| LEDs for CO2 and humidity | list | always on |
| Send CO2 concentration on change of | list | 200 ppm |
| Send CO2 concentration cyclically | list | don´t send cyclically |
| Send humidity value on change of | list | 2 % |
| Send humidity value cyclically | list | don´t send cyclically |
| Send temperature on change of | list | 0.5 °C |
| Send temperature cyclically | list | don´t send cyclically |
| Temperature offset in 0.1°C
(-64..64) | signedInt -64…64 | 0 |
| Threshold CO2 | list | Threshold 1 < Threshold 2 < Threshold 3 |
| ! Conditions for thresholds | list | Threshold 1 < Threshold 2 < Threshold 3 |
| Threshold 1 CO2 (in 10 ppm) | unsignedInt 50…255 | 50 |
| Hysteresis | list | 200 ppm |
| Threshold 2 CO2 (in 10 ppm) | unsignedInt 50…255 | 120 |
| Threshold 3 CO2 (in 10 ppm) | unsignedInt 50…255 | 200 |
| Telegram type for threshold 1 CO2 | list | switching |
| If threshold 1 CO2 is exceeded | list | send following telegram once |
| Telegram | list | ON (down) |
| Telegram | unsignedInt 0…255 | 85 |
| Telegram | list | switch on |
| Telegram | list | 35 % |
| If threshold 1 CO2 is underrun | list | send following telegram once |
| Telegram | list | OFF (up) |
| Telegram | unsignedInt 0…255 | 0 |
| Telegram | list | switch off |
| Telegram | list | 0 % |
| Cycle time for threshold 1 CO2
(if used) | list | every 60 min. |
| Behaviour when setting the lock | list | ignore lock |
| Behaviour when releasing the lock | list | update |
| Telegram type for threshold 2 CO2 | list | switching |
| If threshold 2 CO2 is exceeded | list | send following telegram once |
| Telegram | unsignedInt 0…255 | 170 |
| Telegram | list | 70 % |
| If threshold 2 CO2 is underrun | list | send following telegram once |
| Cycle time for threshold 2 CO2
(if used) | list | every 60 min. |
| Telegram type for threshold 3 CO2 | list | switching |
| If threshold 3 CO2 is exceeded | list | send following telegram once |
| Telegram | unsignedInt 0…255 | 255 |
| Telegram | list | 100 % |
| If threshold 3 CO2 is underrun | list | send following telegram once |
| Cycle time for threshold 3 CO2
(if used) | list | every 60 min. |
| Send given Value | list | (Input in percent) |
| if CO2 below threshold 1 | list | 0 % |
| if CO2 below threshold 1 | unsignedInt 0…255 | 0 |
| if CO2 between thresholds 1 and 2 | list | 35 % |
| if CO2 between thresholds 1 and 2 | unsignedInt 0…255 | 85 |
| if CO2 between thresholds 2 and 3 | list | 70 % |
| if CO2 between thresholds 2 and 3 | unsignedInt 0…255 | 170 |
| if CO2 above threshold 3 | list | 100 % |
| if CO2 above threshold 3 | unsignedInt 0…255 | 255 |
| Value if locked (0-255) | unsignedInt 0…255 | 0 |
| Value if locked | list | 0 % |
| CO2 below threshold 1 | list | Scene 1 |
| CO2 between threshold 1 and 2 | list | Scene 2 |
| CO2 between threshold 2 and 3 | list | Scene 3 |
| CO2 above threshold 3 | list | Scene 4 |
| Scene if locked | list | Scene 1 |
| Threshold 1 relative humidity (in %) | unsignedInt 0…100 | 45 |
| Hysteresis | list | 1 % |
| Threshold 2 relative humidity (in %) | unsignedInt 0…100 | 55 |
| Threshold 3 relative humidity (in %) | unsignedInt 0…100 | 70 |
| Telegram type for threshold 1 humidity | list | switching |
| If threshold 1 humidity is exceeded | list | send following telegram once |
| If threshold 1 humidity is underrun | list | send following telegram once |
| Cycle time for threshold 1 humidity
(if used) | list | every 60 min. |
| Telegram type for threshold 2 humidity | list | switching |
| If threshold 2 humidity is exceeded | list | send following telegram once |
| If threshold 2 humidity is underrun | list | send following telegram once |
| Cycle time for threshold 2 humidity
(if used) | list | every 60 min. |
| If threshold 3 humidity is exceeded | list | send following telegram once |
| If threshold 3 humidity is underrun | list | send following telegram once |
| Cycle time for threshold 3 humidity
(if used) | list | every 60 min. |
| if relative humidity below
threshold 1 | list | 0 % |
| if relative humidity below
threshold 1 | unsignedInt 0…255 | 0 |
| if relative humidity between
threshold 1 and 2 | list | 35 % |
| if relative humidity between
threshold 1 and 2 | unsignedInt 0…255 | 85 |
| if relative humidity between
threshold 2 and 3 | list | 70 % |
| if relative humidity between
threshold 2 and 3 | unsignedInt 0…255 | 170 |
| if rel. humidity above threshold 3 | list | 100 % |
| if rel. humidity above threshold 3 | unsignedInt 0…255 | 255 |
| rel. humidity below threshold 1 | list | Scene 1 |
| rel. humidity between threshold 1 and 2 | list | Scene 2 |
| rel. humidity between threshold 2 and 3 | list | Scene 3 |
| rel. humidity above threshold 3 | list | Scene 4 |
| Temperature threshold | list | 15 °C |
| Hysteresis | list | 1.5 °C |
| Telegram type for temperature-threshold | list | switching |
| If temperature-threshold is exceeded | list | send following telegram once |
| If temperature-threshold is underrun | list | send following telegram once |
| Cycle time for temperature threshold
(if used) | list | every 60 min. |