KNX Database
Theben AG 8559201 KNX-OT-Box S

KNX-OT-Box S 8559201

Theben AG · Order number 8559201 · Gateways › OpenTherm

Control of 2 heating circuits. Can be combined with RAMSES 856 top2 OT.

Download .knxprod KNX-OT- Box S 1.0 · 116 KB

Product

ManufacturerTheben AG
Product nameKNX-OT-Box S
Order number8559201
Product textKNX-OT Gateway S (for OT boiler/RAMSES 856top2 OT)
HardwareKNX-Opentherm-Box
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)70
RegistrationCertified · 2015-02-24
Languagesde-DE, en-US, es-ES, fr-FR, it-IT, nl-NL
Catalog entryM-0048_H-8559201-1_HP-855B-10-BB88_CI-8559201-1
FingerprintBB88
SHA-25669fec6fb209981c22097a16995631d136057b0d899bb8c3f172235aaf7e81bb7
First seen2026-11-25
Markets59 markets

Application program: KNX-OT- Box S 1.0

Application number$855B
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Parameters166
Group objects91
Group objects (91)
NoNameFunctionSizeDPTFlags
0H1 Flow basic set point value in comfort modeDefine flow set point value2 Bytes9.1 temperature (°C)CRWU
1H1 Manual offset of flow set point valueOffset flow set point value2 Bytes9.2 temperature difference (K)CRWU
2H1 Enable central heatingHeating on/off1 Bit1.3 enableCRWU
3H1 Max. actuating value zone/room 1 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
3H1 Max. act. value zone/room 1 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
4H1 Max. actuating value zone/room 2 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
4H1 Max. act. value zone/room 2 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
5H1 Max. actuating value zone/room 3 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
5H1 Max. act. value zone/room 3 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
6H1 Max. actuating value zone/room 4 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
6H1 Max. act. value zone/room 4 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
7H1 Max. actuating value zone/room 5 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
7H1 Max. act. value zone/room 5 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
8H1 Max. actuating value zone/room 6 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
8H1 Max. act. value zone/room 6 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
9H1 Max. actuating value zone/room 7 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
9H1 Max. act. value zone/room 7 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
10H1 Max. actuating value zone/room 8 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
10H1 Max. act. value zone/room 8 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
11H1 Max. actuating value zone/room 9 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
11H1 Max. act. value zone/room 9 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
12H1 Max. actuating value zone/room 10 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
12H1 Max. act. value zone/room 10 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
13Summer modeSummer mode on/off1 Bit1.1 switchCRWU
14H1 HVAC operating mode heatingReceive HVAC operating mode1 Byte5.10 counter pulses (0..255)CRWU
15H1 Lock demand control1 = locked/ 0 = enabled1 Bit1.3 enableCRWU
16H1 Current flow temperatureSend current flow temperature2 Bytes9.1 temperature (°C)CRTU
17H1 Flow set point valueSend curr. flow set point val.2 Bytes9.1 temperature (°C)CRTU
18Flame statusSend flame status1 Bit1.1 switchCRTU
19General errorReport general error1 BitCRTU
20Error code (as per Opentherm ID 5)Report error code1 Byte5.10 counter pulses (0..255)CRTU
21H1 Heating statusReport heating status1 Bit1.1 switchCRTU
22Service requiredReport service requirement1 Bit1.1 switchCRTU
23Outdoor temperatureReceive outdoor temperature2 Bytes9.1 temperature (°C)CRWU
23Outdoor temperatureSend outdoor temperature2 Bytes9.1 temperature (°C)CRT
24Outdoor temperature errorOut. T. missing or incorrect1 Bit1.1 switchCRTU
25Enable domestic hot water (DHW)Domestic water heating on/off1 Bit1.3 enableCRWU
26Current solar supportSolar support option = 11 Bit1.1 switchCRWU
27Expected solar supportSolar support option = 11 Bit1.1 switchCRWU
28HVAC operating mode domestic waterReceive HVAC operating mode1 Byte5.10 counter pulses (0..255)CRWU
29Forced mode domestic waterForced mode = 11 Bit1.1 switchCRWU
30Domestic water set point value in forced modeDefine set point value2 Bytes9.1 temperature (°C)CRWU
31Domestic water temperature set point valueReport dom. water set point2 Bytes9.1 temperature (°C)CRTU
32Currrent domestic water temperatureSend current temperature2 Bytes9.1 temperature (°C)CRTU
33Domestic water statusReport domestic water status1 Bit1.1 switchCRTU
34Degree of modulation in %Report degree of modulation1 Byte5.1 percentage (0..100%)CT
35Lower limit of domestic water set point valueReport boiler setting2 Bytes9.1 temperature (°C)CT
36Upper limit of domestic water set point valueReport boiler setting2 Bytes9.1 temperature (°C)CT
37H1 Lower limit of flow set point valueReport boiler setting2 Bytes9.1 temperature (°C)CT
38H1 Upper limit of flow set point valueReport boiler setting2 Bytes9.1 temperature (°C)CT
39- Nur für Test -Für Endtest1 Byte5.10 counter pulses (0..255)CW
40H2 Flow basic set point value in comfort modeDefine flow set point value2 Bytes9.1 temperature (°C)CRWU
41H2 Manual offset of flow set point valueOffset flow set point value2 Bytes9.2 temperature difference (K)CRWU
42H2 Enable central heatingHeating on/off1 Bit1.3 enableCRWU
43H2 Max. act. value zone/room 11 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
43H2 Max. actuating value zone/room 11 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
44H2 Max. act. value zone/room 12 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
44H2 Max. actuating value zone/room 12 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
45H2 Max. act. value zone/room 13 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
45H2 Max. actuating value zone/room 13 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
46H2 Max. act. value zone/room 14 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
46H2 Max. actuating value zone/room 14 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
47H2 Max. act. value zone/room 15 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
47H2 Max. actuating value zone/room 15 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
48H2 Max. act. value zone/room 16 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
48H2 Max. actuating value zone/room 16 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
49H2 Max. act. value zone/room 17 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
49H2 Max. actuating value zone/room 17 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
50H2 Max. act. value zone/room 18 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
50H2 Max. actuating value zone/room 18 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
51H2 Max. act. value zone/room 19 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
51H2 Max. actuating value zone/room 19 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
52H2 Max. act. value zone/room 20 weather + demandReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
52H2 Max. actuating value zone/room 20 demand-drivenReceive actuating value1 Byte5.1 percentage (0..100%)CRWU
53H2 HVAC operating mode heatingReceive HVAC operating mode1 Byte5.10 counter pulses (0..255)CRWU
54H2 Lock demand control1 = locked/ 0 = enabled1 Bit1.3 enableCRWU
55H2 Current flow temperatureSend current flow temperature2 Bytes9.1 temperature (°C)CRTU
56H2 Flow set point valueSend curr. flow set point val.2 Bytes9.1 temperature (°C)CRTU
57H2 Heating statusReport heating status1 Bit1.1 switchCRTU
58Burner startsOT- Box ID 1162 Bytes7.1 pulsesCRTU
59Burner operating hoursOT- Box ID 1202 Bytes7.1 pulsesCRTU
60H2 boiler temperatureOT- Box ID 1512 Bytes9.1 temperature (°C)CRTU
61H1 Flow temperatureOT- Box ID 1522 Bytes9.1 temperature (°C)CRTU
62H2 buffer temperatureOT- Box ID 1532 Bytes9.1 temperature (°C)CRTU
63Water pressureOT- Box ID 182 Bytes9.6 pressure (Pa)CRTU
64Time (DPT 10.001)OT- Box ID 203 Bytes10.1 time of dayCRWU
64Time (DPT 19.001)OT- Box ID 208 BytesCRWU
65Room set temperatureOT- Box ID 162 Bytes9.1 temperature (°C)CRWU
66Room actual temperatureOT- Box ID 242 Bytes9.1 temperature (°C)CRWU
67Time queryTransmit1 Bit1.1 switchCRTU
68Burner starts/hour counterReset1 Bit1.1 switchCRW
Parameters (111)
ParameterTypeDefault
Generallist25 °C
Download detectionlistdownload
Activate laying readiness heating (heating circuit 1 and 2)listno
Determining the set point value heating circuit 1listvia heating requirement, without weather
Maximum flow temperature during laying readiness heating [°C]unsignedInt 25…5555
Flow temperature after laying readiness heating [°C]unsignedInt 25…5525
Determining the set point value heating circuit 2listvia heating requirement, without weather
Activate domestic water heatinglistyes..
KNX OT interface controlslistOT boiler
Format of the time objectlist8 Byte (DPT 19.001)
Heating 1listno
Control settingslistmanual
Flow set point value after reset [°C]unsignedInt 20…9040
Base point of char.curve in °C (at 20 °C)unsignedInt 20…9040
End of char. curve in °C (at -20 °C)unsignedInt 20…9080
Reduction in standby modelist10 K
Reduction in night modelist15 K
Frost protection temperature [°C]unsignedInt 6…3010
Operating mode after resetlistcomfort mode
CH Enable after resetlistsame as before bus failure
Maximum flow temperature [°C]unsignedInt 30…9070
Maximum increase of flow temperature based on demand in roomslist30 K
Maximum reduction of flow temperature if there is no demandlist20 K
Delay for adjustment of set point valuelist15 min
Targeted maximum actuating valuelist70%
Automatic switch to summer modelistno
Weighting factor for zone 1list1,0
Weighting factor for zone 2list1,0
Weighting factor for zone 3list1,0
Weighting factor for zone 4list1,0
Weighting factor for zone 5list1,0
Weighting factor for zone 6list1,0
Weighting factor for zone 7list1,0
Weighting factor for zone 8list1,0
Weighting factor for zone 9list1,0
Weighting factor for zone 10list1,0
Resend flow set point value with change atlist5 K
Send flow set point value cyclicallylistno
Resend current flow temperature with change atlist2 K
Send current flow temperature cyclicallylistno
Send CH status cyclicallylistno
Send CH pressure cyclicallylistno
Send flame status cyclicallylistno
Send general error cyclicallylistno
Send error code cyclicallylistno
Send service required cyclicallylistno
Send degree of modulation cyclicallylistno
Send limits of flow set point value cyclicallylistno
Send burner hours/burner starts cyclicallylistno
Time for cyclical transmission of all CH reportslist30 minutes
Heating 2listno
Base point of char.curve in °C (at 20 °C)unsignedInt 20…9025
Flow set point value after reset [°C]unsignedInt 20…9025
End of char. curve in °C (at -20 °C)unsignedInt 20…9040
CH2 Enable after resetlistsame as before bus failure
Maximum flow temperature [°C]unsignedInt 30…9040
Weighting factor for zone 11list1,0
Weighting factor for zone 12list1,0
Weighting factor for zone 13list1,0
Weighting factor for zone 14list1,0
Weighting factor for zone 15list1,0
Weighting factor for zone 16list1,0
Weighting factor for zone 17list1,0
Weighting factor for zone 18list1,0
Weighting factor for zone 19list1,0
Weighting factor for zone 20list1,0
Send CH2 status cyclicallylistno
Time for cyclical transmission of all CH2 reportslist30 minutes
Determining outdoor temperaturelistvia object
Resend outdoor temperature with change atlist2 K
Monitoring of outdoor temperaturelistno
Send outdoor temperature cyclically (time see CH reports)listno
Outdoor temperature monitoring timelistevery 60 min
Replacement value with failure or error in outdoor temperaturesignedInt -20…200
Outdoor temperature error or failure (time see CH reports)listreport in event of change
Domestic water heatinglistno
Domestic water set point value in comfort mode [°C]unsignedInt 5…9060
Domestic water set point value in standby mode [°C]unsignedInt 5…9045
Domestic water set point value in night mode [°C]unsignedInt 5…9030
Domestic water set point value frost protection [°C]unsignedInt 5…3010
DHW Enable after resetlistsame as before bus failure
Domestic water set point value in forced mode if not via object [°C]unsignedInt 5…9085
Maximum domestic water set point value [°C]unsignedInt 30…9060
Energy maximisation with solar support optionlistno
Domestic water set point value with solar.. [°C]unsignedInt 5…9045
Activate legionella protectionlistyes
Set point value for legionella protect.unsignedInt 30…9080
Energy-saving legionella protection (performed during comfort mode)listevery 3 days
Unconditional legionella protection (performed with each operating mode)listevery 5 days
Send domestic water set point value in event of changelistyes
Send domestic water set point value cyclicallylistno
Resend current domestic water temperature in event of change atlist2 K
Send current domestic water temperature cyclicallylistno
Send limits of domestic hot water set point value cyclicallylistno
Send DHW status cyclicallylistno
Time for cyclical transmission of all DHW reportslist30 minutes
System selectionlistSystem 1
Boiler base temperaturelistoff
Maximum flow temperature in main circuit [°C]unsignedInt 36…9080
Maximum flow temperature in auxiliary circuit [°C]unsignedInt 30…9040
Boiler temperature hysteresis [K]unsignedInt 1…155
Domestic hot water hysteresis [K]unsignedInt 1…105
Domestic hot water priority/parallel operationlistdomestic hot water has priority
Time delay domestic hot water pumplist10 min
Domestic hot water for frost protectionlistno
Time for domestic hot water circ. pump [s] (0 s = temperature-controlled)unsignedInt 0…990
Perform pump protection atlist12:00
Pump protection duration [min] (0 = no pump protection)unsignedInt 0…9915
Delta T sequence control [K]list1,5 K
Delta T1 pump switch boiler 1 [K]unsignedInt 5…155
Delta T2 pump switch boiler 2 [K]unsignedInt 5…155

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX-OT- Box S 1.0 latest$855BBB882026-11-25116 KBDownload

About this file

This is the official ETS product database for the Theben AG KNX-OT-Box S (8559201), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.