ABB AG - BUSCH-JAEGER 6190/50 AE/A2.1 Analogue Input,2-fold,SM

AE/A2.1 Analogue Input,2-fold,SM 6190/50

ABB AG - BUSCH-JAEGER · Order number 6190/50 · Standard Inputs › Analogue Inputs

Threshold Value Measurement 2f/1.0b

Download .knxprod Threshold Value Measurement 2f/1.0b 1.0 · 167 KB

Product

ManufacturerABB AG - BUSCH-JAEGER
Product nameAE/A2.1 Analogue Input,2-fold,SM
Order number6190/50
HardwareAE/A2.1 Analogeingang,2fach,AP
MediumTwisted Pair
Bus current (mA)8
Rail mountedNo
RegistrationCertified
Languagesde-DE, en-US
Catalog entryM-0007_H-2CDG.20110.20086.20R0011-1-O0002_HP-A04B-10-FB51-O0002_CI-6190.2F50-1
FingerprintFB51
SHA-2566909d43d5a53ffe260f40fcd4f89c1174c988add73f02bfb98473904a4283c2d
First seen2026-11-25
MarketsAustria, Belgium, Germany, Netherlands

Application program: Threshold Value Measurement 2f/1.0b 1.0

Application number$A04B
Version1.0
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Parameters400
Group objects62
Group objects (62)
NoNameFunctionSizeDPTFlags
0Input AOutput value2 BytesCRT
0Input AOutput value1 ByteCRT
0Input AOutput value4 BytesCRT
0Input AOutput value1 BitCRT
1Input ARequest output value1 BitCW
2Input AMeasured value outside range1 BitCRT
3Input A Thresh.v.1Threshold value1 ByteCRT
3Input A Thresh.v.1Threshold value1 BitCRT
4Input A Threshold 1 lower limitModify2 BytesCRW
4Input A Threshold 1 lower limitModify1 ByteCRW
4Input A Threshold 1 lower limitModify4 BytesCRW
5Input A Threshold 1 upper limitModify2 BytesCRW
5Input A Threshold 1 upper limitModify1 ByteCRW
5Input A Threshold 1 upper limitModify4 BytesCRW
6Input A Thresh.v.2Threshold value1 ByteCRT
6Input A Thresh.v.2Threshold value1 BitCRT
7Input A Threshold 2 lower limitModify2 BytesCRW
7Input A Threshold 2 lower limitModify1 ByteCRW
7Input A Threshold 2 lower limitModify4 BytesCRW
8Input A Threshold 2 upper limitModify2 BytesCRW
8Input A Threshold 2 upper limitModify1 ByteCRW
8Input A Threshold 2 upper limitModify4 BytesCRW
9Input BOutput value2 BytesCRT
9Input BOutput value1 ByteCRT
9Input BOutput value4 BytesCRT
9Input BOutput value1 BitCRT
10Input BRequest output value1 BitCW
11Input BMeasured value outside range1 BitCRT
12Input B Thresh.v.1Threshold value1 ByteCRT
12Input B Thresh.v.1Threshold value1 BitCRT
13Input B Threshold 1 lower limitModify1 ByteCRW
13Input B Threshold 1 lower limitModify2 BytesCRW
13Input B Threshold 1 lower limitModify4 BytesCRW
14Input B Threshold 1 upper limitModify1 ByteCRW
14Input B Threshold 1 upper limitModify2 BytesCRW
14Input B Threshold 1 upper limitModify4 BytesCRW
15Input B Thresh.v.2Threshold value1 ByteCRT
15Input B Thresh.v.2Threshold value1 BitCRT
16Input B Threshold 2 lower limitModify2 BytesCRW
16Input B Threshold 2 lower limitModify1 ByteCRW
16Input B Threshold 2 lower limitModify4 BytesCRW
17Input B Threshold 2 upper limitModify2 BytesCRW
17Input B Threshold 2 upper limitModify1 ByteCRW
17Input B Threshold 2 upper limitModify4 BytesCRW
18Calculation 1Send output value1 BitCRT
18Calculation 1Send output value2 BytesCRT
18Calculation 1Send output value4 BytesCRT
18Calculation 1Send output value1 ByteCRT
19Calculation 2Send output value1 BitCRT
19Calculation 2Send output value4 BytesCRT
19Calculation 2Send output value2 BytesCRT
19Calculation 2Send output value1 ByteCRT
20Calculation 3Send output value1 BitCRT
20Calculation 3Send output value4 BytesCRT
20Calculation 3Send output value2 BytesCRT
20Calculation 3Send output value1 ByteCRT
21Calculation 4Send output value1 BitCRT
21Calculation 4Send output value4 BytesCRT
21Calculation 4Send output value2 BytesCRT
21Calculation 4Send output value1 ByteCRT
22SystemIn operation1 BitCRT
23SystemStatus byte1 ByteCRT
Parameters (105)
ParameterTypeDefault
Konvertierbar ab Version 0.1unsignedInt 0…2551
For the parameter attitudes the sensor manufacturer data are to be consideredlist<- Note
Behavior after bus voltage recoverylistno reaction
Behavior after mains voltage recoverylistno reaction
Behavior after programminglistno reaction
Send delay for above parameterslist10 s
Maximum telegram ratelist1 telegram/second
Send object 'In operation'listno
Sending cycle time in s [1...65,535]unsignedInt 1…6553560
Send output value asunsignedInt 0…2550
DummyunsignedInt 1…6553560
Designation for input A (40 characters)text<Text>
Designation for input B (40 characters)text<Text>
Use inputlistno
Sensor typelistTemperature-dependent resistance
Sensor outputlist0-10 V
Sensor outputlistPT100 2-conductor technology [-50...+150 °C]
Sensor outputlistFloating contact interrogation
Manufacturer designationlistKT 100 / 110 / 130
The following ohm values must rise to higher temperatureslist<- Note
Resistance in ohms with -50 °CunsignedInt 0…56001030
Resistance in ohms with -30 °CunsignedInt 0…56001247
Resistance in ohms with -10 °CunsignedInt 0…56001495
Resistance in ohms with +10 °CunsignedInt 0…56001772
Resistance in ohms with +30 °CunsignedInt 0…56002080
Resistance in ohms with +50 °CunsignedInt 0…56002417
Resistance in ohms with +70 °CunsignedInt 0…56002785
Resistance in ohms with +90 °CunsignedInt 0…56003182
Resistance in ohms with +110 °CunsignedInt 0…56003607
Resistance in ohms with +130 °CunsignedInt 0…56004008
Resistance in ohms with +150 °CunsignedInt 0…56004280
Send output value aslist1 byte [0...+255]
Temperature offset in 0.1 K [-50...+50]signedInt -50…500
Line fault compensationlistnone
Length of the cable, single distance [1...30 m]unsignedInt 1…3010
Cable resistance in milliohms [total of forward and return conduct]unsignedInt 0…10000500
Cross-section of the conductor value * 0.01 mm² [1...150]unsignedInt 1…150100
The compensation via cable length is suitable only for CU conductorlist<- Note
Signal ON if contactlistopened
Output value is sent aslist1 bit
Output value is sent aslist1 byte [0...+255]
Lower measuring limit in x % from the upper limit of effective rangesignedInt 0…1000
Output value to be sent for lower measuring limit [0...+255]signedInt 0…2550
Output value to be sent for lower measuring limit [-128...+127]signedInt -128…127-128
Output value to be sent for lower measuring limit [0...+65,535]unsignedInt 0…655350
Output value to be sent for lower measuring limit [-32,768...+32,767]signedInt -32768…32767-32768
Output value to be sent for lower measuring limit [-1,000...+1,000]signedInt -1000…1000-1000
Upper measuring limit in x % from the upper limit of effective rangesignedInt 0…100100
Output value to be sent for upper measuring limit [-1,000...+1,000]signedInt -1000…10001000
Output value to be sent for upper measuring limit [0...+255]signedInt 0…255255
Output value to be sent for lower measuring limit [-128...+127]signedInt -128…127127
Output value to be sent for lower measuring limit [0...+65,535]unsignedInt 0…6553565535
Output value to be sent for upper measuring limit [-32,768...+32,767]signedInt -32768…3276732767
Factor for the output and threshold valueslist1
Factor for the output and threshold valuelist1
Scanning frequency One measuring per secondlist<- Note
Filterlistinactive
Send output valuelistcyclically
Output value is sent from a x% change in the output rangesignedInt 1…1002
Output value is sent from a change of [x 0.1 °C]unsignedInt 1…20010
Output value is sent everylist5 s
Use threshold valuelistno
Tolerance band lower limitunsignedInt 0…655350
Tolerance band lower limitsignedInt -32768…32767-32768
Tolerance band lower limit factor as measuring rangesignedInt -1000…1000-1000
Tolerance band lower limitsignedInt -128…127-128
Tolerance band lower limitsignedInt 0…2550
Tolerance band lower limit input in 0.1 °CsignedInt -500…1500-500
Tolerance band upper limitunsignedInt 0…6553565535
Tolerance band upper limitsignedInt -32768…3276732767
Tolerance band upper limit factor as measuring rangesignedInt -1000…10001000
Tolerance band upper limitsignedInt -128…127127
Tolerance band upper limitsignedInt 0…255255
Tolerance band upper limit Input in 0.1 °CsignedInt -500…15001500
Modify limits via the buslistyes
Data type of threshold value objectlist1 bit
Send if threshold value falls belowlistsend an OFF telegram
Send if threshold value falls below [0...+255]unsignedInt 0…2550
Minimum duration of the underflowlistnone
Send if threshold value exceedslistsend an ON telegram
Send if threshold value exceeds [0...+255]unsignedInt 0…255255
Minimum duration of the overrangelistnone
Send threshold value objectlistafter a change and cyclically
Send if threshold value falls below everylist30 s
Send if threshold value exceeds everylist30 s
Send if signal OFFlistsend an OFF telegram
Send if signal OFF [0...+255]unsignedInt 0…2550
Minimum duration for signal OFFlistnone
Send if signal ONlistsend an ON telegram
Send if signal ON [0...+255]unsignedInt 0…255255
Minimum duration for signal ONlistnone
Send if signal OFF everylist30 s
Send if signal ON everylist30 s
Factor for the output and threshold valueslist1
Use calculationlistno
Calculation typelistcomparative
Input 1listInput A output value
Input 2listInput B output value
FunctionlistInput 1 < Input 2
FunctionlistInput 1 + Input 2
Hysteresis (in x % from outp. range of input 1)signedInt 1…1005
Condition metlistsend an ON telegram
Condition not metlistsend an OFF telegram
Send output valuelistafter a change and cyclically
Output value is sent from a x % change in the output range of input 1signedInt 1…1002

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Threshold Value Measurement 2f/1.0b 1.0 latest$A04BFB512026-11-25167 KBDownload

About this file

This is the official ETS product database for the ABB AG - BUSCH-JAEGER AE/A2.1 Analogue Input,2-fold,SM (6190/50), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.