| 1 | General | In operation | 1 Bit | 1.2 boolean | CRT |
| 3 | General | Request status values | 1 Bit | 1.17 trigger | CW |
| 4 | General | Status Manual operation | 1 Bit | 1.11 state | CRT |
| 5 | General | Enable/block manual operation | 1 Bit | 1.3 enable | CW |
| 10 | Channel A - General | Forced operation, 2-bit | 2 Bit | 2.1 switch control | CW |
| 11 | Channel A - General | Forced operation, 1-bit | 1 Bit | 1.2 boolean | CW |
| 12 | Channel A - General | Error "Heating/cooling changeover" receipt | 1 Bit | 1.5 alarm | CRT |
| 13 | Channel A - General | Error "Window contact" receipt | 1 Bit | 1.5 alarm | CRT |
| 14 | Channel A - General | Error "Dew point alarm" receipt | 1 Bit | 1.5 alarm | CRT |
| 15 | Channel A - General | Error "Fill level alarm" receipt | 1 Bit | 1.5 alarm | CRT |
| 16 | Channel A - General | Error "Operating mode" receipt | 1 Bit | 1.5 alarm | CRT |
| 16 | Channel A - General | Error "Control value" receipt | 1 Bit | 1.5 alarm | CRT |
| 17 | Channel A - General | Status byte channel | 1 Byte | | CRT |
| 18 | Channel - Valve A | Status byte valve A | 1 Byte | | CRT |
| 19 | Channel - Valve A | Status Control value valve A | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 20 | Channel - Valve A | Fault Valve output A | 1 Bit | 1.5 alarm | CRT |
| 21 | Channel - Valve A | Status Valve purge A | 1 Bit | 1.11 state | CRT |
| 22 | Channel - Valve A | Reset fault Valve output A | 1 Bit | 1.15 reset | CW |
| 23 | Channel - Valve A | Activate valve purge A | 1 Bit | 1.17 trigger | CW |
| 24 | Channel - Valve A | Enable/block manual valve override A | 1 Bit | 1.3 enable | CW |
| 25 | Channel - Valve A | Override valve control value A | 1 Byte | 5.1 percentage (0..100%) | CW |
| 27 | Channel A - Input a | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 28 | Channel A - Input a | Error Input | 1 Bit | 1.5 alarm | CRT |
| 29 | Channel A - Input a | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 29 | Channel A - Input a | Window contact | 1 Bit | 1.19 window/door | CRT |
| 29 | Channel A - Input a | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 29 | Channel A - Input a | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 30 | Channel A - Input a | Block input | 1 Bit | 1.3 enable | CW |
| 31 | Channel A - Input b | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 32 | Channel A - Input b | Error Input | 1 Bit | 1.5 alarm | CRT |
| 33 | Channel A - Input b | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 33 | Channel A - Input b | Window contact | 1 Bit | 1.19 window/door | CRT |
| 33 | Channel A - Input b | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 33 | Channel A - Input b | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 34 | Channel A - Input b | Block input | 1 Bit | 1.3 enable | CW |
| 35 | Channel A - Binary input c | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 35 | Channel A - Binary input c | Window contact | 1 Bit | 1.19 window/door | CRT |
| 35 | Channel A - Binary input c | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 35 | Channel A - Binary input c | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 36 | Channel A - Binary input c | Block input | 1 Bit | 1.3 enable | CW |
| 37 | Channel A - Controller | Status Heating/cooling | 1 Bit | 1.100 cooling/heating | CRT |
| 38 | Channel A - Controller | Status Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 38 | Channel A - Controller | Status Control value basic-stage heating | 1 Bit | 1.1 switch | CRT |
| 39 | Channel A - Controller | Status Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 39 | Channel A - Controller | Status Control value additional-stage heating | 1 Bit | 1.1 switch | CRT |
| 40 | Channel A - Controller | Status Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 40 | Channel A - Controller | Status Control value basic-stage cooling | 1 Bit | 1.1 switch | CRT |
| 41 | Channel A - Controller | Status Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 41 | Channel A - Controller | Status Control value additional-stage cooling | 1 Bit | 1.1 switch | CRT |
| 43 | Channel A - Controller | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 44 | Channel A - Controller | External temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 45 | Channel A - Controller | External temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 46 | Channel A - Controller | Fault Actual temperature (master) | 1 Bit | 1.5 alarm | CRT |
| 47 | Channel A - Controller | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 48 | Channel A - Controller | Operating mode normal (master) | 1 Byte | 20.102 HVAC mode | CWTU |
| 49 | Channel A - Controller | Operating mode override (master) | 1 Byte | 20.102 HVAC mode | CWTU |
| 50 | Channel A - Controller | Window contact (master/slave) | 1 Bit | 1.19 window/door | CW |
| 51 | Channel A - Controller | Presence detector (master/slave) | 1 Bit | 1.18 occupancy | CW |
| 52 | Channel A - Controller | Status Heating | 1 Bit | 1.1 switch | CRT |
| 53 | Channel A - Controller | Status Cooling | 1 Bit | 1.1 switch | CRT |
| 54 | Channel A - Controller | Activation of minimum control value (basic load) | 1 Bit | 1.3 enable | CW |
| 55 | Channel A - Controller | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 55 | Channel A - Actuator | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 56 | Channel A - Controller | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 57 | Channel A - Controller | Reset manual setpoint adjustment | 1 Bit | 1.17 trigger | CW |
| 58 | Channel A - Controller | Dew point alarm | 1 Bit | 1.5 alarm | CWTU |
| 59 | Channel A - Controller | Fill level alarm | 1 Bit | 1.5 alarm | CWTU |
| 60 | Channel A - Controller | Outside temperature for summer compensation | 2 Bytes | 9.1 temperature (°C) | CW |
| 61 | Channel A - Controller | Summer compensation active/inactive | 1 Bit | 1.2 boolean | CRT |
| 62 | Channel A - Controller | Comfort setpoint reached | 1 Bit | 1.2 boolean | CRT |
| 63 | Channel A - Controller | Request On/Off (master) | 1 Bit | 1.1 switch | CW |
| 64 | Channel A - Controller | Confirm On/Off (master) | 1 Bit | 1.1 switch | CRT |
| 65 | Channel A - Controller | Setpoint display (master) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 66 | Channel A - Controller | Request setpoint adjustment (master) | 2 Bytes | 9.1 temperature (°C) | CW |
| 66 | Channel A - Controller | Request setpoint adjustment (master) | 2 Bytes | 9.2 temperature difference (K) | CW |
| 66 | Channel A - Controller | Request setpoint adjustment (master) | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 66 | Channel A - Actuator | Request setpoint adjustment (slave) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 66 | Channel A - Actuator | Request setpoint adjustment (slave) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 67 | Channel A - Controller | Confirm setpoint adjustment (master) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 67 | Channel A - Controller | Confirm setpoint adjustment (master) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 67 | Channel A - Controller | Confirm setpoint adjustment (master) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 68 | Channel A - Controller | Request heating/cooling (master) | 1 Bit | 1.100 cooling/heating | CW |
| 73 | Channel A - Controller | Status Controller RHCC | 2 Bytes | 22.101 RHCC status | CRT |
| 74 | Channel A - Controller | Status Controller HVAC (master) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 75 | Channel A - Controller | Current HVAC operating mode | 1 Byte | 20.102 HVAC mode | CRT |
| 76 | Channel A - Controller | Comfort heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 76 | Channel A - Controller | Comfort heating/cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 77 | Channel A - Controller | Comfort cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 78 | Channel A - Controller | Economy heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 79 | Channel A - Controller | Economy cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 80 | Channel A - Controller | Standby heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 81 | Channel A - Controller | Standby cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 82 | Channel A - Controller | Building Protection heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 83 | Channel A - Controller | Building Protection cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 84 | Channel A - Actuator | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 85 | Channel A - Actuator | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 86 | Channel A - Controller | Basic-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 87 | Channel A - Controller | Additional-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 88 | Channel A - Controller | Basic-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 89 | Channel A - Controller | Additional-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 91 | Channel B - General | Forced operation, 2-bit | 2 Bit | 2.1 switch control | CW |
| 92 | Channel B - General | Forced operation, 1-bit | 1 Bit | 1.2 boolean | CW |
| 93 | Channel B - General | Error "Heating/cooling changeover" receipt | 1 Bit | 1.5 alarm | CRT |
| 94 | Channel B - General | Error "Window contact" receipt | 1 Bit | 1.5 alarm | CRT |
| 95 | Channel B - General | Error "Dew point alarm" receipt | 1 Bit | 1.5 alarm | CRT |
| 96 | Channel B - General | Error "Fill level alarm" receipt | 1 Bit | 1.5 alarm | CRT |
| 97 | Channel B - General | Error "Operating mode" receipt | 1 Bit | 1.5 alarm | CRT |
| 97 | Channel B - General | Error "Control value" receipt | 1 Bit | 1.5 alarm | CRT |
| 98 | Channel B - General | Status byte channel | 1 Byte | | CRT |
| 99 | Channel B - Valve B | Status byte valve B | 1 Byte | | CRT |
| 100 | Channel B - Valve B | Status Control value valve B | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 101 | Channel B - Valve B | Fault Valve output B | 1 Bit | 1.5 alarm | CRT |
| 102 | Channel B - Valve B | Status Valve purge B | 1 Bit | 1.11 state | CRT |
| 103 | Channel B - Valve B | Reset fault Valve output B | 1 Bit | 1.15 reset | CW |
| 104 | Channel B - Valve B | Activate valve purge B | 1 Bit | 1.17 trigger | CW |
| 105 | Channel B - Valve B | Enable/block manual valve override B | 1 Bit | 1.3 enable | CW |
| 106 | Channel B - Valve B | Override valve control value B | 1 Byte | 5.1 percentage (0..100%) | CW |
| 108 | Channel B - Input d | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 109 | Channel B - Input d | Error Input | 1 Bit | 1.5 alarm | CRT |
| 110 | Channel B - Input d | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 110 | Channel B - Input d | Window contact | 1 Bit | 1.19 window/door | CRT |
| 110 | Channel B - Input d | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 110 | Channel B - Input d | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 111 | Channel B - Input d | Block input | 1 Bit | 1.3 enable | CW |
| 112 | Channel B - Input e | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 113 | Channel B - Input e | Error Input | 1 Bit | 1.5 alarm | CRT |
| 114 | Channel B - Input e | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 114 | Channel B - Input e | Window contact | 1 Bit | 1.19 window/door | CRT |
| 114 | Channel B - Input e | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 114 | Channel B - Input e | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 115 | Channel B - Input e | Block input | 1 Bit | 1.3 enable | CW |
| 116 | Channel B - Binary input f | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 116 | Channel B - Binary input f | Window contact | 1 Bit | 1.19 window/door | CRT |
| 116 | Channel B - Binary input f | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 116 | Channel B - Binary input f | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 117 | Channel B - Binary input f | Block input | 1 Bit | 1.3 enable | CW |
| 118 | Channel B - Controller | Status Heating/cooling | 1 Bit | 1.100 cooling/heating | CRT |
| 119 | Channel B - Controller | Status Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 119 | Channel B - Controller | Status Control value basic-stage heating | 1 Bit | 1.1 switch | CRT |
| 120 | Channel B - Controller | Status Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 120 | Channel B - Controller | Status Control value additional-stage heating | 1 Bit | 1.1 switch | CRT |
| 121 | Channel B - Controller | Status Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 121 | Channel B - Controller | Status Control value basic-stage cooling | 1 Bit | 1.1 switch | CRT |
| 122 | Channel B - Controller | Status Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 122 | Channel B - Controller | Status Control value additional-stage cooling | 1 Bit | 1.1 switch | CRT |
| 124 | Channel B - Controller | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 125 | Channel B - Controller | External temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 126 | Channel B - Controller | External temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 127 | Channel B - Controller | Fault Actual temperature (master) | 1 Bit | 1.5 alarm | CRT |
| 128 | Channel B - Controller | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 129 | Channel B - Controller | Operating mode normal (master) | 1 Byte | 20.102 HVAC mode | CWTU |
| 130 | Channel B - Controller | Operating mode override (master) | 1 Byte | 20.102 HVAC mode | CWTU |
| 131 | Channel B - Controller | Window contact (master/slave) | 1 Bit | 1.19 window/door | CW |
| 132 | Channel B - Controller | Presence detector (master/slave) | 1 Bit | 1.18 occupancy | CW |
| 133 | Channel B - Controller | Status Heating | 1 Bit | 1.1 switch | CRT |
| 134 | Channel B - Controller | Status Cooling | 1 Bit | 1.1 switch | CRT |
| 135 | Channel B - Controller | Activation of minimum control value (basic load) | 1 Bit | 1.3 enable | CW |
| 136 | Channel B - Controller | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 136 | Channel B - Actuator | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 137 | Channel B - Controller | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 138 | Channel B - Controller | Reset manual setpoint adjustment | 1 Bit | 1.17 trigger | CW |
| 139 | Channel B - Controller | Dew point alarm | 1 Bit | 1.5 alarm | CWTU |
| 140 | Channel B - Controller | Fill level alarm | 1 Bit | 1.5 alarm | CWTU |
| 141 | Channel B - Controller | Outside temperature for summer compensation | 2 Bytes | 9.1 temperature (°C) | CW |
| 142 | Channel B - Controller | Summer compensation active/inactive | 1 Bit | 1.2 boolean | CRT |
| 143 | Channel B - Controller | Comfort setpoint reached | 1 Bit | 1.2 boolean | CRT |
| 144 | Channel B - Controller | Request On/Off (master) | 1 Bit | 1.1 switch | CW |
| 145 | Channel B - Controller | Confirm On/Off (master) | 1 Bit | 1.1 switch | CRT |
| 146 | Channel B - Controller | Setpoint display (master) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 147 | Channel B - Controller | Request setpoint adjustment (master) | 2 Bytes | 9.1 temperature (°C) | CW |
| 147 | Channel B - Controller | Request setpoint adjustment (master) | 2 Bytes | 9.2 temperature difference (K) | CW |
| 147 | Channel B - Controller | Request setpoint adjustment (master) | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 147 | Channel B - Actuator | Request setpoint adjustment (slave) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 147 | Channel B - Actuator | Request setpoint adjustment (slave) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 148 | Channel B - Controller | Confirm setpoint adjustment (master) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 148 | Channel B - Controller | Confirm setpoint adjustment (master) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 148 | Channel B - Controller | Confirm setpoint adjustment (master) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 149 | Channel B - Controller | Request heating/cooling (master) | 1 Bit | 1.100 cooling/heating | CW |
| 154 | Channel B - Controller | Status Controller RHCC | 2 Bytes | 22.101 RHCC status | CRT |
| 155 | Channel B - Controller | Status Controller HVAC (master) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 156 | Channel B - Controller | Current HVAC operating mode | 1 Byte | 20.102 HVAC mode | CRT |
| 157 | Channel B - Controller | Comfort heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 157 | Channel B - Controller | Comfort heating/cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 158 | Channel B - Controller | Comfort cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 159 | Channel B - Controller | Economy heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 160 | Channel B - Controller | Economy cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 161 | Channel B - Controller | Standby heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 162 | Channel B - Controller | Standby cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 163 | Channel B - Controller | Building Protection heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 164 | Channel B - Controller | Building Protection cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 165 | Channel B - Actuator | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 166 | Channel B - Actuator | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 167 | Channel B - Controller | Basic-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 168 | Channel B - Controller | Additional-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 169 | Channel B - Controller | Basic-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 170 | Channel B - Controller | Additional-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 172 | Channel C - General | Forced operation, 2-bit | 2 Bit | 2.1 switch control | CW |
| 173 | Channel C - General | Forced operation, 1-bit | 1 Bit | 1.2 boolean | CW |
| 174 | Channel C - General | Error "Heating/cooling changeover" receipt | 1 Bit | 1.5 alarm | CRT |
| 175 | Channel C - General | Error "Window contact" receipt | 1 Bit | 1.5 alarm | CRT |
| 176 | Channel C - General | Error "Dew point alarm" receipt | 1 Bit | 1.5 alarm | CRT |
| 177 | Channel C - General | Error "Fill level alarm" receipt | 1 Bit | 1.5 alarm | CRT |
| 178 | Channel C - General | Error "Operating mode" receipt | 1 Bit | 1.5 alarm | CRT |
| 178 | Channel C - General | Error "Control value" receipt | 1 Bit | 1.5 alarm | CRT |
| 179 | Channel C - General | Status byte channel | 1 Byte | | CRT |
| 180 | Channel C - Valve C | Status byte valve C | 1 Byte | | CRT |
| 181 | Channel C - Valve C | Status Control value valve C | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 182 | Channel C - Valve C | Fault Valve output C | 1 Bit | 1.5 alarm | CRT |
| 183 | Channel C - Valve C | Status Valve purge C | 1 Bit | 1.11 state | CRT |
| 184 | Channel C - Valve C | Reset fault Valve output C | 1 Bit | 1.15 reset | CW |
| 185 | Channel C - Valve C | Activate valve purge C | 1 Bit | 1.17 trigger | CW |
| 186 | Channel C - Valve C | Enable/block manual valve override C | 1 Bit | 1.3 enable | CW |
| 187 | Channel C - Valve C | Override valve control value C | 1 Byte | 5.1 percentage (0..100%) | CW |
| 189 | Channel C - Input g | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 190 | Channel C - Input g | Error Input | 1 Bit | 1.5 alarm | CRT |
| 191 | Channel C - Input g | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 191 | Channel C - Input g | Window contact | 1 Bit | 1.19 window/door | CRT |
| 191 | Channel C - Input g | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 191 | Channel C - Input g | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 192 | Channel C - Input g | Block input | 1 Bit | 1.3 enable | CW |
| 193 | Channel C - Input h | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 194 | Channel C - Input h | Error Input | 1 Bit | 1.5 alarm | CRT |
| 195 | Channel C - Input h | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 195 | Channel C - Input h | Window contact | 1 Bit | 1.19 window/door | CRT |
| 195 | Channel C - Input h | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 195 | Channel C - Input h | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 196 | Channel C - Input h | Block input | 1 Bit | 1.3 enable | CW |
| 197 | Channel C - Binary input i | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 197 | Channel C - Binary input i | Window contact | 1 Bit | 1.19 window/door | CRT |
| 197 | Channel C - Binary input i | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 197 | Channel C - Binary input i | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 198 | Channel C - Binary input i | Block input | 1 Bit | 1.3 enable | CW |
| 199 | Channel C - Controller | Status Heating/cooling | 1 Bit | 1.100 cooling/heating | CRT |
| 200 | Channel C - Controller | Status Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 200 | Channel C - Controller | Status Control value basic-stage heating | 1 Bit | 1.1 switch | CRT |
| 201 | Channel C - Controller | Status Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 201 | Channel C - Controller | Status Control value additional-stage heating | 1 Bit | 1.1 switch | CRT |
| 202 | Channel C - Controller | Status Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 202 | Channel C - Controller | Status Control value basic-stage cooling | 1 Bit | 1.1 switch | CRT |
| 203 | Channel C - Controller | Status Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 203 | Channel C - Controller | Status Control value additional-stage cooling | 1 Bit | 1.1 switch | CRT |
| 205 | Channel C - Controller | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 206 | Channel C - Controller | External temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 207 | Channel C - Controller | External temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 208 | Channel C - Controller | Fault Actual temperature (master) | 1 Bit | 1.5 alarm | CRT |
| 209 | Channel C - Controller | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 210 | Channel C - Controller | Operating mode normal (master) | 1 Byte | 20.102 HVAC mode | CWTU |
| 211 | Channel C - Controller | Operating mode override (master) | 1 Byte | 20.102 HVAC mode | CWTU |
| 212 | Channel C - Controller | Window contact (master/slave) | 1 Bit | 1.19 window/door | CW |
| 213 | Channel C - Controller | Presence detector (master/slave) | 1 Bit | 1.18 occupancy | CW |
| 214 | Channel C - Controller | Status Heating | 1 Bit | 1.1 switch | CRT |
| 215 | Channel C - Controller | Status Cooling | 1 Bit | 1.1 switch | CRT |
| 216 | Channel C - Controller | Activation of minimum control value (basic load) | 1 Bit | 1.3 enable | CW |
| 217 | Channel C - Controller | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 217 | Channel C - Actuator | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 218 | Channel C - Controller | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 219 | Channel C - Controller | Reset manual setpoint adjustment | 1 Bit | 1.17 trigger | CW |
| 220 | Channel C - Controller | Dew point alarm | 1 Bit | 1.5 alarm | CWTU |
| 221 | Channel C - Controller | Fill level alarm | 1 Bit | 1.5 alarm | CWTU |
| 222 | Channel C - Controller | Outside temperature for summer compensation | 2 Bytes | 9.1 temperature (°C) | CW |
| 223 | Channel C - Controller | Summer compensation active/inactive | 1 Bit | 1.2 boolean | CRT |
| 224 | Channel C - Controller | Comfort setpoint reached | 1 Bit | 1.2 boolean | CRT |
| 225 | Channel C - Controller | Request On/Off (master) | 1 Bit | 1.1 switch | CW |
| 226 | Channel C - Controller | Confirm On/Off (master) | 1 Bit | 1.1 switch | CRT |
| 227 | Channel C - Controller | Setpoint display (master) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 228 | Channel C - Controller | Request setpoint adjustment (master) | 2 Bytes | 9.1 temperature (°C) | CW |
| 228 | Channel C - Controller | Request setpoint adjustment (master) | 2 Bytes | 9.2 temperature difference (K) | CW |
| 228 | Channel C - Controller | Request setpoint adjustment (master) | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 228 | Channel C - Actuator | Request setpoint adjustment (slave) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 228 | Channel C - Actuator | Request setpoint adjustment (slave) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 229 | Channel C - Controller | Confirm setpoint adjustment (master) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 229 | Channel C - Controller | Confirm setpoint adjustment (master) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 229 | Channel C - Controller | Confirm setpoint adjustment (master) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 230 | Channel C - Controller | Request heating/cooling (master) | 1 Bit | 1.100 cooling/heating | CW |
| 235 | Channel C - Controller | Status Controller RHCC | 2 Bytes | 22.101 RHCC status | CRT |
| 236 | Channel C - Controller | Status Controller HVAC (master) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 237 | Channel C - Controller | Current HVAC operating mode | 1 Byte | 20.102 HVAC mode | CRT |
| 238 | Channel C - Controller | Comfort heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 238 | Channel C - Controller | Comfort heating/cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 239 | Channel C - Controller | Comfort cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 240 | Channel C - Controller | Economy heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 241 | Channel C - Controller | Economy cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 242 | Channel C - Controller | Standby heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 243 | Channel C - Controller | Standby cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 244 | Channel C - Controller | Building Protection heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 245 | Channel C - Controller | Building Protection cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 246 | Channel C - Actuator | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 247 | Channel C - Actuator | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 248 | Channel C - Controller | Basic-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 249 | Channel C - Controller | Additional-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 250 | Channel C - Controller | Basic-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 251 | Channel C - Controller | Additional-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 253 | Channel D - General | Forced operation, 2-bit | 2 Bit | 2.1 switch control | CW |
| 254 | Channel D - General | Forced operation, 1-bit | 1 Bit | 1.2 boolean | CW |
| 255 | Channel D - General | Error "Heating/cooling changeover" receipt | 1 Bit | 1.5 alarm | CRT |
| 256 | Channel D - General | Error "Window contact" receipt | 1 Bit | 1.5 alarm | CRT |
| 257 | Channel D - General | Error "Dew point alarm" receipt | 1 Bit | 1.5 alarm | CRT |
| 258 | Channel D - General | Error "Fill level alarm" receipt | 1 Bit | 1.5 alarm | CRT |
| 259 | Channel D - General | Error "Operating mode" receipt | 1 Bit | 1.5 alarm | CRT |
| 259 | Channel D - General | Error "Control value" receipt | 1 Bit | 1.5 alarm | CRT |
| 260 | Channel D - General | Status byte channel | 1 Byte | | CRT |
| 261 | Channel D - Valve D | Status byte valve D | 1 Byte | | CRT |
| 262 | Channel D - Valve D | Status Control value valve D | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 263 | Channel D - Valve D | Fault Valve output D | 1 Bit | 1.5 alarm | CRT |
| 264 | Channel D - Valve D | Status Valve purge D | 1 Bit | 1.11 state | CRT |
| 265 | Channel D - Valve D | Reset fault Valve output D | 1 Bit | 1.15 reset | CW |
| 266 | Channel D - Valve D | Activate valve purge D | 1 Bit | 1.17 trigger | CW |
| 267 | Channel D - Valve D | Enable/block manual valve override D | 1 Bit | 1.3 enable | CW |
| 268 | Channel D - Valve D | Override valve control value D | 1 Byte | 5.1 percentage (0..100%) | CW |
| 270 | Channel D - Input j | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 271 | Channel D - Input j | Error Input | 1 Bit | 1.5 alarm | CRT |
| 272 | Channel D - Input j | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 272 | Channel D - Input j | Window contact | 1 Bit | 1.19 window/door | CRT |
| 272 | Channel D - Input j | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 272 | Channel D - Input j | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 273 | Channel D - Input j | Block input | 1 Bit | 1.3 enable | CW |
| 274 | Channel D - Input k | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 275 | Channel D - Input k | Error Input | 1 Bit | 1.5 alarm | CRT |
| 276 | Channel D - Input k | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 276 | Channel D - Input k | Window contact | 1 Bit | 1.19 window/door | CRT |
| 276 | Channel D - Input k | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 276 | Channel D - Input k | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 277 | Channel D - Input k | Block input | 1 Bit | 1.3 enable | CW |
| 278 | Channel D - Binary input l | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 278 | Channel D - Binary input l | Window contact | 1 Bit | 1.19 window/door | CRT |
| 278 | Channel D - Binary input l | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 278 | Channel D - Binary input l | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 279 | Channel D - Binary input l | Block input | 1 Bit | 1.3 enable | CW |
| 280 | Channel D - Controller | Status Heating/cooling | 1 Bit | 1.100 cooling/heating | CRT |
| 281 | Channel D - Controller | Status Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 281 | Channel D - Controller | Status Control value basic-stage heating | 1 Bit | 1.1 switch | CRT |
| 282 | Channel D - Controller | Status Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 282 | Channel D - Controller | Status Control value additional-stage heating | 1 Bit | 1.1 switch | CRT |
| 283 | Channel D - Controller | Status Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 283 | Channel D - Controller | Status Control value basic-stage cooling | 1 Bit | 1.1 switch | CRT |
| 284 | Channel D - Controller | Status Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 284 | Channel D - Controller | Status Control value additional-stage cooling | 1 Bit | 1.1 switch | CRT |
| 286 | Channel D - Controller | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 287 | Channel D - Controller | External temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 288 | Channel D - Controller | External temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 289 | Channel D - Controller | Fault Actual temperature (master) | 1 Bit | 1.5 alarm | CRT |
| 290 | Channel D - Controller | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 291 | Channel D - Controller | Operating mode normal (master) | 1 Byte | 20.102 HVAC mode | CWTU |
| 292 | Channel D - Controller | Operating mode override (master) | 1 Byte | 20.102 HVAC mode | CWTU |
| 293 | Channel D - Controller | Window contact (master/slave) | 1 Bit | 1.19 window/door | CW |
| 294 | Channel D - Controller | Presence detector (master/slave) | 1 Bit | 1.18 occupancy | CW |
| 295 | Channel D - Controller | Status Heating | 1 Bit | 1.1 switch | CRT |
| 296 | Channel D - Controller | Status Cooling | 1 Bit | 1.1 switch | CRT |
| 297 | Channel D - Controller | Activation of minimum control value (basic load) | 1 Bit | 1.3 enable | CW |
| 298 | Channel D - Controller | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 298 | Channel D - Actuator | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 299 | Channel D - Controller | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 300 | Channel D - Controller | Reset manual setpoint adjustment | 1 Bit | 1.17 trigger | CW |
| 301 | Channel D - Controller | Dew point alarm | 1 Bit | 1.5 alarm | CWTU |
| 302 | Channel D - Controller | Fill level alarm | 1 Bit | 1.5 alarm | CWTU |
| 303 | Channel D - Controller | Outside temperature for summer compensation | 2 Bytes | 9.1 temperature (°C) | CW |
| 304 | Channel D - Controller | Summer compensation active/inactive | 1 Bit | 1.2 boolean | CRT |
| 305 | Channel D - Controller | Comfort setpoint reached | 1 Bit | 1.2 boolean | CRT |
| 306 | Channel D - Controller | Request On/Off (master) | 1 Bit | 1.1 switch | CW |
| 307 | Channel D - Controller | Confirm On/Off (master) | 1 Bit | 1.1 switch | CRT |
| 308 | Channel D - Controller | Setpoint display (master) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 309 | Channel D - Controller | Request setpoint adjustment (master) | 2 Bytes | 9.1 temperature (°C) | CW |
| 309 | Channel D - Controller | Request setpoint adjustment (master) | 2 Bytes | 9.2 temperature difference (K) | CW |
| 309 | Channel D - Controller | Request setpoint adjustment (master) | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 309 | Channel D - Actuator | Request setpoint adjustment (slave) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 309 | Channel D - Actuator | Request setpoint adjustment (slave) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 310 | Channel D - Controller | Confirm setpoint adjustment (master) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 310 | Channel D - Controller | Confirm setpoint adjustment (master) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 310 | Channel D - Controller | Confirm setpoint adjustment (master) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 311 | Channel D - Controller | Request heating/cooling (master) | 1 Bit | 1.100 cooling/heating | CW |
| 316 | Channel D - Controller | Status Controller RHCC | 2 Bytes | 22.101 RHCC status | CRT |
| 317 | Channel D - Controller | Status Controller HVAC (master) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 318 | Channel D - Controller | Current HVAC operating mode | 1 Byte | 20.102 HVAC mode | CRT |
| 319 | Channel D - Controller | Comfort heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 319 | Channel D - Controller | Comfort heating/cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 320 | Channel D - Controller | Comfort cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 321 | Channel D - Controller | Economy heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 322 | Channel D - Controller | Economy cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 323 | Channel D - Controller | Standby heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 324 | Channel D - Controller | Standby cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 325 | Channel D - Controller | Building Protection heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 326 | Channel D - Controller | Building Protection cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 327 | Channel D - Actuator | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 328 | Channel D - Actuator | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 329 | Channel D - Controller | Basic-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 330 | Channel D - Controller | Additional-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 331 | Channel D - Controller | Basic-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 332 | Channel D - Controller | Additional-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |