| Konvertierbar ab Version 0.1 | unsignedInt 0…255 | 1 |
| For the parameter attitudes the sensor
manufacturer data are to be considered | list | <- Note |
| Behavior after bus voltage recovery | list | no reaction |
| Behavior after mains voltage recovery | list | no reaction |
| Behavior after programming | list | no reaction |
| Send delay for above parameters | list | 10 s |
| Maximum telegram rate | list | 1 telegram/second |
| Send object 'In operation' | list | no |
| Sending cycle time in s
[1...65,535] | unsignedInt 1…65535 | 60 |
| Send output value as | unsignedInt 0…255 | 0 |
| Dummy | unsignedInt 1…65535 | 60 |
| Designation for input A
(40 characters) | text | <Text> |
| Designation for input B
(40 characters) | text | <Text> |
| Use input | list | no |
| Sensor type | list | Temperature-dependent resistance |
| Sensor output | list | 0-10 V |
| Sensor output | list | PT100 2-conductor technology [-50...+150 °C] |
| Sensor output | list | Floating contact interrogation |
| Manufacturer designation | list | KT 100 / 110 / 130 |
| The following ohm values must rise
to higher temperatures | list | <- Note |
| Resistance in ohms with -50 °C | unsignedInt 0…5600 | 1030 |
| Resistance in ohms with -30 °C | unsignedInt 0…5600 | 1247 |
| Resistance in ohms with -10 °C | unsignedInt 0…5600 | 1495 |
| Resistance in ohms with +10 °C | unsignedInt 0…5600 | 1772 |
| Resistance in ohms with +30 °C | unsignedInt 0…5600 | 2080 |
| Resistance in ohms with +50 °C | unsignedInt 0…5600 | 2417 |
| Resistance in ohms with +70 °C | unsignedInt 0…5600 | 2785 |
| Resistance in ohms with +90 °C | unsignedInt 0…5600 | 3182 |
| Resistance in ohms with +110 °C | unsignedInt 0…5600 | 3607 |
| Resistance in ohms with +130 °C | unsignedInt 0…5600 | 4008 |
| Resistance in ohms with +150 °C | unsignedInt 0…5600 | 4280 |
| Send output value as | list | 1 byte [0...+255] |
| Temperature offset in 0.1 K
[-50...+50] | signedInt -50…50 | 0 |
| Line fault compensation | list | none |
| Length of the cable, single distance
[1...30 m] | unsignedInt 1…30 | 10 |
| Cable resistance in milliohms [total
of forward and return conduct] | unsignedInt 0…10000 | 500 |
| Cross-section of the conductor
value * 0.01 mm² [1...150] | unsignedInt 1…150 | 100 |
| The compensation via cable length
is suitable only for CU conductor | list | <- Note |
| Signal ON if contact | list | opened |
| Output value is sent as | list | 1 bit |
| Output value is sent as | list | 1 byte [0...+255] |
| Lower measuring limit in x % from the
upper limit of effective range | signedInt 0…100 | 0 |
| Output value to be sent for lower
measuring limit [0...+255] | signedInt 0…255 | 0 |
| Output value to be sent for lower
measuring limit [-128...+127] | signedInt -128…127 | -128 |
| Output value to be sent for lower
measuring limit [0...+65,535] | unsignedInt 0…65535 | 0 |
| Output value to be sent for lower
measuring limit [-32,768...+32,767] | signedInt -32768…32767 | -32768 |
| Output value to be sent for lower
measuring limit [-1,000...+1,000] | signedInt -1000…1000 | -1000 |
| Upper measuring limit in x % from
the upper limit of effective range | signedInt 0…100 | 100 |
| Output value to be sent for upper
measuring limit [-1,000...+1,000] | signedInt -1000…1000 | 1000 |
| Output value to be sent for upper
measuring limit [0...+255] | signedInt 0…255 | 255 |
| Output value to be sent for lower
measuring limit [-128...+127] | signedInt -128…127 | 127 |
| Output value to be sent for lower
measuring limit [0...+65,535] | unsignedInt 0…65535 | 65535 |
| Output value to be sent for upper
measuring limit [-32,768...+32,767] | signedInt -32768…32767 | 32767 |
| Factor for the output and
threshold values | list | 1 |
| Factor for the output and
threshold value | list | 1 |
| Scanning frequency
One measuring per second | list | <- Note |
| Filter | list | inactive |
| Send output value | list | cyclically |
| Output value is sent from a
x% change in the output range | signedInt 1…100 | 2 |
| Output value is sent from a change
of [x 0.1 °C] | unsignedInt 1…200 | 10 |
| Output value is sent every | list | 5 s |
| Use threshold value | list | no |
| Tolerance band lower limit | unsignedInt 0…65535 | 0 |
| Tolerance band lower limit | signedInt -32768…32767 | -32768 |
| Tolerance band lower limit
factor as measuring range | signedInt -1000…1000 | -1000 |
| Tolerance band lower limit | signedInt -128…127 | -128 |
| Tolerance band lower limit | signedInt 0…255 | 0 |
| Tolerance band lower limit
input in 0.1 °C | signedInt -500…1500 | -500 |
| Tolerance band upper limit | unsignedInt 0…65535 | 65535 |
| Tolerance band upper limit | signedInt -32768…32767 | 32767 |
| Tolerance band upper limit
factor as measuring range | signedInt -1000…1000 | 1000 |
| Tolerance band upper limit | signedInt -128…127 | 127 |
| Tolerance band upper limit | signedInt 0…255 | 255 |
| Tolerance band upper limit
Input in 0.1 °C | signedInt -500…1500 | 1500 |
| Modify limits via the bus | list | yes |
| Data type of threshold value object | list | 1 bit |
| Send if threshold value falls below | list | send an OFF telegram |
| Send if threshold value falls below
[0...+255] | unsignedInt 0…255 | 0 |
| Minimum duration of the underflow | list | none |
| Send if threshold value exceeds | list | send an ON telegram |
| Send if threshold value exceeds
[0...+255] | unsignedInt 0…255 | 255 |
| Minimum duration of the overrange | list | none |
| Send threshold value object | list | after a change and cyclically |
| Send if threshold value
falls below every | list | 30 s |
| Send if threshold value
exceeds every | list | 30 s |
| Send if signal OFF | list | send an OFF telegram |
| Send if signal OFF
[0...+255] | unsignedInt 0…255 | 0 |
| Minimum duration for signal OFF | list | none |
| Send if signal ON | list | send an ON telegram |
| Send if signal ON
[0...+255] | unsignedInt 0…255 | 255 |
| Minimum duration for signal ON | list | none |
| Send if signal OFF every | list | 30 s |
| Send if signal ON every | list | 30 s |
| Factor for the output and
threshold values | list | 1 |
| Use calculation | list | no |
| Calculation type | list | comparative |
| Input 1 | list | Input A output value |
| Input 2 | list | Input B output value |
| Function | list | Input 1 < Input 2 |
| Function | list | Input 1 + Input 2 |
| Hysteresis
(in x % from outp. range of input 1) | signedInt 1…100 | 5 |
| Condition met | list | send an ON telegram |
| Condition not met | list | send an OFF telegram |
| Send output value | list | after a change and cyclically |
| Output value is sent from a x % change
in the output range of input 1 | signedInt 1…100 | 2 |