RAMSES 718 S 7189200
Theben AG · Order number 7189200 · Heizung, Klima, Lüftung › Stetig- und 2 Punkt-Regler
Einzelraum-Temperaturregler
Download .knxprod RAMSES 718 S 2.3 · 251 KB
Product
| Manufacturer | Theben AG |
|---|---|
| Product name | RAMSES 718 S |
| Order number | 7189200 |
| Hardware | RAMSES 718 S |
| Medium | Twisted Pair |
| Bus current (mA) | 15 |
| Rail mounted | No |
| Registration | Certified · 2017-11-10 |
| Languages | de-DE, en-US, es-ES, fr-FR, it-IT, nl-NL |
| Catalog entry | M-0048_H-7189200-0_HP-7180-23-0908_CI-7189200-1 |
| Fingerprint | 0908 |
| SHA-256 | 305d744a143d4030091ffe98aa4dd5d2a860d02e94db4231c8195d44fbfae173 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: RAMSES 718 S 2.3
| Application number | $7180 |
|---|---|
| Version | 2.3 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 890 |
| Group objects | 182 |
Group objects (182)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Temperaturwert | Senden | 2 Bytes | DPT.9 | CRT |
| 2 | Geräte-LEDs | Reduziert | 1 Bit | DPT.1 | CW |
| 2 | Geräte-LEDs | Helligkeit | 1 Byte | DPT.5 | CW |
| 10 | Basissollwert | Solltemperatur vorgeben | 2 Bytes | DPT.9 | CW |
| 10 | Basissollwert am Stellrad | Senden | 2 Bytes | DPT.9 | CRT |
| 11 | Manuelle Sollwertverschiebung | Empfangen | 2 Bytes | DPT.9 | CW |
| 11 | Sollwertverschiebung am Stellrad | Senden | 2 Bytes | DPT.9 | CRT |
| 12 | Außentemperaturkompensation | Senden | 2 Bytes | DPT.9 | CRT |
| 12 | Außentemperaturkompensation | Sollwert schieben | 2 Bytes | DPT.9 | CW |
| 13 | Nacht - Standby | 1=Nacht, 0=Standby | 1 Bit | DPT.1 | CW |
| 13 | Betriebsartvorwahl | Empfangen | 1 Byte | DPT.20 | CW |
| 14 | Komfort | Empfangen | 1 Bit | DPT.1 | CW |
| 14 | Präsenz | Empfangen | 1 Bit | DPT.1 | CW |
| 15 | Frost-/Hitzeschutz | Empfangen | 1 Bit | DPT.1 | CW |
| 15 | Fensterstatus | Geschlossen=0, Offen=1 | 1 Bit | DPT.1 | CW |
| 16 | Aktuelle Betriebsart | Senden | 1 Byte | DPT.20 | CRT |
| 17 | Betriebsart als Szene | Speichern/abrufen | 1 Byte | DPT.18 | CWT |
| 18 | Stellgröße Heizen | Senden | 1 Byte | DPT.5 | CT |
| 18 | Stellgröße Heizen | Senden | 1 Bit | DPT.1 | CT |
| 18 | Stellgröße Heizen/Kühlen | Senden | 1 Byte | DPT.5 | CT |
| 18 | Stellgröße Heizen/Kühlen | Senden | 1 Bit | DPT.1 | CT |
| 19 | Stellgröße Heizen Zusatzstufe | Senden | 1 Byte | DPT.5 | CT |
| 19 | PWM Heizen Zusatzstufe | Senden | 1 Bit | DPT.1 | CT |
| 20 | Stellgröße Kühlen | Senden | 1 Byte | DPT.5 | CT |
| 20 | Stellgröße Kühlen | Senden | 1 Bit | DPT.1 | CT |
| 21 | Stellgröße Kühlen Zusatzstufe | Senden | 1 Byte | DPT.5 | CT |
| 21 | PWM Kühlen Zusatzstufe | Senden | 1 Bit | DPT.1 | CT |
| 22 | Heizbetrieb/Kühlbetrieb senden | 0 = Kühlen, 1 = Heizen | 1 Bit | DPT.1 | CRT |
| 22 | Heizbetrieb/Kühlbetrieb senden | 0 = Heizen, 1 = Kühlen | 1 Bit | DPT.1 | CRT |
| 22 | Umschalten zwischen Heizen und Kühlen | 0 = Kühlen, 1 = Heizen | 1 Bit | DPT.1 | CW |
| 22 | Umschalten zwischen Heizen und Kühlen | 0 = Heizen, 1 = Kühlen | 1 Bit | DPT.1 | CW |
| 23 | Aktueller Sollwert | Setzen/senden | 2 Bytes | DPT.9 | CRWT |
| 24 | Istwert für Regelung | Senden | 2 Bytes | DPT.9 | CRT |
| 25 | Externer Istwert | Empfangen | 2 Bytes | DPT.9 | CW |
| 26 | Istwertausfall | Senden | 1 Bit | DPT.1 | CRT |
| 27 | Außentemperatur | Empfangen | 2 Bytes | DPT.9 | CW |
| 28 | Taupunktalarm | Empfangen | 1 Bit | DPT.1 | CW |
| 30 | Kanal I1 | Schalten | 1 Bit | DPT.1 | CT |
| 30 | Kanal I1 | Schalten | 1 Bit | DPT.1 | CWT |
| 30 | Kanal I1 | Step / Stop | 1 Bit | DPT.1 | CT |
| 30 | Kanal I1.1 | Schalten | 1 Bit | DPT.1 | CWT |
| 30 | Kanal I1.1 | Priorität | 2 Bit | DPT.2 | CT |
| 30 | Kanal I1.1 | Wert senden | 1 Byte | DPT.5 | CT |
| 30 | Kanal I1.1 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 30 | Kanal I1.1 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 30 | Kanal I1.1 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 31 | Kanal I1 | Heller / Dunkler | 4 Bit | DPT.3 | CT |
| 31 | Kanal I1 | Auf / Ab | 1 Bit | DPT.1 | CWT |
| 31 | Kanal I1 | Auf | 1 Bit | DPT.1 | CT |
| 31 | Kanal I1 | Ab | 1 Bit | DPT.1 | CT |
| 31 | Kanal I1.2 | Schalten | 1 Bit | DPT.1 | CWT |
| 31 | Kanal I1.2 | Priorität | 2 Bit | DPT.2 | CT |
| 31 | Kanal I1.2 | Wert senden | 1 Byte | DPT.5 | CT |
| 31 | Kanal I1.2 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 31 | Kanal I1.2 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 31 | Kanal I1.2 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 32 | Kanal I1.1 | Schalten | 1 Bit | DPT.1 | CWT |
| 32 | Kanal I1.1 | Priorität | 2 Bit | DPT.2 | CT |
| 32 | Kanal I1.1 | Wert senden | 1 Byte | DPT.5 | CT |
| 32 | Kanal I1.1 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 32 | Kanal I1.1 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 32 | Kanal I1.1 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 32 | Kanal I1.1 | Höhe % | 1 Byte | DPT.5 | CT |
| 32 | Kanal I1.3 | Schalten | 1 Bit | DPT.1 | CWT |
| 32 | Kanal I1.3 | Priorität | 2 Bit | DPT.2 | CT |
| 32 | Kanal I1.3 | Wert senden | 1 Byte | DPT.5 | CT |
| 32 | Kanal I1.3 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 32 | Kanal I1.3 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 32 | Kanal I1.3 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 33 | Kanal I1.2 | Lamelle % | 1 Byte | DPT.5 | CT |
| 34 | Kanal I1 | Sperren = 1 | 1 Bit | DPT.1 | CW |
| 34 | Kanal I1 | Sperren = 0 | 1 Bit | DPT.1 | CW |
| 35 | Kanal I2 | Schalten | 1 Bit | DPT.1 | CT |
| 35 | Kanal I2 | Schalten | 1 Bit | DPT.1 | CWT |
| 35 | Kanal I2 | Step / Stop | 1 Bit | DPT.1 | CT |
| 35 | Kanal I2.1 | Schalten | 1 Bit | DPT.1 | CWT |
| 35 | Kanal I2.1 | Priorität | 2 Bit | DPT.2 | CT |
| 35 | Kanal I2.1 | Wert senden | 1 Byte | DPT.5 | CT |
| 35 | Kanal I2.1 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 35 | Kanal I2.1 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 35 | Kanal I2.1 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 36 | Kanal I2 | Heller / Dunkler | 4 Bit | DPT.3 | CT |
| 36 | Kanal I2 | Auf / Ab | 1 Bit | DPT.1 | CWT |
| 36 | Kanal I2 | Auf | 1 Bit | DPT.1 | CT |
| 36 | Kanal I2 | Ab | 1 Bit | DPT.1 | CT |
| 36 | Kanal I2.2 | Schalten | 1 Bit | DPT.1 | CWT |
| 36 | Kanal I2.2 | Priorität | 2 Bit | DPT.2 | CT |
| 36 | Kanal I2.2 | Wert senden | 1 Byte | DPT.5 | CT |
| 36 | Kanal I2.2 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 36 | Kanal I2.2 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 36 | Kanal I2.2 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 37 | Kanal I2.1 | Schalten | 1 Bit | DPT.1 | CWT |
| 37 | Kanal I2.1 | Priorität | 2 Bit | DPT.2 | CT |
| 37 | Kanal I2.1 | Wert senden | 1 Byte | DPT.5 | CT |
| 37 | Kanal I2.1 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 37 | Kanal I2.1 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 37 | Kanal I2.1 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 37 | Kanal I2.1 | Höhe % | 1 Byte | DPT.5 | CT |
| 37 | Kanal I2.3 | Schalten | 1 Bit | DPT.1 | CWT |
| 37 | Kanal I2.3 | Priorität | 2 Bit | DPT.2 | CT |
| 37 | Kanal I2.3 | Wert senden | 1 Byte | DPT.5 | CT |
| 37 | Kanal I2.3 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 37 | Kanal I2.3 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 37 | Kanal I2.3 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 38 | Kanal I2.2 | Lamelle % | 1 Byte | DPT.5 | CT |
| 39 | Kanal I2 | Sperren = 1 | 1 Bit | DPT.1 | CW |
| 39 | Kanal I2 | Sperren = 0 | 1 Bit | DPT.1 | CW |
| 40 | Kanal I3 | Schalten | 1 Bit | DPT.1 | CT |
| 40 | Kanal I3 | Schalten | 1 Bit | DPT.1 | CWT |
| 40 | Kanal I3 | Step / Stop | 1 Bit | DPT.1 | CT |
| 40 | Kanal I3.1 | Schalten | 1 Bit | DPT.1 | CWT |
| 40 | Kanal I3.1 | Priorität | 2 Bit | DPT.2 | CT |
| 40 | Kanal I3.1 | Wert senden | 1 Byte | DPT.5 | CT |
| 40 | Kanal I3.1 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 40 | Kanal I3.1 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 40 | Kanal I3.1 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 40 | Kanal I3 | Istwert Temperatur | 2 Bytes | DPT.9 | CRT |
| 41 | Kanal I3 | Heller / Dunkler | 4 Bit | DPT.3 | CT |
| 41 | Kanal I3 | Auf / Ab | 1 Bit | DPT.1 | CWT |
| 41 | Kanal I3 | Auf | 1 Bit | DPT.1 | CT |
| 41 | Kanal I3 | Ab | 1 Bit | DPT.1 | CT |
| 41 | Kanal I3.2 | Schalten | 1 Bit | DPT.1 | CWT |
| 41 | Kanal I3.2 | Priorität | 2 Bit | DPT.2 | CT |
| 41 | Kanal I3.2 | Wert senden | 1 Byte | DPT.5 | CT |
| 41 | Kanal I3.2 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 41 | Kanal I3.2 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 41 | Kanal I3.2 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 42 | Kanal I3.1 | Schalten | 1 Bit | DPT.1 | CWT |
| 42 | Kanal I3.1 | Priorität | 2 Bit | DPT.2 | CT |
| 42 | Kanal I3.1 | Wert senden | 1 Byte | DPT.5 | CT |
| 42 | Kanal I3.1 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 42 | Kanal I3.1 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 42 | Kanal I3.1 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 42 | Kanal I3.1 | Höhe % | 1 Byte | DPT.5 | CT |
| 42 | Kanal I3.3 | Schalten | 1 Bit | DPT.1 | CWT |
| 42 | Kanal I3.3 | Priorität | 2 Bit | DPT.2 | CT |
| 42 | Kanal I3.3 | Wert senden | 1 Byte | DPT.5 | CT |
| 42 | Kanal I3.3 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 42 | Kanal I3.3 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 42 | Kanal I3.3 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 43 | Kanal I3.2 | Lamelle % | 1 Byte | DPT.5 | CT |
| 44 | Kanal I3 | Sperren = 1 | 1 Bit | DPT.1 | CW |
| 44 | Kanal I3 | Sperren = 0 | 1 Bit | DPT.1 | CW |
| 45 | Kanal I4 | Schalten | 1 Bit | DPT.1 | CT |
| 45 | Kanal I4 | Schalten | 1 Bit | DPT.1 | CWT |
| 45 | Kanal I4 | Step / Stop | 1 Bit | DPT.1 | CT |
| 45 | Kanal I4.1 | Schalten | 1 Bit | DPT.1 | CWT |
| 45 | Kanal I4.1 | Priorität | 2 Bit | DPT.2 | CT |
| 45 | Kanal I4.1 | Wert senden | 1 Byte | DPT.5 | CT |
| 45 | Kanal I4.1 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 45 | Kanal I4.1 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 45 | Kanal I4.1 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 45 | Kanal I4 | Istwert Temperatur | 2 Bytes | DPT.9 | CRT |
| 46 | Kanal I4 | Heller / Dunkler | 4 Bit | DPT.3 | CT |
| 46 | Kanal I4 | Auf / Ab | 1 Bit | DPT.1 | CWT |
| 46 | Kanal I4 | Auf | 1 Bit | DPT.1 | CT |
| 46 | Kanal I4 | Ab | 1 Bit | DPT.1 | CT |
| 46 | Kanal I4.2 | Schalten | 1 Bit | DPT.1 | CWT |
| 46 | Kanal I4.2 | Priorität | 2 Bit | DPT.2 | CT |
| 46 | Kanal I4.2 | Wert senden | 1 Byte | DPT.5 | CT |
| 46 | Kanal I4.2 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 46 | Kanal I4.2 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 46 | Kanal I4.2 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 47 | Kanal I4.1 | Schalten | 1 Bit | DPT.1 | CWT |
| 47 | Kanal I4.1 | Priorität | 2 Bit | DPT.2 | CT |
| 47 | Kanal I4.1 | Wert senden | 1 Byte | DPT.5 | CT |
| 47 | Kanal I4.1 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 47 | Kanal I4.1 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 47 | Kanal I4.1 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 47 | Kanal I4.1 | Höhe % | 1 Byte | DPT.5 | CT |
| 47 | Kanal I4.3 | Schalten | 1 Bit | DPT.1 | CWT |
| 47 | Kanal I4.3 | Priorität | 2 Bit | DPT.2 | CT |
| 47 | Kanal I4.3 | Wert senden | 1 Byte | DPT.5 | CT |
| 47 | Kanal I4.3 | Prozentwert senden | 1 Byte | DPT.5 | CT |
| 47 | Kanal I4.3 | 2 Byte DPT 9.x | 2 Bytes | DPT.9 | CT |
| 47 | Kanal I4.3 | 4 Byte DPT 14.x | 4 Bytes | DPT.14 | CT |
| 48 | Kanal I4.2 | Lamelle % | 1 Byte | DPT.5 | CT |
| 49 | Kanal I4 | Sperren = 1 | 1 Bit | DPT.1 | CW |
| 49 | Kanal I4 | Sperren = 0 | 1 Bit | DPT.1 | CW |
| 50 | Firmware | Version | 2 Bytes | DPT.217 | CRT |
| 51 | Alarm | Info | 6 Bytes | DPT.219 | CRT |
| 53 | Alarm | Fehlertext | 14 Bytes | DPT.16 | CRT |
Parameters (147)
| Parameter | Type | Default |
|---|---|---|
| PID_HARDWARE_TYPE_PARAMETER | list | |
| PAR_ALG_DOWNLOAD_KENNNUNG | unsignedInt 0…255 | 255 |
| Helligkeit der LEDs reduzieren | list | nie |
| Wert für reduzierte Helligkeit | unsignedInt 0…100 | 30 |
| Objekttyp | list | über Schaltobjekt |
| Luxwert für Dunkelheit (wenn Wert erreicht) | unsignedInt 0…255 | 1 |
| Hysterese für Luxwert | unsignedInt 0…255 | 2 |
| Funktion der externen Eingänge I3+I4 | list | Binäreingang.. |
| Temperatur senden bei Änderung von (Interner Fühler) | list | 0,5 K |
| Temperatur zyklisch senden | list | nicht zyklisch senden |
| Temperaturabgleich | signedInt -64…64 | 0 |
| PAR_RTR_NURSOLGEB | list | Raumtemperaturregler |
| Regelung | list | Nur Heizungsregelung |
| Funktion des Stellrades | list | Gesperrt |
| Manuelle Verschiebung wirkt | list | bei Komfort-, Standby- und Nachtbetrieb |
| Manuelle Verschiebung am Ende des Nachtbetriebs | list | Nicht ändern |
| Fußbodentemperaturbegrenzung verwenden (Fühler an I4) | list | Nein |
| Sollwertkorrektur bei hohen Außentemperaturen | list | Keine |
| Quelle für Istwert | list | Interner Fühler |
| Istwert für Regelung senden bei Änderung von | list | 0,5 K |
| Istwert für Regelung zyklisch senden | list | Nein |
| Istwert überwachen | list | Nein |
| Überwachungszeit für ext. Istwert | list | 10 min |
| Notprogramm bei Istwertausfall | list | bei PI-Regler: 10%, bei 2-Punktregler: Ein |
| Telegramm Istwertfehler | list | nur im Fehlerfall zyklisch senden |
| Zyklisch senden | list | alle 30 min |
| Betriebsart nach Reset | list | Standby |
| Objekte zur Festlegung der Betriebsart | list | Neu: Betriebsart, Präsenz, Fensterstatus |
| Art des Präsenzsensors (Obj. Präsenz) | list | Präsenztaster |
| Bei Temperaturerhöhung am Stellrad | list | Präsenzobjekt nicht setzen |
| Funktion der Tasten | list | Gesperrt |
| Zeit für Komfortverlängerung | list | 2 h |
| Zyklisch Senden der aktuellen Betriebsart | list | nicht zyklisch senden |
| Art der Regelung | list | stetig |
| Zahl der Heizstufen | list | Nur eine Heizstufe |
| Hysterese des 2-Punkt Reglers | list | 1 K |
| Rückführung der Hysterese nach Schaltpunkt | list | Keine |
| Einstellung der Regelparameter | list | Über Anlagentyp |
| Anlagentyp | list | Radiatorenheizung |
| Proportionalband des Heizungsreglers | list | 2,5 K |
| Integrierzeit des Heizungsreglers | list | 90 min. |
| Proportionalband des Heizungsreglers | list | 4 K |
| Integrierzeit des Heizungsreglers | list | 30 h |
| Senden der Stellgröße Heizen | list | Bei Änderung um 5 % |
| Zyklisch senden der Stellgröße Heizen | list | nicht zyklisch senden |
| Basissollwert nach Laden der Applikation | list | 21 °C |
| Minimal gültiger Basissollwert | list | 10 °C |
| Maximal gültiger Basissollwert | list | 32 °C |
| Maximal gültige Sollwertverschiebung | list | +/- 3 K |
| Absenkung im Standbybetrieb (bei Heizen) | list | 2 K |
| Absenkung im Nachtbetrieb (bei Heizen) | list | 5 K |
| Sollwert für Frostschutzbetrieb (bei Heizen) | list | 6 °C |
| Aktueller Sollwert im Komfortbetrieb | list | Tatsächlicher Wert (Heizen - Kühlen) |
| Maximale Fußbodentemperatur | list | 30 °C |
| Zyklisch senden des aktuellen Sollwertes | list | nicht zyklisch senden |
| Art der Stellgröße | list | Prozent |
| Differenz zw. Hauptstufe und Zusatzstufe | list | 2 K |
| Proportionalband | list | 4 K |
| PWM-Periode | unsignedInt 3…30 | 5 |
| Senden der Stellgröße | list | Bei Änderung um 5 % |
| Zyklisch senden | list | nicht zyklisch senden |
| Zahl der Kühlstufen | list | Nur eine Kühlstufe |
| Anlagentyp | list | Kühldecke |
| Proportionalband des Kühlenreglers | list | 5 K |
| Integrierzeit des Kühlenreglers | list | 4 h |
| Proportionalband des Kühlenreglers | list | 4 K |
| Integrierzeit des Kühlenreglers | list | 180 min. |
| Umschalten zwischen Heizen und Kühlen | list | Automatisch |
| Format Objekt Heizen/Kühlen | list | DPT1.100 (Heizen=1 / Kühlen=0) |
| Ausgabe der Stellgröße Kühlen | list | Auf separatem Obj. (4-Rohr-Systeme) |
| Senden der Stellgröße Kühlen | list | Bei Änderung um 5 % |
| Zyklisch senden der Stellgröße Kühlen | list | nicht zyklisch senden |
| Totzone zw. Heizen und Kühlen | list | 2 K |
| Totzone zw. Heizen und Kühlen (+ Hysterese Heizen + Hysterese Kühlen) | list | 2 K |
| Totzone zw. Heizen und Kühlen (+ Hysterese Kühlen) | list | 2 K |
| Totzone zw. Heizen und Kühlen (+ Hysterese Heizen) | list | 2 K |
| Anhebung im Standbybetrieb (bei Kühlen) | list | 2 K |
| Anhebung im Nachtbetrieb (bei Kühlen) | list | 5 K |
| Sollwert für Hitzeschutzbetrieb (bei Kühlen) | list | 42 °C d.h. quasi kein Hitzeschutz |
| Sollwertkorrektur ab | list | 25 °C |
| Anpassung | list | 1 K pro 3 K Außentemperatur |
| Format der Sollwertanpassung | list | relativ |
| Startsollwert | list | 21 °C |
| Maximale Anpassung | list | +5 K |
| Maximale Anpassung | list | bis Hitzeschutztemperatur erreicht |
| Sollwertanpassung senden | list | nicht zyklisch senden |
| Kanal aktivieren | list | Aus |
| Funktion des Kanals | list | Schalter |
| Entprellzeit | list | 50 ms |
| Angeschlossener Taster | list | Schließer |
| Langer Tastendruck ab | list | 300 ms |
| Zeit für Doppelklick | list | 300 ms |
| Zusatzfunktion Doppelklick | list | Nein |
| Anzahl der Telegramme | list | Ein Telegramm |
| Sperrfunktion aktivieren | list | Nein |
| Sperrtelegramm | list | Sperren mit 1 (Standard) |
| Reaktion auf lang / kurz | list | Eintastenbedienung |
| Schrittweite für Dimmen | list | 100 % |
| Reaktion bei Bus- oder Netzwiederkehr | list | keine |
| Reaktion beim Setzen der Sperre | list | Sperre ignorieren |
| Reaktion beim Aufheben der Sperre | list | Keine Reaktion |
| Objekttyp | list | Schalten (1 Bit) |
| Telegramm | list | Ein |
| Telegramm | list | Priorität Ein |
| Telegramm | unsignedInt 0…255 | 0 |
| Telegramm | unsignedInt 0…100 | 0 |
| Telegramm | float -670760…670760 | 0 |
| Telegramm | float -1e+38…1e+38 | 0 |
| Reaktion bei Buswiederkehr | list | keine |
| Reaktion beim Aufheben der Sperre | list | keine Reaktion |
| Bedienung | list | Einflächenbedienung |
| Stoppen der Fahrbewegung durch | list | Kurze Bedienung |
| Höhe | unsignedInt 0…100 | 0 |
| Lamelle | unsignedInt 0…100 | 0 |
| Senden wenn Eingang = 1 | list | Ja |
| Senden wenn Eingang = 0 | list | Ja |
| Zyklisch senden | list | Nein |
| Reaktion bei Buswiederkehr | list | Keine |
| Senden nach kurzer Bedienung | list | Telegramm senden |
| Senden nach langer Bedienung | list | Telegramm senden |
| Senden nach Doppelklick | list | Telegramm senden |
| PAR_BM_I2_FUNKTION_TEMP | list | Temperatureingang |
| Sensortyp | list | Fernfühler 1 (9070191) |
| Temperatur senden bei Änderung von | list | 0,5 K |
| PAR_BM_I3_FUNKTION_TEMP | list | Temperatureingang |
| PAR_ALARM_0_TEXT | text | CO2 Fault |
| PAR_ALARM_0_CODE | unsignedInt 0…4294967295 | 1 |
| PAR_ALARM_1_TEXT | text | Humidity Fault |
| PAR_ALARM_1_CODE | unsignedInt 0…4294967295 | 2 |
| PAR_ALARM_2_TEXT | text | Temp Fault |
| PAR_ALARM_2_CODE | unsignedInt 0…4294967295 | 3 |
| PAR_ALARM_3_TEXT | text | Wheel Fault |
| PAR_ALARM_3_CODE | unsignedInt 0…4294967295 | 4 |
| PAR_ALARM_ALS_TEXT | text | ALS Fault |
| PAR_ALARM_ALS_CODE | unsignedInt 0…4294967295 | 5 |
| PAR_ALARM_THRESHOLDS_CO2_TEXT | text | Thresholds CO2 |
| PAR_ALARM_THRESHOLDS_CO2_CODE | unsignedInt 0…4294967295 | 101 |
| PAR_ALARM_THRESHOLDS_HUM_TEXT | text | Thresholds Hum |
| PAR_ALARM_THRESHOLDS_HUM_CODE | unsignedInt 0…4294967295 | 102 |
| PAR_ALARM_EXTIN3_TEXT | text | I3 Temp Fault |
| PAR_ALARM_EXTIN3_CODE | unsignedInt 0…4294967295 | 6 |
| PAR_ALARM_EXTIN4_TEXT | text | I4 Temp Fault |
| PAR_ALARM_EXTIN4_CODE | unsignedInt 0…4294967295 | 7 |
| PAR_INFO_0_TEXT | text | CO2 CAL OK |
| PAR_INFO_1_TEXT | text | CO2 CAL ERROR |
| PAR_INFO_2_TEXT | text | CO2 CAL RESET |
| Hysterese Fußbodentemperatur * | list | 3 K |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| RAMSES 718 S 2.3 latest | $7180 | 0908 | 2026-11-25 | 251 KB | Download |
About this file
This is the official ETS product database for the Theben AG RAMSES 718 S (7189200), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Theben AG
- FCA 1 4920200
- FCA 2 4920210
- RAM 712 7129200
- RAM 713 S 7139201
- RAM 713 Fan Coil 7139202
- AMUN 716 S 7169230
- RAMSES 718 P 7189210
- RAM 770 7709200
- VARIA 824 / 826 8249200 / 8269200
- Set basic KNX Multi 9070900
- Theben dummy device secure -
- TheLuxa P300 1019610