JM 8 T 24V 4940265
Theben AG · Order number 4940265 · Ausgabe › JM 8 T 24V
8x FIX2 blind actuator
Download .knxprod FIX2 JM 8 T 1.3 · 233 KB
Product
| Manufacturer | Theben AG |
|---|---|
| Product name | JM 8 T 24V |
| Order number | 4940265 |
| Product text | JM 8 T 24V (8x FIX2 blind actuator) |
| Hardware | FIX2 Series JM 8 T |
| Medium | Twisted Pair |
| Bus current (mA) | 4 |
| Rail mounted | Yes |
| Width (mm) | 144 |
| Registration | Certified · 2014-09-17 |
| Languages | de-DE, en-US, es-ES, fr-FR, it-IT, nl-NL |
| Catalog entry | M-0048_H-4940255-1_HP-4945-13-A09D_CI-4940265-1 |
| Fingerprint | A09D |
| SHA-256 | 7dfb47d3ae0f260f20c2a11dabe9c4836f9ebe5c65bd5224a9a34fb1dd6852dd |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: FIX2 JM 8 T 1.3
| Application number | $4945 |
|---|---|
| Version | 1.3 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 1438 |
| Group objects | 206 |
Group objects (206)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Channel C1 | UP/DOWN | 1 Bit | CRWU | |
| 1 | Channel C1 | Step/stop | 1 Bit | CRWU | |
| 2 | Channel C1 | % Height | 1 Byte | CRWU | |
| 3 | Channel C1 | % Lamella | 1 Byte | CRWU | |
| 4 | Channel C1 | Lock comfort/automatic | 1 Bit | CRWU | |
| 5 | Channel C1 | 1 = Lock | 1 Bit | CRWU | |
| 5 | Channel C1 | 1 = Release | 1 Bit | CRWU | |
| 6 | Channel C1 | Call up/save scenes | 1 Byte | CRWU | |
| 7 | Channel C1 | Enable scenes = 1 | 1 Bit | CRW | |
| 7 | Channel C1 | Lock scenes = 1 | 1 Bit | CRW | |
| 8 | Channel C1 | Priority on safety | 2 Bit | CRWU | |
| 9 | Channel C1 | Presence | 1 Bit | CRW | |
| 9 | Channel C1 | Position A | 1 Bit | CRWU | |
| 10 | Channel C1 | Heating support | 1 Bit | CRWU | |
| 10 | Channel C1 | Position B | 1 Bit | CRWU | |
| 11 | Channel C1 | Cooling support | 1 Bit | CRWU | |
| 11 | Channel C1 | Position C | 1 Bit | CRWU | |
| 12 | Channel C1 | Room temperature | 2 Bytes | CRWU | |
| 13 | Channel C1 | Height feedback 1 bit | 1 Bit | CRTU | |
| 13 | Channel C1 | Height feedback % | 1 Byte | CRTU | |
| 14 | Channel C1 | Lamella feedback % | 1 Byte | CRTU | |
| 15 | Reserve object 15 | Reserve | 2 Bytes | CRWU | |
| 16 | Channel C1 | Start-up mode | 1 Bit | CRWU | |
| 17 | Channel C1 | Receive runtime | 2 Bytes | CRW | |
| 17 | Channel C1 | Send runtime | 2 Bytes | CRT | |
| 20 | Channel C2 | UP/DOWN | 1 Bit | CRWU | |
| 21 | Channel C2 | Step/stop | 1 Bit | CRWU | |
| 22 | Channel C2 | % Height | 1 Byte | CRWU | |
| 23 | Channel C2 | % Lamella | 1 Byte | CRWU | |
| 24 | Channel C2 | Lock comfort/automatic | 1 Bit | CRWU | |
| 25 | Channel C2 | 1 = Lock | 1 Bit | CRWU | |
| 25 | Channel C2 | 1 = Release | 1 Bit | CRWU | |
| 26 | Channel C2 | Call up/save scenes | 1 Byte | CRWU | |
| 27 | Channel C2 | Enable scenes = 1 | 1 Bit | CRW | |
| 27 | Channel C2 | Lock scenes = 1 | 1 Bit | CRW | |
| 28 | Channel C2 | Priority on safety | 2 Bit | CRWU | |
| 29 | Channel C2 | Presence | 1 Bit | CRW | |
| 29 | Channel C2 | Position A | 1 Bit | CRWU | |
| 30 | Channel C2 | Heating support | 1 Bit | CRWU | |
| 30 | Channel C2 | Position B | 1 Bit | CRWU | |
| 31 | Channel C2 | Cooling support | 1 Bit | CRWU | |
| 31 | Channel C2 | Position C | 1 Bit | CRWU | |
| 32 | Channel C2 | Room temperature | 2 Bytes | CRWU | |
| 33 | Channel C2 | Height feedback 1 bit | 1 Bit | CRTU | |
| 33 | Channel C2 | Height feedback % | 1 Byte | CRTU | |
| 34 | Channel C2 | Lamella feedback % | 1 Byte | CRTU | |
| 36 | Channel C2 | Start-up mode | 1 Bit | CRWU | |
| 37 | Channel C2 | Receive runtime | 2 Bytes | CRW | |
| 37 | Channel C2 | Send runtime | 2 Bytes | CRT | |
| 40 | Channel C3 | UP/DOWN | 1 Bit | CRWU | |
| 41 | Channel C3 | Step/stop | 1 Bit | CRWU | |
| 42 | Channel C3 | % Height | 1 Byte | CRWU | |
| 43 | Channel C3 | % Lamella | 1 Byte | CRWU | |
| 44 | Channel C3 | Lock comfort/automatic | 1 Bit | CRWU | |
| 45 | Channel C3 | 1 = Lock | 1 Bit | CRWU | |
| 45 | Channel C3 | 1 = Release | 1 Bit | CRWU | |
| 46 | Channel C3 | Call up/save scenes | 1 Byte | CRWU | |
| 47 | Channel C3 | Lock scenes = 1 | 1 Bit | CRW | |
| 47 | Channel C3 | Enable scenes = 1 | 1 Bit | CRW | |
| 48 | Channel C3 | Priority on safety | 2 Bit | CRWU | |
| 49 | Channel C3 | Presence | 1 Bit | CRW | |
| 49 | Channel C3 | Position A | 1 Bit | CRWU | |
| 50 | Channel C3 | Heating support | 1 Bit | CRWU | |
| 50 | Channel C3 | Position B | 1 Bit | CRWU | |
| 51 | Channel C3 | Cooling support | 1 Bit | CRWU | |
| 51 | Channel C3 | Position C | 1 Bit | CRWU | |
| 52 | Channel C3 | Room temperature | 2 Bytes | CRWU | |
| 53 | Channel C3 | Height feedback 1 bit | 1 Bit | CRTU | |
| 53 | Channel C3 | Height feedback % | 1 Byte | CRTU | |
| 54 | Channel C3 | Lamella feedback % | 1 Byte | CRTU | |
| 56 | Channel C3 | Start-up mode | 1 Bit | CRWU | |
| 57 | Channel C3 | Receive runtime | 2 Bytes | CRW | |
| 57 | Channel C3 | Send runtime | 2 Bytes | CRT | |
| 60 | Channel C4 | UP/DOWN | 1 Bit | CRWU | |
| 61 | Channel C4 | Step/stop | 1 Bit | CRWU | |
| 62 | Channel C4 | % Height | 1 Byte | CRWU | |
| 63 | Channel C4 | % Lamella | 1 Byte | CRWU | |
| 64 | Channel C4 | Lock comfort/automatic | 1 Bit | CRWU | |
| 65 | Channel C4 | 1 = Lock | 1 Bit | CRWU | |
| 65 | Channel C4 | 1 = Release | 1 Bit | CRWU | |
| 66 | Channel C4 | Call up/save scenes | 1 Byte | CRWU | |
| 67 | Channel C4 | Enable scenes = 1 | 1 Bit | CRW | |
| 67 | Channel C4 | Lock scenes = 1 | 1 Bit | CRW | |
| 68 | Channel C4 | Priority on safety | 2 Bit | CRWU | |
| 69 | Channel C4 | Presence | 1 Bit | CRW | |
| 69 | Channel C4 | Position A | 1 Bit | CRWU | |
| 70 | Channel C4 | Heating support | 1 Bit | CRWU | |
| 70 | Channel C4 | Position B | 1 Bit | CRWU | |
| 71 | Channel C4 | Cooling support | 1 Bit | CRWU | |
| 71 | Channel C4 | Position C | 1 Bit | CRWU | |
| 72 | Channel C4 | Room temperature | 2 Bytes | CRWU | |
| 73 | Channel C4 | Height feedback 1 bit | 1 Bit | CRTU | |
| 73 | Channel C4 | Height feedback % | 1 Byte | CRTU | |
| 74 | Channel C4 | Lamella feedback % | 1 Byte | CRTU | |
| 76 | Channel C4 | Start-up mode | 1 Bit | CRWU | |
| 77 | Channel C4 | Receive runtime | 2 Bytes | CRW | |
| 77 | Channel C4 | Send runtime | 2 Bytes | CRT | |
| 78 | C1 - C4 | Manual | 1 Bit | CRWTU | |
| 80 | Channel C5 | UP/DOWN | 1 Bit | CRWU | |
| 81 | Channel C5 | Step/stop | 1 Bit | CRWU | |
| 82 | Channel C5 | % Height | 1 Byte | CRWU | |
| 83 | Channel C5 | % Lamella | 1 Byte | CRWU | |
| 84 | Channel C5 | Lock comfort/automatic | 1 Bit | CRWU | |
| 85 | Channel C5 | 1 = Lock | 1 Bit | CRWU | |
| 85 | Channel C5 | 1 = Release | 1 Bit | CRWU | |
| 86 | Channel C5 | Call up/save scenes | 1 Byte | CRWU | |
| 87 | Channel C5 | Lock scenes = 1 | 1 Bit | CRW | |
| 87 | Channel C5 | Enable scenes = 1 | 1 Bit | CRW | |
| 88 | Channel C5 | Priority on safety | 2 Bit | CRWU | |
| 89 | Channel C5 | Presence | 1 Bit | CRW | |
| 89 | Channel C5 | Position A | 1 Bit | CRWU | |
| 90 | Channel C5 | Heating support | 1 Bit | CRWU | |
| 90 | Channel C5 | Position B | 1 Bit | CRWU | |
| 91 | Channel C5 | Cooling support | 1 Bit | CRWU | |
| 91 | Channel C5 | Position C | 1 Bit | CRWU | |
| 92 | Channel C5 | Room temperature | 2 Bytes | CRWU | |
| 93 | Channel C5 | Height feedback 1 bit | 1 Bit | CRTU | |
| 93 | Channel C5 | Height feedback % | 1 Byte | CRTU | |
| 94 | Channel C5 | Lamella feedback % | 1 Byte | CRTU | |
| 95 | Reserve object 15 | Reserve | 2 Bytes | CRWU | |
| 96 | Channel C5 | Start-up mode | 1 Bit | CRWU | |
| 97 | Channel C5 | Receive runtime | 2 Bytes | CRW | |
| 97 | Channel C5 | Send runtime | 2 Bytes | CRT | |
| 100 | Channel C6 | UP/DOWN | 1 Bit | CRWU | |
| 101 | Channel C6 | Step/stop | 1 Bit | CRWU | |
| 102 | Channel C6 | % Height | 1 Byte | CRWU | |
| 103 | Channel C6 | % Lamella | 1 Byte | CRWU | |
| 104 | Channel C6 | Lock comfort/automatic | 1 Bit | CRWU | |
| 105 | Channel C6 | 1 = Lock | 1 Bit | CRWU | |
| 105 | Channel C6 | 1 = Release | 1 Bit | CRWU | |
| 106 | Channel C6 | Call up/save scenes | 1 Byte | CRWU | |
| 107 | Channel C6 | Enable scenes = 1 | 1 Bit | CRW | |
| 107 | Channel C6 | Lock scenes = 1 | 1 Bit | CRW | |
| 108 | Channel C6 | Priority on safety | 2 Bit | CRWU | |
| 109 | Channel C6 | Presence | 1 Bit | CRW | |
| 109 | Channel C6 | Position A | 1 Bit | CRWU | |
| 110 | Channel C6 | Heating support | 1 Bit | CRWU | |
| 110 | Channel C6 | Position B | 1 Bit | CRWU | |
| 111 | Channel C6 | Cooling support | 1 Bit | CRWU | |
| 111 | Channel C6 | Position C | 1 Bit | CRWU | |
| 112 | Channel C6 | Room temperature | 2 Bytes | CRWU | |
| 113 | Channel C6 | Height feedback 1 bit | 1 Bit | CRTU | |
| 113 | Channel C6 | Height feedback % | 1 Byte | CRTU | |
| 114 | Channel C6 | Lamella feedback % | 1 Byte | CRTU | |
| 116 | Channel C6 | Start-up mode | 1 Bit | CRWU | |
| 117 | Channel C6 | Receive runtime | 2 Bytes | CRW | |
| 117 | Channel C6 | Send runtime | 2 Bytes | CRT | |
| 120 | Channel C7 | UP/DOWN | 1 Bit | CRWU | |
| 121 | Channel C7 | Step/stop | 1 Bit | CRWU | |
| 122 | Channel C7 | % Height | 1 Byte | CRWU | |
| 123 | Channel C7 | % Lamella | 1 Byte | CRWU | |
| 124 | Channel C7 | Lock comfort/automatic | 1 Bit | CRWU | |
| 125 | Channel C7 | 1 = Lock | 1 Bit | CRWU | |
| 125 | Channel C7 | 1 = Release | 1 Bit | CRWU | |
| 126 | Channel C7 | Call up/save scenes | 1 Byte | CRWU | |
| 127 | Channel C7 | Lock scenes = 1 | 1 Bit | CRW | |
| 127 | Channel C7 | Enable scenes = 1 | 1 Bit | CRW | |
| 128 | Channel C7 | Priority on safety | 2 Bit | CRWU | |
| 129 | Channel C7 | Presence | 1 Bit | CRW | |
| 129 | Channel C7 | Position A | 1 Bit | CRWU | |
| 130 | Channel C7 | Heating support | 1 Bit | CRWU | |
| 130 | Channel C7 | Position B | 1 Bit | CRWU | |
| 131 | Channel C7 | Cooling support | 1 Bit | CRWU | |
| 131 | Channel C7 | Position C | 1 Bit | CRWU | |
| 132 | Channel C7 | Room temperature | 2 Bytes | CRWU | |
| 133 | Channel C7 | Height feedback 1 bit | 1 Bit | CRTU | |
| 133 | Channel C7 | Height feedback % | 1 Byte | CRTU | |
| 134 | Channel C7 | Lamella feedback % | 1 Byte | CRTU | |
| 136 | Channel C7 | Start-up mode | 1 Bit | CRWU | |
| 137 | Channel C7 | Receive runtime | 2 Bytes | CRW | |
| 137 | Channel C7 | Send runtime | 2 Bytes | CRT | |
| 140 | Channel C8 | UP/DOWN | 1 Bit | CRWU | |
| 141 | Channel C8 | Step/stop | 1 Bit | CRWU | |
| 142 | Channel C8 | % Height | 1 Byte | CRWU | |
| 143 | Channel C8 | % Lamella | 1 Byte | CRWU | |
| 144 | Channel C8 | Lock comfort/automatic | 1 Bit | CRWU | |
| 145 | Channel C8 | 1 = Lock | 1 Bit | CRWU | |
| 145 | Channel C8 | 1 = Release | 1 Bit | CRWU | |
| 146 | Channel C8 | Call up/save scenes | 1 Byte | CRWU | |
| 147 | Channel C8 | Enable scenes = 1 | 1 Bit | CRW | |
| 147 | Channel C8 | Lock scenes = 1 | 1 Bit | CRW | |
| 148 | Channel C8 | Priority on safety | 2 Bit | CRWU | |
| 149 | Channel C8 | Presence | 1 Bit | CRW | |
| 149 | Channel C8 | Position A | 1 Bit | CRWU | |
| 150 | Channel C8 | Heating support | 1 Bit | CRWU | |
| 150 | Channel C8 | Position B | 1 Bit | CRWU | |
| 151 | Channel C8 | Cooling support | 1 Bit | CRWU | |
| 151 | Channel C8 | Position C | 1 Bit | CRWU | |
| 152 | Channel C8 | Room temperature | 2 Bytes | CRWU | |
| 153 | Channel C8 | Height feedback 1 bit | 1 Bit | CRTU | |
| 153 | Channel C8 | Height feedback % | 1 Byte | CRTU | |
| 154 | Channel C8 | Lamella feedback % | 1 Byte | CRTU | |
| 156 | Channel C8 | Start-up mode | 1 Bit | CRWU | |
| 157 | Channel C8 | Receive runtime | 2 Bytes | CRW | |
| 157 | Channel C8 | Send runtime | 2 Bytes | CRT | |
| 158 | C5 - C8 | Manual | 1 Bit | CRWTU | |
| 243 | Central recall/save scenes | JM 8 T | 1 Byte | CRWTU | |
| 244 | Central Safety 1 | JM 8 T | 1 Bit | CRWU | |
| 245 | Central Safety 2 | JM 8 T | 1 Bit | CRWU | |
| 246 | Central Safety 3 | JM 8 T | 1 Bit | CRWU | |
| 247 | Central UP/DOWN | JM 8 T | 1 Bit | CRWU | |
| 248 | Central Safety Rain | JM 8 T | 1 Bit | CRWU | |
| 249 | Central Safety Frost | JM 8 T | 1 Bit | CRWU | |
| 250 | BCU version | Transmit | 14 Bytes | CRTU | |
| 251 | Version of C1 - C4 | Transmit | 14 Bytes | CRTU | |
| 252 | Version of C5 - C8 | Transmit | 14 Bytes | CRTU |
Parameters (83)
| Parameter | Type | Default |
|---|---|---|
| No. Of general parameters | unsignedInt 1…3 | 3 |
| Download 101 | list | yes |
| Type of basic module | list | JMG 4 T |
| Type | list | JM 4 T/JM 4 T 24V |
| Type of second extension module | list | JM 4 T/JM 4 T 24V |
| Time for cycl. Transm. of feedback obj. (MIX 1 series, order no.491...) | list | 15 min |
| Function of manual push button | list | valid until reset via object |
| Manual operation of channels | list | enabled |
| Relay switching delay | list | none |
| Channel function | list | shutters/blinds |
| Type of motor | list | electromechanical |
| Drive application | list | blinds.. |
| Setting the drive runtime | list | via ETS |
| Response after download | list | maintain runtime |
| Activate sun protection mode | list | no |
| Activate lock function | list | no |
| Activate scenes | list | no |
| Direction of drive run | list | normal |
| Lock Comfort/Auto on UP/DOWN/STOP command (dev. from 08.2016) | list | no, only via object Comfort/Automatic |
| Format feedback height (dev. from 08.2016) | list | % |
| Complete runtime Down (s) | unsignedInt 5…500 | 50 |
| Runtime adjustment for ascent (s) | signedInt -15…15 | 0 |
| Step duration of Step/Stop object | list | 1 s |
| Complete lamella turn (x 100 ms) | unsignedInt 4…250 | 10 |
| Tighten fabric (awnings) | list | no |
| No. of steps for a complete turn | list | 7 steps |
| On receipt of a step/stop command | list | process immediately (recommended) |
| Pause time before reversal of direction | list | 0.5 s |
| Automatic execution of lamella object value (%) after the height object (%) | list | yes |
| Assignment of the 0% position to the lamella object (%) | list | 0% corresponds to slats position on lowering |
| Participation in central UP/DOWN object | list | yes |
| Transmission of feedback | list | only at change |
| Time for cyclical transmission of feedback | list | 15 min |
| Desired room temperature during sun protection mode | list | 21 °C |
| Resp. to presence in sun protection mode (presence object = 1) | list | update (height/lamella) |
| Response to heating support | list | top end position |
| Response when heating support is no longer needed | list | no reaction, unchanged |
| Response to cooling support | list | bottom end position |
| Response when cooling support is no longer needed | list | no reaction, unchanged |
| Lock telegram | list | Lock with ON telegram |
| Response when setting the lock | list | unchanged (stopped upon command) |
| Response when cancelling the lock | list | update (height/lamella) |
| Priority of safety objects | list | 1. Wind 2. Rain, 3. Frost |
| Monitor safety objects cyclically | list | no |
| Participation in safety WIND | list | no |
| Source(s) | list | safety object 1 + 2 +3 (OR linked) |
| Start | list | top end position |
| End | list | same as before safety |
| Participation in safety RAIN | list | no |
| Participation in safety FROST | list | no |
| Response after priority on safety | list | no reaction, unchanged |
| Height | list | 0% |
| Lamella | list | 100% |
| Height | list | 40% |
| Height | list | 50% |
| Height | list | 60% |
| Height | list | 70% |
| Height | list | 80% |
| Height | list | 90% |
| Height | list | 100% |
| Lock telegram for scenes | list | Lock with ON telegram |
| All scene statuses of channel | list | overwrite when downloading |
| Participation in object Central scene | list | no |
| Response when unlocking the scene (with scene value 63) | list | no reaction |
| Channel reacts to | list | scene number 1 (value = 0) |
| Comment for this scene number | text | [Name eingeben] |
| Lock comfort/automatic during this scene | list | no |
| Permit teach-in | list | yes |
| Channel reacts to | list | scene number 2 (value = 1) |
| Channel reacts to | list | scene number 3 (value = 2) |
| Channel reacts to | list | scene number 4 (value = 3) |
| Channel reacts to | list | scene number 5 (value = 4) |
| Channel reacts to | list | scene number 6 (value = 5) |
| Channel reacts to | list | scene number 7 (value = 6) |
| Channel reacts to | list | scene number 8 (value = 7) |
| Response when receiving a 1 | list | top end position |
| Response when receiving a 0 | list | no reaction |
| Response in the event of download and bus failure | list | no reaction |
| Response when bus or mains power restored | list | no reaction |
| Copy main parameters from channel C1 | list | no |
| Position | list | 80% |
| Copy main parameters from channel C5 | list | no |
| - | list | - |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| FIX2 JM 8 T 1.3 latest | $4945 | A09D | 2026-11-25 | 233 KB | Download |
About this file
This is the official ETS product database for the Theben AG JM 8 T 24V (4940265), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Theben AG
- RMG 8 490 0 251
- JMG 4 24VDC 490 0 253
- RMG 4 S 4910204
- RMG 4 C-Last 4910206
- JMG 4 S 4910250
- RMG 8 T 4930200
- RMG 4 I 4930210
- RMG 8 S 4930220
- RMG 4 U 4930223
- JMG 4 T 4930250
- JMG 4 T 24V 4930260
- RM 8 T 4940200