Power Supply IPS640 IPS 640
TAPKO Technologies · Order number IPS 640 · System Devices › Power Supplies
Download .knxprod Device/Busline Diagnostics 1.0 · 88 KB
Product
| Manufacturer | TAPKO Technologies |
|---|---|
| Product name | Power Supply IPS640 |
| Order number | IPS 640 |
| Product text | KNX Power Supply 640 mA |
| Hardware | PS HW |
| Medium | Twisted Pair |
| Bus current (mA) | 640 |
| Rail mounted | Yes |
| Width (mm) | 35 |
| Device kind | PowerSupply, Choke |
| Registration | Certified · 2016-10-11 |
| Languages | de-DE, en-US, fr-FR |
| Catalog entry | M-0072_H-IPS.2064001-0_HP-3001-10-A7BD_CI-IPS.20640-1 |
| Fingerprint | A7BD |
| SHA-256 | d9a6ba5b43c4ffc2cd9e464c756540d13b7f73008c9d722905b4249c8bed4640 |
| First seen | 2026-11-25 |
| Markets | 60 markets |
Application program: Device/Busline Diagnostics 1.0
| Application number | $3001 |
|---|---|
| Version | 1.0 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 284 |
| Group objects | 44 |
Group objects (44)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Output voltage | Send measured value | 4 Bytes | 14.27 electric potential (V) | CRT |
| 0 | Output voltage | Send measured value | 2 Bytes | 9.20 voltage (mV) | CRT |
| 1 | Output voltage threshold | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 2 | Output current | Send measured value | 2 Bytes | 7.12 current (mA) | CRT |
| 2 | Output current | Send measured value | 2 Bytes | 9.21 current (mA) | CRT |
| 2 | Output current | Send measured value | 4 Bytes | 14.19 electric current (A) | CRT |
| 3 | Output current threshold | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 4 | Output current maximum | Send measured value | 2 Bytes | 7.12 current (mA) | CRT |
| 4 | Output current maximum | Send measured value | 2 Bytes | 9.21 current (mA) | CRT |
| 4 | Output current maximum | Send measured value | 4 Bytes | 14.19 electric current (A) | CRT |
| 5 | Temperature | Send measured value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 6 | Temperature threshold | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 7 | Temperature maximum | Send measured value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 8 | Input voltage | Send measured value | 2 Bytes | 9.21 current (mA) | CRT |
| 8 | Input voltage | Send measured value | 4 Bytes | 14.19 electric current (A) | CRT |
| 9 | Input voltage threshold | Send alarm status | 1 Bit | 1.1 switch | CRT |
| 10 | Telegram traffic | Send measured value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 11 | Telegram traffic threshold | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 12 | Overload number | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 13 | Overload duration | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 14 | Short circuit number | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 15 | Load detached duration | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 16 | KNX bus reset | Initialize | 1 Bit | 1.1 switch | CWTU |
| 17 | KNX bus reset number | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 18 | Total operating time | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 19 | Operating time since startup | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 20 | Startup number | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 21 | Duration 1 | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 22 | Counter 1 | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 23 | Threshold 1 | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 24 | Duration 2 | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 25 | Counter 2 | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 26 | Threshold 2 | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 27 | Duration 3 | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 28 | Counter 3 | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 29 | Threshold 3 | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 30 | Duration 4 | Send counter value | 4 Bytes | 13.100 time lag (s) | CRT |
| 31 | Counter 4 | Send counter value | 2 Bytes | 7.1 pulses | CRT |
| 32 | Threshold 4 | Send alarm status | 1 Bit | 1.5 alarm | CRT |
| 33 | Counter reset | Reset all | 1 Bit | 1.1 switch | CWT |
| 34 | Measured values | Send all | 1 Bit | 1.1 switch | CWT |
| 35 | Counter values | Send all | 1 Bit | 1.1 switch | CWT |
| 36 | Power supply is on | Send info value 1 | 1 Bit | 1.1 switch | CRT |
| 37 | Heartbeat | Send info value 1 | 1 Bit | 1.17 trigger | CRT |
Parameters (94)
| Parameter | Type | Default |
|---|---|---|
| ### | unsignedInt 0…255 | 0 |
| 8/24/2016 | text | 8/24/2016 |
| Heartbeat period [s] | unsignedInt 10…32000 | 60 |
| Induce a KNX bus reset | list | with 1 |
| Time traffic Led | unsignedInt 0…64000 | 10 |
| Delay time for "Power Supply is on" (obj. 36) | list | 1 min |
| Output voltage [V] | list | disable |
| Object type | list | 4-byte (DPT14) |
| Sending difference | list | 2 V |
| Cyclic sending | list | disabled |
| Threshold type | list | Threshold exceeded |
| Upper Value | unsignedInt 28…400 | 32 |
| Lower Value | unsignedInt 24…400 | 28 |
| Threshold alarm | list | disable |
| Behaviour on alarm activation | list | send value 1 |
| Behaviour on alarm deactivation | list | send value 0 |
| Output current [mA] | list | disable |
| Sending difference | list | disabled |
| Threshold | unsignedInt 0…800 | 640 |
| Hysteresis | unsignedInt 0…640 | 1 |
| Device temperature [°C] | list | disable |
| Object type | list | DPT9 |
| Sending difference | list | 2 °C |
| Threshold | unsignedInt 0…110 | 70 |
| Hysteresis | unsignedInt 0…40 | 1 |
| Tracking period [s] | unsignedInt 10…32000 | 1800 |
| Output current maximum [mA] | list | disable |
| Automatic sending | list | do not send |
| Threshold | unsignedInt 0…800 | 0 |
| Hysteresis | unsignedInt 0…640 | 0 |
| Device temperature maximum [°C] | list | disable |
| Threshold | unsignedInt 0…110 | 0 |
| Hysteresis | unsignedInt 0…40 | 0 |
| Input voltage | list | enable |
| Object type | list | 0 |
| Alarm settings | list | disable |
| Upper Value | unsignedInt 0…255 | 0 |
| Lower Value | unsignedInt 0…240 | 0 |
| Telegram traffic [%] | list | disable |
| Object type | list | DPT5 |
| Sending difference | unsignedInt 0…100 | 10 |
| Threshold | unsignedInt 0…100 | 80 |
| Hysteresis | unsignedInt 0…70 | 10 |
| Number of overloads | list | disable |
| Object type | list | DPT7 |
| Sending difference | unsignedInt 0…1000 | 0 |
| Threshold | unsignedInt 0…500 | 0 |
| Hysteresis | unsignedInt 0…500 | 0 |
| Duration of overloads [s] | list | disable |
| Object type | list | DPT13 |
| Sending difference | unsignedInt 0…32000 | 0 |
| Threshold | unsignedInt 0…26000000 | 0 |
| Hysteresis | unsignedInt 0…26000000 | 0 |
| Number of short circuits | list | disable |
| Sending difference | unsignedInt 0…500 | 0 |
| Duration of load detached [s] | list | disable |
| Sending difference | unsignedInt 0…32000 | 20 |
| Number of KNX bus resets | list | disable |
| Number of device startups | list | disable |
| Sending difference | unsignedInt 0…500 | 1 |
| Total operating time [s] | list | disable |
| Sending difference | unsignedInt 0…2600000 | 0 |
| Operating time since last device startup [s] | list | disable |
| shortCircuit_timeDetached | unsignedInt 0…64000 | 20 |
| shortCircuit_timeBeforeDetach | unsignedInt 0…64000 | 10 |
| shortCircuit_timeShortCircCheck | unsignedInt 0…64000 | 10 |
| PS | list | 640 |
| shortCircuit_shortCircuitCurrent | unsignedInt 0…26000000 | 1100 |
| Overload current | unsignedInt 0…128000 | 900 |
| nominal Current | unsignedInt 0…128000 | 640 |
| Value LED minimum Output voltage | unsignedInt 0…26000000 | 28000 |
| Value LED maximum Output voltage | unsignedInt 0…26000000 | 32000 |
| Value LED minimum Input voltage | unsignedInt 0…26000000 | 190000 |
| Value LED maximum Input voltage | unsignedInt 0…26000000 | 270000 |
| Maximum device temperature | unsignedInt 0…26000000 | 75 |
| Minimum Device Temperature | unsignedInt 0…1000 | 0 |
| Count Working Time | unsignedInt 0…64000 | 1 |
| Check Time | unsignedInt 0…64000 | 1 |
| Convert time | unsignedInt 0…64000 | 20 |
| Time send limit | unsignedInt 0…64000 | 1 |
| Reset Time | unsignedInt 0…64000 | 20 |
| Alarm 1 | list | disable |
| Measurement source | list | Output current |
| Threshold | unsignedInt 40…95 | 70 |
| Hysteresis | unsignedInt 5…100 | 5 |
| Threshold | unsignedInt 10…800 | 640 |
| Hysteresis | unsignedInt 5…500 | 5 |
| Threshold | unsignedInt 28…32 | 31 |
| Hysteresis | unsignedInt 1…32 | 5 |
| Alarmtype | list | Threshold exceeded |
| Alarm 2 | list | disable |
| Alarm 3 | list | disable |
| Alarm 4 | list | disable |
| xxx | list | Threshold exceeded |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Device/Busline Diagnostics 1.0 latest | $3001 | A7BD | 2026-11-25 | 88 KB | Download |
About this file
This is the official ETS product database for the TAPKO Technologies Power Supply IPS640 (IPS 640), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from TAPKO Technologies
- KNX Power Supply KPS640 KPS 640
- IP TP Coupler MECip MECip
- IP TP Segment Coupler MECip-Sec MECip-Sec
- Line Repeater/Power Supply MECps640 MECps640
- TP RF Segment Coupler MECrf MECrf
- TP Line Repeater MECtp MECtp
- TP Line/Segment Coupler MECtp-Sec MECtp-Sec
- TP RF Segment Coupler/Secure Proxy MEXrf MEXrf
- IP KNX Data Server SIMip SIMip
- Contact Interface TIO4-Sec TIO4-Sec
- KNX IP Interface UIMip UIM KNX IP
- USB RF Interface UIMrf UIM-KNX RF