?listno
Polarity function block groups switch-overlist0 = Group 1 / 1 = Group 2
Switch-over behaviourlistimmediately
Active group after bus voltage returnlistGroup 1 active
ApplicationlistMotion detector
Application typelistSingle device
Operating modelistFully automatic (Auto ON, Auto OFF)
Behaviour after bus voltage returnlistno reaction
Behaviour after ETS programminglistno reaction
Function ouput 1listSwitching
Function ouput 2listNo function
Function ouput 1listSignalling
Allocation PIR-Sector Alistassigned
Allocation PIR-Sector Blistassigned
Allocation PIR-Sector Clistassigned
detection of the brightness value bylistinternal sensor
Weighting of the brightness value internal to externallist50% to 50%
Evaluation of the twilight level ?listyes (brightness dependent operation)
Twilight level (10...2,000 Lux)unsignedInt 10…2000500
Overwrite twilight level in device for ETS-Download ?listyes
Object "Presetting twilight level"listdisabled
Feedback "Active twilight level"listactive signalling object
Evaluation of the twilight level on external motion telegramlistyes (brightness dependent operation)
Use Teach function ?listno
Polarity for object "Teach twilight level"list0 = inactive / 1 = active
Evaluation of the twilight levellistin main unit and extension
Evaluation of the twilight level ?listdeactivated
Send cyclical transmission during the detection?listno
Time for cyclical transmission Minutes (0...59)unsignedInt 0…590
Seconds (0...59)unsignedInt 0…5910
Use evaluation delay?listno
Delay time Minutes (0...59)unsignedInt 0…590
Seconds (0...59)unsignedInt 0…5930
Monitoring time minutes (0...59)unsignedInt 0…590
Number of motion impulses in the monitoring time (1...255) (typ. 20)unsignedInt 1…25520
Type of additional transmission delaylistaccording to parameter
Additional transmission delay Minutes (0...59)unsignedInt 0…590
Time extension for additional transmission delaylistno extension
Minimum additional transmission delay minutes (0...59)unsignedInt 0…590
Maximum additional transmission delay minutes (0...59)unsignedInt 0…593
Evaluation brief presencelistno
Time window detec. of brief presence Seconds (10...59)unsignedInt 10…5910
Measurement of the time period after end of the last motionlistdeactivated
Feedback "Time after last motion"listactive signalling object
Cycle time for autom. transmission of Hours (0...59)unsignedInt 0…590
Minutes (10...59)unsignedInt 10…5910
Main unit "Staircase function" with run-on-time in the actuator?listno
Hysteresis for switch-off brightness presence detector (10...800 lux)unsignedInt 10…800300
Teach function for switch-off brightnesslistdisabled
Overwrite switch-off brightness in device for ETS-Download ?listyes
Operating mode Teachlist0 = inactive / 1 = active
Transmission delay after reaching the switch-off brightnesslistlike additional transmission delay
Time for switch-off delay Minutes (0...59)unsignedInt 0…595
Function of the output: "Switching"listcan be set under "FB - General"
Send telegram at the beginning of the detection?listyes
Telegram at the beginning of the detectionlistON telegram
Telegram triggering on retriggering?listno
Send telegram at the end of the detection?listyes
Telegram at the end of the detectionlistOFF telegram
Function of the output: "Staircase function"listcan be set under "FB - General"
Function of the output: "Switching with forced position"listcan be set under "FB - General"
Forced position at the beginning of the detectionlistForced position active, ON
Forced position at the end of the detectionlistForced position active, OFF
Function of the output: "Dimming value transmitter"listcan be set under "FB - General"
Dimming value at the beginning of the detection(0...100 %)unsignedInt 0…100100
Dimming value at the end of the detection(0...100 %)unsignedInt 0…1000
Function of the output: "Light scene extension"listcan be set under "FB - General"
Light scene number at the beginning of the detection (1...64)unsignedInt 1…641
Light scene number at the end of the detection (1...64)unsignedInt 1…641
Function of the output: "Temperature value transmitter"listcan be set under "FB - General"
Temperature value at the beginning of the detectionlist23 °C
Temperature value at the end of the detectionlist21 °C
Function of the output: "Brightness value transmitter"listcan be set under "FB - General"
Brightness value at the beginning of the detectionlist1,000 lux
Brightness value at the end of the detectionlist750 lux
Function of the output: "Operat mode room temperature ctrl"listcan be set under "FB - General"
Operating mode at the beginning of the detectionlistComfort
Operating mode at the end of the detectionlistStandby
Function of the output: "No function"listcan be set under "FB - General"
Send telegram at the beginning of the detection?listno
Send telegram at the end of the detection?listno
Polarity of the disabling objectlist0 = enable / 1 = disable
Behaviour at the beginning of the disabling functionlistdisable and send no telegram
Telegram at the beginning of the disabling functionlistOFF telegram
Forced position at the beginningof disabling functionlistForced position active, OFF
Dimming value at the beginning of the disabling function (0...100 %)unsignedInt 0…1000
Light scene number at beginning of disabling function (1...64)unsignedInt 1…641
Temperature at the beginning of the disabling functionlist21 °C
Brightness at the beginning of the disabling functionlist750 lux
Operating mode at the beginning of disabling functionlistStandby
Behaviour at the end of the disabling functionlistenable and send no telegram
Function of the output: "Detector"listcan be set under "FB - General"
Message telegram at beginning of the detectionlistON telegram
Message telegram at the end of the detectionlistOFF telegram
Light controllistenabled
Präsenzmelder mit Lichtregelung ?listyes
Effect of the brightness value- feedback on the actuatorlistactive signalling object
Adaptation of the control dynamic in the brightness rangelistStandard
Maximale Beleuchtungsstärke "Maximalwert"list24 lux (Setpoint 20 lux)
Lower brightness threshold "darkness value" (0...2,000 lux)unsignedInt 0…2000200
Maximum illuminance "Maximum value" (10...2,000 lux)unsignedInt 10…2000720
Setpointlist600 lux
Setpoint (10...2,000 Lux)unsignedInt 10…2000600
Hysteresis setpoint (+10...+50 %)unsignedInt 10…5010
Overwrite setpoint in the device for ETS download ?listyes
Object "Preset setpoint"listdisabled
Allow setpoint shift ?listno
Upper limit setpoint shift (10...2,000 lux)unsignedInt 10…20002000
Lower limit setpoint shift (10...2,000 lux)unsignedInt 10…200010
Validity of the setpoint shiftlistpermanently
Teach functionlistdisabled
Feedback "setpoint effective" ?listno
Effect of the feedbacklistactive signalling object
Number of lighting channels to be controlledlist1 (Channel 1)
Offset behaviour for channel 2listOffset fixed with increasing control output
Offset channel 2 for channel 1 (-128...127)signedInt -128…12750
ON/OFF hysteresis if negative Offset channel 2 (0...90)unsignedInt 0…9020
Offset channel 2 for channel 1 (1...200 %)unsignedInt 1…200150
Start-offset channel 2 for channel 1 (-128...127)signedInt -128…12750
Ctr output of channel 1 for synchroniz. to channel 2 (0...255)unsignedInt 0…255200
Offset behaviour for channels 2 and 3listOffset fixed with increasing control output
Offset channel 3 for channel 1 (-128...127)signedInt -128…127-50
ON/OFF hysteresis if negative Offset channel 2 and 3 (0...90)unsignedInt 0…9020
Offset channel 3 for channel 1 (1...200 %)unsignedInt 1…20050
Start-offset channel 3 for channel 1 (-128...127)signedInt -128…127-50
Ctr output of channel 1 for synchroniz. to channel 3 (0...255)unsignedInt 0…255200
Startup control behaviourlistControl output presetting (brightness value)
Dimming step widthlist100%
Telegram repetition ?listno
Time for telegram repetition Seconds (0...59)unsignedInt 0…590
Milliseconds (0...9 x 100)unsignedInt 0…95
Dimming value (1...100 %)unsignedInt 1…100100
Waiting time after startup control seconds (1...59)unsignedInt 1…595
Control behaviourlistControl output presetting (brightness value)
Minimum dimming step widthlist3%
Minimum control output change per dimming step (2...32)unsignedInt 2…324
Minimum repeat time for control outp. seconds (1..59)unsignedInt 1…592
Influence behaviour for lower control output limit ?listno
Behaviour on falling short of lower control output limitlistno reaction
Addit hysteresis setpoint for switch-off bright. (0...+100 %)unsignedInt 0…10010
Lower control output limit (1...128)unsignedInt 1…1281
Behaviour at the beginning of the step down control phaselistsend minimum control output
Verhalten zu Beginn der Abregelphaselistno
Switch off bylistSwitching telegram (1-bit)
Step down control behaviourlistControl output presetting (brightness value)
Minutes (0...59)unsignedInt 0…590
Behaviour on new presence detection during wating timelistCancel step down phase and startup control anew
Behaviour after expiry of the waiting timelistSwitch off
Control output (1...100 %)unsignedInt 1…10050
Feedback"Status disabling function light control" ?listno
Data format of the telegramlistSwitching telegram (1-bit)
Telegram at the beginning of the disabling functionlistOFF telegram
Dimming value at beginning of disabling function (0...100 %)unsignedInt 0…1000
Allow superimposed operation ?listno
Enable after superimposed operationlistautomatic at the end of the presence
Function brightness limit valueslistdisabled
Anzahl der zu steuernden Grenzwertelistno limiting value evaluation
Number of limiting values to be controlledlist1 (Output 1)
Limiting value definitionlistLimiting value is lower threshold
Limiting value (10...2,000 lux) (upper threshold)unsignedInt 10…20001000
Hysteresis (lower threshold)list-10%
Hysteresis (upper threshold)list10%
Limiting value (10...2,000 lux) (lower threshold)unsignedInt 10…20001000
Overwrite limiting value in device for ETS download ?listyes
Object "Limit value extern presetting"listdisabled
Operating mode Teachlist0 = inactive / 1 = active
Feedback "limiting value effective" ?listno
Effect of the feedbacklistactive signalling object
FunctionlistSwitching
Send telegram on exceeding the upper threshold ?listno
Telegram on exceeding the upper thresholdlistON telegram
Send telegram on not reaching lower threshold ?listno
Telegram on not reaching lower thresholdlistOFF telegram
Telegram on exceeding the upper threshold (0...100 %)unsignedInt 0…100100
Telegram on not reaching lower threshold (0...100 %)unsignedInt 0…1000
Telegram on exceeding the upper threshold (1...64)unsignedInt 1…641
Telegram on not reaching lower threshold (1...64)unsignedInt 1…641
Telegram on exceeding the upper thresholdlistOFF telegram
Telegram on exceeding the upper threshold (0...100 %)unsignedInt 0…1000
Use disabling function ?listno
Polarity of the disabling objectlist0 = enable / 1 = disable
Status of the disabling function after bus voltage returnlistdeactivated
State of the disabling function after ETS programminglistdeactivated
IR remote controllistdisabled
Operating mode presettinglist1 / Auto / 0
Button "Test" for walking test functionlistdeactivated
Polarity of the disabling objectlist0 = enable / 1 = disable

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Presence detector Universal A01112 1.2 latest$A01140DE2026-11-25574 KBDownload
Presence detector Universal A01111 1.1$A01163BD2026-11-25527 KBDownload

About this file

This is the official ETS product database for the Albrecht Jung Presence detector Universal (3361-1), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Albrecht Jung

All Albrecht Jung products