HCC/S2.2.2.1 Heating/Cooling Circuit Controller,3-point,manual operation,2-fold,MDRC 2CDG 110 221 R0011
ABB AG - STOTZ-KONTAKT · Order number 2CDG 110 221 R0011 · Heating, Ventilation and Air Conditioning › Central HVAC Controllers
Heating/Cooling Circuit Controller, 3-point, manual operation, 2-f/1.2
Download .knxprod Heating/Cooling Circuit Controller, 3-point, manual operation, 2-f/1.2 1.2 · 303 KB
Product
| Manufacturer | ABB AG - STOTZ-KONTAKT |
|---|---|
| Product name | HCC/S2.2.2.1 Heating/Cooling Circuit Controller,3-point,manual operation,2-fold,MDRC |
| Order number | 2CDG 110 221 R0011 |
| Hardware | HCC/S2.2.2.1 Heiz-/Kühlkreis Controller,3-Punkt,manuelle Bedienung,2-fach,REG |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Width (mm) | 70 |
| Registration | Certified · 2021-11-18 |
| Languages | en-US, de-DE, es-ES, fr-FR, it-IT, nl-NL, pl-PL, ru-RU |
| Catalog entry | M-0002_H-2CDG.20110.20221.20R0011-2_HP-A0BA-12-48FA_CI-2CDG.20110.20221.20R0011-1 |
| Fingerprint | 48FA |
| SHA-256 | 8a6a4d0314c8c3dcbe24947ca36e414379c10bea990af5a58df1c2adbe0ae8be |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Heating/Cooling Circuit Controller, 3-point, manual operation, 2-f/1.2 1.2
| Application number | $A0BA |
|---|---|
| Version | 1.2 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 456 |
| Group objects | 118 |
Group objects (118)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | General | In operation | 1 Bit | 1.2 boolean | CRT |
| 3 | General | Request status values | 1 Bit | 1.17 trigger | CW |
| 4 | General | Status Manual operation | 1 Bit | 1.11 state | CRT |
| 5 | General | Enable/block manual operation | 1 Bit | 1.3 enable | CW |
| 10 | Channel A - General | Forced operation, 2-bit | 2 Bit | 2.1 switch control | CW |
| 11 | Channel A - General | Forced operation, 1-bit | 1 Bit | 1.2 boolean | CW |
| 12 | Channel A - General | Error "Heating/cooling changeover" receipt | 1 Bit | 1.5 alarm | CRT |
| 13 | Channel A - General | Error "Setpoint temperature" receipt | 1 Bit | 1.5 alarm | CRT |
| 13 | Channel A - General | Error "Control value" receipt | 1 Bit | 1.5 alarm | CRT |
| 14 | Channel A - General | Error "Pump fault" receipt | 1 Bit | 1.5 alarm | CRT |
| 15 | Channel A - General | Error "Pump repair switch" receipt | 1 Bit | 1.5 alarm | CRT |
| 16 | Channel A - General | Status byte channel | 1 Byte | CRT | |
| 17 | Channel A - Valve B/C | Status byte valve B/C | 1 Byte | CRT | |
| 18 | Channel A - Valve B/C | Status Control value valve B/C | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 19 | Channel A - Valve B/C | Fault Valve output B/C | 1 Bit | 1.5 alarm | CRT |
| 20 | Channel A - Valve B/C | Status Valve purge B/C | 1 Bit | 1.11 state | CRT |
| 21 | Channel A - Valve B/C | Reset fault Valve output B/C | 1 Bit | 1.15 reset | CW |
| 22 | Channel A - Valve B/C | Activate valve purge B/C | 1 Bit | 1.17 trigger | CW |
| 23 | Channel A - Valve B/C | Enable/block manual valve override B/C | 1 Bit | 1.3 enable | CW |
| 24 | Channel A - Valve B/C | Override valve control value B/C | 1 Byte | 5.1 percentage (0..100%) | CW |
| 26 | Channel A - Pump | Override pump | 1 Bit | 1.1 switch | CW |
| 27 | Channel A - Pump | Status pump relay | 1 Bit | 1.9 open/close | CRT |
| 29 | Channel A - Pump | Pump fault | 1 Bit | 1.5 alarm | CWTU |
| 30 | Channel A - Pump | Pump repair switch | 1 Bit | 1.11 state | CWTU |
| 31 | Channel A - Pump | Status pump master/slave (1=Master, 0=Slave) | 1 Bit | 1.11 state | CRT |
| 32 | Channel A - Pump | Enable/block manual pump override | 1 Bit | 1.3 enable | CW |
| 33 | Channel A - Pump | Status pump automatic mode | 1 Bit | 1.11 state | CRT |
| 34 | Channel A - Pump | Set time | 3 Bytes | 10.1 time of day | CW |
| 35 | Channel A - Pump | Master/slave changeover | 1 Bit | 1.17 trigger | CW |
| 37 | Channel A - Input a | Supply flow temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 38 | Channel A - Input a | Error Input | 1 Bit | 1.5 alarm | CRT |
| 39 | Channel A - Input b | Return flow temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 40 | Channel A - Input b | Error Input | 1 Bit | 1.5 alarm | CRT |
| 41 | Channel A - Binary input c | Status pump | 1 Bit | 1.11 state | CRT |
| 41 | Channel A - Binary input c | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 42 | Channel A - Binary input c | Block input | 1 Bit | 1.3 enable | CW |
| 43 | Channel A - Binary input d | Pump fault alarm | 1 Bit | 1.5 alarm | CRT |
| 43 | Channel A - Binary input d | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 44 | Channel A - Binary input d | Block input | 1 Bit | 1.3 enable | CW |
| 45 | Channel A - Binary input e | Pump repair switch | 1 Bit | 1.11 state | CRT |
| 45 | Channel A - Binary input e | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 46 | Channel A - Binary input e | Block input | 1 Bit | 1.3 enable | CW |
| 47 | Channel A - Controller | Status Heating/cooling | 1 Bit | 1.100 cooling/heating | CRT |
| 48 | Channel A - Controller | Status Control value heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 50 | Channel A - Controller | Status Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 54 | Channel A - Controller | Supply flow temperature receipt | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 56 | Channel A - Controller | Fault Supply flow temperature | 1 Bit | 1.5 alarm | CRT |
| 57 | Channel A - Controller | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 62 | Channel A - Controller | Status Heating | 1 Bit | 1.1 switch | CRT |
| 63 | Channel A - Controller | Status Cooling | 1 Bit | 1.1 switch | CRT |
| 64 | Channel A - Controller | Activation of minimum control value (basic load) | 1 Bit | 1.3 enable | CW |
| 65 | Channel A - Controller | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 65 | Channel A - Actuator | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 73 | Channel A - Controller | Activate/deactivate control | 1 Bit | 1.1 switch | CW |
| 74 | Channel A - Controller | Status Control | 1 Bit | 1.1 switch | CRT |
| 86 | Channel A - Controller | Heating setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 87 | Channel A - Controller | Cooling setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 94 | Channel A - Actuator | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 95 | Channel A - Actuator | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 96 | Channel A - Controller | Temperature, safety shutdown heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 98 | Channel A - Controller | Temperature, safety shutdown cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 100 | Channel A - Controller | Status Safety shutdown | 1 Bit | 1.5 alarm | CRT |
| 101 | Channel B - General | Forced operation, 2-bit | 2 Bit | 2.1 switch control | CW |
| 102 | Channel B - General | Forced operation, 1-bit | 1 Bit | 1.2 boolean | CW |
| 103 | Channel B - General | Error "Heating/cooling changeover" receipt | 1 Bit | 1.5 alarm | CRT |
| 104 | Channel B - General | Error "Setpoint temperature" receipt | 1 Bit | 1.5 alarm | CRT |
| 104 | Channel B - General | Error "Control value" receipt | 1 Bit | 1.5 alarm | CRT |
| 105 | Channel B - General | Error "Pump fault" receipt | 1 Bit | 1.5 alarm | CRT |
| 106 | Channel B - General | Error "Pump repair switch" receipt | 1 Bit | 1.5 alarm | CRT |
| 107 | Channel B - General | Status byte channel | 1 Byte | CRT | |
| 108 | Channel B - Valve E/F | Status byte valve E/F | 1 Byte | CRT | |
| 109 | Channel B - Valve E/F | Status Control value valve E/F | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 110 | Channel B - Valve E/F | Fault: valve output E/F | 1 Bit | 1.5 alarm | CRT |
| 111 | Channel B - Valve E/F | Status valve purge E/F | 1 Bit | 1.11 state | CRT |
| 112 | Channel B - Valve E/F | Reset fault Valve output E/F | 1 Bit | 1.15 reset | CW |
| 113 | Channel B - Valve E/F | Activate valve purge E/F | 1 Bit | 1.17 trigger | CW |
| 114 | Channel B - Valve E/F | Enable/block manual valve override E/F | 1 Bit | 1.3 enable | CW |
| 115 | Channel B - Valve E/F | Override valve control value E/F | 1 Byte | 5.1 percentage (0..100%) | CW |
| 117 | Channel B - Pump | Override pump | 1 Bit | 1.1 switch | CW |
| 118 | Channel B - Pump | Status pump relay | 1 Bit | 1.9 open/close | CRT |
| 120 | Channel B - Pump | Pump fault | 1 Bit | 1.5 alarm | CWTU |
| 121 | Channel B - Pump | Pump repair switch | 1 Bit | 1.11 state | CWTU |
| 122 | Channel B - Pump | Status pump master/slave (1=Master, 0=Slave) | 1 Bit | 1.11 state | CRT |
| 123 | Channel B - Pump | Enable/block manual pump override | 1 Bit | 1.3 enable | CW |
| 124 | Channel B - Pump | Status pump automatic mode | 1 Bit | 1.11 state | CRT |
| 128 | Channel B - Input f | Supply flow temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 129 | Channel B - Input f | Error Input | 1 Bit | 1.5 alarm | CRT |
| 130 | Channel B - Input g | Return flow temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 131 | Channel B - Input g | Error Input | 1 Bit | 1.5 alarm | CRT |
| 132 | Channel B - Binary input h | Status pump | 1 Bit | 1.11 state | CRT |
| 132 | Channel B - Binary input h | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 133 | Channel B - Binary input h | Block input | 1 Bit | 1.3 enable | CW |
| 134 | Channel B - Binary input i | Pump fault alarm | 1 Bit | 1.5 alarm | CRT |
| 134 | Channel B - Binary input i | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 135 | Channel B - Binary input i | Block input | 1 Bit | 1.3 enable | CW |
| 136 | Channel B - Binary input j | Pump repair switch | 1 Bit | 1.11 state | CRT |
| 136 | Channel B - Binary input j | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 137 | Channel B - Binary input j | Block input | 1 Bit | 1.3 enable | CW |
| 138 | Channel B - Controller | Status Heating/cooling | 1 Bit | 1.100 cooling/heating | CRT |
| 139 | Channel B - Controller | Status Control value heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 141 | Channel B - Controller | Status Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 145 | Channel B - Controller | Supply flow temperature receipt | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 147 | Channel B - Controller | Fault Supply flow temperature | 1 Bit | 1.5 alarm | CRT |
| 148 | Channel B - Controller | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 153 | Channel B - Controller | Status Heating | 1 Bit | 1.1 switch | CRT |
| 154 | Channel B - Controller | Status Cooling | 1 Bit | 1.1 switch | CRT |
| 155 | Channel B - Controller | Activation of minimum control value (basic load) | 1 Bit | 1.3 enable | CW |
| 156 | Channel B - Controller | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 156 | Channel B - Actuator | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 164 | Channel B - Controller | Activate/deactivate control | 1 Bit | 1.1 switch | CW |
| 165 | Channel B - Controller | Status Control | 1 Bit | 1.1 switch | CRT |
| 177 | Channel B - Controller | Heating setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 178 | Channel B - Controller | Cooling setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 185 | Channel B - Actuator | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 186 | Channel B - Actuator | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 187 | Channel B - Controller | Temperature, safety shutdown heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 189 | Channel B - Controller | Temperature, safety shutdown cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 191 | Channel B - Controller | Status Safety shutdown | 1 Bit | 1.5 alarm | CRT |
Parameters (164)
| Parameter | Type | Default |
|---|---|---|
| Hardware_Type | list | HW |
| Device function | list | Standalone |
| Sending and switching delay after bus voltage recovery | unsignedInt 2…255 | 2 |
| Value after sending and switching delay has expired | list | Last value received |
| Limit number of telegrams | list | No |
| Enable group object "In operation" | list | No |
| Send value of group object "In operation" | list | Value 1 |
| In period | list | 1 s |
| Maximum number of telegrams | unsignedInt 1…50 | 20 |
| i-bus Tool access | list | Full access |
| Sending cycle | time | 60 |
| Channel function | list | Controller channel |
| Control value after ETS download | list | Unchanged |
| Control value | unsignedInt 0…100 | 0 |
| Status after ETS download | list | Unchanged |
| Monitor receipt of group object "Setpoint heating/cooling temperature" | list | Deactivated |
| Monitor receipt of group objects "Heating/cooling control value" | list | Deactivated |
| Cyclical monitoring | list | Deactivated |
| Monitor receipt of group object "Heating/cooling changeover" | list | Deactivated |
| Forced operation | list | Deactivated |
| Control value on exceeding the monitoring time | unsignedInt 0…100 | 25 |
| Control value on input fault | unsignedInt 0…100 | 25 |
| Monitor supply flow temperature | list | Deactivated |
| Control value on forced operation | unsignedInt 0…100 | 0 |
| Control value during forced operation active "ON" | unsignedInt 0…100 | 0 |
| Control value during forced operation active "OFF" | unsignedInt 0…100 | 0 |
| Time interval for cyclical monitoring | time | 300 |
| Operating mode on exceeding the monitoring time | list | Unchanged |
| Valve output | list | Motor-driven (3-point) |
| Send status values | list | After change or on request |
| Resistance in ohms at +120°C | unsignedInt 650…4600 | 3607 |
| Send cyclically every | time | 300 |
| Temperature offset | float -10…10 | 0 |
| Cable length, single distance | float 1…100 | 10 |
| Cross-section of conductor Value* 0.01 mm² | unsignedInt 1…150 | 100 |
| Cable resistance (total of fwd and rtn conductor) | unsignedInt 0…10000 | 500 |
| Value is sent from a change of | float 0.2…10 | 1 |
| Send cyclically every | time | 30 |
| Temperature input | list | Deactivated |
| Input | list | Deactivated |
| Input | list | Pump status input |
| Input | list | Pump error input |
| Minimum control value for basic load > 0 | list | Always active |
| I-proportion | unsignedInt 5…600 | 60 |
| Type of cooling control value | list | PI continuous (0...100%) |
| Control value direction | list | Normal |
| Extended settings | list | No |
| Control value difference for sending control value | list | 5 % |
| Send control value cyclically (0 = deactivated) | unsignedInt 0…60 | 15 |
| xP-proportion | float 1…100 | 60 |
| Maximum control value | unsignedInt 1…100 | 100 |
| Min. control value (basic load) | unsignedInt 0…100 | 0 |
| Manual operation | list | Enabled |
| Automatic reset from manual operation to KNX operation | list | No |
| Object value request on restart and bus voltage recovery | list | No |
| Automatic adjustment of valve drive | list | No |
| Valve purge | list | Automatic or via group object |
| Resistance in ohms at +80°C | unsignedInt 650…4600 | 2785 |
| Send value of group object "Status Valve purge" | list | No, update only |
| Reversing time | unsignedInt 50…1000 | 500 |
| Purge cycle in weeks | unsignedInt 1…12 | 4 |
| Resistance in ohms at +100°C | unsignedInt 650…4600 | 3182 |
| Reset purge cycle from control value greater than or equal to | unsignedInt 1…99 | 99 |
| Switch on time for valve drive from 0 to 100% | unsignedInt 10…6000 | 120 |
| Cable error compensation | list | None |
| Send temperature value | list | After change |
| Temperature sensor type | list | PT1000 [-30...+110 °C] |
| KTY type | list | KT 100/110/130 |
| NTC type | list | NTC 10-01 [-15...+100 °C] |
| Filter | list | Inactive |
| Resistance in ohms at -20°C | unsignedInt 650…4600 | 1247 |
| Resistance in ohms at 0°C | unsignedInt 650…4600 | 1495 |
| Resistance in ohms at +20°C | unsignedInt 650…4600 | 1772 |
| Resistance in ohms at +40°C | unsignedInt 650…4600 | 2080 |
| Resistance in ohms at +60°C | unsignedInt 650…4600 | 2417 |
| Reaction on event 1 | list | On |
| Number of changes until adjustment | unsignedInt 30…65535 | 500 |
| GP_CD_A0B9011F | text | |
| Convertible from version 0.1 | unsignedInt 0…255 | 1 |
| Switch on pump when control value greater than | unsignedInt 0…99 | 5 |
| Switch off pump when control value less than (0% = deactivated) | unsignedInt 0…100 | 2 |
| Switch-off delay | time | 5 |
| Send cyclically every | time | 60 |
| Enable manual pump override | list | No |
| Pump reaction on bus voltage failure | list | Unchanged |
| Pump reaction after bus voltage recovery | list | Adopts control value |
| Use pump channel A | list | Main pump |
| Channel bundling for double pumps | list | No |
| Changeover point weekday | list | Monday |
| Changeover point time | unsignedInt 1…24 | 1 |
| Changeover time | signedInt -60…60 | 0 |
| Input | list | Pump repair status input |
| Monitor receipt of pump status group object | list | Deactivated |
| Monitor receipt of group object "Pump fault" | list | Deactivated |
| Monitor receipt of group object "Pump repair switch" | list | Deactivated |
| Reaction on exceeding the monitoring time | list | Cooling control value = 0% |
| Type of heating control value | list | PI continuous (0...100%) |
| Supply flow temperature limitation | list | No |
| Return flow temperature limitation | list | No |
| Heating/cooling changeover | list | Via group object or via slave |
| Supply flow temperature limit | unsignedInt 10…90 | 40 |
| Return flow temperature limit | unsignedInt 10…90 | 40 |
| Control starts again after supply flow temperature change by | float 0…50 | 5 |
| Control starts again after return flow temperature change by | float 0…50 | 5 |
| Operating mode after bus voltage recovery | list | As before bus voltage failure |
| Control value after bus voltage recovery | list | As before bus voltage failure |
| Temperature input | list | Via physical device input |
| I-proportion with safety shutdown | list | Freeze |
| Activate safety shutdown | list | No |
| Safety shutdown hysteresis | float 0.5…5 | 1 |
| Activate heating via | list | Valve output |
| Output for heating stage | list | Valve output |
| Time for automatic reset to KNX operation | time | 300 |
| Activate cooling via | list | Valve output |
| Output for cooling stage | list | Valve output |
| On group object value | list | 0 or 1 |
| Cooling temperature setpoint | unsignedInt 1…30 | 10 |
| Run-on behavior after pump shutdown via manual operation | list | Yes |
| Indicate active forced operation with flashing pump status LED | list | No |
| Minimum heating setpoint temperature | unsignedInt 10…100 | 20 |
| Maximum heating setpoint temperature | unsignedInt 10…100 | 80 |
| Minimum cooling setpoint temperature | unsignedInt 1…45 | 8 |
| Maximum cooling setpoint temperature | unsignedInt 1…45 | 12 |
| Use pump channel B | list | Main pump |
| Close valve when pump is switched off | list | Yes |
| Permit pump changeover via manual operation | list | Yes |
| Automatic pump shutdown on valve closure via manual operation | list | No |
| Pump reaction during forced operation active "OFF" | list | Off |
| Controller setting cooling | list | Deactivated |
| Controller setting heating | list | Medium temperature accuracy / medium number of valve movements |
| Safety shutdown temperature | unsignedInt 25…100 | 80 |
| Input for temperature limit sensor | list | Via group object |
| Safety shutdown temperature | unsignedInt 1…30 | 8 |
| Enable manual valve override | list | No |
| When closing the contact | float 0…100 | 1 |
| When opening the contact | float 0…100 | 1 |
| Long operation after | float 1…10 | 1 |
| Monitor pump status | list | Deactivated |
| Monitor pump error | list | Deactivated |
| Monitor pump repair switch | list | Deactivated |
| Return from manual pump override to automatic mode | list | Via group object or automatic |
| Reset time | time | 300 |
| Pump reaction after ETS download | list | Adopts control value |
| GP_CD_A0BA011F | text | |
| Operating mode after ETS download/reset | list | Heating |
| Cooling setpoint temperature on exceeding the monitoring time | unsignedInt 1…30 | 10 |
| Basic load active when controller off | list | No |
| Send inactive control values cyclically | list | No |
| Heating temperature setpoint | unsignedInt 20…100 | 50 |
| Temperature setpoint after bus voltage recovery | list | As before bus voltage failure |
| Temperature setpoint after ETS download | list | Unchanged |
| Pump reaction during forced operation active "ON" | list | On |
| Pump reaction on forced operation | list | On |
| Control value on exceeding the monitoring time | unsignedInt 0…100 | 50 |
| Heating setpoint temperature on exceeding the monitoring time | unsignedInt 20…100 | 50 |
| Scan input after download, ETS reset or bus voltage recovery | list | Yes |
| Active detected if | list | Contact closed |
| Send status values | list | After change |
| Enable group object "Block input" | list | No |
| Input on operation | list | Closed |
| Activate minimum signal duration | list | No |
| Distinction between long and short operation | list | No |
| Reaction on event 0 | list | Off |
| Switch on pump automatically when pump automatic Off | list | Yes |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Heating/Cooling Circuit Controller, 3-point, manual operation, 2-f/1.2 1.2 latest | $A0BA | 48FA | 2026-11-25 | 303 KB | Download |
About this file
This is the official ETS product database for the ABB AG - STOTZ-KONTAKT HCC/S2.2.2.1 Heating/Cooling Circuit Controller,3-point,manual operation,2-fold,MDRC (2CDG 110 221 R0011), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from ABB AG - STOTZ-KONTAKT
- PS5604-KNX AC500 1SAP 195 800 R0101
- RDF/A x.1 RTR fan coil with display, SM 2CDG 006 138 R001x
- ES/S4.1.2.1 Electronic Switch Actuator,4f,1A,MDRC 2CDG 110 058 R0011
- ES/S8.1.2.1 Electronic Switch Actuator,8f,1A,MDRC 2CDG 110 059 R0011
- VAA/S6.230.2.1 Valve Drive Actuator, 6f, 230V,MDRC 2CDG 110 116 R0011
- VAA/S12.230.2.1 Valve Drive Actuator, 12f, 230V 2CDG 110 117 R0011
- FCL/S1.6.1.1 Blower Actuator, 1f, 6 A, MDRC 2CDG 110 163 R0011
- FCL/S2.6.1.1 Blower Actuator, 2f, 6 A, MDRC 2CDG 110 164 R0011
- AC/S1.1.1 Application Controller,Basic 2CDG 110 205 R0011
- AC/S1.2.1 Application Controller,BACnet 2CDG 110 206 R0011
- FCC/S1.4.1.1 Fan Coil Controller,PWM,3-speed,2-pipe,MDRC 2CDG 110 209 R0011
- FCC/S1.1.1.1 Fan Coil Controller,PWM,3-speed,MDRC 2CDG 110 210 R0011