RT/U 1.1.ZW Thermostat 2CSY244280R1202
ABB SpA-SACE Division · Order number 2CSY244280R1202 · Heating, air conditioning, ventilation › Thermostat with display
Download .knxprod Thermostat/2.0 2.12 · 151 KB
Product
| Manufacturer | ABB SpA-SACE Division |
|---|---|
| Product name | RT/U 1.1.ZW Thermostat |
| Order number | 2CSY244280R1202 |
| Hardware | Termostato solo TP |
| Medium | Twisted Pair |
| Bus current (mA) | 12 |
| Rail mounted | No |
| Registration | Certified · 2021-06-11 |
| Languages | en-US, it-IT, de-DE, es-ES |
| Catalog entry | M-000E_H-E0002D-1_HP-000D-2C-5AC1_CI-2CSY244280R1202-1 |
| Fingerprint | 5AC1 |
| SHA-256 | 87554d5bbeff2581873d4830a37b616bf1be4591304f6aafc76d2ba779df36e5 |
| First seen | 2026-11-25 |
| Markets | France, Germany, Greece, Italy, Saudi Arabia, Spain |
Application program: Thermostat/2.0 2.12
| Application number | $000D |
|---|---|
| Version | 2.12 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 118 |
| Group objects | 47 |
Group objects (47)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | General | In operation | 1 Bit | 1.1 switch | CT |
| 1 | Operating mode | Frost/heat protection | 1 Bit | 1.1 switch | CRW |
| 2 | Operating mode | Night mode | 1 Bit | 1.1 switch | CRW |
| 3 | Operating mode | Comfort/Stand by mode | 1 Bit | 1.1 switch | CRWT |
| 8 | Operating mode | Operating mode switching | 1 Byte | CRWT | |
| 9 | Control | Temper. sending | 2 Bytes | 9.1 temperature (°C) | CRT |
| 10 | Control | Heating status | 1 Bit | 1.3 enable | CRWTU |
| 10 | Control | Heating status | 1 Bit | 1.3 enable | CRWT |
| 12 | Control | Cooling status | 1 Bit | 1.3 enable | CRWTU |
| 12 | Control | Cooling status | 1 Bit | 1.3 enable | CRT |
| 13 | Control | Heat. contr.value (switching) | 1 Bit | 1.1 switch | CRT |
| 13 | Control | Heat. contr.value (count) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 13 | Control | Heat./Cool. contr.value (count | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 13 | Control | Heat./Cool. contr.value (switc | 1 Bit | 1.1 switch | CRT |
| 14 | Control | Cool. contr.value (count) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 14 | Control | Cool. contr.value (switching) | 1 Bit | 1.1 switch | CRT |
| 15 | Control | Current setpoint - Cool. | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 16 | Control | Current setpoint - Heat. | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 17 | Control | Communication obj. for reset | 1 Bit | 1.1 switch | CW |
| 18 | Control | Base setpoint | 2 Bytes | 9.1 temperature (°C) | CRW |
| 18 | Control | Base setpoint | 2 Bytes | 9.1 temperature (°C) | CWT |
| 19 | General | Device ON/OFF | 1 Bit | 1.1 switch | CRWT |
| 20 | Fan auto/man | Manual On/Off | 1 Bit | 1.1 switch | CRWT |
| 20 | Fan auto/man | Automatic On/Off | 1 Bit | 1.1 switch | CRWT |
| 21 | Manual fan | Fan 1 byte manual control | 1 Byte | 5.10 counter pulses (0..255) | CRWT |
| 21 | Manual fan | Fan 1 byte manual control | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 23 | Manual fan | Fan stage manual control 1 | 1 Bit | 1.1 switch | CRWT |
| 24 | Manual fan | Fan stage manual control 2 | 1 Bit | 1.1 switch | CRWT |
| 25 | Manual fan | Fan stage manual control 3 | 1 Bit | 1.1 switch | CRWT |
| 26 | Operating mode | Switching heating/cooling | 1 Bit | 1.1 switch | CRWT |
| 26 | Operating mode | Switching heating/cooling | 1 Bit | 1.1 switch | CRT |
| 27 | Control | Comfort setpoint - Heat. | 2 Bytes | 9.1 temperature (°C) | CW |
| 28 | Control | Setpoint Stand By - Heat. | 2 Bytes | 9.1 temperature (°C) | CW |
| 29 | Control | Night setpoint - Heat. | 2 Bytes | 9.1 temperature (°C) | CW |
| 30 | Control | Setpoint frost protection | 2 Bytes | 9.1 temperature (°C) | CW |
| 31 | Control | Comfort setpoint - Cool. | 2 Bytes | 9.1 temperature (°C) | CW |
| 32 | Control | Setpoint Standby - Cooling | 2 Bytes | 9.1 temperature (°C) | CW |
| 33 | Control | Night setpoint - Cool. | 2 Bytes | 9.1 temperature (°C) | CW |
| 34 | Control | Heat setpoint - Cooling | 2 Bytes | 9.1 temperature (°C) | CW |
| 35 | Control | Receiving actuator status | 1 Bit | 1.1 switch | CW |
| 36 | Fan automatic | Fan autom. Level 1 | 1 Bit | 1.3 enable | CRT |
| 37 | Fan automatic | Fan autom. Level 2 | 1 Bit | 1.3 enable | CRT |
| 38 | Fan automatic | Fan autom. Level 3 | 1 Bit | 1.3 enable | CRT |
| 39 | Control | Add. heat. contr.value | 1 Bit | 1.1 switch | CRT |
| 39 | Control | Add. heat. contr.value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 40 | Control | Add. cool. contr.value | 1 Bit | 1.1 switch | CRT |
| 40 | Control | Add. cool. contr.value | 1 Byte | 5.1 percentage (0..100%) | CRT |
Parameters (74)
| Parameter | Type | Default |
|---|---|---|
| General | list | Comfort/Stand by/OFF |
| "In operation" telegram cyclic sending | list | Cyclic sending value 0 |
| Transmission period [0......65535] seconds | unsignedInt 0…65535 | 0 |
| Temperature unit of measurement | list | Celsius |
| Display heat/cond is active | list | Only if operating mode is active |
| Operating mode switchover | list | 1 bit (3 x DPT_Switch) |
| 1 = Comfort, 2 = Night, 3 = Stand by 4 = Frost/heat protection | list | <----------------------------------------NOTE |
| Switching Comfort/Stand by via button | list | Comfort/Stand by |
| Operation mode after reset | list | Comfort |
| Offset for room temp. \measured ((-30.....30) * 0.1 °C) | list | 0 |
| Minimum temperature variation so that it is sent over the bus | list | Inactive |
| Period of room temperature cyclic sending (0 - not active) min | unsignedInt 0…60 | 0 |
| Thermostat functions | list | Heating |
| Switchover between heating and cooling | list | Automatic |
| Add. heating control | list | no |
| Add. cooling control | list | no |
| Number of output chann. | list | 1 channel for heating/cooling |
| Status send heat requirement | list | no |
| Cycle time control value sending 0...60 min. (0 - inactive) | unsignedInt 0…60 | 0 |
| Control mode | list | 2points |
| Hysteres | list | 1.0°C |
| Minimum control value variation so that it is sent over the bus | unsignedInt 0…15 | 5 |
| Minimum value variation so that it is sent over the bus | unsignedInt 0…15 | 5 |
| Minimum variation of the value sent over the bus | unsignedInt 0…15 | 5 |
| Invert heating | list | no |
| Status send cool requirement | list | no |
| Invert cooling | list | no |
| Control type | list | 1 bit control |
| Invert control value | list | no |
| Additional control value interval (0…127) x 0.1°C | unsignedInt 0…127 | 30 |
| Cyclic sending of setpoint 0...60 minutes (0 – inactive, min) | unsignedInt 0…60 | 0 |
| Select base setpoint | list | Dependent setpoints |
| Reference base setpoint | list | Heating |
| Manual setpoint adjustment at reset of change from night/to night | list | no |
| Manual setpoint adjustment | list | yes |
| Maximum manual setpoint increase | list | 5°C |
| Maximum manual setpoint reduction | list | 5°C |
| Setpoints reset trough comunication object | list | no |
| When receiving a new base setpoint | list | Retain manual setpoint adjust. |
| Setpoint in Comfort mode | list | 21.0 °C |
| Setpoint in Comfort mode | list | 23.0 °C |
| Heating setpoint comfort mode | list | 21.0 °C |
| Heating setpoint comfort mode | list | 21.0 °C |
| Heating setpoint standby mode | list | 19.0 °C |
| Cooling setpoint decrease Stand by mode | list | 2.0°C |
| Cooling setpoint decrease Stand by mode | list | 19.0 °C |
| Cooling setpoint increase Stand by mode | list | 2.0°C |
| Heating setpoint night mode | list | 15.0 °C |
| Heating setpoint in Stand by mode | list | 25.0 °C |
| Cooling setpoint decrease night mode | list | 4.0°C |
| Cooling setpoint decrease night mode | list | 15.0 °C |
| Cooling setpoint increase night mode | list | 4.0°C |
| Heating setpoint night mode | list | 27.0 °C |
| Cooling setpoint comfortmode | list | 23.0 °C |
| Setpoint \frost protection | list | 7°C |
| Setpoint \heat protection | list | Check disabled |
| Cooling setpoint standby mode | list | 25.0 °C |
| Cooling setpoint night mode | list | 27.0 °C |
| Minimum distance between heating and cooling setpoint | list | 2.0°C |
| Number of fan levels | list | 3 Levels |
| The manual mode is indicated to actuator through | list | Communication object "On/Off Automatic" |
| Object manual fan stage send has the following code | list | 1 1-byte CO with values from 0 to 100% |
| Send cycle time of actuator in sec [0...65535] (0-disab) | unsignedInt 0…65535 | 0 |
| FanCoil stage after reset | list | Automatic |
| Step limit in ight mode | list | No limit |
| Cycle time PWM control value (min) | unsignedInt 0…60 | 10 |
| Return to automatic mode from manual adjustment (0 - not active,min) | unsignedInt 0…60 | 0 |
| Minimum percentage for termovalve activation | unsignedInt 0…30 | 10 |
| Return to auto mode from FanCoil OFF | list | yes |
| Maximum percentage for termovalve deactivation | unsignedInt 70…100 | 90 |
| Stage1 threshold (%) | unsignedInt 0…100 | 10 |
| PWM cycle is 100% up to \control value | unsignedInt 70…100 | 90 |
| Stage2 threshold (%) | unsignedInt 0…100 | 40 |
| Stage3 threshold (%) | unsignedInt 0…100 | 70 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Thermostat/2.0 2.12 latest | $000D | 5AC1 | 2026-11-25 | 151 KB | Download |
About this file
This is the official ETS product database for the ABB SpA-SACE Division RT/U 1.1.ZW Thermostat (2CSY244280R1202), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from ABB SpA-SACE Division
- RA/U 2.8.1 Switch actuator, 2 chan 8A, 2 butt. 2CSY242150R1106
- RS/U 1.1 Binary input ,1 switch/1 2CSY244490R1012
- RB/U 1.1 Shutter actuator, 230V, 1 rocker button 2CSY247240R1105
- RS/U 2.1 2 binary input, 2 switch 2CSY247450R1003
- RA/U 1.16.1 Switch actuator, 1 chan 16A, 2 buttons 2CSY249580R1103